0% found this document useful (0 votes)
498 views1 page

Mycom Data Sheet

The document provides performance specifications for a MYCOM S200VL*-HE single stage ammonia screw compressor. Key specifications include a capacity of 258.6 kW at a compression ratio of 21, absorbed power of 186.7 kW from a 220 kW motor, and a coefficient of performance (COP) of 1.39. The compressor has a swept volume of 1460 m3/h and operates at speeds of 3550 min-1.

Uploaded by

Ashraf N Hania
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
498 views1 page

Mycom Data Sheet

The document provides performance specifications for a MYCOM S200VL*-HE single stage ammonia screw compressor. Key specifications include a capacity of 258.6 kW at a compression ratio of 21, absorbed power of 186.7 kW from a 220 kW motor, and a coefficient of performance (COP) of 1.39. The compressor has a swept volume of 1460 m3/h and operates at speeds of 3550 min-1.

Uploaded by

Ashraf N Hania
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DATE : 06-23-2022

MYCOM SCREW COMPRESSOR PERFORMANCE SINGLE STAGE (BOOSTER)

Title:
MODEL : N200VL*-HE
REFRIGERANT : AMMONIA

RECOMMENDED PORT : H

Vi : [-] 8.39
COMPRESSION RATIO : [-] 21.0

CAPACITY : [kW] 258.6


CAPACITY : [TR] 73.5
ABSORBED POWER : [kW] 186.7 220 Kw Motor

DRIVE SHAFT SPEED : [min-1] 3550 with VFD


COMPRESSOR SPEED : [min-1] 3550
INDICATOR POSITION : [%] 100
CONDENSING TEMP. : [degC] 37.0
EVAPORATIVE TEMP. : [degC] -41.0
SUCTION SUPERHEAT : [degC] 0.00
LIQUID SUBCOOLING : [degC] 5.00
SUCTION TEMP. : [degC] -41.0
OIL SUPPLY TEMP. : [degC] 50.0
SUCTION PRESS. : [MPaA] 0.068
DISCHARGE PRESS. : [MPaA] 1.43
OIL SUPPLY PRESS. : [MPaA] 1.63
SUCTION PRES. DROP : [MPa] 0.000
DISCHARGE PRES. DROP : [MPa] 0.000

SWEPT VOLUME : [m3/h] 1460


LOAD(SUCTION VOL. FLOW RATE) : [%] 100
DISCHARGE TEMP. : [degC] 86.6
REFRIG. FLOW RATE SUC. : [m3/h] 1180
REFRIG. FLOW RATE DIS. : [m3/h] 99.4
REFRIG. FLOW RATE SUC. : [kg/h] 721.2
REFRIG. FLOW RATE DIS. : [kg/h] 879.4
INJECT. OIL FLOW RATE : [L/min] 61.4
LUB. OIL FLOW RATE : [L/min] 56.8
F.SIDE OIL FLOW RATE : [L/min] 9.99
*TOTAL* OIL FLOW RATE : [L/min] 128
OIL HEAT REJECTION : [kW] 132.6
OIL SPEC HT : [J/kgK] 1930
OIL DENSITY : [kg/m3] 880

COP : [-] 1.39

--- SUPER HEAT is NOT counted in refrigeration capacity ---

--- WITH THERMO-SIPHON OIL COOLER ---

--- WITH LIQUID SUBCOOLER ---


INTERMED. TEMP. : [degC] -23.8
INTERMED. PRESS. : [MPaA] 0.160
INTERMED. SUPERHEAT : [degC] 0.00
LIQUID APPROACH TEMP. : [degC] 5.00
REFRIG. FLOW RATE : [m3/h] 116
REFRIG. FLOW RATE : [kg/h] 157.9
HEAT REJECTION : [kW] 47.4

--- Refrigeration oil is not soluble with refrigerant (mineral oil) ---

--- When choosing the motor set a safety factor of more than 10% for the brake power. ---

--- Please check carefully the operating range. ---


--- Reference temperature : Dew Point ---
! All data herein is for reference only.
! Content is subject to change without notice.

*** MYCOMW26 compressor performance table is valid until the end of March, 2023. ***

SP
MYCOM SCREW COMPRESSOR PERFORMANCE 26
MAYEKAWA MFG. CO., LTD. * All data herein is for reference only.
MYCOMW 26E * Content is subject to change without notice.