This document provides an overview and operation plan for a substation automation system involving a REF615 relay, RIO600 I/O module, and industrial Ethernet switch. It describes the 18 binary inputs and 13 binary outputs being used by the REF615 relay and 2 sets of 4 binary inputs and 2 binary outputs being used by each of the 2 SCM8_L I/O modules. The system will transfer switch position and alarm signals to allow remote operation and monitoring of circuit breakers, disconnectors, and other equipment from a SCADA system via IEC61850.
This document provides an overview and operation plan for a substation automation system involving a REF615 relay, RIO600 I/O module, and industrial Ethernet switch. It describes the 18 binary inputs and 13 binary outputs being used by the REF615 relay and 2 sets of 4 binary inputs and 2 binary outputs being used by each of the 2 SCM8_L I/O modules. The system will transfer switch position and alarm signals to allow remote operation and monitoring of circuit breakers, disconnectors, and other equipment from a SCADA system via IEC61850.
Original Title
Abb Tur Bi Bo Led Signal List Cyi With Rio 2021 r05 (1)
This document provides an overview and operation plan for a substation automation system involving a REF615 relay, RIO600 I/O module, and industrial Ethernet switch. It describes the 18 binary inputs and 13 binary outputs being used by the REF615 relay and 2 sets of 4 binary inputs and 2 binary outputs being used by each of the 2 SCM8_L I/O modules. The system will transfer switch position and alarm signals to allow remote operation and monitoring of circuit breakers, disconnectors, and other equipment from a SCADA system via IEC61850.
This document provides an overview and operation plan for a substation automation system involving a REF615 relay, RIO600 I/O module, and industrial Ethernet switch. It describes the 18 binary inputs and 13 binary outputs being used by the REF615 relay and 2 sets of 4 binary inputs and 2 binary outputs being used by each of the 2 SCM8_L I/O modules. The system will transfer switch position and alarm signals to allow remote operation and monitoring of circuit breakers, disconnectors, and other equipment from a SCADA system via IEC61850.
CV CYI / Oct.2021 / R05 + (Industrial Ethernet Switch - FL SWITCH SFNB 5TX) BI total: BI BO total: BO Signal Nr COMMAND From: Signal Nr Incoming Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615 1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615 2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615 3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615 4 BI-4 to REF615 DISCONNECTOR - OFF REF615 5 BI-5 to REF615 EARTH SWITCH - ON REF615 6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L 7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWTICH CLOSE 1st SCM8_L 8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L 9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L 10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L
11 BI-7 to REF615 Gas pressure NORMAL REF615
12 BI-8 to REF615 Gas pressure LOW REF615 13 BI-9 to REF615 Directional Fault Indicator A REF615 14 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS 15 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP 16 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP 17 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP 18 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP 19 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP 20 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP 21 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP 22 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP LED9 49 THERMAL TRIP LED10 74TC TCS ALARM LED11 COMMUNICATION ALARM OVERVIEW OPERATION PLAN: REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the 1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via IEC61850. 2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850. 3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection. 4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX 5) "Pendant" eqipment will be used for all "C" and "V" fields motor control. 6) IEC61850 communication test report for all signals shall be provided for each FAT report. Classification: Internal Purpose #
CCV CYI / Oct.2021 / R05 + (Industrial Ethernet Switch - FL SWITCH SFNB 5TX) BI total: BI BO total: BO Signal Nr COMMAND From: Signal Nr Incoming Outgoing 1 Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615 1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615 2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615 3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615 4 BI-4 to REF615 DISCONNECTOR - OFF REF615 5 BI-5 to REF615 EARTH SWITCH - ON REF615 6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L 7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWITCH CLOSE 1st SCM8_L 8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L 9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L 10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L 7 BO-1 from SCM8_L 1 OUTGOING FIELD-1 - LOAD BREAK SWITCH OPEN 2nd SCM8_L 11 BI-1 to SCM8_L LOAD BREAK- ON 2nd SCM8_L 8 BO-2 from SCM8_L 2 OUTGOING FIELD-1 - LOAD BREAK SWITCH CLOSE 2nd SCM8_L 12 BI-2 to SCM8_L LOAD BREAK - OFF 2nd SCM8_L 13 BI-3 to SCM8_L EARTH SWITCH - ON 2nd SCM8_L 14 BI-4 to SCM8_L EARTH SWITCH - OFF 2nd SCM8_L
15 BI-7 to REF615 Gas pressure NORMAL REF615
16 BI-8 to REF615 Gas pressure LOW REF615 17 BI-9 to REF615 Directional Fault Indicator A REF615 18 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS 19 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP 20 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP 21 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP 22 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP 23 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP 24 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP 25 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP 26 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP LED9 49 THERMAL TRIP LED10 74TC TCS ALARM LED11 COMMUNICATION ALARM OVERVIEW OPERATION PLAN: REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the 1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via IEC61850. 2nd SCM8_L 4BI & 2 BO in use 2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850. 3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection. 4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX 5) "Pendant" eqipment will be used for all "C" and "V" fields motor control. 6) IEC61850 communication test report for all signals shall be provided for each FAT report. Classification: Internal Purpose #
CCCV CYI / Oct.2021 / R05 + (Industrial Ethernet Switch - FL SWITCH SFNB 5TX) BI total: BI BO total: BO Signal Nr COMMAND From: Signal Nr Incoming Outgoing 1 Outgoing 2 Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615 1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615 2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615 3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615 4 BI-4 to REF615 DISCONNECTOR - OFF REF615 5 BI-5 to REF615 EARTH SWITCH - ON REF615 6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L 7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWITCH CLOSE 1st SCM8_L 8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L 9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L 10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L 7 BO-1 from SCM8_L 1 OUTGOING FIELD-1 - LOAD BREAK SWITCH OPEN 2nd SCM8_L 11 BI-1 to SCM8_L LOAD BREAK- ON 2nd SCM8_L 8 BO-2 from SCM8_L 2 OUTGOING FIELD-1 - LOAD BREAK SWITCH CLOSE 2nd SCM8_L 12 BI-2 to SCM8_L LOAD BREAK - OFF 2nd SCM8_L 13 BI-3 to SCM8_L EARTH SWITCH - ON 2nd SCM8_L 14 BI-4 to SCM8_L EARTH SWITCH - OFF 2nd SCM8_L 9 BO-1 from SCM8_L 1 OUTGOING FIELD-2 - LOAD BREAK SWITCH OPEN 3rd SCM8_L 15 BI-1 to SCM8_L LOAD BREAK - ON 3rd SCM8_L 10 BO-2 from SCM8_L 2 OUTGOING FIELD-2 - LOAD BREAK SWITCH CLOSE 3rd SCM8_L 16 BI-2 to SCM8_L LOAD BREAK - OFF 3rd SCM8_L 17 BI-3 to SCM8_L EARTH SWITCH - ON 3rd SCM8_L 18 BI-4 to SCM8_L EARTH SWITCH - OFF 3rd SCM8_L 19 BI-7 to REF615 Gas pressure NORMAL REF615 20 BI-8 to REF615 Gas pressure LOW REF615 21 BI-9 to REF615 Directional Fault Indicator A REF615 22 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS 23 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP 24 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP 25 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP 26 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP 27 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP 28 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP 29 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP 30 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP LED9 49 THERMAL TRIP LED10 74TC TCS ALARM LED11 COMMUNICATION ALARM OVERVIEW OPERATION PLAN: REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the 1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via IEC61850. 2nd SCM8_L 4BI & 2 BO in use 2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to 3rd SCM8_L 4BI & 2 BO in use operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850. 3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection. 4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX 5) "Pendant" eqipment will be used for all "C" and "V" fields motor control. 6) IEC61850 communication test report for all signals shall be provided for each FAT report. Classification: Internal Purpose #