Abb Tur Bi Bo Led Signal List Cyi With Rio 2021 r05

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Classification: Internal Purpose #

REF615: HBFDACAFNBALBNN21G (18BI/13BO) + (RIO600 1xSCM8_L)


CV CYI / Oct.2021 / R05
+ (Industrial Ethernet Switch - FL SWITCH SFNB 5TX)
BI total: BI BO total: BO Signal Nr COMMAND From:
Signal Nr Incoming Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615
1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615
2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615
3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615
4 BI-4 to REF615 DISCONNECTOR - OFF REF615
5 BI-5 to REF615 EARTH SWITCH - ON REF615
6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L
7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWTICH CLOSE 1st SCM8_L
8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L
9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L
10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L

11 BI-7 to REF615 Gas pressure NORMAL REF615


12 BI-8 to REF615 Gas pressure LOW REF615
13 BI-9 to REF615 Directional Fault Indicator A REF615
14 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS
15 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP
16 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP
17 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP
18 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP
19 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP
20 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP
21 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP
22 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP
LED9 49 THERMAL TRIP
LED10 74TC TCS ALARM
LED11 COMMUNICATION ALARM
OVERVIEW OPERATION PLAN:
REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the
1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via
IEC61850.
2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to
operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850.
3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection.
4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX
5) "Pendant" eqipment will be used for all "C" and "V" fields motor control.
6) IEC61850 communication test report for all signals shall be provided for each FAT report.
Classification: Internal Purpose #

REF615: HBFDACAFNBALBNN21G (18BI/13BO) + (RIO600 2xSCM8_L)


CCV CYI / Oct.2021 / R05
+ (Industrial Ethernet Switch - FL SWITCH SFNB 5TX)
BI total: BI BO total: BO Signal Nr COMMAND From:
Signal Nr Incoming Outgoing 1 Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615
1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615
2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615
3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615
4 BI-4 to REF615 DISCONNECTOR - OFF REF615
5 BI-5 to REF615 EARTH SWITCH - ON REF615
6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L
7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWITCH CLOSE 1st SCM8_L
8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L
9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L
10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L 7 BO-1 from SCM8_L 1 OUTGOING FIELD-1 - LOAD BREAK SWITCH OPEN 2nd SCM8_L
11 BI-1 to SCM8_L LOAD BREAK- ON 2nd SCM8_L 8 BO-2 from SCM8_L 2 OUTGOING FIELD-1 - LOAD BREAK SWITCH CLOSE 2nd SCM8_L
12 BI-2 to SCM8_L LOAD BREAK - OFF 2nd SCM8_L
13 BI-3 to SCM8_L EARTH SWITCH - ON 2nd SCM8_L
14 BI-4 to SCM8_L EARTH SWITCH - OFF 2nd SCM8_L

15 BI-7 to REF615 Gas pressure NORMAL REF615


16 BI-8 to REF615 Gas pressure LOW REF615
17 BI-9 to REF615 Directional Fault Indicator A REF615
18 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS
19 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP
20 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP
21 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP
22 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP
23 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP
24 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP
25 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP
26 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP
LED9 49 THERMAL TRIP
LED10 74TC TCS ALARM
LED11 COMMUNICATION ALARM
OVERVIEW OPERATION PLAN:
REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the
1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via
IEC61850.
2nd SCM8_L 4BI & 2 BO in use
2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to
operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850.
3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection.
4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX
5) "Pendant" eqipment will be used for all "C" and "V" fields motor control.
6) IEC61850 communication test report for all signals shall be provided for each FAT report.
Classification: Internal Purpose #

REF615: HBFDACAFNBALBNN21G (18BI/13BO) + (RIO600 3xSCM8_L)


CCCV CYI / Oct.2021 / R05
+ (Industrial Ethernet Switch - FL SWITCH SFNB 5TX)
BI total: BI BO total: BO Signal Nr COMMAND From:
Signal Nr Incoming Outgoing 1 Outgoing 2 Transformer Feeder To: 1 BO-1 from REF615 1 TRANSFORMER FEEDER - CB OPEN REF615
1 BI-1 to REF615 CIRCUIT BREAKER - ON REF615 2 BO-2 from REF615 2 TRANSFORMER FEEDER - CB CLOSE REF615
2 BI-2 to REF615 CIRCUIT BREAKER - OFF REF615 3 BO-3 from REF615 3 TRANSFORMER FEEDER - DISCONNECTOR OPEN REF615
3 BI-3 to REF615 DISCONNECTOR - ON REF615 4 BO-4 from REF615 4 TRANSFORMER FEEDER - DISCONNECTOR CLOSE REF615
4 BI-4 to REF615 DISCONNECTOR - OFF REF615
5 BI-5 to REF615 EARTH SWITCH - ON REF615
6 BI-6 to REF615 EARTH SWITCH - OFF REF615 5 BO-1 from SCM8_L 1 INCOMING FIELD - LOAD BREAK SWITCH OPEN 1st SCM8_L
7 BI-1 to SCM8_L LOAD BREAK - ON 1st SCM8_L 6 BO-2 from SCM8_L 2 INCOMING FIELD - LOAD BREAK SWITCH CLOSE 1st SCM8_L
8 BI-2 to SCM8_L LOAD BREAK - OFF 1st SCM8_L
9 BI-3 to SCM8_L EARTH SWITCH - ON 1st SCM8_L
10 BI-4 to SCM8_L EARTH SWITCH - OFF 1st SCM8_L 7 BO-1 from SCM8_L 1 OUTGOING FIELD-1 - LOAD BREAK SWITCH OPEN 2nd SCM8_L
11 BI-1 to SCM8_L LOAD BREAK- ON 2nd SCM8_L 8 BO-2 from SCM8_L 2 OUTGOING FIELD-1 - LOAD BREAK SWITCH CLOSE 2nd SCM8_L
12 BI-2 to SCM8_L LOAD BREAK - OFF 2nd SCM8_L
13 BI-3 to SCM8_L EARTH SWITCH - ON 2nd SCM8_L
14 BI-4 to SCM8_L EARTH SWITCH - OFF 2nd SCM8_L 9 BO-1 from SCM8_L 1 OUTGOING FIELD-2 - LOAD BREAK SWITCH OPEN 3rd SCM8_L
15 BI-1 to SCM8_L LOAD BREAK - ON 3rd SCM8_L 10 BO-2 from SCM8_L 2 OUTGOING FIELD-2 - LOAD BREAK SWITCH CLOSE 3rd SCM8_L
16 BI-2 to SCM8_L LOAD BREAK - OFF 3rd SCM8_L
17 BI-3 to SCM8_L EARTH SWITCH - ON 3rd SCM8_L
18 BI-4 to SCM8_L EARTH SWITCH - OFF 3rd SCM8_L
19 BI-7 to REF615 Gas pressure NORMAL REF615
20 BI-8 to REF615 Gas pressure LOW REF615
21 BI-9 to REF615 Directional Fault Indicator A REF615
22 BI-10 to REF615 Directional Fault Indicator B REF615 Signal Nr LEDS
23 BI-11 to REF615 Directional Fault Indicator A REF615 LED1 GENERAL TRIP
24 BI-12 to REF615 Directional Fault Indicator B REF615 LED2 50N EARTH PICK-UP
25 BI-13 to REF615 Directional Fault Indicator A REF615 LED3 50 SHORTCIRCUIT PICK-UP
26 BI-14 to REF615 Directional Fault Indicator B REF615 LED4 51/49 O.C. / THRM. PICK-UP
27 BI-15 to REF615 Monitoring Batterie level REF615 LED5 50N TRIP
28 BI-16 to REF615 Fuse Contact for circuit breaker for auxiliary power REF615 LED6 50-1 LV S.C. TRIP
29 BI-17 to REF615 Trip circuit supervision REF615 LED7 50-2 MV S.C. TRIP
30 BI-18 to REF615 SCADA Control Available REF615 LED8 51 OVERLOAD TRIP
LED9 49 THERMAL TRIP
LED10 74TC TCS ALARM
LED11 COMMUNICATION ALARM
OVERVIEW OPERATION PLAN:
REF615 18 BI & 4 BO in use 1) All disconnector,load break and earth switches& circuit breaker positions will be transferred as Binary Inputs to the
1st SCM8_L 4BI & 2 BO in use RIO600 and REF615 so WF OWNER can transfer all positions and alarms to WF Owner's SUBSTATION SCADA system via
IEC61850.
2nd SCM8_L 4BI & 2 BO in use
2) Binary outputs from RIO600 and REF615 will be transferred to circuit breaker and disconnector switches in order to
3rd SCM8_L 4BI & 2 BO in use operate them remotely from WF Owner's SUBSTATION SCADA system, via IEC61850.
3) "Local-Remote-SCADA" 3-position rotational switch will be use for selection.
4) 5xRJ45 port industrial switch will be used - FL SWITCH SFNB 5TX
5) "Pendant" eqipment will be used for all "C" and "V" fields motor control.
6) IEC61850 communication test report for all signals shall be provided for each FAT report.
Classification: Internal Purpose #

CYI / Oct.2021 / R05


HBFDACAFNBALBNN21G

LOCAL: Manual operation only.


REMOTE: Operation with "pendant" equipment only.
SCADA: IEC61850 remote operation only.

Industrial Ethernet Switch


FL SWITCH SFNB 5TX