Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony Timer Relays
Complementary
Contacts type and composition 1 C/O timed contact, cadmium free
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Dec 9, 2022 1
Immunity to microbreaks 10 ms
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (steady) for power ON
Width 22.5 mm
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Product certifications GL
UL
CSA
RCM
CCC
CE
EAC
Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
2
Dec 9, 2022
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Packing Units
Unit Type of Package 1 PCE
Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
known to the State of California to cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
Dec 9, 2022 3
Product data sheet RE22R1MKMR
Dimensions Drawings
Dimensions
4
Dec 9, 2022
Product data sheet RE22R1MKMR
Connections and Schema
Wiring Diagram
Dec 9, 2022 5
Product data sheet RE22R1MKMR
Technical Description
Description
On energisation of power supply, the output(s) R close(s).On de-energisation of power supply, timing period T starts and at the end of this
period, the output(s) R revert(s) to its/their initial state.The energization of power supply > Tk is necessary to sustain the timing period T.
Function: 1 Output
Tk > 1s
Function: 2 Outputs
Tk > 80ms
6
Dec 9, 2022
Product data sheet RE22R1MKMR
Technical Description
Description
After energisation of power supply > 80ms followed by deenergization of power supply, the output(s) R closes() for the duration of a timing
period T then revert(s) to its/their initial state.Energisation of power supply < 80ms followed by deenergization of power supply,the output(s) R
close(s) and WILL NOT ABLE TO sustain for the duration of a timing period T before revert(s) to its/their initial state.
Function: 1 Output
Legend
Relay de-energised
Relay energised
Output open
Output closed
U- Supply
T- Timing period
Recommended replacement(s)
Dec 9, 2022 7