Crowbar Protection For Doubly-Fed Induction Generators Under Grid Faults
Crowbar Protection For Doubly-Fed Induction Generators Under Grid Faults
Yutana Chongjarearn
Department of Electrical Engineering, Faculty of Engineering, Dhurakij Pundit University
110/1-4 Prachachuen Rd., Laksi, Bangkok, Thailand, 10210, Tel. 02-954-7300 Ext. 585, E-Mail: [email protected]
Keywords DFIG, Crowbar, Fault Ride Through. 2. Wind Turbine and DFIG Model
2.1 Wind turbine model
1. Introduction The power in the wind is extracted and then
The Doubly Fed Induction Generators (DFIGs ) are converted into mechanical power. The extracted wind
increasingly used in wind power generation. More than power (Pw) is described by the equation as follows
70% of the installed wind turbines are based on this type o f
induction machine [soter2007]. Many advantages of Pw 0.5R 2 v 3 C p , (1)
variable-speed DFIGs compared with fix-speed ind uct io n
generators which were identified in [1], [2] and [3]. As th e where ρis the air density, R is the turbine radius,
amount of installed wind turbine increases, it is b eco min g
v is the wind speed, CP is the power coefficient, an d θis
increasingly more important that turbine remain connected
to the grid during faults so-called fault ride through (FRT) , the pitch angle of rotor, γ =ωR/v is the tip speed ratio
as required by various national grid codes[4]. (TSR). The relationship between CP and γ for given values
The DFIG ride through system generally has a of pitch angle (θ) is displayed in [ref yc2011].
crowbar in the rotor circuit which will short-circuit the rotor
circuit in order to protect the rotor side converter from The output wind turbine torque related to the win d
over-currents[ref]. The crowbar may be consisted of either power is given by
bidirectional or unidirectional power electronic switches Tw Pw / w (2)
that will bypass the over-current, which cause the damages
the converter, into a crowbar resistor. Differen t v alu es o f where ωw is the turbine rotor speed in per unit (p u )
the crowbar resistor are used in the wind turbine system with respect to the synchronous speed.
resulting in a different behavior. A schematic diagram o f a The single-mass model is used as the drive train in
DFIG wind turbine including a crowbar is shown in Fig. 1. which the parameters are referred to the generator sid e . A
In this paper, the behaviors of the DFIG system per unit of the model can be given by
under grid faults influenced by the value of crowbar d
resistors are investigated. The paper provid es DFIG win d Te Tw 2 H (3)
turbine model with a grid supply connected to stator dt
winding, a rotor winding of the DFIG which two voltage where H is an inertia constant , ω is a per unit rot o r
source converters : a rotor-side converter (RSC) and a grid - speed, Te is a per unit generator torque and Tw is a per u n it
side converter (GSC) connected back-to-back in a d c lin k turbine torque.
2.2 DFIG model and power control
The dynamic model of DFIG is represented by the For GSC control, it can be concluded that t h e DC-
space vector representation of electrical quantities for stator link voltage is controlled by the d-axis GSC current (idg)
and rotor voltage referred to their natural frame: while the reactive power is controlled by the q-axis GSC
rotor current component (iqg). A block diagram of RSC
and GSC control is shown in Fig. 5.
1 d s
s
V ss R s i ss (4)
b dt Vdc Idg
1 d r
r + -
Idgref +
V rr R r i rr
- mg Vg
(5) Vdcref
b dt PI
Iqgref +
PI
Transfer to
stator frame
Qgref
Stator and rotor flux-linkage can be given by + - - GSC
Qg Iqg
ss L s i ss Lm i rs (6)
Ps Idr
rr Lr i rr Lm i sr (7)
- Idrref + - mr RSC
Psref + Vr
Transfer to
where superscript s and r refer to a stator an d ro t o r +
PI
Iqrref +
PI
rotor frame
-4
5. Simulation Results and Analysis Speed
The simulation scenario is defined as follow s : -6 Te
the DFIG is controlled to generate stator power of 1 Tw
-8
pu at unity power factor at normal operation, stator
-10
side of the DFIG remaining connected to the grid 9.8 10 10.2 10.4 10.6 10.8
time(sec)
during faults, as long as rotor over-current higher than
2 pu, a set of the crowbar resistors is activated to
Fig. 10 Simulation results for Speed, Electromechanical torque
connect to the rotor side of the generator while the
and T urbine torque
The peak rotor currents are decreased resulting with
Fig.9 apparently shows that the rotor current reaches using higher crowbar resistance values. Moreover, the
about 2pu at fault initiation but around 4.5 pu after fault currents are precipitated in a safety level of 2 pu wit h t h e
clearance. These high rotor currents can damage the ro t o r - usage of a minimum crowbar resistance value of 30 t imes
side converter (RSC) if it has no protection. During the of the rotor resistance value (30Rr) as shown in Fig. 12. As
fault occurrence (between time=10 and 10.15 sec) a result, the RSC will be protected from high rotor
electromechanical torque (Te ) falls from 1 pu to 0 pu currents.
because of demagnetization of the DFIG while turbine Rotor Currents (pu)
4.5
torque (Tw) remains constant at 1 pu. As a result, the turbine 4
speed (ωm) slightly rises but is rather constant b ecause o f 3.5
having speed control as shown in Fig 10. After fault 3
clearance at time =10.15 sec, turbine torque is immediately 2.5
decreased to zero and then a speed controller has res t art ed 2
to control the generator speed, thus reducing high speed to a 1.5
normal speed of 1.2 pu.
No CB 10 20 30 40 50
Crowbar resistance values (times of rotor resistance)
5.2 DFIG behavior under fault conditions, with
crowbar protection Fig. 12 Relations between crowbar resistance (times of rotor
resistance) and rotor current (pu)
The DFIG is operated as mentioned above in
beginning of section 5 and also has a crowbar p ro t ectio n. 6. Conclusion
Three different crowbar resistors are investigate; i.e. Rcb = This paper presents a stator voltage vector co nt rol
10Rr, 20Rr and 30Rr. The simulation results are shown in of DFIG wind turbine under normal and fault condit io ns.
Fig.11. The results show that stator active and reactive power can
Rotor Currents (pu) be independently controlled by manipulation of the d-axis
3
ira and q-axis rotor current components, respectively. Durin g
irb
2 irc
three-phase voltage fault, high rotor currents rise sharply .
1 This can damage the rotor-side converter and also high
0 DC-link voltage can occur. Finally, during the fault,
-1 unbalance of power in the shaft will cause the speed of the
-2 DFIG wind turbine to increase to a large extent if t h ere is
-3 no protection. Further research will use this developed
9.8 10 10.2 10.4 10.6 10.8
model to study the ride-through operation o f DFIG win d
time (sec) turbine.
a) 10Rr References
Rotor Currents (pu)
3 [1] S. Muller, M. Deicke, and R. W. De Doncker,
ira
2 irb "Doubly fed induction generator systems for wind
irc turbines," in IEEE Industry Applications Mag azin e.
1
vol. 8, 2002, pp. 26-33.
0 [2] I. Serban, F. Blaabjerg, I. Boldea, and Z. Chen, "A
-1 study of the Doubly-Fed Wind Power Generator
-2
Under Power System," in 2003 EPE Power
Electronics and Applications, 10th European
-3
9.8 10 10.2 10.4 10.6 10.8 Conference Proceedings, 2003, pp. 1-10.
time (sec)
b) 20Rr [3] L. Xu and Y. Wang, "Dynamic modeling and control
Rotor Currents (pu) of DFIG-based wind turbines under, unbalanced
3
ira network conditions," IEEE Transactions o n Po wer
2 irb Systems, vol. 22, 2007, pp. 314-323.
irc
1
[4] M. Tsili, S. Papathanassiou, G. Georgantzis, and G.
Antonopoulos, "Grid code requirements for large
0 wind farms: A review of technical regulations and
-1 available wind turbine technologies," in Proc.
-2
EWEC'08, Brussels , 2008, pp. 1-11.
[5] M. Yin, G. Li, M. Zhou, G. Liu, and C. Zhao, "Study
-3
9.8 10 10.2 10.4 10.6 10.8 on the control of DFIG and its responses to grid
time (sec)
disturbances," in IEEE Power Engineeri ng S ociety
c) 30Rr General Meeting Montreal, Que., 2006, pp. 1-6.
Fig.11 Simulated Rotor currents in various cro wbar [6] W. Sae-kok, "Simulation and Experimental System
resistance a) 10Rr b) 20Rr and c) 30Rr of a Doubly-Fed Induction Generator," in EECON
32th Electrical Engineering Conference. Prachinburi,
Thailand, 2009.