TA330 Operating Manual
TA330 Operating Manual
Copyright Information
© 2015 Trust Automation, Inc. All rights reserved.
This document is provided for Trust Automation, Inc. customers, solely for the purpose of
assisting our customers in the use and installation of our products. Other uses are unauthor-
ized without the written permission of Trust Automation, Inc. The text and graphics included
are for purpose of illustration only and information is subject to change without notice. Trust
Automation, Inc. and the Trust Automation, Inc. logo are trademarks of Trust Automation, Inc,
a California corporation.
For information regarding re-use of this material or to report errors, omissions, inconsisten-
cies, etc, please contact Technical Support at:
High voltages are present in some Trust Automation products. Maintenance or repair should
only be performed by qualified personnel and only under power down conditions. Mainte-
nance and repair shall be limited to those items described in this operating manual as user
approved. All other repair and maintenance shall be performed by Trust Automation, Inc.
CAUTION
Do not attempt to service this product yourself except as authorized and explained in
this operation manual. Failure to follow recommendations may result in product and/or
personal injury.
Table of Contents
1.0 Features and Setup ....................................................................................................................................... 5
1.1 Introduction........................................................................................................................................... 5
1.2 Setup ..................................................................................................................................................... 6
1.3 Drive Modes .......................................................................................................................................... 6
1.4 Command Input .................................................................................................................................... 7
1.5 Upgrading from a TA320 or TA330...................................................................................................... 8
1.6 Transconductance Ratio ...................................................................................................................... 8
1.7 Thermal Limits ...................................................................................................................................... 9
1.8 Dynamic Transconductance Selection................................................................................................ 9
1.9 Enable Input ........................................................................................................................................ 10
1.10 Fault Output ...................................................................................................................................... 11
1.11 Ground Connections......................................................................................................................... 12
1.12 Drive Power Supply........................................................................................................................... 12
1.13 Optional External 24VDC Supply ..................................................................................................... 13
1.14 Power Dissipation Calculations....................................................................................................... 13
1.15 Motor Connections........................................................................................................................... 15
1.16 Serial Monitoring .............................................................................................................................. 16
2.0 General Specifications................................................................................................................................ 19
2.1 Electrical Specifications..................................................................................................................... 19
2.2 Mechanical Specifications................................................................................................................. 20
2.3 Environmental Specifications ............................................................................................................ 20
2.4 TA330 Safe Operating Area Curve (SOA) .......................................................................................... 21
2.5 TA330 Output Frequency Response.................................................................................................. 23
3.0 Mechanical Information ............................................................................................................................. 24
3.1 Dimensions ......................................................................................................................................... 25
4.0 Connector and Switch Information............................................................................................................ 25
4.1 Front Panel Connector and Switch Layout........................................................................................ 25
4.2 Connector Types................................................................................................................................. 26
4.3 J1 – External 24VDC Supply.............................................................................................................. 26
4.4 J2 – Serial Monitoring Port................................................................................................................ 26
4.5 J3 – Command Signals...................................................................................................................... 27
4.6 J4 – Hall Sensor Input........................................................................................................................ 28
4.7 J5 – Motor Signals ............................................................................................................................. 28
4.8 J6 – Motor Power............................................................................................................................... 29
4.8 SW1 – Switch Settings....................................................................................................................... 29
4.9 SW1 – Switch 3 and 4, Fixed Gain and DTS Settings ....................................................................... 30
4.10 SW1 – Switch 5-8 Motor type .......................................................................................................... 31
4.11 Isolation Diagram ............................................................................................................................. 32
4.12 Isolation Diagram ............................................................................................................................. 33
5.0 Application Examples ................................................................................................................................. 34
5.1 Brushless Motor, Sinusoidal ............................................................................................................. 34
5.2 Brushless Motor, Trapezoidal Hall Commutation............................................................................. 35
5.3 Single Brush Motor or Voice Coil Motor in Bridge Mode ................................................................. 36
5.4 Dual Brush Motor, Dual Motor Mode ................................................................................................. 37
5.5 Stepper Motor, Sinusoidal Commutation .......................................................................................... 38
6.0 TA330 Hardware Revision History............................................................................................................. 39
7.0 TA330 Manual Revision History................................................................................................................. 39
8.0 Warranty....................................................................................................................................................... 40
Tables
The TA330-E01 is a highly configurable device with four common configuration modes:
The TA330-E01 features Digital on-the-fly gain control (Dynamic Transconductance or DTS).
This allows an application to modify the drive transconductance on-the-fly, permitting both
high acceleration control and high resolution control. Normally one of these parameters is
sacrificed in favor of the other due to DAC limitations at the driving motion controller.
The TA330-E01 features a true Class-AB linear power stage with a fast current feedback loop
to put it in torque mode. This means that the output is a pure current signal with virtually no
distortion around zero, eliminating all of the side effects of a PWM drive. Some Class-C linear
designs, which have a dead band at zero volts out, attempt to mask this with a fast current
loop. This works for some applications, but performance will suffer in ultra-high precision
applications.
Two important considerations where linear servo amplifiers are utilized are cooling and power
supply selection. A linear servo amplifier acts similarly to a large electronic variable resistor.
Any power supply voltage not delivered to the load is dumped as heat into the heatsink.
Power supply voltages should be matched closely to the required load voltage with a small
margin for overhead. Excessive supply voltage will result in amplifier overheating. Cooling
linear servo amplifiers is often overlooked or not well understood. Many products are avail-
able with similar current output specifications, but require the user to supply heatsinks or
fans. The TA330-E01 incorporates a large heatsink with integral cooling fans to accommo-
date most demanding applications provided there is adequate air space around the chassis
and the ambient temperature does not exceed specification. The TA330-E01 intelligently
monitors temperature and compensates its internal dissipation to protect the drive from
damage due to high temperatures. The TA330-E01 has a serial diagnostics port to monitor
application performance and power levels to aid in assuring optimal performance and a long
life.
All Trust Automation drive products are built for safety, installation ease and long life. The
TA330-E01 offers a fully isolated user interface for safe operation in high voltage applica-
tions. In addition the housing reduces the risk of operator injury and protects the drive, ensur-
ing longer useful life. All connections utilize pluggable terminal connectors making them easy
to install and remove while reducing risk of connection error.
1.2 Setup
The TA330-E01 is configurable for several drive motor type options and configurations. All
configurations require the use of bipolar supplies that can be in the range of 24 to 75V. Cur-
rent outputs are adjustable from 6 to 18A.
In sinusoidal mode, the TA330-E01 is designed to accept two command signals (A and B @
±10V) from a motion controller that is performing the commutation based upon encoder
feedback. The TA330-E01 derives the third phase internally (C = - (A+B)). (See application
example 5.1)
Trapezoidal
Trapezoidal operation is the simplest configuration used to drive a DC brushless motor. The
TA330-E01 reduces the audible tick often associated with Hall commutation by smoothing
the transitions without sacrificing performance. As a practical limitation, Hall commutation is
limited to ~ 3 kHz throughput. In this mode, the motors Hall Sensors are connected to J4. If
the motor has differential Hall outputs, only connect the “+” Hall outputs to J4 and leave the
“–” Hall signals unconnected. (Do not tie to ground, the motor will be damaged.)
The motion command signal (±10V) is connected to the “A” command input. (See application
example 5.2)
Brushed-Bridge
Brushed-bridge mode supports operating a traditional brushed or voice coil-type motor,
bridged across the A & C output phases. The command signal (±10V) is connected to the “A”
command input. (See application example 5.3)
Brushed-Dual
This mode supports driving two independent brushed or voice coil-type motors. This mode
could also be used to drive a stepper motor in sinusoidal mode. The first motor (winding)
would be connected to the “A” phase output and the common ground of the bipolar power
supply. The second motor (winding) would connect to the “B” phase output and the common
ground. The command inputs (±10V) are connected to the “A” and “B” command inputs. (See
application examples 5.5 and 5.6)
Differential Inputs
Using differential input helps reduce or eliminate potential noise susceptibility from other
sources. Connect the motion controller ± command outputs to the TA330-E01 ± inputs at J3.
For best immunity use a twisted pair cable. Terminate the motion controller signal ground to
the TA330-E01 ISO ground connection at J3. (See application examples 5.1)
Single-Ended Inputs
Many motion controllers only offer single-ended command signals with a common ground.
Single-ended configurations are accommodated by referencing the A+ and B+ signals to the
command output and referencing the A- and B- signals to the motion controller signal ground.
It is good practice to use a twisted pair cable for the “+” command, terminating the “-” com-
mand at the controller signal ground. Terminate the motion controller signal ground to the
TA330-E01 ISO ground connection at J3. (See application example 5.3)
The original TA320 and TA330-D01 linear amplifiers operated with inverted outputs, meaning
a positive command induces a negative current. The TA330-E01 is a non-inverting amplifier
(positive command = positive current)
Examples:
• Differential inputs would place the motion controller’s + signal on the TA330-E01 –
command input and the controller’s – signal on the TA330-E01 + command input.
• Single-ended configurations place the motion controller’s command output on the
TA330-E01 - command inputs and terminate the TA330-E01’s + command inputs to
the motion controller’s signal ground and the TA330-E01 ISO Ground connection.
Example:
If: Io desired = 14A and Vc (max) = 10V
Then: gm = 14 / 10 or 1.4A/V
For every 1 Volt of command 1.4A of current will be driven.
TA330-E01 is factory configured for 6A, 10A, 14A and 18A for a commanded input voltage of
±10V, set at SW1, positions 3 and 4. (See table 4.9)
Note: 18A output duration is limited by the SOA graph and temperature. (See SOA section
2.4)
Due to the digital nature of most motion controllers there is limited DAC resolution to cover
both the high and low currents with sufficient resolution. By switching the transconductance
on the fly, the motion controller’s DAC can be utilized at its full resolution for both high current
moves and precision motion.
The DTS inputs are logically “OR”ed with the DTS switch inputs. In this way a highest current
setting can be chosen by the switches and logic can “OR” with this data to set a lower setting.
The TA330-E01 accomplishes this by allowing the motion controller to logically control the
DTS bits D0 and D1 through pins 5 and 6 of J3 (5V TTL).
The input must be pulled to logic low (ISO GND) or logic high (ISO +5) for the TA330-E01 to
operate. The ENABLE line is pulled up internally to ISO +5. The TA330-E01 provides an
isolated +5V source at connector J3 and J4 with a maximum draw of 100mA. If the applica-
tion requires more current, the user must supply an external 5V that must be referenced to the
ISO ground connection.
The TA330-E01 must not be enabled during power up. If the drive is powered up when
enabled, the drive will not enable and will assert FAULT. The ENABLE input must then be
cleared and re-asserted to enable the drive.
Note: Logic low input minimum voltage (VIL) is 0.8V. Logic high input minimum voltage (VIH) is
2.0V with a maximum on 5.2V.
+5V +5 AUX
1K
INPUT
GND
Figure 1 - Enable Circuit
+5V +5 AUX
10K
OUTPUT
AUX GND
ISO Ground and all user interface signals on J2, J3 and J4 are isolated from drive power GND
and the External 24V GND with a minimum 1500V High-pot separation.
When using the TA330-E01 or any linear servo amplifier, power supply voltage that is not
delivered to the motor will be lost as heat in the amplifier. (See section 1.14)
When selecting supplies for a given motor application it is recommended that the total volt-
age be approximately 20V more than the required motor voltage. (The TA330-E01 can drive to
within ~ 8V of the supply). Excessive supply voltages will result in higher peak wattage dissi-
pation. Reference the SOA graph for actual currents allowed. (See section 2.4)
J4
1
24-75V - -V
Power
Supply +
2
Gnd
24-75V -
Power
+ 3
Supply +V
Connect the positive supply positive (+) to V+ and the positive supply negative (-) to GND.
Connect the negative supply positive (+) to GND and the negative supply negative (-) to V-.
(See figure 3 above)
Note: When designing a system E-stop, never cut the motor leads. Doing so will result in a
runaway condition and may damage the TA330-E01. Always cut the incoming DC supply,
(crowbar with a low value resistor), to the TA330-E01 to produce a rapid stop.
The TA330-E01 features a microprocessor that constantly monitors the wattage across the
drive to protect the Class-AB power stage from damage. At any given moment in time there is
one power device (upper or lower) that is handling the majority of the drive wattage regard-
less of whether the load is a floating brushless motor or a ground-referenced brushed-type
load. Calculations are based on the highest current and voltage across any phase with
respect to the power supply ground.
When predicting SOA wattage limits with a brushless motor (or single brushed-type motor in
bridge mode), use half of the expected voltage across any pair of phase leads against the
voltage of one of the two supplies.
For a brushed-type load that is directly referenced to the power supply ground, use the full
predicted voltage across the motor against one of the two supplies.
Brushless example:
Assume you have a pair of 48V supplies and a motor that is expected to require 15A peak
load at a phase voltage requirement of 12V according to our calculations. Because a brush-
less motor voltage is specified as phase to phase, we will divide the predicted voltage in half
to give a ground referenced motor voltage of 6V.
PD = Imotor (Vsupply – Vmotor)
Imotor = 15A [calculated based on required torque]
Vmotor = 6V [calculated based on velocity]
Vsupply = 48V [one of two 48V supplies]
PD = 15A (48V-6V)
= 630W *
* This is just over the 600W continuous dissipation rating so there will be a short time limit
applied based on the SOA chart before a fault will be generated. See the SOA chart, section 2.4.
Note: When designing a system E-stop, never cut the motor leads. This will result in a runaway
condition and may damage the TA330-E01. Always cut the incoming DC supply, (crowbar with a
low value resistor) to the TA330-E01 to produce a rapid stop.
Brushless motor
The phase outputs, A,B and C correlate to most motor callouts as U, V and W and in some
cases they are referred to as R, S and T. (See application examples 5.1 and 5.2)
To drive a single brush type motor in bridged mode, connect the motor (+) lead to the A phase
output and the motor (–) lead to the C phase output. This configuration allows the full bipolar
supply voltage to be driven across the motor in any direction of rotation. The motor can be a
traditional brush type motor or a voice coil type.
Stepper Motor
Two coil sets on a stepper type motor may be driven in this configuration. This configuration
is the same as the dual brushed mode except that the two coil sets are in the same motor.
The linear commands are driven on command A and B with a motion controller setup to drive
a stepper motor sinusoidally. (See application example 5.6)
An optional TTL to USB serial cable may be ordered as CBLZ-0910-01 to facilitate connection
to a PC.
Reference the FTDI installation guide for installing the TTL to USB serial cable.
(www.ftdichip.com VCP drivers)
TA330 R 5.0
Brushless Mode
Once the TA330-E01 in enabled, data will begin transmitting in the following format:
Figure 6 shows the drive is set to brushless motor mode, there are no faults, the heatsink is at
22°C, the positive supply is at 24V and the negative supply is at 24V. There is less than 1A
current flow and integer math has placed the dissipation at 9W.
The data stream may be stopped by transmitting “s” followed by “Rtn.” The data stream will
resume upon sending the “s” + “Rtn” sequence again. Data layout is formatted as:
0x0002 Temp Over temp fault at 70c, the TA330-E01 will disable at 90c
0x0004 Current Over current fault based on time limit and SOA
0x0010 Peak Wattage Peak wattage limit based on time and SOA
Temperature (ambient)
Continuous 350W
Humidity
Current Limit
For currents that result in a dissipation wattage below 350W, the processor limits the time
logarithmically from infinite time at 6A down to 500ms at 18A (see current vs. time graph).
Wattage Limit
If the resulting dissipation wattage exceeds 350W, the time to fault is much shorter as it is
now operating in the “knee” of the SOA curve (See wattage vs. time graph)
Temperature limit
The microprocessor also takes into account the heatsink temperature when calculating the
wattage time limit. Time to fault is de-rated at about 15ms per 20°C rise. If the heatsink tem-
perature exceeds 70°C a Fault will be generated, and at 90°C the drive will shutdown.
100
10
1
1.00 10.00 75.00 100.00
Drive Voltage (V) = Supply (V) - Winding (V)
17
15
13
Current
11
5
500 1500 2500 3500 4500 5500 6500
Time (ms)
Figure 9 - Output Current vs. Time Graph for Time to Fault at ~30˚C
550
500
450
400
350
300
0 20 40 60 80 100
Time (ms)
Figure 11 – Temperature Derating, Time to Fault for Dissipation Wattages vs. Heatsink Tempera-
ture
Example (How to use the above chart)
If wattage is between 651 to 668 @ 60ºC, then you have 20ms before the unit will shut down.
Lower inductance motors (0.10mH) will yield a higher bandwidth and higher inductance
motors (10-15mH) will yield a lower bandwidth. There is no actual limit on how high the induc-
tance can be, but there are practical limitations based on Ohm’s Law that limit actual band-
width response in a motor. Excessively low inductances (<0.1mH) can result in current loop
instability and result in uncontrolled oscillations.
The TA330-E01 has been factory tuned to give optimal performance over a wide variety of
industry standard motors. If the intended application for the TA330-E01 requires a motor
outside the usual inductance range, and the full 5 kHz throughput is required, please contact
[email protected] to discuss your requirements.
The following was plotted with a 1V command into a 0.820mH load with a DC resistance of
0.65Ω.
3.1 Dimensions
2 Common (Isolated)
1 ISO Gnd
3 VISO
4 TXD
5 RXD
J2 provides a TTL level serial port to monitor the operating conditions on the load and the
internal health of the TA330-E01. The separately orderable TTL Serial to USB cable provides a
convenient conversion for viewing the data with any terminal program such as Windows
HyperTerminal. (See section 1.16) The J2 connector is not supplied by Trust Automation
9 ISO Gnd
2 ISO Gnd)
3 Hall A
4 Hall B
5 Hall C
Note: If the motor has differential Hall outputs, only connect the (+) Hall outputs to J4 and leave
the (–) Hall signals unconnected (Do not tie to ground, the motor will be damaged.)
Note: If the Hall sensors require more than 20ma, an external +5V must be supplied. (See appli-
cation example 5.3)
2 Motor Phase A
3 Motor Phase B
4 Motor Phase C
Note: Phase A, B and C are the same as U, V and W or R, S and T found on most commercial
motors.
1 B- Supply
2 Common (Isolated)
3 B+ Supply
1 /ENABLE (drive enabled on low Input) ENABLE (drive enabled on high input)
2 /FAULT (FAULT low true output) FAULT (FAULT high true output)
3 Gain and DTS Settings See Following Chart for Function Selection
4 Gain and DTS Settings See Following Chart for Function Selection
Note: “Down” is toward the heatsink, “Up” is away from the heatsink
6A 10A
1 Up 1 Up
0 Down 0 Down
1
2
DTS D0 3
DTS D1 4
5
6
7
8
1
2
DTS D0 3
DTS D1 4
5
6
7
8
14A 18A
1 Up 1 Up
0 Down 0 Down
1
2
DTS D0 3
DTS D1 4
5
6
7
8
1
2
DTS D0 3
DTS D1 4
5
6
7
8
Brushless motor, Trapezoidal Commutation, 120° Halls Down (0) Up (1) Up (1) Up (1)
Brushless motor, Trapezoidal Commutation, 60° Halls Down (0) Down (0) Up (1) Up (1)
Single Brushed Motor (or voice coil) Bridged Mode Up (1) Up (1) Down (0) Up (1)
Dual Brushed Motor (voice coil or stepper) (unbridged) Up (1) Up (1) Down (0) Down (0)
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
60° / 120°
60° / 120°
60° / 120°
Trap / Sine
Dual / Bridge
Trap / Sine
Dual / Bridge
Trap / Sine
Brush / Brushless
Dual / Bridge
Brush / Brushless
Brush / Brushless
1
2
3
4
5
6
7
8
60° / 120°
60° / 120°
Trap / Sine
Trap / Sine
Dual / Bridge
Dual / Bridge
Brush / Brushless
Brush / Brushless
3 5
70555-0040 VCC RXD
4
Iso Ground
TXD Iso Pwr (5V)
U2
R2
6 2 8
Mate - Molex RTS
1K
1 Gnd CTS 2 6
3
0022552062 5
Iso Ground
R3
1 +5V HALL A 3 2 15
665 U3B
3 14
R4
C2 4 4 13
HALL B
665 U3C
0.1 5 12
R5
2 GND HALL C 5 6 11
665
C3 C4 C5
Iso Ground
0.01uf 0.01uf 0.01uf
Iso Ground
5V DC/DC
1
C7 C8
+
0.1
100uf/50V
2
Iso Ground
R6
J3 10K
U4
FAULT 8 4 1
C9 3 2
Iso Pwr (5V) 0.01uf
U3D
7 10
C6
R7
0.1 7 8 9
/ENABLE
1K U5A
1 16
C10
9 0.01uf 2 15
AUX GND
U5B
Iso Ground Iso Ground 3 14
R8
DTS D0 5 4 13
1K
U5C
5 12
R9
DTS D1 6 6 11
1K
C11 C12
0.01uf 0.01uf
Iso Ground
R10
10K
SIG A+ 1
Analog Isolator
SIG A- 2
R11
10K
SIG B+ 3
Analog Isolator
SIG B- 4
TA-AMP SIGNAL
TA330 - E01
USB port
Optional 24v Input
1 +24V External Supply
AUX 24V
J1
+ -
2 Common
J4
ISO GND 2
HALL A 3
FAULT 8 0 1 HALL B
HALL C
4
5
GND 9
Enable LVL 1
Fault LVL 2
DTS D0 3
DTS D1 4 S1
Trap/Sine 5
60º / 120º 6 Brushless
Brush / Brushless 7 POWER Motor
Dual / Bridge 8 ENABLE
FAIULT
Down
Up
SHIELD 1
1 Shield
J5
MOTOR A 2
2 Common Common 2
J6
3 B+ B+ 3
24-75V -
Power
Supply +
The figure shows the TA330-E01 operating in sinusoidal mode with differential command
inputs. Active low enable, active low fault, driving a single brushless servo motor. The TA330-
E01 is set for a fixed current limit of 10A with a transconductance of 1.0A/V.
TA330 - E01
USB port
Optional 24v Input
1 +24V External Supply
AUX 24V
J1
+ -
2 Common
J4 5 Hall C
ISO GND 2
HALL A 3
FAULT 8 0 1 HALL B
HALL C
4
5
GND 9
Enable LVL 1 Hall Sensors
Fault LVL 2
DTS D0 3
DTS D1 4 S1
Trap/Sine 5
60º / 120º 6 Brushless
Brush / Brushless 7 POWER Motor
Dual / Bridge 8 ENABLE
FAIULT
Down
Up
SHIELD 1
1 Shield
J5
MOTOR A 2
MOTOR B 3 2 Phase A Motor Power
24-75V - MOTOR C 4
3 Phase B
4 Phase C
Power
Supply + 1 B- B- 1
2 Common 2
J6
3 B+ B+ 3
24-75V -
Power
Supply +
This figure shows the TA330-E01 operating in trapezoidal mode with single ended command
input. Active low enable, active low fault, driving a single brushless servo motor, using Hall
Effect sensors at 120° timing for trapezoidal commutation. The TA330-E01 is set for a fixed
current limit of 14A with a transconductance of 1.4A/V.
Hall Sensors are connected to J4. If the motor has differential Hall outputs, only connect the +
Hall outputs to J4 and leave the – Hall signals unconnected. (Do not tie to ground, the motor
will be damaged.)
**Note that Hall 5V power supplied by the TA330-E01 is limited to 20ma. If the motor hall
sensors require >20ma for operation, an external 5V power source must be used.
TA330 - E01
USB port
Optional 24v Input
1 +24V External Supply
AUX 24V
J1
+ -
2 Common
J4
ISO GND 2
HALL A 3
FAULT 8 0 1 HALL B
HALL C
4
5
GND 9
Enable LVL 1
Fault LVL 2
DTS D0 3
DTS D1 4 S1
Trap/Sine 5
60º / 120º 6
Brush / Brushless 7 POWER
FAIULT
Down
Up
1 Shield
SHIELD 1
2 Phase A A
J5
MOTOR A 2
MOTOR B 3
3 Phase B NC
4 Phase C C
24-75V - MOTOR C 4
Power
Supply + 1 B- B- 1
2 Common Common 2
J6
3 B+ B+ 3
24-75V -
Power
Supply +
This figure shows the TA330-E01. Active low enable, active high fault, driving a single brush-
less servo or voice coil motor. The TA330-E01 is set for a fixed current limit of 14A with a
transconductance of 1.4A/V
TA330 - E01
USB port
Optional 24v Input
1 +24V External Supply
AUX 24V
J1
+ -
2 Common
J4
ISO GND 2
HALL A 3
FAULT 8 0 1 HALL B
HALL C
4
5
GND 9
Enable LVL 1
Fault LVL 2
DTS D0 3
DTS D1 4 S1
Trap/Sine 5
60º / 120º 6
Brush / Brushless 7 POWER
FAIULT
Down
Up
+ -
1 Shield
SHIELD 1
2 Phase A
J5
MOTOR A 2
MOTOR B 3
3 Phase B
4 Phase C NC
24-75V - MOTOR C 4
Power + -
Supply + 1 B- B- 1
2 Common Common 2
J6
3 B+ B+ 3
24-75V -
Power
Supply +
This figure shows the TA330-E01 operating in brushed bridge mode with differential com-
mand inputs. Active low enable, active low fault, driving a single brush type servo motor. The
TA330-E01 is set for a fixed current limit of 18A with a transconductance of 1.8A/V.
TA330 - E01
USB port
Optional 24v Input
1 +24V External Supply
AUX 24V
J1
+ -
2 Common
J4
ISO GND 2
HALL A 3
FAULT 8 0 1 HALL B
HALL C
4
5
GND 9
Enable LVL 1
Fault LVL 2
DTS D0 3
DTS D1 4 S1
Trap/Sine 5
60º / 120º 6
Brush / Brushless 7 POWER
FAIULT
Down
Up
1 Shield NC
SHIELD 1
2 Phase A
J5
MOTOR A 2
MOTOR B 3 3 Phase B
24-75V - MOTOR C 4 4 Phase C NC
Power
Supply + 1 B- B- 1
2 Common B A
Common 2
J6
3 B+ B+ 3
C
24-75V -
Power D
Supply +
This figure shows the TA330-E01 operating in brushed dual mode with differential command
inputs. Active low enable, active low fault, driving a stepper motor sinusoidally. The TA330-
E01 is set for a fixed current limit of 6A with a transconductance of 0.6A/V.
V0.16 22 Sep 10 Added reference to FTDI VCP driver for TTL to USB conversion and
monitoring. Added full hardware revision history
V0.17 24 Jan 12 Added notation about the J2 connector, cable as an orderable option.
Not supplied J2 is not supplied, J1, J3-J6 are supplied.
8.0 Warranty
Trust Automation, Inc.
Limited 1 Year, Non-Transferrable Warranty
GENERAL - All hardware products sold by Trust Automation Inc. are warranted against defects
in material and workmanship for a period of one (1) year from the date of shipment. If you
believe that a Trust Automation Inc. hardware product you have purchased has a defect in
material or workmanship, or has failed during normal use within the warranty period, please
contact Trust Automation Inc. at 805.544.0761 for assistance and/or a Return Material Autho-
rization Number (RMA#).
If product repair or replacement is necessary, the Customer will be responsible for all return
shipping charges, freight, insurance and proper packaging to prevent damage in transit,
whether or not the product is covered by this warranty. During the warranty period, product
determined by Trust Automation Inc. to be defective in form or function will be repaired or, at
Trust Automation Inc.'s option, replaced at no charge. Trust Automation Inc. will pay the return
shipping charges (ground for US based shipments, most economical air for international
shipment. Customer may elect to change shipment method and pay the difference.), for prod-
ucts that have been repaired or replaced. All duties and taxes remain the responsibility of the
customer. All shipments of repaired or replaced products will be EXW at Trust Automation,
Inc. headquarters in San Luis Obispo, California.
For tracking purposes, products to be repaired or replaced must be returned to Trust Automa-
tion Inc. with a Trust Automation Inc. RMA#, and a Purchase Order. The minimum charge for
non-warranty repair work is $130 and the standard rate is $130 per hour, plus parts. Trust
Automation will provide a repair cost estimate prior to performance of out of warranty repair
work. Send product to:
Trust Automation, Inc.
143 Suburban Road, Bldg. 100
San Luis Obispo, CA. 93401
ATTN: RMA# xxxxxx
Material and workmanship used in the repair and replacement of Trust Automation products
under this warranty are warranted additionally against defects for a period of ninety (90) days
from the date of return shipment to the customer.
LIMITATIONS - This non-transferrable warranty does not apply to damage resulting from
accidents or any Customer actions, such as mishandling, misuse, improper interfacing, opera-
tion outside of design limits or unauthorized repair or modification. No other warranties are
expressed or implied. Trust Automation Inc. liability shall be limited to the actual purchase
price of any defective unit or units of equipment to which a claim is made and shall in no
event include the Customer's manufacturing costs, lost profits or goodwill, or any other direct,
indirect, special, incidental or consequential damages.