Manual & Troubleshooting CC3
Manual & Troubleshooting CC3
Manual & Troubleshooting CC3
Allma CC3
All used trademarks and word marks, even if not expressly stated as such,
remain the property of their respective owners.
Limited rights:
Copying or printing for in-house purposes of the machine operator is
expressly permitted (e.g. for training of operating staff), however, a
copyright notice should be made.
Table of Contents
2 Safety............................................................................. 2-3
10 Service..................................................................... 10-145
These start-up and trouble shooting instructions form part of the machine and
describe how to safely and correctly start-up the machine and help in trouble-
shooting.
WARNING
Be careful with electronic parts!
The following instructions may only be carried out by qualified
personnel. The applicable accident prevention guidelines are to be
observed at all times.
Electrostatic charges
▪ Equip place of work in such a way that it complies with the requirements of
ESD. You can do this by using a conductive working plate, an earthing
wrist band, a soldering iron with earthed soldering bit.
1.2 Validity
These start-up and trouble shooting instructions are only valid for the Allma
CC3.
These start-up and trouble shooting instructions are intended for use by
qualified technicians and must be carried out by trained specialists only.
The machine may only be used by persons who have been instructed in its
proper handling and operation.
1.4 Copyright
2 Safety
3 General preparations
▪ Clip-on ammeter
▪ Make sure the nominal voltage is correct! (See nameplate of the machine)
NOTE
Operating the machine at a wrong voltage may destroy the
electronic system of the machine
Survey ----
Machine ----
Material
Yarn path
Yarn
Delays
Creel yarn
tensioner
Settings
Basics
Fault
Package build-up
Thread reserve
(optional)
Length ----
Logbook ----
Versions ----
Machine status
IOs Machine
Spindles
Diagnosis
Archive
Battery test
(Option)
Servicing Spindles
Start-up CordGuard
(Option)
FC spindle
FC winding
FC capstan
Parameterisation
FC traverse
motion
FC operating unit
Shift Calendar
User interface
Units
Display
MC-configuration Machine
Spindles
Network
Options
▪ Cooling units:
Set thermostat in cooling unit +L-E102 / +R-E202 to 35°C
▪ Fix the door switch +L-S106 / +R-S206 during start-up by using a rubber or
the like
▫ Power switch of fan transformer (not with cooling unit) +L-Q110 / +R-
Q210 = see circuit diagram
▫ -X2:1b = L1
▫ -X2:3b = L2
▫ -X2:5b = L3
4. Check connection L1 between power switch and power supplies:
Supply cable 1. Disconnect all fuses and power switches (see circuit diagram as well):
start-up
▫ Intermediate circuit fuses +L-F124 to F129 / +R-F224 to F229
21. The voltage on the outlet terminals of the 24V fuses +L-F101 to F106 / +R-
F201 to 206 must be 26.80VDC
22. The voltage on all operating modules +FRn-A1 and +FLn-A1 (left / right
machine side) must be greater than 24V (ST1: 1 +) and (ST1: 2 -) (Pay
attention to polarity!)
23. Switch on power switch of cooling unit +L-Q108 / +R-Q208 (if available)
24. The cooling unit +L-E102 / +R-E202 must be running (if available)
25. Main switch OFF
⇒ Checking:
16. Use ▲ ▼ to select parameter 385 (Baudrate)
17. Press ENT
18. Parameter value should be 6
19. Repeat the procedure for all frequency converters
CAUTION
After the update the default values are loaded!
If you want the current settings to be effective for all menus after
updating, the settings have to be saved in advance and reloaded after
updating
After the software update, the Ethernet address must be defined again
4. Main switch ON
5. After booting the screen must be calibrated
⇒ 4 circles appear one after the other. Each circle has to be touched:
⇒ Finally an image appears in which a valid licence code and the desired
machine version has to be entered
If there are two or more control modules with the same address in the
machine (e.g. during the initial start-up of the machine or when
replacing a module), the control must be interrupted during the boot
sequence so that the addressing can be done.
⇒ all yellow indicator lights on the control modules for the respective
machine side begin flashing quickly
3. Starting from the headstock, actuate all start buttons on the control
modules one after the other:
⇒ the respective indicator light must stop flashing after actuating
⇒ the addressing progress can be viewed on the controller screen
4. On left side of the machine only:
⇒ After addressing last spindle Æ Addressing conveyor belt module
For further error messages (see 9.3 Problems with control modules in network,
p. 9-141)
▶ The machine must not be switched off during the software update!
Addressing test 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Select menu item ServiceÆ Start-upÆ Spindle
4.8 Settings
4.8.1 Setting the default values for all menus
Settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Set the default values for all settings by pressing Default All in the menu
AdministrationÆ ConfigurationÆ Machine and answering the prompt with
"Yes"
Table 4-2: Setting of max. spindle current for spindle sizes 205, 230, 250
Spindle current
Altitude of installation
168 Spi 160 Spi 152 Spi ≤ 144 Spi
< 1000 m 1700 mA 1800 mA 1900 mA 2000 mA
1000 to 2000 m 1600 mA 1700 mA 1800 mA 1800 mA
2000 to 3000 m 1500 mA 1600 mA 1700 mA 1700 mA
Table 4-3: Setting of max. spindle current for spindle sizes 290, 310,
Spindle current
Altitude of installation
168 Spi 160 Spi 152 Spi ≤ 144 Spi
< 1000 m ---- 1800 mA 1900 mA 2000 mA
1000 to 2000 m ---- 1700 mA 1800 mA 1800 mA
2000 to 3000 m ---- 1600 mA 1700 mA 1700 mA
Settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Enter the following settings in menu AdministrationÆ ConfigurationÆ
Spindles
WARNING
Incorrect setting for the spindle current can lead to damaging the
spindle motors!
Length counter and yarn 1. Use the global button to enter Machine engineer (see 3.3.2 Password
count system/Code levels, p. 3-7)
2. Make the following settings in menu AdministrationÆ SettingsÆ Units
▫ Titre to dtex
▫ Length to Metre
Parameterisation of 1. Use the Global Button to enter the password Machine engineer
Spindle drive
2. Set the spindle type in menu AdministrationÆ ConfigurationÆ Spindle
⇒ Symbols in the Status line show whether the parameter setting is running
( ), has been run ( ) or is faulty ( )
4. Re-insert plug X10 on FC traverse motion +L-T101 / +R-T201
Parameterisation of 1. Use the global button to enter Machine engineer (see 3.3.2 Password
winding drive system/Code levels, p. 3-7)
2. Set the parameters of the
winding drive in menu Service Æ
ParameterisationÆ FC Winding (Actuate button Run)
⇒ Symbols in the Status line show whether the parameter setting is running
( ), has been run ( ) or is faulty ( )
Parameterisation of 1. Use the global button to enter Machine engineer (see 3.3.2 Password
capstan drive system/Code levels, p. 3-7)
2. Set the parameters of the capstan drive in menu Service Æ
ParameterisationÆ FC capstan (Actuate button Run)
⇒ Symbols in the Status line show whether the parameter setting is running
( ),has been run ( ) or is faulty ( )
3. Re-insert plug X10 on FC traverse motion +L-T101 / +R-T201
Parameterisation of 1. Use the global button to enter Machine engineer (see 3.3.2 Password
traverse motion drive system/Code levels, p. 3-7)
2. Set the parameters of the traverse motion drive in menu Service Æ
ParameterisationÆ FC traverse motion (Actuate button Run)
⇒ Symbols in the Status line show whether the parameter setting is running
( ),has been run ( ) or is faulty ( )
3. Re-insert plug X10 on FC traverse motion +L-T101 / +R-T201
Checking the 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-7, p. 8-98)
machine status
⇒ The machine status is shown from bit 0 to F. ( = 24 VDC, = 0
2. Check the status of the machine (Bit0=1, Bit4=1, Bit8=1). all others = 0)
FC spindle 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-8, p. 8-99)
inputs
2. Actuate and unlock again the emergency stop button +L-S102 (emergency
stop relay +L-K104 drops out)
⇒ After 5 sec: Bit 0 = 0, Bit 1 = 0 and Bit 2 = 0
3. Standby ON (Emergency stop relay +L-K104 picks up)
⇒ Bit 0 = 1, Bit 1 = 1 and Bit 2 = 1
4. With suction unit option. Disconnect wire on terminal X210A:5 from FC
spindle +L-T104 / +R-T204
⇒ Bit 3 = 1 (wire connected)
⇒ Bit 3 = 0 (wire disconnected)
5. Fuse of power supplies: Alternately connect and disconnect +L-Q102 / +R-
Q202
⇒ Bit 4 = 1 +L-Q102 / +R-Q202 ON)
⇒ Bit 4 = 0 +L-Q102 / +R-Q202 OFF)
6. Fuse circuit: Alternately connect and disconnect +L-F119 / +R-F219, +L-
Q104 / +R-Q204 (braking voltage), +L-Q107 / +R-Q207 (roof fan), +L-Q108
/ +R-Q208 (cooling unit) and +L-Q109 (conveyor belt Æ left side only)
⇒ Bit 5 = 1 (all ON)
⇒ Bit 5 = 0 (all OFF)
7. Power supply trouble. Alternately disconnect the signalling contacts +L-
G101 to G103 / +R-G201 to G203: 1+/ 2-
FC traverse 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-8, p. 8-99)
inputs
2. Actuate and unlock again the emergency stop button +L-S102 (emergency
stop relay +L-K104 drops out)
⇒ After 5 sec: Bit 0 = 0, Bit 1 = 0 and Bit 2 = 0
3. Standby ON (Emergency stop relay +L-K104 picks up)
⇒ Bit 0 = 1, Bit 1 = 1 and Bit 2 = 1
4. Normally open button Standby on (clockwise)
⇒ Bit 3 = 1 (upon actuation)
⇒ Bit 3 = 0 (idle)
5. Normally closed button Standby off (anticlockwise)
⇒ Bit 4 = 1 (idle)
⇒ Bit 4 = 0 (upon actuation)
6. Standby OFF
7. Move traverse rod by hand. Sensor +L-B104 / +R-B204 is covered by the
referencing ruler for half of the traversing distance, the other half it is not
⇒ Bit 5 = 1 (traverse sensor covered by plate)
⇒ Bit 5 = 0 (traverse sensor not covered by plate)
FC winding 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-8, p. 8-99)
inputs
2. Actuate and unlock again the emergency stop button +L-S102 (emergency
stop relay +L-K104 drops out)
⇒ After 5 sec: Bit 0 = 0, Bit 1 = 0 and Bit 2 = 0
3. Standby ON (Emergency stop relay +L-K104 picks up)
⇒ Bit 0 = 1, Bit 1 = 1 and Bit 2 = 1
4. Actuate button Machine start briefly, several times
⇒ Bit 3 = 1 (button pressed)
⇒ Bit 3 = 0 (button not pressed)
5. Pressure regulator fault: Switch off compressed air
⇒ Bit 4 = 0 and buzzer starts
6. Switch compressed air back on
FC capstan inputs 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-8, p. 8-99)
2. Actuate and unlock again the emergency stop button +L-S102 (Emergency
stop relay +L-K104 drops out)
⇒ After 5 sec: Bit 0 = 0, Bit 1 = 0 and Bit 2 = 0
3. Standby ON (Emergency stop relay +L-K104 picks up)
⇒ Bit 0 = 1, Bit 1 = 1 and Bit 2 = 1
4. Actuate button Machine stop briefly, several times
⇒ Bit 3 = 1 (button not pressed)
⇒ Bit 3 = 0 (button pressed)
5. Motor temperature contact: Disconnect wire in terminal X210B:6 on FC
capstan +L-T103 / +R-T203
⇒ Bit 5 = 0
6. Connect wire in terminal X210B:6 again
⇒ Bit 5 = 1
7. Standby OFF
Testing the FC outputs 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Go to menu ServiceÆ DiagnosticsÆ Machine status (see Fig. 8-8, p. 8-99)
3. Activate Test outputs
⇒ All outputs are set to 0
4. Test all outputs according to the following table
▪ Do not remove the spindle pot to allow the spindle to turn for checking the
rotation direction because the bearing will lose its lubricant
4.13.1 Preparation
Making settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Make the following settings:
Antipatterning 1,0°
angle α
Settings Æ Length Nominal length 400 m Fig. 3-6 ,
Prewarning doffing 100 m p.3-10
Checking machine 1. Use the global button to enter Machine engineer (see 3.3.2 Password
functions system/Code levels, p. 3-7)
2. Standby ON
⇒ Standby LED illuminated
3. Actuate Machine start (2-3 s)
⇒ Lamp in the button flashes
⇒ Buzzer sounds
⇒ Machine starts running
⇒ Machine run-up is ended, when the button is illuminated continuously
▫ Data record = 0
▫ Type = DINT
⇒ The rpm of the traverse is changed continually.
The value deviates between 0 and ± 120 RPM
12. Actuate Machine stop
13. Pay attention to the traverse motion
⇒ Traverse remains at home position (Traverse centre)
14. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
Checking the direction of 1. Use the global button to enter Machine engineer (see 3.3.2 Password
rotation system/Code levels, p. 3-7)
2. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
▫ Direction of twist = S
3. Standby ON
4. Actuate Machine start (2-3 s)
⇒ Machine starts running
5. Switch on spindle position 1
6. Spindle motor turns to the left (top view!)
7. Check the rotation direction of capstan Clockwise (viewed from headstock)
8. Check the rotation direction of winding: Clockwise (viewed from
headstock)
9. Actuate Machine stop
10. Wait until all motors stop completely
11. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
▫ Direction of twist = Z
12. Actuate Machine start (2-3 s)
⇒ Machine starts running
13. Switch on spindle position 1
14. Spindle motor turns to the right (top view!)
15. Check the rotation direction of capstan Clockwise (viewed from headstock)
16. Check the rotation direction of winding: Clockwise (viewed from
headstock)
17. Actuate Machine stop
18. Wait until all motors stop completely
19. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
▫ Direction of twist = S
20. Standby OFF
Safety first!
For the connection test the phone number of the modem should be
known!
Checking the 1. Go to menu ServiceÆ DiagnosticsÆ Spindle (see Fig. 8-9, p. 8-101)
spindle status
⇒ The spindle status is shown from bit 0 to F ( = 24 VDC, = 0
2. Spindle stopped
⇒ Bit 0 = 1
3. Press Spindle start
⇒ Bit 1 = 1 (during run-up)
4. After run-up of spindle:
▷ Bit 2 = 1
5. Press Spindle stop
⇒ Bit 3 = 1 (during shutdown)
6. After spindle has stopped:
▷ Bit 0 = 1
Testing the FC outputs 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Go to menu ServiceÆ DiagnosticsÆ Spindle (see Fig. 8-9, p. 8-101)
3. Activate Test outputs
⇒ All outputs are set to 0
4. Test all outputs according to the following table
WARNING
The brake contactor output must only be set for max. 20 sec.
Otherwise the spindle motor may be damaged or destroyed!
▶ Do not remove the spindle pot to run the spindle or for checking the
rotation direction because the bearing will lose its lubricant
5.6.1 Preparation
Settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Make the following settings:
▷ Standby OFF
Making settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Make the following settings:
▫ Direction of twist = Z
8. Actuate Machine start (2-3 s)
9. Switch on spindle positions 18
10. Spindle motors turn to the right (top view!)
11. Actuate Machine stop
12. Wait until all motors stop completely
13. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
▫ Direction of twist = S
▪ All necessary connecting lines are provided (Prior to installing the conveyor
belt, check the polarity of the +24V-supply to the control modules at the
terminal strips X1 in the middle of the section!)
▪ Fix the door switch +L-S106 / +R-S206 during start-up by using a rubber or
the like
NOTE
Interchanged supply lines will destroy the control modules
Supply cable 1. Disconnect all fuses and power switches (see circuit diagram as well):
start-up
▫ Intermediate circuit fuses +L-F124 to F129 / +R-F224 to F229
If there are two or more control modules with the same address in the
machine (e.g. during the initial start-up of the machine or when
replacing a module), the control must be interrupted during the boot
sequence so that the addressing can be done.
⇒ all yellow indicator lights on the control modules for the respective
machine side begin flashing quickly
3. Starting from the headstock, actuate all start buttons on the control
modules one after the other
⇒ The respective indicator light must stop flashing after actuating
⇒ the addressing progress can be viewed on the controller screen
4. On left side of the machine only:
⇒ After addressing last spindle Æ Addressing conveyor belt module
For further error messages see 9.3 Problems with control modules in network,
p. 9-141).
▶ The machine must not be switched off during the software update!
Addressing test 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Select menu item ServiceÆ Start-upÆ Spindle
6.6 Settings
6.6.1 Unit for length counting and yarn count
Length counter and yarn 1. Use the global button to enter Machine engineer (see 3.3.2 Password
count system/Code levels, p. 3-7)
2. Make the following settings in menu AdministrationÆ SettingsÆ Units
Setting the 1. Use the global button to enter Machine engineer (see 3.3.2 Password
shift times system/Code levels, p. 3-7)
2. Select menu item AdministrationÆ Operator interfaceÆ Shift
6.6.3 Material
Setting the material 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Select menu item SettingsÆ YarnÆ Material
3. Set Material
Fig. 6-10: Menu item SettingsÆ YarnÆ Material Selecting preset material
Setting date and time 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. For settings Date / time, go to menu AdminÆ Operator interfaceÆ Date /
Time
Setting the Ethernet 1. Use the global button to enter Machine engineer (see 3.3.2 Password
address system/Code levels, p. 3-7)
2. To set the Ethernet address, go to menu AdminÆ MC-Config.Æ Network
Setting the display 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. To set the display, go to menu AdminÆ Operator interfaceÆ Display
Checking the 1. Go to menu ServiceÆ DiagnosticsÆ Machine status (see 8.3.2, p. 8-98).
machine status
⇒ The machine status is shown from bit 0 to F ( = 24 VDC, = 0
2. Check the status of the machine (Bit0=1, Bit4=1, Bit8=1). all others = 0)
Safety first!
▪ Do not remove the spindle pot to allow the spindle to turn for checking the
rotation direction because the bearing will lose its lubricant
6.9.1 Preparation
Making settings 1. Use the global button to enter Machine engineer (see 3.3.2 Password
system/Code levels, p. 3-7)
2. Make the following settings:
Checking machine 1. Use the global button to enter Machine engineer (see 3.3.2 Password
functions system/Code levels, p. 3-7)
2. Standby ON
⇒ Standby LED illuminated
3. Actuate Machine start (2-3 s)
⇒ Lamp in the button flashes
⇒ Buzzer sounds
⇒ Machine starts running
⇒ Machine run-up is ended, when the button is illuminated continuously
▫ Data record = 0
▫ Type = DINT
⇒ The rpm of the traverse is changed continually.
The value deviates between 0 and ± 120 RPM
12. Actuate Machine stop
13. Pay attention to the traverse motion
⇒ Traverse remains at home position (Traverse centre)
14. Go to menu SettingsÆ YarnÆ Yarn path (see Fig. 3-3, p. 3-8)
For the connection test the phone number of the modem should be
known!
To check the data exchange via modem with the Oerlikon Saurer
Service in Kempten, please send the modem phone number and the
Ethernet addresses of all connected machines to Oerlikon Saurer,
Allma Produktlinie. An Oerlikon Saurer Service technician will then
check the connections to each connected machine.
7 Replacement instructions
NOTE
The following instructions may only be carried out by qualified
personnel
▶ The applicable accident prevention guidelines are to be observed
at all times
▫ 4.10 Testing the saving and loading procedures (with a USB stick), p.
(4-38)
▫ 4.10 Testing the saving and loading procedures (with a USB stick),
p. 4-38)
8 Machine diagnostics
The Allma CC3 is equipped with an extended machine diagnostics programme
that enables quick troubleshooting. Almost all error states that would lead to
the machine shutting down or a spindle position are registered and stored.
8.1 Logbook
The error messages that are generated by the system and the machine are
displayed via the ÆReports > Logbook area.
▪ Machine warnings
The machine can still be operated when a warning is active.
For a complete list of warnings see 9.1.2 Machine warnings, p. 9-124
▪ Spindle warnings
Warnings do not lead to the spindle position being shut off, but should bring
the attention of the operator to a non-critical irregularity
For a complete list of warnings see 9.2.2 Spindle warnings, p. 9-136
▪ System messages
For a complete list see 9.4 System messages, p. 9-144
Use button Active error to switch to a view in which only the active errors are
listed.
Use button Reset error to delete the list (these will remain in the error history
list).
If errors still exist, these are entered into the logbook again as active.
Display of:
Display of:
▪ Yarn tension actual value (average determined via 130 yarn tension
values)
Display of:
▪ Yarn tension actual value (average determined via 130 yarn tension
values)
It is possible to put a spindle position into test operation mode for trouble
shooting.
Bit allocation:
0 = Machine stopped
1 = Machine run-up
2 = Machine in operation
3 = Machine shutting down (in power failure or emergency stop as well!)
4 = Machine start mode SINGLE
5 = Machine start mode COMPLETE
6 = Machine start mode BLOCKDOFF
7 = Tensioning yarns with Blockdoff
8 = Status Button Reset Spindle length counter (1 = yes, 0 = no)
9 = Reset shift counter
A = Power-save mode (1 = active, 0 = off)
B = Power failure (> 1 sec)
C = Power failure (< 1 sec)
D = Parameter change
E = EMERGENCY STOP
F = -----
The states of the digital inputs of frequency converters (FC) are displayed.
▪ FC spindle
0 = Controller enable
1 = Quick stop
2 = Secure stop
3 = Option suction faults
4 = Power pack fuse
5 = Fuse circuit
6 = Fault power supply
7 to 9 Not used
▪ FC traverse motion
0 = Controller enable
1 = Quick stop
2 = Secure stop
3 = Button Standby ON
4 = Button Standby OFF
5 = Reference sensor signal
6 = Temperature contact
7 to 9 Not used
▪ FC winding
0 = Controller enable
1 = Quick stop
2 = Secure stop
3 = Button ON
4 = Fault Pressure controller
5 = Temperature contact
6 = Emergency stop circuit
7 = Main switch ON
8 to 9 Not used
▪ FC capstan
0 = Controller enable
1 = Quick stop
2 = Secure stop
3 = Button OFF
4 = Not used
5 = Temperature contact
6 to 9 Not used
▪ FC spindle
0 = Operating hours counter
1 to 3 Not used
▪ FC traverse motion
0 = Signal lamp Standby
1 = Battery contactor
2 = Conveyor belt contactor
3 Not used
▪ FC winding
0 = Signal lamp Button ON
1 = Signal lamp blue
2 = Signal lamp yellow
3 = Buzzer
▪ FC capstan
0 to 3 Not used
The states of the inputs and outputs of every spindle position are displayed.
Bit allocation:
▪ Spindle status
0 = Spindle stopped
1 = Run up
2 = Spindle in operation
3 = Shutdown spindle
4 = Warning
5 = Spindle was in operation and manually set to status Stopped
6 = Prewarning Doffing
7 = Start refusal
8 = Not used
9 = Button OFF activated
A = Button OFF for a time longer MTR_RESETTIME activated
B = Not used
C = Calibration of CordGuard carried out
D = Not used
E = Not used
F = Module status: Preoperational = 1 / operational = 0
▪ Input byte
0 = Hall sensor
1 to 3 Not used
4 = Button ON
5 = Button OFF
6 and 7 Not used
▪ Output byte
0 = Winding
1 = Motor contactor
2 = Brake contactor
3 = Capstan clutch
4 = Control panel LED GREEN
5 = Control panel LED YELLOW
6 = Control panel LED RED
7 = Control panel LED CAN
8 = Creel yarn tensioner
9 to F Not used
Software versions of the IPCs, control modules and the different drives can be
read out.
Survey
No. Description
No. Description
Description
Possible causes:
▪ Check all emergency switches:
⇒ Error message is displayed and machine is switched off after about 20 sec
Possible causes:
▪ HTL encoder +A-B102/-B202 defective or not correctly adjusted
▪ In the event that the aforementioned causes do not apply, check pulses at
the terminals X210A:6 and X210A:7 of winding converter +L-T102 / +R-
T202 (machine in operation)
⇒ If pulses are measured, replace the frequency converter module
The central control does not detect any pulses for more than 2 seconds when
the machine is running or after actuating Machine ON.
Possible causes:
▪ HTL encoder +A-B102/-B202 defective or not correctly adjusted
▪ In the event that the aforementioned causes do not apply, check pulses at
the terminals X210A:6 and X210A:7 of winding converter +L-T102 / +R-
T202 (machine in operation)
⇒ If pulses are measured, replace the frequency converter module
⇒ Error message appears and machine is switched off after about 20 sec
Possible causes:
▪ HTL encoder +A-B103/-B203 defective or not correctly adjusted
▪ In the event that the aforementioned causes do not apply, check pulses at
the terminals X210A:6 and X210A:7 of capstan converter +L-T103 / +R-
T203 (machine in operation)
⇒ If pulses are measured, replace the frequency converter module
The central control does not detect any pulses for more than 2 seconds when
the machine is running or after actuating Machine ON.
Possible causes:
▪ HTL encoder +A-B103/-B203 defective or not correctly adjusted
▪ In the event that the aforementioned causes do not apply, check pulses at
the terminals X210A:6 and X210A:7 of capstan converter +L-T103 / +R-
T203 (machine in operation)
⇒ If pulses are measured, replace the frequency converter module
Possible causes:
▪ CAN bus line to frequency converter +L-T104 / +R-T204 interrupted.
⇒ Check by using an ohmmeter (pin configuration see circuit diagram)
Possible causes:
▪ CAN bus line to frequency converter +L-T102 / +R-T202 interrupted
⇒ Check by using an ohmmeter (pin configuration see circuit diagram)
Possible causes:
▪ CAN bus line to frequency converter +L-T103 / +R-T203 interrupted
⇒ Check by using an ohmmeter (pin configuration see circuit diagram)
Possible causes:
▪ CAN bus line to frequency converter +L-T101 / +R-T201 interrupted
⇒ Check by using an ohmmeter (pin configuration see circuit diagram)
08 Circuitry 00 Circuitry voltage too low ▪ Producing machine switched off with Main
switch OFF
voltage (24V)
▪ Check output voltage of power supply +L-
G101 to G103 / +R-G201 to G203 (see
4.3.2 Starting up the 24VDC supply, p. 4-
17)
01 Circuitry voltage too high ▪ Check output voltage of power supply +L-
G101 to G103 / +R-G201 to G203 (see
4.3.2 Starting up the 24VDC supply, p. 4-
17)
11 Output 00 Output frequency too Check control signals or contact the Oerlikon
frequency 01 high Saurer Service in Kempten
Max. frequency reached
by control system
12 Safety function 01 Diagnostics error of At least one of the switch-off paths STOA and
STO function STO STOB is faulty
▪ Check wiring
05 Error message of 5s- The switch-off paths STOA and STOB have not
monitoring been switched simultaneously, but with a time
lag of more than 5 sec
⇒ Check activation of switch-off paths or
operation of safety device
23 Number of resolver pairs The ratio from number of motor pole pairs to
is not valid. number of resolver pole pairs must be integer.
Check parameters Number of pole pairs 373 for
the motor and Number of pole pairs 381 for the
resolver and correct if necessary
Possible causes:
▪ Spindle motor overloaded because of heavy material
⇒ Reduce spindle speed
The temperature should not exceed 40°C. If the temperature reaches approx.
45 °C, the prewarning W04 to W07 is shown. In case of a further temperature
rise (approx. 50 °C), the machine is switched off.
Possible causes:
▪ Temperature sensor defective
Possible causes:
▪ Check fan +M-M104/-204 for function
Possible causes:
▪ Frequency converter overloaded
▪ Setpoint not reached or frequency converter does not show the bit
"Setpoint reached" (monitoring time exceeded)
Possible causes:
see E07
Possible causes:
▪ Failure IPC+L-A1
Possible causes:
See E08
Possible causes:
See E09
Possible causes:
▪ Reference switch defective (wire break?) or wrongly adjusted
⇒ Required distance of pulse generator +L-B104 / +R-B2042.0 ± 0.5 mm
Possible causes:
See E10
Possible causes:
Malfunction IPC +L-A1 Contact Oerlikon Saurer Service in Kempten and inform
them of the displayed CODE!
Possible causes:
▪ Drive belt of traverse gear defective
If the problem persists for more than 15 min, the machine is switched off.
Possible causes:
▪ Motor too hot. Temperature contact has tripped.
If the problem persists for more than 15 min, the machine is switched off.
Possible causes:
▪ Motor too hot. Temperature contact has tripped
Possible causes:
Pressure switch has tripped. Compressed air is still < 5 bar after the set time.
If the problem persists for more than 15 min, the machine is switched off.
Possible causes:
▪ Motor too hot Temperature sensor has tripped
Survey
No. Description
Description
Check LEDs of power supplies and replace the respective power supply during
the next machine stop or correct the fault in order to avoid a permanent
overload of the still functioning power supplies.
Possible causes:
The signalling circuit 1 (see circuit diagram) must be closed for a proper
function of the machine.
Possible causes:
▪ Fuse or switch has tripped.
⇒ Only when the cause of the tripped fuse (e.g. short-circuit) has been
removed, may the circuit be closed again.
The frequency converter +L-T104 / +R-T204 regularly informs the control of the
total power consumption. This value is divided by the number of running
spindles. Thus the control obtains an average value of the power consumption
per spindle.
If this value is higher than the max. allowable current value plus 3 % tolerance,
this error message appears.
The user can reduce the spindle rpm of the respective machine side, thus
reducing the total power consumption.
If the current value is not within the set limits within 3 minutes, the machine is
switched off with error message E16.
Possible causes:
▪ Cooling unit +L-E102 / +R-E202 failed
Possible causes:
▪ Fan of power section FC Spindles .+L-T104 / +R-T204 defective
Possible causes:
Software error. Please contact Oerlikon Saurer Service in Kempten!
Possible causes:
Possible causes:
▪ Motor too hot. Temperature contact has tripped
Possible causes:
▪ Motor too hot. Temperature contact has tripped
Possible causes:
Pressure switch has tripped
Æ The air pressure must be min. 5 bar
Possible causes:
▪ Cooling unit +L-K110 defective
Survey
No. Description
S02 ----
S03 ----
S04 ----
No. Description
S14 ----
S23 24V-monitoring
Description
S05:
Tolerance window Switch-Off 1 (tolerance + measuring time) from SettingsÆ
CordGuard (selflearning function) exceeded.
S06:
Tolerance window Switch-Off 1 (tolerance + measuring time) from SettingsÆ
CordGuard (selflearning function) not reached.
S07:
Tolerance window Switch-Off 2 (tolerance + measuring time) from SettingsÆ
CordGuard (selflearning function) exceeded.
S08:
Tolerance window Switch-Off 2 (tolerance + measuring time) from SettingsÆ
CordGuard (selflearning function) not reached.
Possible causes:
▪ Unwinding troubles of spindle or creel yarn
▪ Yarn break
S09:
Tolerance window (tolerance + measuring time) from SettingsÆ CordGuard
(manual) exceeded.
S10:
Tolerance window (tolerance + measuring time) from SettingsÆ CordGuard
(manual) not reached.
Possible causes:
▪ Unwinding troubles of spindle or creel yarn
▪ Yarn break
Possible causes:
▪ Wrongly adjusted spindle yarn tensioner
Possible causes:
▪ Unwinding troubles of spindle or creel yarn
▪ Yarn break
Possible causes:
▪ Unwinding troubles of spindle or creel yarn
▪ Yarn break
Possible causes:
▪ Motor +Fx-M1…3 overloaded
Possible causes:
▪ Overload because spindle rpm are too high (reduce speed until motor is no
longer overloaded)
Possible causes:
▪ Power switch +Fx-Q1 has tripped
Possible causes:
▪ Defective operating unit+Fx-A1
Then the machine can be switched off by means of the main switch. When the
machine is switched on again, the machine variables in the operating unit are
checked.
In case an error is found, the above message appears. The operating unit is
reset and the default setting is loaded (length counter = 0, spindle state to
Spindle stopped).
Possible causes:
▪ Machine variables could not be completely saved (e.g. short-circuit in
24VDC mains)
Possible causes:
▪ Brake defective.
Possible causes:
▪ Operating unit +Fx-A1 defective.
It is a start refusal when after pressing Spindle start the red LED lights up once
and the spindle does not start.
Survey
No. Description
B02 ----
B06 ----
B07 ----
B09 24V-monitoring
Description
In case this is not obtained within approx. 0.5 sec, the above start refusal
cause appears.
Start is disabled if more than 3 spindle positions are put in operation at the
same time within 10sec, in order to avoid overload of spindle frequency
converter.
After approx. 10 min. waiting time, the spindle position can be started again.
Æ Actuate control module +Fx-A1 to reset (press spindle stop for 3 sec b) or
replace module.
Survey
No. Description
Description
If the spindle rpm rise above or fall below this tolerance limit, the above
warning appears.
Survey
OFF
Lit up permanently
Description
States
Table 9-9: Blink codes
permanently
No. Description
The control modules communicate with the control +L-A1 via CAN bus.
If a network error has been detected (e.g. during the boot process or during
operation), the respective control module is no longer addressed by the control
and a respective message is generated.
Possible causes:
▪ Control module +Fx-A1 is missing
Possible causes:
▪ Control module +Fx-A1 is defective
Possible causes:
Control module +Fx-A1 is defective
Possible causes:
▪ Control module +Fx-A1 is defective
Possible causes:
▪ Control module +Fx-A1 is defective
No. Description
M1 ---
M2 System initialising
M3 … 6 ---
M7 Battery empty
9.4.2 Description
M2 SYSTEM INITIALISING
Is shown every time the IPC has booted.
M7 BATTERY EMPTY
The IPC is equipped with a lithium coin cell. This message appears when the
coin cell is empty.
10 Service
Sales of original parts
Oerlikon Saurer
Allma Product Line
Zweigniederlassung der Oerlikon Textile GmbH & Co. KG
Leonhardstraße 19
87437 Kempten/Allgäu
Germany
If you need a service fitter, please inform us of this requirement. He will then
visit you without you having to wait too long.
After-Sales Service
Oerlikon Saurer
Allma Product Line
Zweigniederlassung der Oerlikon Textile GmbH & Co. KG
Leonhardstraße 19
87437 Kempten/Allgäu
Germany
You should keep original parts and wearing parts which cannot be
supplied quickly in storage on site.
The original parts catalogue provided by Oerlikon Saurer, Allma Product Line
will assist in repair work since it contains diagrams for localising the machine
parts to be replaced.
Orders
▫ volume needed
When using SECOS, you can order all the original parts you need for your
machine as quickly as possible. The parts will be delivered quickly.
Once installed, you can order original parts straight away from the Internet.
If you are interested in SECOS, then simply register for the package at
www.secos.myoerlikon.com.