NORME CEI

INTERNATIONALE IEC
INTERNATIONAL 62305-2
STANDARD Edition-1
2004-01

Structure's Attributes: Structure's Dimensions:


Length of structure (m): 30 Location relative to surroundings: Isolated structure
Width of structure (m): 15 Location density (service line density): Suburban
Height of roof plane (m)*: 8 Number thunderdays: 40 days/year
Equivalent area (m2): 4.420 m2 Equivalent annual flash density: 4,0 flashes/km2

Structure's Attributes: Protection Measures:


Risk of fire or physical damage: Low LPS type: No protection
Structure screening effectiveness: Poor Fire protection level: No measures
Internal wiring type: Unscreened Surge protection: Service entrances only

Conductive Service Lines: Other Overhead Services:


Number of conductive services: 0
Type of external cable: Unscreened
Power Line:
Type of service to the structure: Buried cable
Type of external cable: Unscreened Other Underground Services:
Presence of MV / LV transformer: No Transformer Number of conductive services: 1
Type of external cable: Unscreened

Loss Categories: Category 3 - Loss of Cultural Heritage:


Cultural heritage lost due to fire: No heritage value
Category 1 - Loss of Human Life:
Special hazards to life: Low panic level
Life loss due to fire: Other structures
Category 4 - Economic Loss:
Special economic hazards: No special hazards
Life loss due to overvoltages: No safety critical systems
Economic loss due to fire: Other structures
Economic loss due to overvoltage: Other structures
Step - touch potential loss factor: No shock risk
Category 2 - Loss of Essential Services: Tolerable risk of economic loss: 1 in 10 yrs
Services lost due to fire: No service exist
Services lost due to overvoltages: No service exist

Calculated Risks:
Tolerable Direct Strike Indirect Strike Calculated
Risk Rt Risk Rd Risk Ri Risk R
Loss of Human Life: 1,00E-05 3,71E-07 1,20E-06 1,57E-06
Loss of Essential Services: 1,00E-03 0,00E+00 0,00E+00 0,00E+00
Loss of Cultural Heritage: 1,00E-03 0,00E+00 0,00E+00 0,00E+00
Economic Loss: 1,00E-01 1,77E-06 1,86E-04 1,88E-04

IEC Risk Assessment Calculator: Version 3.0.3 Database: Version 1.0.6