Lab Manual Switchgear and Protection Sap
Lab Manual Switchgear and Protection Sap
Apparatus required:
Voltmeter, Ammeter, Loading CT, Auto Transformer, Instantaneous relay, Time rotary switch
etc.
Features:
Application:
The relay type CAG 17 relay is a highest instantaneous over current unit with low transient over-
reach and a high drop –off/pick ratio.
Because of its continuously variable settings and immunity to offset transients, this relay has
special advantages for the protection of transformer feeders and feeders connected to high MVA
sources. Conventional instantaneous over current protection gives good discrimination and
economy on these lines ,but a relay set to detect symmetrical faults at the far end will overreach
and cause tripping for offset faults which are outside the protected zone .The over current setting
must, therefore, be raised in proportion to the overreach of the relay, with consequent loss of
coverage for symmetrical faults at the far end of the line CAG 17 can be accurately set to cover
all feeder faults up to the transformer secondary bushings and ensures correct discrimination at
high speed under maximum offset fault condition.
Description:
The relay comprises a standard DC hinged armature unit fed via a single phase transformer and a
full wave bridge rectifier. A residual screw is fitted with armature of the relay to achieve a high
drop-off/ pick up ratio. A potentiometer is connected in parallel to the relay coil and adjustment
of this varies the effective operating current of the relay. The transformer primary winding is
multi tapped to give further adjustment of the relay operating current and together with
potentiometer gives an overall adjustment of the current setting. Selection of transformer primary
tapping is by means of a miniaturized plug board.
INSTANTANTANEOUS OVER CURRENT RELAY
(II) PS=1 A or 5A
Result: From the current characteristics ,it can be concluded that with increase in PSM ,operating
time decrease for a very small rise in fault current above plug setting = 1A the drop is extremely
large.
Experiment No.2
Aim: -
To plot the characteristics of single pole over current or earth fault using static I.D.M.T.
relays
Apparatus: -
1) Timer
2) IDMT relay
3) Auxiliary D.C. supplies = 110V
6) Ammeter AC (0-15A)
8) Experiment Kit
9)Connecting wires
Circuit diagram
Procedure: -
1. Make the connection as shown in fig.
2. Set current and time setting of relays as per requirement
3. Set phase trip to 50% and set phase time at X1 with phase TMS at maximum position.
4. Switch on variac and check power ON indication provided on relay front panel.
5. Vary dimmer state with fault current of 1A,relayb will trip after certain time delay.
6. Switch OFF dimmer state without disrobing its position and change the position of DPT
switch. Also reset time.
7. Switch ON dimmer state changes the position of switch and measure the relay time from
timer.
8. Repeat same procedure for varying a different fault current.
Operation: -
With supply on load are continuously monitored Electronic comparator checks this
value with set value (N) of phase & earth fault trip, which can be adjusted on front plate.
Pick up response is (1.1 N) IDMT timing is applicable to over current above 2N as per
chosen curve. Time setting multiplier for actual tripping time delay. TMS is adjusted by
11-position switch & with variable preset pot. These pots adjusted time for intermediate
values indicated on TMS switch. Tripping cause is indicated by LED lamp (OC/EF).
When over current trips the circuit relay ‘ NO’ contact changes to ‘NC’ when relay trips
indicating LED to ‘NC’ when relay trip indicating LED to ‘NC’ when relay trips
indicating LED to ‘NC’ when relay trip indicating LED flag will remain ON till
manually reset.
IDMT RELAY
Observation table
Fault
Sr. current PSM Timer time for Timer time for Timer time for
No. (A) TSM = TSM= TSM=
1
2
.
.
10
Result:
For lower values of current the “time current”characteristics are inverse and for higher value
of current, time observed is constant.
Viva Question
3 Importance of DC supply
6 Why IDMT relay suitable for protection of long length of LV/MV TL.
Experiment No-3
Aim-
To determine the characteristics of the given biased differential relay.
Apparatus required:
A differential relay trainer kit
Introduction:
A Differential relay has two electromagnets one attracting magnet and one stabilizing magnet.
which accurate a balanced beam in opposite directions. a spring operates together with the
stabilization magnet and the tension of the spring may be altered and its position is graduated.
This construction is used in high speed differential relays. Refer to when used as a differential
relay, one carries the through current and the other the difference current. The force at each end
of the beam is proportional to the square of the gap flux and hence to the square of the current.
Result:
Experiment No-4
Aim- To study working of gas actuated Buchholz relay.
Apparatus required:
1. Buchholz relay fitted on stand with pipe line, valves and conservator
2. Air compressor to produce air pressure
3. Control panel
Introduction:
Gas produced by abnormal conditions in the transformer collects in the relay, which lowers the
oil level show that the top float gradually comes down and ultimately operates the mercury
switch which it reaches it certain level .this switch is usually connected to an external alarm
circuit.
Faults which cause operation of this type are:
1. Low oil level in the transformer due to any reason
2. Accumulation of air
3. Fault in the core laminations.
4. Local over heating in the winding.
5. Bad connections.
6. Break down of core bolt insulations.
7. Bad switch contacts.
Abnormal conditions associated with major faults cause a surge in the oil which moves towards
the expansion vessel .this search displaces the lower float operating the switch associated with it.
it is customary to connect this switch in the trip circuit to ensure that the transformer is this
connected on the operation of the switch and thus prevent further damage.
Faults which may cause operation of this switch are :
1. Internal short circuit between turns.
2. Short circuit between phase and earth.
3. phase to phase short circuit.
4. Insulation breakdown of a major nature.
The switch would also operate if the oil level false below that of float due to any reason.
The relay is provided with two glass window both of these have a graduated level to indicate the
volume of gas collected in side.
The alarm and trip circuit terminals are brought in to a terminal box on the cover. The terminal
box has arrangement of conduct connections from the left or right.A drain hole with plug
provided under the relay body.
Installation:
the operation of the surge float (lower float) is caused by the flow of oil to the relay,
consequently to the pipe connection to the relay should be straight and, as long as possible, with
and up ward slope varying between three and seven degrees from the horizontal. a machined
surface is provided on the top of the relay case show that the relay can be mounted with surface
set horizontally at right angle to the direction of oil flow.
It is important that the connecting pipe between transformer tank and expansion vessel be so
located that there is no risk of any gas being trapped under the cover or bypassing the relay.
General:
Not only does the gas and oil relay provide protection against a number of internal faults, but it
also is able to indicate, in several cases, the type of fault, dour and composition, indicate where
the fault may be and what its nature is.
It will thus be seen that fitting of such a relay is a must on all oil immersed power transformers
particularly transformers or 1000kva and above.
The characteristics of the gas and oil relay are as follows:
1. The relay is particularly and sensitive and a simple indicator for internal faults of all kinds in
all oil immersed transformer, by examining the gases collected it is possible to infer the nature of
fault thus
a) If the gas is colors less odour less or with only a faint odour of oil the gas is air trapped in the
oil or the insulation.
b) If the gas is grayish white with sharp and penetrating odour and none in flammable , it is due
to over heated or faulty insulation.
c) If the gas is yellowish in colour inflammable it may be due to surface leakage on material like
wood.
d) If the gas is dark grey in flammable it may be due to flash over in oil or due to excessive over
heating of the oil, caused a fault in the winding or the core.
2. Due to high sensitivity combine with quick operation of the tripping contacts the relay
effectively limits the damage and reduces the cost of repair.
3. On the operation of the alarm, investigation of the collected gas does not indicate a serious
fault; it is possible to leave the transformer in the service till it is convenient to carry out a
thorough inspection.
4. The relay can serve to sum extent as a protection against heavy over loads but can not be
trusted for all over loads and should be backed by a temp. Operated devices to prevent sustained
over loads.
5. The relay is not responsive to external fault unless they are of the nature of heavy over loads
leading to excessive heating.
Description:
The gas and oil relay comprise an oil tight case with cover. it is provided with two hinged floats
which separate mercury switches connected to customers protective alarm or tripping circuits. It
is connected in the pipe connections between transformer and the expansion vessel so the
normally it is completely filled with oil.
Buchholz Relay
Circuit diagram
Procedure:
1. Connect the ph & N in to side strip.
2. Connect output to the motor.
3. Connect alarm point to the alarm point of the relay.
4. Connect trip point to the trip point of relay.
5. Push the green button, now motor with start.
6. By opening the wall slowly
Experiment No.05
Introduction :
Static relay
The conventional relay type of electromagnet relays can be replaced by static relays which
essentially consist of electronic circuitry to develop all those characteristics which are achieved
by moving parts in an electro-magnetic relay.
For example, in an induction type relay, the operating time can be adjusted by adjusting the
distance travelled by the disc whereas in a static relay it can be achieved by adjusting the value
of the resistance in the R-C time delay circuit. In other words static relays are capable of
performing the same functions with the use of electronic circuit control as an electro-magnetic
relay performs with the use of moving parts or elements.
1. The moving parts and the contacts are largely eliminated. The only moving element in a
static relay is the final tripping contact.
2. C.T.s and P.T.s employed are of lesser VA rating as static relays require a very little volt-
ampere for their operation.
3. More precise and high speed operation.
Structure
1. Auxiliary Voltage Supply:24 V DC supply is required for energizing the circuitry of the
static relay. This is obtained by converting 230 V AC to 24 V DC and in some cases
station battery voltage of 110 V to 24 V DC.
2. Comparator:It compares the actual quantity with the pre-set quantity. For example in an
over-current relay it will compare the actual current supplied by CT with the pre-
determined set current over which tripping is required.
3. Time delay Elements:The required operation time is achieved here by adjusting the values
of R and C.
4. Logic Circuit:By using the gate circuits conditions of operation of relays are set and relay
can only be operated when these conditions are satisfied.
5. Output Device:The actual tripping of relay can be achieved by firing the SCR or
operating the attracted armature relay by feeding the signal coming from logic circuit
output.
Experiment No.06
Aim: Determination of transmission line parameters using MATLAB
Over view:
Transmission line parameters are the most important aspects that can ever be considered when
dealing with transmission lines. Transmission lines are often categorized in three major
categories which are, the short lines, the medium lines and the long lines. Upon obtaining the
transmission line parameters, it is often much easier to predict the performance of a transmission
line through efficiency measurement and per unit analysis
Introduction
The steady state operation of a transmission line is a very important state when it comes to
transmission line modelling. Results obtained from the steady state analysis are often ideally
used in the analysis of transmission line and apply when the line conditions are balanced and also
during unbalance. The ABCD parameters of a transmission line have a handful of importance
and knowing them enables us to predict and manipulate the performance of a transmission line.
During design one often tends to look for the most efficient power system ad yet also considers
the costs to erect the power system. This all start with the analysis and acquisition of the power
system’s ABCD parameters and hence continues with the further manipulation of these
parameters to obtain the required system The are basically three types of transmission lines.
These are the short transmission line model, the medium transmission, the model and the ling
transmission line model. The medium transmission line model is further subdivided into the T
lines and the PI lines.
Short transmission lines
These are transmission lines that are usually less than 80KM long.
In the analysis of these lines, the capacitance and the leakage resistance to the earth are
neglected and hence only the wire resistance and the inductive reactance are considered.
This is a simple series circuit and hence the current flowing through the circuit is simply
the same.
This is the easily analysed transmission line and it is not commonly used in power systems due
to the fact that transmission lines are usually aimed to go for a long distance as to reduce the
transmission costs.
Π Modeled transmission line
Medium lines usually have a length that varies between 80KM to 250km
In the model for this line’s parameters, the total shunt capacitance is usually lumped
together and is located half at each end.
T modeled transmission line
This is another form of representing a medium transmission line. In this line model, half
of the line impedance is lumped at the end of each line. This line also is analyzed by
assuming a wye connected circuit.
Long transmission line
These are the types of transmission lines that usually cover very long distances and could
represent a minimum distance of 250KM.
They represent very high voltage transmission lines because long distance transmission
with high voltage reduce the line power losses.
In this transmission lines, the current is kept to it very minimum to avoid effects of
overheating and hence reduce maintenance costs as they might take long to repair in
times of damages.
The equivalent circuit is somehow very similar to the alternative PI representation but the
elements are now represented using trigonometric ratios such as cosh and sinh.The
ABCD parameters are now derived from the equivalent circuit diagrams and are purely
functions of impedance and admittance values.
Program outline
1. The program must allow for its user to enter the values that are provided and will be the
baseline for the whole simulation.
2. The program will then be able to evaluate the impedance and admittance of the line.
3. Since the ABCD parameters are represented using the impedances and admittances, they
are than evaluated.
4. Since the values of Vs and Is are now obtained, one is now able to evaluate the sending
end power, the voltage regulation, the efficiency, the sending end power factor.
5. This part of the program should than be the part where the bases of for the system are
chosen in order to give all the circuit quantities in per unit.
6. The per unit quantities are thus evaluated and displayed.
7. The program should then go on and allow the user to enter the power factor that they
want their system to be corrected to.
8. It will than calculate the value of the reactive power that needs to be supplied by the
capacitor bank and also the per phase capacitance of the capacitor bank.
9. The program for the short line is than modified so that it accommodates a looping
structure and also be able to obtain the different values of the capacitance bank when the
length of line is being veried.
Codes used for the simulation of the transmission lines
%program for short lines
clear;
clc;
p=power/3;
res=r*length;
z=complex(res,xl);
A=1;
B=z;
C=0;
D=1;
vlo=vl/sqrt(3);
ilmag=p/(vlo*pf);
il=complex(ilmag*cos(acos(pf)),-ilmag*sin(acos(pf)));
vload=complex(vlo,0);
vs=A*vload + B*il;
is=C*vload + D*il;
s=conj(is)*vs;
vr=((abs(vs)-abs(vlo))/abs(vlo))*100;
%calculate efficiency
pin=real(s);
pout=p;
n=(pout/pin)*100;
theta=atan(imag(s)/ real(s));
pfactor=cos(theta);
fprintf ('VS=');
disp(vs);
fprintf('IS=');
disp(is);
disp(pfactor);
disp(s);
fprintf('voltage regulation=');
disp(vr);
fprintf('effiency=');
disp(n);
vbase=vlo;
sbase=p/pf;
zbase=mpower(vbase,2)/sbase;
ibase=sbase/vbase;
zpu=z/zbase;
vreceivingpu=vload/vbase;
ireceivingpu=il/ibase;
vsendingpu=vs/vbase;
isendingpu=is/ibase;
ssendingpu=s/sbase;
precevingpu=p/sbase;
disp(zpu);
disp(vreceivingpu);
disp(ireceivingpu);
disp(vsendingpu);
fprintf('the per unit value of the sending end current=');
disp(isendingpu);
disp(ssendingpu);
disp(precevingpu);
thetanew=acos(pfdesired);
qold=imag(s);
qnew=real(s)*tan(thetanew);
qc=qold-qnew;
c=qc/(mpower(abs(vs),2)*2*pi*f);
disp(c);
disp(qc);
%program for medium pie lines
clear;
clc;
x=d;
ca = x*(mpower(10,-1.05*m));
length=7*d;
xl=l*length*pi*2*f;
p=power/3;
xc=ca*length*2*pi*f;
res=r*length;
vlo=vl/sqrt(3);
z=complex(res,xl);
yc=complex(0,xc);
squ=mpower(yc,2);
A=(0.5*(z*yc))+1;
B=z;
C=yc+(0.25*(squ*z));
D=1+(0.5*(z*yc));
ilmag=p/(vlo*pf);
il=complex(ilmag*cos(acos(pf)),-ilmag*sin(acos(pf)));
vload=complex(vlo,0);
vs=A*vload + B*il;
is=C*vload + D*il;
s=conj(is)*vs;
theta=atan(imag(s)/ real(s));
pfactor=cos(theta);
%calculate voltage regulation
vr=((abs(vs)-vlo)/vlo)*100;
%calculate efficiency
pin=3*abs(vs)*abs(is)*pfactor;
pout=3*abs(vload)*abs(il)*pf;
n=(pout/pin)*100;
disp(vs);
disp(is);
disp(pfactor);
disp(s);
fprintf('voltage regulation=');
disp(vr);
fprintf('effiency=');
disp(n);
vbase=vlo;
sbase=p/pf;
zbase=mpower(vbase,2)/sbase;
ibase=sbase/vbase;
zpu=z/zbase;
ycpu=yc/zbase;
vreceivingpu=vload/vbase;
ireceivingpu=il/ibase;
vsendingpu=vs/vbase;
isendingpu=is/ibase;
ssendingpu=s/sbase;
precevingpu=p/sbase;
disp(zpu);
disp(vreceivingpu);
disp(ireceivingpu);
disp(vsendingpu);
disp(isendingpu);
disp(ssendingpu);
disp(precevingpu);
disp(ycpu);
thetanew=acos(pfdesired);
qold=imag(s);
qnew=real(s)*tan(thetanew);
qc=qold-qnew;
capa=qc/(mpower(abs(vs),2)*2*pi*f);
disp(capa);
efficiency= 94.3378
the per unit value of the receiving end current= 0.8500 - 0.5268i
the per unit value of the sending end voltage= 1.1525 + 0.2175i
the per unit value of the sending end current= 0.8141 - 0.1712i
the per unit value of the sending end apparent power= 0.9010 + 0.3744i
the per unit value of the receiving end real power= 0.8500
Unfortunately, faults could happen as a result of natural events or accidents where the
phase will establish a connection with another phase, A falling tree on a transmission lines could
cause a three-phase fault where all phases share a point of contact called fault location. In
different occasions, fault could be a result of insulation deterioration, wind damage or human
vandalism.
Faults can be defined as the flow of a massive current through an improper path which
could cause enormous equipment damage which will lead to interruption of power, personal
injury, or death. In addition, the voltage level will alternate which can affect the equipment
insulation in case of an increase or could cause a failure of equipment start-up if the voltage is
below a minimum level. As a result, the electrical potential difference of the system neutral will
increase. Hence, People and equipment will be exposed to the danger of electricity which is not
accepted.
In order to prevent such an event, power system fault analysis was introduced. The
process of evaluating the system voltages and currents under various types of short
circuits is called fault analysis. Which can determine the necessary safety measures & the required
protection system?
There are two types of faults which can occur on any transmission lines; balanced faults &
unbalanced faults. In addition, unbalanced faults can be classified into single line-to-ground faults,
double line faults and double line-to-ground faults.
The most common types taking place in reality are as follow: Line-to-ground fault: this type
of fault exists when one phase of any transmission lines establishes a connection with the ground
either by ice, wind, falling tree or any other incident. 70% of all transmission lines faults are
classified under this category. Line-to-line fault: as a result of high winds, one phase could touch
anther phase & line-to-line fault takes place. 15% of all transmission lines faults are considered line-
to-line faults. Double line-to-ground: two phases will be involved instead of one at the line-to-ground
faults scenarios. 10% of all transmission lines faults are under this type of faults . Three phase fault:
in this case, falling tower, failure of equipment or even a line breaking and touching the remaining
phases can cause three phase faults. In reality, this type of fault not often exists which can be seen
from its share of 5% of all transmission lines faults.
In order to analyze any unbalanced power system, C.L. Fortescue introduced a method called
symmetrical components in 1918 to solve such system using a balanced representation. Its
mathematical model will be presented. After that, a 6-bus system will be under fault for analysis.
This analysis will take place using the manual calculations. These results will be compared later with
the results of Matlab codes.
In general, a fault is any event, unbalanced situation or any asymmetrical situation that interferes
with the normal current flow in a power system and forces voltages and currents to differ from each
other. It is important to distinguish between series and shunt faults in order to make an accurate fault
analysis of an asymmetrical three-phase system. When the fault is caused by an unbalance in the line
impedance and does not involve a ground, or any type of inter-connection between phase conductors
it is known as a series fault. On the other hand, when the fault occurs and there is an inter-connection
between phase-conductors or between conductor(s) and ground and/or neutral it is known as a shunt
fault.Statistically, series faults do not occur as often as shunt faults does. Because of this fact only the
shunt faults are explained here in detail since the emphasis in this project is on analysis of a power
system under shunt faults.
Three-Phase Fault
By definition a three-phase fault is a symmetrical fault. Even though it is the least frequent fault, it is
the most dangerous. Some of the characteristics of a three-phase fault are a very large fault current
and usually a voltage level equals to zero at the site where the fault takes place. A general
representation of a balanced three-phase fault is shown in Figure 3.8 where F is the fault point with
impedances Zf and Zg . Figure 3.9 shows the sequences networks interconnection diagram.
The single line-to-ground fault is usually referred as “short circuit” fault and occurs when one
conductor falls to ground or makes contact with the neutral wire. The general representation of a
single line-to-ground fault where F is the fault point with impedances Z f. . Phase a is usually assumed
to be the faulted phase, this is for simplicity in the fault analysis calculations.
Line-to-Line Fault
A line-to-line fault may take place either on an overhead and/or underground transmission system
and occurs when two conductors are short-circuited. One of the characteristic of this type of fault is
that its fault impedance magnitude could vary over a wide range making very hard to predict its
upper and lower limits. It is when the fault impedance is zero that the highest asymmetry at the line-
to-line fault occurs.
A double line-to-ground fault represents a serious event that causes a significant asymmetry in a
three-phase symmetrical system and it may spread into a three-phase fault when not clear in
appropriate time. The major problem when analyzing this type of fault is the assumption of the fault
impedance Zf , and the value of the impedance towards the ground Z g
Outcome of the simulation stage can be listed in the following points:
1. In three-phase fault, the voltages at faulted bus phases dropped to zero during the fault. The
faulted bus is bus number four where Phase A, B and C has a zero voltage potential.
2. However, only voltage at Phase A is equal to zero in single line-to-ground fault. In addition,
only Phase A has current since it is the faulted phase in this type of fault as we assumed
earlier in the mathematical model. This current is the second highest fault currents of all
types.
3. Since Phase B and Phase C are in contact in line-to-line fault, the voltages at both phases are
equal. The fault current are passing from B to C. in Phase A, the current is equal to zero
compared to the fault current.
4. In double line-to-ground fault, Phase B and C voltages are equal to zero. The faulted current
is flowing through both phases only. In addition, this type of fault is the most sever fault on
the system which can be seen from its current value.
Experiment No.8
Aim:
To study Sulphur Hexafluoride (SF6) circuit breaker.
Theory:
In such circuit breaker, Sulphur hexaflouride (SF6) gas is used as the arc quenching medium.
The SF6 is an electro-negative gas and has a strong tendency to absorb free electrons. The
contacts of the beaker are opened in a high pressure flow of SF6 gas and an arc is struck between
them. The conducting free electrons in the arc are rapidly captured by the gas to form relatively
immobile negative ions. This loss of electrons in the arc are quickly builds up enough insulation
strength to extinguish the arc. The SF6 circuit breakers have been found to be very effective for
high power & high voltage service.
Circuit diagram
Construction:
It consists of fixed and moving contacts enclosed in a chamber called arc interruption chamber,
Containing SF6 gas. This chamber is connected to SF6, gas reservoir. When the contacts of
beaker arc opened, the valve mechanism permits a high pressure SF6 gas from the reservoir to
flow towards the arc interruption chamber.
The fixed chamber is a hollow cylindrical current carrying contact fitted with an arc horn. The
moving contact is also a hollow cylinder with rectangular holes in the sides to permit the SF6 gas
to let over through these holes after flowing along and across the arc. The tips are fixed contacts,
moving contacts and arcing horns are coated with copper-tungsten arc resistance materials. Since
SF6 gas is costly, it is recondition and reclaimed by suitable auxiliary system after each
operation of the breakers.
Working:
In the closed position of the breaker, the contacts remains surrounds by SF6 gas at a pressure of
about 2-8 kg/cm2.when the break operates, the moving contacts are pulled apart and an arc is
struck between the contacts. The movement of the moving contact is synchronize with the
opening of valve which permits SF6 gas at 14 kg/cm2,pressure from the reservoir to the arc
interruption chamber .The high pressure flow of SF6 rapidly absorb the free electrons in the arc
path to form immobile negative ions which are ineffective as charge carriers. the result is that
medium between the contacts quickly builds up high dielectric strength and causes the quickly
the extinction of the arc. After the breaker operation, the valve is closed by the action of the a set
of spring.
Application:
1. A typical SF6 circuit breaker consist of interruption units each capable of dealing with current
up to 60 KA and voltage in the range of 50-80 KV
2. A no of unit are connected in series according for voltage 115 KV to 230 KV, power rating 10
MVA to 20 MVA and interrupting time less than 3 sec.
Result:
Every steps inside the working principle is explained along with the function of each part used in
this relay. It work at higher voltage rating than the voltage of other circuit breaker.
Experiment No.9
Aim:
To study of Bus bar, Transformer, Alternator and Busbar
Introduction :
Busbar Protection | Busbar Differential Protection Scheme
The scheme of busbar protection, involves, Kirchoff’s current law, which states that, total
current entering an electrical node is exactly equal to total current leaving the node.
Hence, total current entering into a bus section is equal to total current leaving the bus section.
The principle of differential busbar protection is very simple. Here, secondaries of CTs are
connected parallel. That means, S1 terminals of all CTs connected together and forms a bus wire.
Similarly S2 terminals of all CTs connected together to form another bus wire.
During explaining working principle of current differential protection of busbar, we have shown
a simple non sectionalized busbar. But in moderate high voltage system electrical bus
sectionalized in than one sections to increase stability of the system. It is done because, fault in
one section of bus should not disturb other section of the system. Hence during bus fault, total
bus would be interrupted.
Let us draw and discuss about protection of busbar with two sections.
This section busbar differential protection scheme operates in some manner simple current
differential protection of busbar.
That is, any fault in zone A, with trip only CB1, CB2 and bus CB.
Any fault in zone B, will trip only CB5, CB6 and bus CB.
Hence, fault in any section of bus will isolate only that portion from live system.
In current differential protection of busbar, if CT secondary circuits, or bus wires is open the
relay may be operated to isolate the bus from live system. But this is not desirableDC Circuit of
Differential Busbar ProtectionA typical DC circuit for busbar differential protection scheme is
given below.
As the length of electrical power transmission line is generally long enough and it runs through
open atmosphere, the probability of occurring fault in electrical power transmission line is much
higher than that of electrical power transformers and alternators. That is why a transmission line
requires much more protective schemes than a transformer and an alternator.
1. During fault, the only circuit breaker closest to the fault point should be tripped.
2. If the circuit breaker closest the faulty point, fails to trip the circuit breaker just next to
this breaker will trip as back up.
3. The operating time of relay associated with protection of line should be as minimum as
possible in order to prevent unnecessary tripping of circuit breakers associated with other
healthy parts of power system.
These above mentioned requirements cause protection of transmission line much different
from protection of transformer and other equipment of power systems. The main three methods
of transmission line protection are –
This may also be referred simply as over-current protection of electrical power transmission line.
Let’ discuss different schemes of time graded over current protection.
In radial feeder, the power flows in one direction only, that is from source to load. This type of
feeders can easily protected by using either definite time relays or inverse time relays.
This protection scheme is very simple. Here total line is divided into different sections and each
section is provided with definite time relay. The relay nearest to the end of the line has minimum
time settin
g while time setting of other relays successively increased, towards the source.
The main advantage of this scheme is simplicity. The second major advantage is, during fault,
only nearest CB towards the source from fault point will operate to isolate the specific position
of the line.
If the number of sections in the line is quite large, the time setting of relay nearest to the source,
would be very long. So during any fault nearer to the source will take much time to be isolated.
This may cause severe destructive effect on the system.
The drawback as we discussed just in definite time over current protection of transmission line,
can easily be overcome by using inverse time relays. In inverse relay the time of operation is
inversely proportional to fault current.
In the above figure, overall time setting of relay at point D is minimum and successively this
time setting is increased for the relays associated with the points towards the point A.
In case of any fault at point F will obviously trip CB-3 at point D. In failure of opening CB-3,
CB-2 will be operated as overall time setting is higher in relay at point C.
Although, the time setting of relay nearest to the source is maximum but still it will trip in
shorter period, if major fault occurs near the source, as the time of operation of relay is inversely
proportional to faulty current.
For maintaining stability of the system it is required to feed a load from source by two or more
than two feeders in parallel. If fault occurs in any of the feeders, only that faulty feeder should be
isolated from the system in order to maintain continuity of supply from source to load. This
requirement makes the protection of parallel feeders little bit more complex than simple non
direction over current protection of line as in the case of radial feeders. The protection of parallel
feeder requires to use directional relays and to grade the time setting of relay for selective
tripping.
There are two feeders connected in parallel from source to load. Both of the feeders have non-
directional over current relay at source end. These relays should be inverse time relay. Also both
of the feeders have directional relay or reverse power relay at their load end. The reverse power
relays used here should be instantaneous type. That means these relays should be operated as
soon as flow of power in the feeder is reversed. The normal direction of power from source to
The general winding faults in transformer are either earth faults or inter-turns faults. Phase to
phase winding faults in a transformer is rare. The phase faults in an electrical transformer may be
occurred due to bushing flash over and faults in tap changer equipment. Whatever may be the
faults, the transformer must be isolated instantly during fault otherwise major breakdown may
occur in the electrical power system.
Incipient faults are internal faults which constitute no immediate hazard. But it these faults are
over looked and not taken care of, these may lead to major faults. The faults in this group are
mainly inter-lamination short circuit due to insulation failure between core lamination, lowering
the oil level due to oil leakage, blockage of oil flow paths. All these faults lead to overheating.
So transformer protection scheme is required for incipient transformer faults also. The earth
fault, very nearer to neutral point of transformer star winding may also be considered as an
incipient fault.
There are mainly two conditions for earth fault current to flow during winding to earth faults,
1. A current exists for the current to flow into and out of the winding.
2. Ampere-turns balance is maintained between the windings.
The value of winding earth fault current depends upon position of the fault on the winding,
method of winding connection and method of earthing. The star point of the windings may be
earthed either solidly or via a resistor. On delta side of the transformer the system is earthed
through an earthing transformer. Grounding or earthing transformer provides low impedance
path to the zero sequence current and high impedance to the positive and negative sequence
currents.
The electric motor is most essential drive in modern era of industrialization. From fractional hp
AC motor used for different home appliances to giant synchronous motor and induction motor of
up to 10,000 hp used for different industrial applications, should be protected against different
electrical and mechanical faults for serving their purposes smoothly. The motor characteristics
must be very carefully considered in selecting the right motor protection scheme.
The abnormalities in motor or motor faults may appear due to mainly two reasons –
Unbalanced supply voltages, under-voltage, reversed phase sequence and loss of synchronism (in
the case of synchronous motor) come under former category. The later category includes bearing
failures, stator winding faults, motor earth faults and overload etc.
The degree of motor protection system depends on the costs and applications of the electrical
motor.
Generally motors up to 30 hp are considered in small category. The small motor protection in
this case is arranged by HRC fuse, bimetallic relay and under voltage relay – all assembled into
the motor contractor – starter itself.
Most common cause of motor burn outs on LV fuse protected system is due to single phasing.
This single phasing may remain undetected even if the motors are protected by conventional
bimetallic relay. It can not be detected by a set of voltage relays connected across the lines.
Since, even when one phase is dead, the motor maintains substantial back emf on its faulty phase
terminal and hence voltage across the voltage relay is prevented from dropping – off.
The difficulties of detecting single phasing can be overcome by employing a set of three current
operated relays as shown in the small motor protection circuit given below.
The current operated relays are very simple instantaneous relays. There are mainly two parts in
this relay one is a current coil and other is one or more normally open contacts (NO Contacts).
The NO contacts are operated by the mmf of the current coil. This relay is connected in series
with each phase of the supply and backup by HRC fuse. When the electrical motor starts and
runs the supply current passes through the current coil of the protective relay. The mmf of the
current coil makes the NO contacts closed. If suddenly a single phasing occurs the corresponding
current through the current coil will falls and the contacts of the corresponding relay will become
to its normal open position. The NO contacts of the all three relays are connected in series to
hold – in the motor contractor. So if any one relay contact opens, results to release of motor
contractor and hence motor will stop running.
Aim:
To determine the di- electric strength of transformer oil.
Apparatus Required:
One insulating test set cell of transformer oil.
Description of the test set:
The set test which operates on 230v, 50hz supply has been mainly two transformers. One is the
toroidal wound autotransformer used to supply steeples continuously variable voltage the other
H.T. Transformer operates at low flux density ensuring distortion free output voltage .It is a
60kv. 0.5 capacity Transformer , it so designed that S/c current of the secondary is more than
20mA at all voltage above 10kv. The max s/c current does not exceed 200mA thus preventing
the unnecessary pitting of electrodes. The test consist of an overload relay which trips and
disconnects the H.T. Transformer when the breakdown occurs across the gaps. The oil to be put
in the cells. Only after removing a plastic enclosure provided. When the enclosures is removed, it
actuates micro switch shutting of the supply to the unit. A zero return interlock arrangement
makes it obligatory to bring the H.T. voltage to zero after every breakdown test. Test panel board
of the test set consists of voltage control push, a moving ion voltmeter to indicate the voltage
applied in KV, three indicator lamps to indicate the mains ‘ON’ and H.T. ‘OFF’ . It also consists
of main switch, a, H.T., ON switch and a H.T. off switch.
Transformer Oil Testing Kit
Preparation of The Sample :
1. The sampling vessel containing the test oil shall be gently against and turned over several
times in such a way as to ensure as for as possible a homogeneous distribution of the
impurities contains in the oil without causing the formation of air bubbles.
2. Immediately before use, the shall be cleaned by rising with test oil before proceeding to
the final fittings
3. Immediately after this, the sample should be poured down in to the test cell, slowly in
order to avoid air bubbles forming (a clean glass rod may be used)
4. The oil temp. at the time of test shall be same as that of the ambient air, preferably in the
neighborhood at 27 and noted.
Procedure :
Operation Method
First check the gap of electrodes with go & no go gauges provided in the exp. Fill the oil
under test in the oil cup fit the oil cup in the oil test set at the clamp stand close the plastics
top and see the micro switch beneath closes.
Connect the main plug switch to A.C. main supply 230v 50hz. As per panel lay out shown
above switch on the H.T. on Toggle switch and other toggle switch on the position. Now
push on the H.T. on push and keep toggle switch on the. position you will not the H.T.
voltage will go on incr. till the breakdown of insulation and H.T. voltage will denote the
Breakdown voltage of the oil.
You can repeat this experiment.
Result: