SPR3 Series
• Product ×1 • Insulating barrier ×4 It is recommended to use the included interphase barriers for insulation between Model SPR3-1▭ SPR3-2▭ SPR3-3▭ SPR3-4▭
• 11-pin connector ×1 phases and reduce influence from conductive material. Control phase 3-Phase
• Unit: mm, For the detailed drawings, • With the insulating barrier
INSTRUCTION MANUAL
110 VACᜠ 50 / 220 VACᜠ 50 / 380 VACᜠ 50 / 440 VACᜠ 50 /
Rated load voltage
follow the Autonics website. A 60 Hz 60 Hz 60 Hz 60 Hz
Manual Rated load current Rated load current 25 / 35 / 50 / 70 / 100 / 150 A
B
For the detailed information about communication, etc., please refer to the manuals, Display method 3 digit 7segment LED
2.5
and be sure to follow cautions written in the technical descriptions. Indicators
Operation / manual control indicator (green)
Alarm / output / unit (V, A) indicator (red)
3.8
Visit Autonics website to download manuals.
DRW180136AE 55 DC 4 - 20 mA, 1 - 5 VDCᜡ, ON / OFF contact (non-voltage input), pulse
Auto control input
voltage (5 - 12 VDCᜡ)
1.5
C
DAQMaster Manual control input External adjuster (10 kΩ), internal adjuster (output limit)
Digital input (DI) RUN / STOP selectable, AUTO / MAN selectable, RESET
42.5
Thank you for choosing our Autonics product. • DAQMaster is comprehensive device management program. It is available for
40
Alarm output 250 VACᜠ 3 A, 30 VDCᜡ 3 A, 1c resistance load
Read and understand the instruction manual and manual thoroughly before parameter setting, monitoring. RS485 comm. output Modbus RTU method
• Visit Autonics website to download the manual and the program.
using the product. Rated load current 25 / 35 / 50 A: natural cooling
Rated load current A B C Cooling method
For your safety, read and follow the below safety considerations before using. Rated load current 70 / 100 / 150 A: forced air cooling (with cooling fan)
25 / 35 / 50 A 30 28.2 300 Rated load current 25 / 35 / 50 A: ≈ 4.1 kg (≈ 4.9 kg)
For your safety, read and follow the considerations written in the instruction
Ordering Information 70 A 30 28.2 300
Unit weight
(packaged)
Rated load current 70 A: ≈ 4.2 kg (≈ 5 kg)
manual, other manuals and Autonics website. Rated load current 100 / 150 A: ≈ 8.7 kg (≈ 9.7 kg)
100 / 150 A 40.5 50 370
Keep this instruction manual in a place where you can find easily. This is only for reference. Approval ᜢ
The specifications, dimensions, etc. are subject to change without notice for product For selecting the specified model, follow the Autonics website.
improvement. Some models may be discontinued without notice. Control method Phase control Cycle control ON/OFF control
Follow Autonics website for the latest information. SPR 3 - ❶ ❷ ❸ ❹ ❺ Cautions during Installation Normal /
constant current feedback /
Control mode Fixed cycle -
constant voltage feedback /
❶ Rated load voltage ❹ Feedback control High Temperature Caution constant power feedback
Safety Considerations 1: 110 VACᜠ
2: 220 VACᜠ
N: Normal control
F: Normal, feedback control (constant
While supplying power to the load or right after turning off the power of the load, Applied load
Resistance load,
Resistance load
Resistance load,
do not touch the body and heatsink. inductive load inductive load
3: 380 VACᜠ current / constant voltage / constant Failure to follow this instruction may result in a burn due to the high temperature. Output range 0 to 98% 0 to 100% 0 / 100%
• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
4: 440 VACᜠ power) Normal control: within ± 10% F.S. of rated load voltage
• symbol indicates caution due to special circumstances in which hazards may occur.
❷ Rated load current ❺ Fuse ■ Mount space 4-Ø6 Panel
Phase control Constant current feedback control: within ± 3% F.S. of rated load current
output accuracy Constant voltage feedback control: within ± 3% F.S. of rated load voltage
Number: Rated load current (unit: A) N: None
Warning
100
Failure to follow instructions may result in serious injury or death. • When installing multiple power controllers, Constant power feedback control: within ± 3% F.S. of rated load power
F: Supports fuse
keep space between power controllers for heat
❸ Option output Power supply 100 - 240 VACᜠ ±10% 50 / 60 Hz
01. Fail-safe device must be installed when using the unit with machinery that N: Alarm output radiation.
may cause serious injury or substantial economic loss.(e.g. nuclear power Min. load current 1A
T: A
larm output + RS485 comm. output Horizontal: ≥ 50 mm, vertical: ≥ 100 mm
control, medical equipment, ships, vehicles, railways, aircraft, combustion Rated load current 25 / 35 / 50 A: ≤ 14 VA
Power
apparatus, safety equipment, crime / disaster prevention devices, etc.) 50 Rated load current 70 A: ≤ 22 VA
consumption
Failure to follow this instruction may result in personal injury, economic loss or fire. Rated load current 100 / 150 A: ≤ 32 VA
100
02. Do not use the unit in the place where flammable / explosive / corrosive gas, Dimensions Insulation
≥ 200 MΩ (500 VDCᜡ megger)
high humidity, direct sunlight, radiant heat, vibration, impact or salinity may resistance
be present. • Unit: mm, For the detailed drawings, follow the Autonics website.
Dielectric strength 2,000 VACᜠ 50 / 60 Hz for 1 min (between input and power terminal)
Failure to follow this instruction may result in explosion or fire. ■ Rated load current 25 / 35 / 50 A Unit Descriptions Output leakage
03. Install on the device panel, and ground to the bolt for grounding separately. ≤ 10 mArms
105 currents
Failure to follow this instruction may result in fire or electric shock. 92.2 261 Noise immunity ±2 kV the square wave noise (pulse width: 1 ㎲) by the noise simulator
04. Do not connect, repair, or inspect the unit while connected to a power source. 68 4-Ø6 203.1
Memory retention ≈ 10 years (when using non-volatile semiconductor memory type)
Failure to follow this instruction may result in fire or electric shock.
6.8
05. Check ‘Connections’ before wiring. 10 0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction
Vibration
21.8
80
227
200
09
• Use the product, after 3 sec of supplying power. Indicator Function Stop bit 1-bit, 2-bit
• Before use, set the mode and function according to the specification. Especially, RUN Operation indicator (green) Turns on in the RUN mode.
be cautious that the product does not operate when OUT ADJ. is set to 0%. Since Turns on when adjusting load output in
MAN Manual control indicator (green)
changing the mode / parameter during operation may result in malfunction, set the
Load Output Formula
the manual control mode.
mode and function after disconnecting load output. ALM Alarm indicator (red) Flashes in alarming status.
25
• Re-supply the power to the unit after the unit is discharged completely. Failure to OUT Output indicator (red) Turns on when load control outputs.
follow this instruction may result in malfunction. Type Input Formula
• To ensure the reliability of the product, install the product on the panel or metal ■ Rated load current 100 / 150 A 03. Display part Current DC 4 - 20 mA Load output [%]
surface vertically to the ground. 170 RUN mode: Displays depending the front display setting Auto
158 326.5 Voltage 1 - 5 VDCᜡ = Control input [%] × output slope [%]
• Install the unit in the well ventilated place. Setting mode: Displays parameter and setting value (AUTO)
• While supplying power to the load or right after turning off the power of the load, do 140 4 - Ø 6.5 233.2
04. Unit indicator (V, A) 07. Output limit adjuster (OUT ADJ) RS485 communication Load output [%] = RS485 [%]
not touch the body and heat sink. Failure to follow this instruction may result in a burn Dependent on the display setting. Limits output from 0 to 100%. Internal adjuster Load output [%] = internal adjuster [%]
due to the high temperature. 08. Control input /
30
• Install a power switch or circuit breaker in the easily accessible place for supplying or Display setting V A Manual Output External adjuster Load output [%] = external adjuster [%]
Resistance and input OFF OFF comm. output terminal (MAN) limit
disconnecting the power. Internal / external Load output [%]
(11-pin connector terminal)
• Do not wire to terminals which are not used. Voltage ON OFF adjuster = internal adjuster [%] × External adjuster [%]
• Since inter element can be damaged when using with coil load, inductive load, etc., 09. Terminal protection cover
80 Current OFF ON
the inrush current must be under the rated load current. 10. R, S, T load input terminal
Power ON ON 11. Alarm output / power input terminal
• Do not use near the equipment which generates strong magnetic force or high 80
270
210
■C
ontrol input / comm. ■ Load input / output terminal P1-2 SOFT UP time U-T 3 0 to 100 sec
on priority.
output terminal
P1-3 SOFT DOWN time D-T 3
Output low-limit
(11-pin connector) Operation P1-4
value
L-L 0
Priority Type Display Alarm release Model 0 ≤ L-L ≤ H-L ≤ 100 %
①
Alarm Output Output high-limit
P1-5
Noise filter01) 1 SCR error Feedback control value
H-L 100
②
SCR
VR • Error 0 to 100%
Over • Re-supply
Rapid 2 Feedback control • In case of auto control (AUTO), set the output
③ current
O-C display power. P1-6 Output slope
01)
≤ 3.5 [MODE] → Monitoring group [MODE] 3 sec → Over current alarm [Feedback control model]
P2-8
delay time 0 to 100 sec
Derating Curve
OCT 5
≤ 1.5
[MODE] 2 sec → Parameter 1 group [MODE] 3 sec → Over voltage alarm [Feedback control model]
P2-9
value
■ Rated load current 25 A ■ Rated load current 35 A
0 to 120%
■ Alarm output / power input & R, S, U load output terminal
OVV 120
■ Monitoring group
01) Set the below parameters available depends on the control input.