Eazy-Rl Vt2.3 Manual Controlador Da Gpu

This document provides instructions for operating an EAZY-RL VT2.3 controller. It has 8 operating modes including timer functions from 1-999 seconds or minutes, voltage control of loads based on preset voltage limits, and voltmeter display from 0-99.9V. The controller can be used for automatic control, product testing, and DIY projects. It has various relay parameters and operating ranges to meet control needs at low cost while ensuring safety and reliability.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
409 views6 pages

Eazy-Rl Vt2.3 Manual Controlador Da Gpu

This document provides instructions for operating an EAZY-RL VT2.3 controller. It has 8 operating modes including timer functions from 1-999 seconds or minutes, voltage control of loads based on preset voltage limits, and voltmeter display from 0-99.9V. The controller can be used for automatic control, product testing, and DIY projects. It has various relay parameters and operating ranges to meet control needs at low cost while ensuring safety and reliability.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

EAZY-RL VT2.

3 Controller User’s Manual


Thank you for using this product of our company, the “EAZY-RL” controller is compatible with a
variety of operating modes, LED digital tube displays, procedures for intelligent control, to
achieve the timing relay functions, the voltage control function, and voltmeter functions, applies
to automatic control field, product testing, DIY etc.
This product is designed to meet electrical safety rules, with industrial reliability, it meet a variety
of control requirements at lowest cost.
In case of any printing or translation error, we apologize for the inconvenience.
Features
Operating modes:
P-1: Timer ( 1-999 S / 1-999 Min)
P-2: Delay timer ( 1-999 S / 1-999 Min)
P-3: Voltage control relay ( control the load on/off)
P-4: Voltage control Timer- A (release first)
P-5: Voltage control Timer- B (close first)
P-6: Voltage range control relay
P-7: Voltage range control Timer
P-8: Set display off
Timing Range: 0-999 seconds or 0-999 minutes (0.1s-999s optional)
Voltmeter display range: DC 0-99.9 V
Voltage detection error: ± 0.1V
Operating Power: DC10~16V (5V,24V optional)
Relay parameters:
Coil Voltage: DC 12V (5V,24V optional)
A set of conversion (normally open and normally closed)
Contact load: 10A/277V AC or 10A/30V DC
Contact resistance: ≤ 100mΩ (1A 6VDC)
Mechanical durability: 10 millions
Electricity durability: > 100,000 (10A-250VAC)
Operating Temperature: -40 ~ 85℃
External signal input: (5~ 12V) or passive switch (9 levels delay time can be set)
Timer mode can set the relay contact close and release time, the implementation of a single
timing loop
In voltage control mode, can preset upper and lower voltage values limits
Set display shut, the minimum current values are 6mA/12V (delay released)
The pre-set parameters can be saved after power off.

1
Attention:
Do not reverse input voltage polarity!
Use this product to control the high-voltage electrical equipment
must electrical professionals to operate,high voltage danger!

Figure 1

2
2 operating modes:
Connect to power, LED digital tube displays words "E-A-Z-Y-t” in turn, system enter into
the selection state, the initial mode selection is displayed as "P-0", press the “SET” button
to select "P-1~P-8" mode, press “ENTER” to enter the corresponding mode.while any
mode running, press the “ENTER” button for 3 seconds, system will return to the mode
selection state.
Press the “SET” and “ENTER” button to connect the power, the controller will be restored
to factory settings.

2.1 Timer mode (P-1)


Press the “SET” button to select "P-1", controller system will enter into the timer mode.
“P-1”/ “P-2”: 1-999 seconds /minute can be set.
Cyclic run:
In the timer mode, the user can set the relay’s close time T1 and the release time T2,
such as setting T1 for 3 seconds, T2 for 7 seconds, the relay will be closed for three
seconds then release for 7 seconds, cyclic run.
User also can set cyclic times.
When you have set the values of the T1 and T2 , the system saved the settings, the next
time system will be loaded automatically T1 time to wait running.
Timer:
If you set T1 with a specified time, set T2 (release time) with 0, the relay will stop after the
timer run T1 time, no longer running, it can be used as a timer, with running time end, the
normally open contact of relay release, then press the “ENTER” button, the system
re-start the timer for T1 time.
In timer state, you can use external switch or pulse signal input Interface ( Figure 1)on
controller to start the timer (trigger).
Timer setting steps:

SET 000 000 000 save

T1 T2 cycles

1) For the first time of set , select "P-1” time relay mode, LED digital tube display" 000 ";
2) Press the “SET” button, system will enter into the T1 time values settings first, the
digital LED that wait for set flashing with 1Hz frequency, press “ENTER” to select the
number of values, press the “SET” button for three times to enter the T2 time values

3
settings, and cyclic times, press the “SET” button to exit the set state, the system waits to
press “ENTER” button to start running.
3) In the time setting state ,time values’ unit can be switched to minutes unit or second
unit, press the “SET” button to enter the time set by state (set LED digital tube
flashing) ,at this time Press the “SET” button for 3 seconds to release ,the LED digital
tube will light the right decimal points, it means that timing values with minutes unit, if the
decimal point dose not light, it means that timing values with seconds unit.
After setting is completed, press the “SET” button to exit the setting state, press “ENTER”
to start timing, if timing values is set with second unit, seconds values will display with
countdown form. If timing values is set with minute unit, the right decimal point flashing
with 1Hz frequency, means the countdown is running. While timer is running, the normally
open contact of relay connected, the normally closed contact of relay disconnect, press
the “ENTER” to halt run, press the “ENTER” for three seconds to return mode selection
state “P-0”.

2.2 Delay timer (P-2)


The Setting method of “P- 2” is the same as “P- 1”, in the mode of “P-2”, the relay will first
execute release of T1 time then closed with T2 time.

2.3 Voltage control relay mode (P-3)

SET 11.5 10.5 0.0 save

Upper limit Lower limit Voltage Correction

In mode selection state(“P-0”), press the “SET” button to select "P-3", then press the
“ENTER” to enter the voltage comparison control mode, the controller will detect voltage
from “VOL” Interface ( Figure 1)and display values (DC 0-99.9V),it also can be used as a
DC voltmeter ,the default initial run state relay contact is closed (normally closed contact
is disconnected, normally open switch on), press the “SET “button to set the three bit
values, the LED digital tube is set to flashing with1Hz frequency, first to be set upper limit
voltage values , press the “SET” button three times, lower limit values of voltage to be set,
press the “ENTER” button to increase the number of values, the lower limit voltage can
not exceeds the upper limit, press the “SET” button to make digital tube is no longer
flashing, this time system enter into voltage control mode , the controller detects DC
voltage from external input Interface ( Figure 1) , when voltage detection exceed the
4
upper limit of the pre-set, the relay close (normally open contact connect ,normally closed
disconnect), until the voltage drops below the lower limit pre-set, the relay will release
(normally closed contact connect , normally open contact disconnect).
In voltage control condition, press the “SET” button for three seconds then release the
button, the contact of relay state will be reversed. such as: the relay close when detect
voltage below the lower limit voltage.
If the pre-set voltage upper and lower limits set to the same, such as 12.0V, when
controller detect volts at 12.0 fluctuations may cause the relay contact frequent action, we
recommend to set the voltage to maintain the difference between the upper and lower
limits.
Note: The detection voltage terminal must connected reliable, have not loose wiring
around the circuit board insulation ,may lead to the induced voltage detection values is
not accurate.

2.4 Voltage control Timer mode (P-4 / P-5)


“P-4” or “P-5” mode is composed of “P-1” and “P-3” or “P-2” and “P-3”.
When the system switched to “P-4” from “P-1”or“P-2”,it will enter the voltage control timer
mode, the controller will detect voltage from “VOL” Interface ,when detect voltage exceed
the upper limit of the pre-set voltage, the timer will start , until the volts drops below the
lower limit pre-set , the timer stop.
If you set time in “P-1” mode previous, then enter the “P-4” mode , the relay will close with
timer first ,then release, If you set time in “P-2” mode previous, then enter the “P-4” mode ,
the relay release with timing then closed.
The difference between “P-4” and “P-5” is the relay’s Initial state, “P-4” mode relay
release first, but “P-5” mode relay close first.
Press the button of “SET” last for 3 seconds, the timer will start in the case of the voltage
is below the lower limit. the setting method of limit pre-set voltage, please refer to section
2.3.
For example:
(1) In P-2 mode , set T1 005, T2 000, then enter P-4 mode , voltage detection exceed the
upper limit of the pre-set the relay will close after 5 seconds, voltage drops below the
lower limit pre-set the relay release Immediately.
(2) In P-1 mode , set T1 005, T2 000, then enter P-5 mode, voltage below the lower limit
pre-set the relay close immediately, voltage detection exceed the upper limit of the
pre-set the relay will release after delay 5 seconds.
Voltage control logic can be reversed with press SET key for 3 seconds.

5
2.5 Voltage range control relay (P-6)
If the voltage controller detects exceed the upper limit of the pre-set voltage, or the
voltage drops below the lower limit pre-set voltage, the relay will close, otherwise the
relay release between upper limit and lower limit range. Press the button of “SET” last for
3 seconds, the relay reversed. The relay will close between upper limit and lower limit.

2.6 Voltage range control Timer (P-7)


If the voltage controller detects exceed the upper limit of the pre-set voltage, or the
voltage drops below the lower limit pre-set voltage, the relay will run follow time relay
mode that has been set in P-1 or P-1 mode previous.
When voltage values between the upper limit and lower limit range, press SET key for 3
seconds, relay reversed between close and release (ON/OFF).
For example:
In P-1 mode, set T1 005, T2 000, then enter P-7 mode, set relay close between upper
limit and lower limit range. When voltage below lower limit or exceed upper limit, the relay
will release after 5 seconds.

2.7 Set display shut (P-8)


The display shows “d-0” means keep bright, you can press the button of “SET” set 0-9
minutes for display shut.

-END-