TUNU FIELD
DEVELOPMENT PROJECT
PHASE 8
TURBOCOMPRESSOR TRAIN A
PRE-COOLERS
OPERATIONAL TEST PROCEDURE
SUB-SYSTEM 6004
00 18/02/02 D.P / C.H For Comment
REV DATE ORIGINATOR DESCRIPTION APPROVED
CHECKED BY CSL
. BY START-UP
TOTAL OR PARTIAL REPRODUCTION AND/OR UTILISATION OF THIS DOCUMENT ARE
FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE COMPANY
TOTALFINAELF E&P INDONESIE
COMMISSIONING
DOCUMENT NUMBER REVISION
COM OTP NCP 6004 01 00 PAGE : 1 OF 11
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 2 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
SUMMARY
There are 4 Gas Compressor Pre-Coolers per train tagged 5-A 0160
A/B/C/D (Train A) and 5-A 0170 A/B/C/D (Train B).
They are of the air-cooled forced draft design.
Each cooler can be stopped or started independently of each other, either
by local or remote signals, and all are equipped with independent
vibration switches
P&ID Reference : NCP-12-1-013-C Rev D
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 3 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
1 TEST SUMMARY
1.1 AIMS OF OPERATIONAL TEST
The object of this OTP is to prove the start / stop logic of the
Compressor Pre-Cooler Train A, No 5-A 0160 to the PCS and
Electrical MCC’s.
To ensure fans stop when the vibration protection switches are activated
1.2 TEST DESCRIPTION
To check that the equipment has been correctly installed and
prepared for commissioning in accordance with the vendors’
instruction.
Prepare the test for checking function of the Fans.
1.3 TEMPORARY INSTALLATIONS
None
1.4 SPECIAL PRECAUTIONS
Refer to Safe Operating Procedures.
Check that the Permit for the work is in force.
Check that all warning / precaution signs are in place.
Check that all non-essential personnel have been cleared from the
area.
Ask the Control Room for a PA announcement to be made.
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 4 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
2 PLANNING AND MANPOWER
2.1 PLANNING TASKS
Complete the OTP test in one (1) day
2.2 MANPOWER ESTIMATE
Mechanical 1
Electrical 1
Start-up 1
2.3 TEST DURATION ESTIMATE
1 day
2.4 POSITION IN COMMISSIONNIG SEQUENCE
After RFC is signed
2.5 VENDOR ASSISTANCE
None
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 5 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
3 TEST REQUIREMENTS
3.1 PRECOMMISSIONING ACHIEVEMENTS
Verify that the Pre-Commissioning is completed.
RFC is signed.
No Level A punch list items are pending.
Preliminary check by disciplines to verify the Gas Pre-Cooler package for
completeness in accordance with the latest drawings and revisions.
This includes relevant specifications and P&ID’s.
Produce a punch list as applicable
E&I function tests are complete.
Hydro-test is completed and that all spades are removed
Check that shipping lugs and locks have been removed from bundles ends
3.2 COMMISSIONING ACHIEVEMENTS
Verify that the Commissioning Dossiers is completed.
RFC is signed.
OTP agreed upon and signed
3.3 STATUS OF OTHER SUBSYSTEMS
7403 PCS ready
7401 ESD ready
7305/6 Normal power distribution 400V ready
3.4 SPECIAL TOOL AND TEST EQUIPMENT
None
3.5 CONSUMABLES
None
3.6 SPARES
As per commissioning spares list
3.7 SAFETY
Refer to Safe Operating Procedures.
Check that the Permit for the work is in force.
Check that all warning / precaution signs are in place.
Check that all non-essential personnel have been cleared from the area.
Ask the Control Room for a PA announcement to be made.
3.8 UTILITIES
None
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 6 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
4 TEST PREPARATION
4.1 BLIND LIST
None
4.2 JUMPERS LIST
None
4.3 MECHANICAL PREPARATION TASKS
To provide assistance with the test
To ensure all grease connections are available and grease lines are full
To control that the shipping lugs and locks have been removed
To check belt, pulleys, guards installation
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 7 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
5 START-UP, TUNING & PROCEDURE
5.1 START-UP STEP-BY-STEP PROCEDURE
DEMONSTRATION OF GAS COMPRESSOR PRE-COOLER TRAIN A,
Tags 5-A- 0160A/B/C/D
Fan Control for 5 - A 0160 A
1 Inform control room of intention to run Pre-Cooler 5-A 0160 A
2 Push in STOP Button PB 0160 A2
3 Check that the Pre-Cooler Fan 5-A 0160 A cannot be started from
the local START button PB 0160 A1
4 Check that the FAULT alarm XA 0160 A1 is seen on PCS
5 Reset the local STOP button PB0160 A2 Check that the FAULT
alarm XA 0160 A1 is cleared
6 Check that STOP indication XL 0160 A2 is shown on the PCS.
7 Start the Pre-Cooler Fan 5-A 0160 A from the local START
PB 0160 A1 Check that the Pre-Cooler Fan starts OK.
8 Check that RUN indication XL 0160 A2 is shown on the PCS.
9 Check the Fan is rotating in the correct direction. Check the Fan
condition for a few minutes, while checking the fan blades tip
clearance with housing.
10 Simulate an Electrical Fault (over current) on the Pre-Cooler Fan
5-A 0160 A Motor. Check that the Fan stops.
11 Check that the FAULT alarm XA0160 A1 is on PCS
12 Reset the motor trip and restart the Fan.
13 Stop Cooling Fan using the local STOP Push Button PB0160 A2.
When Cooling Fan has stopped reset the STOP push button.
14 Start the pre-cooler Fan 5-A 0160 A using the local Push Button
PB0160 A1. Simulate a vibration by hammering the structure
supporting the cooler until the VSHH 0161 A trips
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 8 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
15 The motor should be stopped.
Check that the VSHH 0161 A alarm is seen on
Check locally that the motor is stopped. Reset the motor trip.
16 Select REMOTE mode on local switch HS-0160 A1
17 Verify that XL-0160 A1 shows Remote position
18 Start Fan from PCS PB-0160 A3
19 Ensure RUNNING indication is on XL-0160 A2
20 Stop fan from PCS PB-0160 A4
Demonstration of Fan Control for 5 - A 0160 A is now complete
Fan Control for 5 - A 0160 B
1 Inform control room of intention to run Pre-Cooler 5-A 0160 B
2 Push in STOP Button PB 0160 B2
3 Check that the Pre-Cooler Fan 5-A 0160 B cannot be started from
the local START button PB 0160 B1
4 Check that the FAULT alarm XA 0160 B1 is seen on PCS
5 Reset the local STOP button PB0160 B2 Check that the FAULT
alarm XA 0160 B1 is cleared
6 Check that STOP indication XL 0160 B2 is shown on the PCS.
7 Start the Pre-Cooler Fan 5-A 0160 B from the local START
PB 0160 B1 Check that the Pre-Cooler Fan starts OK.
8 Check that RUN indication XL 0160 B2 is shown on the PCS.
9 Check the Fan is rotating in the correct direction. Check the Fan
condition for a few minutes, while checking the fan blades tip
clearance with housing.
10 Simulate an Electrical Fault (over current) on the Pre-Cooler Fan
5-A 0160 B Motor. Check that the Fan stops.
11 Check that the FAULT alarm XA0160 B1 is on PCS
12 Reset the motor trip and restart the Fan.
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 9 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
13 Stop Cooling Fan using the local STOP Push Button PB0160 B2.
When Cooling Fan has stopped reset the STOP push button.
14 Start the pre-cooler Fan 5-A 0160 B using the local Push Button
PB0160 B1. Simulate a vibration by hammering the structure
supporting the cooler until the VSHH 0161 B trips
15 The motor should be stopped.
Check that the VSHH 0161 B alarm is seen on
Check locally that the motor is stopped. Reset the motor trip.
16 Select REMOTE mode on local switch HS-0160 B1
17 Verify that XL-0160 B1 shows Remote position
18 Start Fan from PCS PB-0160 B3
19 Ensure RUNNING indication is on XL-0160 B2
20 Stop fan from PCS PB-0160 B4
Demonstration of Fan Control for 5 - A 0160 B is now complete
Fan Control for 4 - A 0160 C
1 Inform control room of intention to run Pre-Cooler 5-A 0160 C
2 Push in STOP Button PB 0160 C2
3 Check that the Pre-Cooler Fan 5-A 0160 C cannot be started from
the local START button PB 0160 C1
4 Check that the FAULT alarm XA 0160 C1 is seen on PCS
5 Reset the local STOP button PB0160 C2 Check that the FAULT
alarm XA 0160 C1 is cleared
6 Check that STOP indication XL 0160 C2 is shown on the PCS.
7 Start the Pre-Cooler Fan 5-A 0160 C from the local START
PB 0160 C1 Check that the Pre-Cooler Fan starts OK.
8 Check that RUN indication XL 0160 C2 is shown on the PCS.
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 10 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
9 Check the Fan is rotating in the correct direction. Check the Fan
condition for a few minutes, while checking the fan blades tip
clearance with housing.
10 Simulate an Electrical Fault (over current) on the Pre-Cooler Fan
5-A 0160 C Motor. Check that the Fan stops.
11 Check that the FAULT alarm XA0160 C1 is on PCS
12 Reset the motor trip and restart the Fan.
13 Stop Cooling Fan using the local STOP Push Button PB0160 C2.
When Cooling Fan has stopped reset the STOP push button.
14 Start the pre-cooler Fan 5-A 0160 C using the local Push Button
PB0160 C1. Simulate a vibration by hammering the structure
supporting the cooler until the VSHH 0161 C trips
15 The motor should be stopped.
Check that the VSHH 0161 C alarm is seen on
Check locally that the motor is stopped. Reset the motor trip.
16 Select REMOTE mode on local switch HS-0160 C1
17 Verify that XL-0160 C1 shows Remote position
18 Start Fan from PCS PB-0160 C3
19 Ensure RUNNING indication is on XL-0160 C2
20 Stop fan from PCS PB-0160 C4
Demonstration of Fan Control for 5 - A 0160 C is now complete
Fan Control for 4 - A 0160 D
1 Inform control room of intention to run Pre-Cooler 5-A 0160 D
2 Push in STOP Button PB 0160 D2
3 Check that the Pre-Cooler Fan 5-A 0160 D cannot be started from
the local START button PB 0160 D1
4 Check that the FAULT alarm XA 0160 D1 is seen on PCS
5 Reset the local STOP button PB0160 D2 Check that the FAULT
alarm XA 0160 D1 is cleared
/conversion/tmp/activity_task_scratch/637390635.doc
TOTALFINAELF OPERATIONAL TEST PROCEDURE TUNU 8
SUB-SYS: 6004 DESCR: Pre Coolers Train A LOCATION : NCP PAGE : 11 OF 11
DATE NAME AND
STEP TASK DESCRIPTION COMPLETED SIGNATURE
6 Check that STOP indication XL 0160 D2 is shown on the PCS.
7 Start the Pre-Cooler Fan 5-A 0160 D from the local START
PB 0160 D1 Check that the Pre-Cooler Fan starts OK.
8 Check that RUN indication XL 0160 D2 is shown on the PCS.
9 Check the Fan is rotating in the correct direction. Check the Fan
condition for a few minutes, while checking the fan blades tip
clearance with housing.
10 Simulate an Electrical Fault (over current) on the Pre-Cooler Fan
5-A 0160 D Motor. Check that the Fan stops.
11 Check that the FAULT alarm XA0160 D1 is on PCS
12 Reset the motor trip and restart the Fan.
13 Stop Cooling Fan using the local STOP Push Button PB0160 D2.
When Cooling Fan has stopped reset the STOP push button.
14 Start the pre-cooler Fan 5-A 0160 D using the local Push Button
PB0160 D1. Simulate a vibration by hammering the structure
supporting the cooler until the VSHH 0161 D trips
15 The motor should be stopped.
Check that the VSHH 0161 D alarm is seen on
Check locally that the motor is stopped. Reset the motor trip.
16 Select REMOTE mode on local switch HS-0160 D1
17 Verify that XL-0160 D1 shows Remote position
18 Start Fan from PCS PB-0160 D3
19 Ensure RUNNING indication is on XL-0160 D2
20 Stop fan from PCS PB-0160 D4
Demonstration of Fan Control for 5 - A 0160 D is no w complete