D1204 USER MANUAL Jolin

The document provides a user manual for an EEDS238-2 ZN/S(D1204) type multi-function energy meter. The meter measures single phase AC active energy and variable parameters in compliance with IEC standards. It has advantages of high stability, overload capability, low power loss, and small volume. The meter displays measurements including voltage, current, power, power factor, frequency, and energy consumption in kWh. It has an RS485 communication port supporting MODBUS protocol to retrieve register data including total energy, import/export energy, and real-time measurements.

Uploaded by

Haytham Aldamen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views5 pages

D1204 USER MANUAL Jolin

The document provides a user manual for an EEDS238-2 ZN/S(D1204) type multi-function energy meter. The meter measures single phase AC active energy and variable parameters in compliance with IEC standards. It has advantages of high stability, overload capability, low power loss, and small volume. The meter displays measurements including voltage, current, power, power factor, frequency, and energy consumption in kWh. It has an RS485 communication port supporting MODBUS protocol to retrieve register data including total energy, import/export energy, and real-time measurements.

Uploaded by

Haytham Aldamen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

USER’S MANUAL

1. General Description
EEDS238-2 ZN/S(D1204) type multi-function energy meter is designed to measure single
phase two wire AC active energy and variable parameter. All of its functions comply with the
relative technical requirement for class 1 single phase watt hour meter in IEC62053-21 and its
data communication rules obey the requirement of DL/T645 or MODBUS-RTU. It is a long life
meter with the advantage of high stability, high over load capability, low power loss and small
volume.
The meter should be installed in suitable environment with ambient temperature range between
-25℃ ~ +55℃ , the relative humidity less than 75% and temperature limits between-
40℃ ~+70 ℃.
The meter is manufactured complying with international standard IEC62052-11 on “Electricity
metering equipment (AC) General requirements tests and test conditions” and IEC62053-21 on
“Static meters for active energy (classes 1 and 2)”.

2. Specification and Technical Parameters


2.1 Specification
Meter type EEDS238-2 ZN/S
Rate frequency 50 or 60 Hz
Rated current 5(65)A 10(100)A
Rate voltage 120V / 220V / 230V /240V
Normal voltage range 90%Un~110%Un
Limits voltage range 70%Un~120%Un
Accuracy Class 1
Pulse constant See meter
RS485 port MODBUS-RTU protocol, 1200 ~ 9600bps,None
parity, default 9600bps

2.2 Technical Parameters


2.2.1 Basic tolerance
Load current(A) Power factor Basic error(%)
(CosΦ) 1.0 class 2.0 class
0.05Ib 1.0 +1.5 +2.5
0.1Ib—Imax 1.0 +1.0 +2.0

0.1Ib 0.5(lag) +1.5 +2.5


0.8(advanced) +1.5
02Ib—Imax 0.5(lag) +1.0 +2.0
0.8(advanced) +1.0

2.2.2 Self-consumption
Current circuit is less than 1.5VA
Voltage circuit is less than 1W/5VA
2.2.3 Starting current
Under the rated voltage, rated frequency and COSΦ=1, the meter shall start and continue to
register on application of 0.2% In (if CT is used) or 0.4% Ib.
2.2.4 Anti-creeping
The meter has anti-creeping logical circuit. When 115%Un is connected to the meter and
current circuit is cut, the meter shall not create more than one pulse in a stipulated time
2.2.5 Average-life
The meter can be used for at least 10 years in normal operation specified in this manual
2.2.6 LCD: 5+1 (99999.9 kWh)

3. Basic Features
3.1 Measuring positive & negative active energy with negative energy accumulated into positive
energy, LCD display with backlight.
3.2 The meter also display three phase real voltage, real current, real active power, real power
factor, real frequency.
3.3 Pulse LED indicates working of meter , Pulse output with optical coupling isolation
18~27V 27mA .
3.4 RS485 communication port.
3.5 Measuring active energy without calibration under long term operation.
3.6 display step by step with button.

4. Working principles
Single phase voltage and current are sampled from respective sampling circuit and
transformed into suitable signal, which is carried into integrated circuit, then the meter output
pulse signal in positive appropriation to measured power to drive step-motor counter or LCD
counter to realize energy measurement. The meter has energy pulse output for testing with
pulse width of 80+20ms

Diagram for Working Principles

5. Structure
The meter consists of meter base, meter cover, terminal base, terminal cover. there are lead
seal on meter cover and terminal cover. A special screw is used to fix the terminal cover on
which a lead seal can be installed.
6. Usage
6.1 Connection diagram

Note: If reverse wire connection as photo 2, the total energy still can measure.

6.2 Installation
The meter can be installed on a 35 mm DIN rail
6.2.1 The meter can not installed and used until it is checked goods and sealed before delivery
6.2.2 The meter should be install in the water proof box indoor or outdoor. the meter’s box
should be fixed on strong and flame-resistant wall with a recommended height of about 1.8 m,
where there is no corrosive gas around.
6.2.3 The meter should be install fully in accordance with connection diagram on the terminal
cover, it is better to use copper as the leading wire for connection. All screws should be
tightened.
6.2.4 Diagram for installation dimension

7. Transportation and Storage


7.1 Heavy impact should be burdened to the products while transportation and unpacking.
7.2 The products should be stored in the original package and kept in place with temperature
between -40℃ ~+70℃ the relative humidity less than 75% and no corrosive gas around.
7.3 In storehouse, the meter should be placed on the shelf when kept in stock, there should not
be more than 7 cartons piled up in vertical. Single-packed meters can not be piled up with more
than 5 meters in vertical.

8. Warranty period
Within 24 months from the day of selling and provided that users operate correctly
according to the requirement of the user’s manual, if the meter doesn’t reach its technical
specification. It can be repaired or replaced in free of charge by the manufacturer.

9. Frame format
9.1 Read command(function code 03)
Send frame
Meter ID Function code Register address Data number Check code (CRC)
1byte 1byte 2byte 2byte 2byte

Receive frame
Meter ID Function code Data length n Data area Check code (CRC)
1byte 1byte 1byte n byte 2byte

9.2 Write command(function code 10)


Send frame
Function Register Data Data Check code
Meter ID Data length n
code address number area (CRC)
1byte 1byte 2byte 2byte 1byte n byte 2byte

Receive frame
Meter ID Function code Register address Data number Check code (CRC)
1byte 1byte 2byte 2byte 2byte

9.3 Energy meter register address


Register Data number Data item Data format Data unit
address
0x0000
2 Total kWh XXXXXX.XX kWh
0x0001
0x0008
2 Export kWh XXXXXX.XX kWh
0x0009
0x000A
2 Import kWh XXXXXX.XX kWh
0x000B
0x000C 1 Voltage XXX.X V
0x000D 1 Current XX.XX A
0x000E 1 Active power XXX.XXX kW
0x0010 1 Power factor X.XXX
0x0011 1 frequency XX.XX Hz
First byte is ID No.,the second byte is
0x0015 1 ID + baud rate baud rate,01~04 is means Respectively
9600、4800、2400、1200、
Note 1: one register address is store 2 byte data, so the data length read as 4 byte when
data number is 2.
Note 2::you can use ID ID(0x00) to broadcast and got data when you do not know the meter
ID. But this ways is only for 1 pcs meter to connection on RS485 wire

10. Display item


INFORMATION LCD DISPLAY
01 Meter ID ID 001 ★
02 Real voltage V U 000.0 ★
03 Real current A A 00.00 ★
04 Real power W P 0.0 ★
05 Power factor COSФ PF 0.00 ★
06 Real frequency Hz F 00.00 ★
07 Total energy kWh T00 00000.0 ★
08 Positive kWh T00-00000 ☆
09 Reverse kWh T00-00000 ☆
10 Reset energy EP000000 ☆
Note: ★ Standard function,☆ special order function (It will reset energy to zero, after you
pull the button last 10s,if you have order reset function)