Harmony Timer Relays - RE22R1MKMR

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Product data sheet

Specifications

Modular timing relay, Harmony, 5A,


1 CO, 0.05s…300s, delay on and
pulse on de energization, 24...240V
AC DC
RE22R1MKMR

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony Timer Relays

Product or component type Dual function relay

Discrete output type Relay

Device short name RE22

Nominal output current 5 A

Complementary
Contacts type and composition 1 C/O timed contact, cadmium free

Time delay type Pulse-on de-energization


Delay on de-energization

Time delay range 0.3...3 s


0.05...0.5 s
3...30 s
0.1...1 s
30...300 s
10...100 s
1...10 s

Control type Rotary knob

[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz

Release input voltage <= 2.4 V

Voltage range 0.85...1.1 Us

Supply frequency 50...60 Hz +/- 5 %

Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Tightening torque 0.6…1 N.m conforming to IEC 60947-1

Housing material Self-extinguishing

Repeat accuracy +/- 0.5 % conforming to IEC 61812-1

Temperature drift +/- 0.05 %/°C

Voltage drift +/- 0.2 %/V

Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1

Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1

Recovery time 50 ms on de-energisation

Dec 9, 2022 1
Immunity to microbreaks 10 ms

Power consumption in VA 3 VA at 240 V AC

Power consumption in W 2 W at 240 V DC

Switching capacity in VA 1250 VA

Minimum switching current 10 mA at 5 V DC

Maximum switching current 5 A

Maximum switching voltage 250 V AC

Electrical durability 100000 cycles, 2 A at 24 V, DC-1


100000 cycles, 5 A at 250 V, AC-1

Mechanical durability 10000000 cycles

Rated impulse withstand 5 kV for 1.2…50 µs conforming to IEC 60664-1


voltage

Power on delay 100 ms

Creepage distance 4 kV/3 conforming to IEC 60664-1

Overvoltage category III conforming to IEC 60664-1

Safety reliability data B10d = 180000


MTTFd = 194 years

Mounting position Any position

Mounting support 35 mm DIN rail conforming to EN/IEC 60715

Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (steady) for power ON

Width 22.5 mm

Net weight 0.1 kg

Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1

Standards IEC 61812-1


UL 508

Directives 2006/95/EC - low voltage directive


2004/108/EC - electromagnetic compatibility

Product certifications GL
UL
CSA
RCM
CCC
CE
EAC

Ambient air temperature for -20…60 °C


operation

Ambient air temperature for -40…70 °C


storage

IP degree of protection IP40 housing: conforming to IEC 60529


IP50 front face: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529

Pollution degree 3 conforming to IEC 60664-1

Vibration resistance 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6

Shock resistance 15 gn not operating for 11 ms conforming to IEC 60068-2-27


5 gn in operation for 11 ms conforming to IEC 60068-2-27

Relative humidity 95 % at 25…55 °C

Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2

2
Dec 9, 2022
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 2.5 cm

Package 1 Width 8.3 cm

Package 1 Length 9.5 cm

Package 1 Weight 91.0 g

Unit Type of Package 2 S02

Number of Units in Package 2 40

Package 2 Height 15.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 4.088 kg

Unit Type of Package 3 P06

Number of Units in Package 3 640

Package 3 Height 80.0 cm

Package 3 Width 80.0 cm

Package 3 Length 60.0 cm

Package 3 Weight 73.38 kg

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)


EU RoHS Declaration

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
known to the State of California to cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov

Dec 9, 2022 3
Product data sheet RE22R1MKMR
Dimensions Drawings

Dimensions

4
Dec 9, 2022
Product data sheet RE22R1MKMR
Connections and Schema

Wiring Diagram

Dec 9, 2022 5
Product data sheet RE22R1MKMR
Technical Description

Function K: Delay On De-energization without Auxillary Supply

Description
On energisation of power supply, the output(s) R close(s).On de-energisation of power supply, timing period T starts and at the end of this
period, the output(s) R revert(s) to its/their initial state.The energization of power supply > Tk is necessary to sustain the timing period T.

Function: 1 Output

Tk > 1s

Function: 2 Outputs

Tk > 80ms

6
Dec 9, 2022
Product data sheet RE22R1MKMR
Technical Description

Function He: Pulse-on De-energization

Description
After energisation of power supply > 80ms followed by deenergization of power supply, the output(s) R closes() for the duration of a timing
period T then revert(s) to its/their initial state.Energisation of power supply < 80ms followed by deenergization of power supply,the output(s) R
close(s) and WILL NOT ABLE TO sustain for the duration of a timing period T before revert(s) to its/their initial state.

Function: 1 Output

Legend
Relay de-energised

Relay energised

Output open

Output closed

U- Supply

T- Timing period

R1/R2 - 2 timed outputs

Recommended replacement(s)

Dec 9, 2022 7