FusionModule5000 Smart Modular Data Center

V100R001C05
Product Description

Issue 04

Date 2020-01-14

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. i


FusionModule5000 Smart Modular Data Center
Product Description About This Document

About This Document

Purpose
This document describes the smart modular data center (smart module for short) as well as its
application scenarios and system architecture, providing the systemic information about the
smart module.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates a hazard with a high level of risk which, if not avoided,
will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided,
could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided,
could result in equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule5000 Smart Modular Data Center
Product Description About This Document

Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.

Issue 04 (2020-01-14)
Updated the USB description.

Issue 03 (2019-11-29)
Updated the USB description.

Issue 02 (2019-03-15)
Updated the manual name and so on.

Issue 01 (2018-11-27)
This issue is the first official release.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule5000 Smart Modular Data Center
Product Description Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Product Model .............................................................................................................................................................. 1
1.2 Positioning .................................................................................................................................................................... 1
1.3 Features ......................................................................................................................................................................... 1

2 Typical Application Scenarios and Configurations ............................................................... 3


2.1 Typical Application Scenarios ...................................................................................................................................... 3
2.2 Typical Configurations.................................................................................................................................................. 3
2.2.1 Configurations for the Single-Row 1200 mm Wide Aisle Containment .................................................................... 4
2.2.2 Configurations for the Dual-Row 1200 mm Wide Aisle Containment ...................................................................... 6

3 System Architecture ...................................................................................................................... 8


3.1 Structural System .......................................................................................................................................................... 8
3.1.1 Components of the Single-Row 1200 mm Wide Aisle Containment ......................................................................... 8
3.1.2 Components of the Dual-Row 1200 mm Wide Aisle Containment ........................................................................... 9
3.1.3 IT Cabinet ................................................................................................................................................................ 11
3.1.4 Network Cabinet ...................................................................................................................................................... 12
3.1.5 Skylight .................................................................................................................................................................... 13
3.1.6 Aisle End Door ........................................................................................................................................................ 14
3.1.7 Sealing Plate ............................................................................................................................................................ 15
3.1.8 Cable Trough ........................................................................................................................................................... 16
3.1.9 (Optional) Cable Tray .............................................................................................................................................. 16
3.1.10 (Optional) Adaptive Frame .................................................................................................................................... 17
3.2 Power Supply and Distribution System ...................................................................................................................... 17
3.2.1 Power Supply and Distribution System for Smart Module B .................................................................................. 18
3.2.2 Precision PDC.......................................................................................................................................................... 20
3.2.3 New Main Way ........................................................................................................................................................ 27
3.2.4 PDU2000 ................................................................................................................................................................. 28
3.3 Cooling System ........................................................................................................................................................... 29
3.3.1 NetCol5000-C Positioning ....................................................................................................................................... 29
3.3.2 NetCol5000-C Features ........................................................................................................................................... 29
3.3.3 NetCol5000-C Components ..................................................................................................................................... 30
3.3.3.1 NetCol5000-C Cooling Components .................................................................................................................... 30

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule5000 Smart Modular Data Center
Product Description Contents

3.3.3.2 NetCol5000-C Controller ..................................................................................................................................... 32


3.3.3.2.1 Appearance and Ports......................................................................................................................................... 32
3.3.3.2.2 Functions and Features ...................................................................................................................................... 34
3.3.3.3 NetCol5000-C Monitoring System ....................................................................................................................... 36
3.3.4 NetCol5000-C Operating Conditions ...................................................................................................................... 38
3.3.5 NetCol5000-C Technical Specifications .................................................................................................................. 40
3.4 Management System ................................................................................................................................................... 42
3.4.1 System Description .................................................................................................................................................. 43
3.4.2 Server ....................................................................................................................................................................... 45
3.4.3 ECC800 ................................................................................................................................................................... 46
3.4.4 Video System ........................................................................................................................................................... 51
3.4.4.1 IP Camera ............................................................................................................................................................. 51
3.4.4.2 VCN500 ................................................................................................................................................................ 53
3.4.5 Skylight Actuator ..................................................................................................................................................... 54
3.4.6 Access Control System ............................................................................................................................................ 57
3.4.6.1 Access Actuator .................................................................................................................................................... 57
3.4.6.2 (Optional) Aisle Access Control System ............................................................................................................... 60
3.4.6.3 (Optional) Cabinet Access Control System .......................................................................................................... 64
3.4.7 (Optional) Water Sensor .......................................................................................................................................... 66
3.4.8 (Optional) Smoke Detector ...................................................................................................................................... 67
3.4.9 (Optional) Temperature Sensor ................................................................................................................................ 68
3.4.10 Temperature and Humidity Sensor......................................................................................................................... 69
3.4.11 Multi-functional Sensor ......................................................................................................................................... 69
3.4.12 Rack Environment Unit ......................................................................................................................................... 71
3.4.13 Smart ETH Gateway .............................................................................................................................................. 73
3.4.14 WiFi Converter ...................................................................................................................................................... 75
3.4.15 Alarm Beacon ........................................................................................................................................................ 76
3.4.16 (Optional) LAN Switch ......................................................................................................................................... 77
3.4.17 PAD........................................................................................................................................................................ 78
3.5 Cable Management System ........................................................................................................................................ 80
3.6 Lighting System .......................................................................................................................................................... 82
3.6.1 AC Actuator ............................................................................................................................................................. 82
3.6.2 Aisle Light ............................................................................................................................................................... 84
3.7 Surge Protection and Grounding System .................................................................................................................... 85
3.7.1 Surge Protection Solution ........................................................................................................................................ 85
3.7.2 Grounding Solution ................................................................................................................................................. 85
3.8 Integrated Cabling System .......................................................................................................................................... 86
3.8.1 Cable Trough ........................................................................................................................................................... 86
3.8.2 Cable Routes for a Dual-Row Aisle Containment (New Main Way) ....................................................................... 88
3.8.3 Cables ...................................................................................................................................................................... 90

A Acronyms and Abbreviations .................................................................................................. 91

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. v


FusionModule5000 Smart Modular Data Center
Product Description 1 Overview

1 Overview

1.1 Product Model


Table 1-1 Product model description

Product Name Scenario

FusionModule: smart modular data center 5000: using chilled water smart cooling
products

1.2 Positioning
The smart modular data center solution is designed for medium- and large-sized data centers
that use chilled water for cooling. The solution applies to data centers for telecom, finance,
government, energy, power, and traffic sectors, Internet service providers (ISPs), and
large-sized enterprises.

1.3 Features
The smart modular data center features high integration, outstanding security and reliability,
space saving, high energy efficiency, quick installation, optimal compatibility, fast and
flexible deployment, and excellent monitoring. It is a new-generation smart modular data
center solution.

High Integration
 The smart module integrates a cabinet system, power supply and distribution system,
cooling system, facility management system, surge protection and grounding system,
auxiliary fire extinguishing system, and integrated cabling system. It provides an overall
solution.
 The integrated power supply and distribution system distributes power to smart cooling
products and IT equipment.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule5000 Smart Modular Data Center
Product Description 1 Overview

Outstanding Security and Reliability


 The smart module supports optional aisle and cabinet access control, which prevents
unauthorized personnel from entering the smart module and improves security.
 The auxiliary fire extinguishing system is used. It improves the data center safety. It
consists of the rotating skylight which opens automatically in case of fire and the
emergency button which helps open the door in case of emergency.
 The smart module supports two power inputs.
 Strong-current and weak-current cables, optical fibers, and network cables are routed
separately to minimize electromagnetic interference.

Space Saving and Energy Efficiency


 The smart module can be placed in a room of an office building.
 The smart module can be directly installed on a concrete floor in a building, which
simplifies engineering.
 Aisle lighting is available, saving electric energy.
 The smart module is delivered within a few days and can be quickly installed onsite.

Quick Installation
 The design minimizes the workload of engineering.
 The standardized installation procedures reduce the installation time and workload.

Optimal Compatibility
Modular power distribution allows for smooth expansion to meet various requirements.

Fast and Flexible Deployment


 The integrated design supports relocation of equipment with offices.
 Single-row cabinets or dual-row cabinets are deployed based on the equipment room size,
power consumption of a single cabinet, and expansion requirements.
 IT cabinets are flexibly equipped with servers as well as storage and network equipment
to meet enterprise requirements for web application and internal services.

Excellent Monitoring
 Various sensors monitor functional modules in the data center in real time.
 The web-based monitoring system enables remote management of functional modules.

Stable Cooling
The NetCol5000-C features efficient cooling, effective energy saving, high reliability, wide
working conditions, wide power range, high compatibility, intelligent monitoring, and easy
maintenance.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule5000 Smart Modular Data Center
Product Description 2 Typical Application Scenarios and Configurations

2 Typical Application Scenarios and


Configurations

2.1 Typical Application Scenarios


For smart module B, the UPS and batteries are installed outside the module while the
precision power distribution cabinet (PDC) or new main way is inside the module.

Customers should prepare dehumidifiers in customer equipment rooms to control the room humidity.

2.2 Typical Configurations


Typical configurations involve the single-row and dual-row 1200 mm wide aisle
containments.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule5000 Smart Modular Data Center
Product Description 2 Typical Application Scenarios and Configurations

2.2.1 Configurations for the Single-Row 1200 mm Wide Aisle


Containment
Figure 2-1 Single-row aisle containment (precision PDC)

Figure 2-2 Single-row aisle containment (new main way)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule5000 Smart Modular Data Center
Product Description 2 Typical Application Scenarios and Configurations

Figure 2-3 Floor plan of the single-row 1200 mm wide aisle containment (precision PDC)

In the above figures, NetCol5000-C065 in-row chilled water smart cooling product is used as an
example.

Table 2-1 Key technical specifications

Item Technical Specifications

Number of IT cabinets 6–24 cabinets


Equipment room space  In the scenario where the new main way is deployed,
the minimum floor height is 2.8 m when 2.0 m high IT
cabinets are deployed, 3.0 m when 2.2 m high IT
cabinets are deployed, and 3.3 m when 2.5 m high IT
cabinets are deployed.
 In the scenario where the new main way is not
deployed, the minimum floor height is 2.6 m when 2.0
m high IT cabinets are deployed, 2.8 m when 2.2 m
high IT cabinets are deployed, and 3.1 m when 2.5 m
high IT cabinets are deployed.
Cooling  NetCol5000-C030&032 in-row chilled water smart
cooling product
 NetCol5000-C065&080 in-row chilled water smart
cooling product
Power distribution Smart module B: precision PDC or new main way
Aisle 1200 mm wide single-row cold or hot aisle containment

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule5000 Smart Modular Data Center
Product Description 2 Typical Application Scenarios and Configurations

2.2.2 Configurations for the Dual-Row 1200 mm Wide Aisle


Containment
Figure 2-4 Dual-row aisle containment (precision PDC)

Figure 2-5 Dual-row aisle containment (new main way)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule5000 Smart Modular Data Center
Product Description 2 Typical Application Scenarios and Configurations

Figure 2-6 Floor plan of the dual-row 1200 mm wide aisle containment (precision PDC)

In the above figures, NetCol5000-C065 in-row chilled water smart cooling product is used as an
example.

Table 2-2 Key technical specifications

Item Technical Specifications


Number of IT 6–48 cabinets (max. 24 cabinets in an N+1 system; max. 48 cabinets in
cabinets a 2N system; max. module length: 15 m)
Equipment room  In the scenario where the new main way is deployed, the minimum
space floor height is 2.8 m when 2.0 m high IT cabinets are deployed, 3.0
m when 2.2 m high IT cabinets are deployed, and 3.3 m when 2.5
m high IT cabinets are deployed.
 In the scenario where the new main way is not deployed, the
minimum floor height is 2.6 m when 2.0 m high IT cabinets are
deployed, 2.8 m when 2.2 m high IT cabinets are deployed, and 3.1
m when 2.5 m high IT cabinets are deployed.
Cooling  NetCol5000-C030&032 in-row chilled water smart cooling product
 NetCol5000-C065&080 in-row chilled water smart cooling product
Power Smart module B: precision PDC or new main way
distribution
Aisle 1200 mm wide dual-row cold or hot aisle containment

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3 System Architecture

3.1 Structural System


3.1.1 Components of the Single-Row 1200 mm Wide Aisle
Containment
Overview
The single-row 1200 mm wide aisle containment can be a cold or hot aisle containment.

Figure 3-1 Components of the single-row 1200 mm wide cold aisle containment (precision PDC)

(1) End door (2) Control skylight (3) Flat or rotating skylight
(4) Cable trough (5) Precision PDC (6) IT cabinet
(7) Smart cooling product

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-2 Components of the single-row 1200 mm wide cold aisle containment (new main way)

(1) End door (2) Control skylight (3) Flat or rotating skylight
(4) New main way (5) Cable trough (6) IT cabinet
(7) Smart cooling product

3.1.2 Components of the Dual-Row 1200 mm Wide Aisle


Containment
The dual-row 1200 mm wide aisle containment can be a cold or hot aisle containment.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-3 Components of the dual-row 1200 mm wide cold aisle containment (precision PDC)

(1) End door (2) Control skylight (3) Flat or rotating skylight
(4) Cable trough (5) Precision PDC (6) IT cabinet
(7) Smart cooling product

Figure 3-4 Components of the dual-row 1200 mm wide cold aisle containment (new main way)

(1) End door (2) Control skylight (3) Flat or rotating skylight

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

(4) New main way (5) Cable trough (6) IT cabinet


(7) Smart cooling product

3.1.3 IT Cabinet
An IT cabinet used in the smart module complies with the International Electrotechnical
Commission (IEC) 60297-1 standard and provides stable installation space for servers in the
smart module, thereby ensuring safe operation of servers.

Figure 3-5 IT cabinet

The cabinet provides the following features:


 The ventilation rate of the front and rear doors is at least 70%.
 Two power distribution units (PDU2000s) can be vertically installed at the rear inside the
cabinet.
 The position of each U is marked on the vertical mounting bars.
 The front and rear doors are locked and can be unlocked only with dedicated keys.
 The cabinet supports a door status sensor and electronic access control.
 The static load is 1500 kg.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-1 Cabinet technical specifications

Item Technical Specifications


External dimensions  2000 mm x 600 mm x 1200 mm
(H x W x D)  2200 mm x 600 mm x 1200 mm
 2500 mm x 600 mm x 1200 mm
Color Black
Material High-intensity class A carbon cold rolled steel plate and zinc-coated
steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 A 2500 mm high cabinet provides 54 U available space.
 The cabinet depth for devices is 750 mm upon delivery. The
maximum depth for installing devices inside the cabinet can be
extended to 850 mm by adjusting the mounting bars every 25
mm.
 Positions for vertically installing two PDU2000s are provided at
the rear of the cabinet.
Installation mode Installed on a concrete floor, a base, or an ESD floor
Door opening mode The front door is a single door, and the rear door is a double one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2200 mm x 600 mm x 1200 mm: 137 kg
The weight of an  2500 mm x 600 mm x 1200 mm: 150 kg
empty cabinet
includes the weight
of the front and rear
doors.
Protection level IP20

3.1.4 Network Cabinet


The network cabinet provides space for integrated cabling and the cable management
interface for the smart module. For the network cabinet exterior, refer to the IT cabinet
exterior.

Table 3-2 Network cabinet technical specifications

Item Technical Specifications


External dimensions  2000 mm x 600 mm x 1200 mm
(H x W x D)  2200 mm x 600 mm x 1200 mm
 2500 mm x 600 mm x 1200 mm

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Technical Specifications


Color Black
Material High-intensity class A carbon cold rolled steel plate and zinc-coated
steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 A 2500 mm high cabinet provides 54 U available space.
 The distance between the front and rear rack rails can be
adjusted for every 25 mm. Positions for vertically installing two
PDU2000s are provided at the rear of the cabinet.
Installation mode Installed on a concrete floor, a base, or an ESD floor
Door opening mode The front door is a single door, and the rear door is a double one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2200 mm x 600 mm x 1200 mm: 137 kg
The weight of an  2500 mm x 600 mm x 1200 mm: 150 kg
empty cabinet
includes the weight
of the front and rear
doors.
Protection level IP20

3.1.5 Skylight
A skylight is used for sealing an aisle containment. Skylights are classified as control
skylights, rotating skylights, and flat skylights.
Control skylights are used for installing control devices and routing cables.

Table 3-3 Skylight technical specifications

Item Dimensions (H x W x D)

Control skylight 341 mm x 605 mm x 1334 mm


Flat or rotating skylight 341 mm x 605 mm x 1334 mm

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-6 Control skylight

(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel

Figure 3-7 Flat or rotating skylight

(1) Magnetic lock fixing position (2) Glass skylight (3) Skylight connective plate

3.1.6 Aisle End Door


End doors are classified into sliding doors and revolving doors. End doors are installed on
both ends of the aisle containment, which makes the module independent, improves
equipment efficiency, and helps onsite personnel or devices move into or out of the aisle
containment.
Sliding doors are opened horizontally, and double revolving doors are opened outward, with
an opening angle of 90°.

 Sliding doors can be opened only sideways, and therefore may involve risks during fire
extinguishing system acceptance.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 Only revolving doors can be configured for a single-row aisle.

Table 3-4 Aisle door dimensions

Aisle Door Type 2000 mm High 2200 mm High 2500 mm High


Scenario (H x W x Scenario (H x W x Scenario (H x W x
D) D) D)

Sliding door 2300 mm x 1400 2500 mm x 1400 2800 mm x 1400


mm x 54 mm mm x 54 mm mm x 54 mm
Revolving door 2300 mm x 1400 2500 mm x 1400 2800 mm x 1400
mm x 80 mm mm x 80 mm mm x 80 mm

Figure 3-8 Sliding door

Figure 3-9 Double revolving door

3.1.7 Sealing Plate


Sealing plates are used to seal aisles and apply to single-row aisle scenarios and scenarios
with a column.
Sealing plates are 600 mm wide, and can be 2000 mm, 2200 mm, or 2500 mm high.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-10 Sealing plate

3.1.8 Cable Trough


Cabinet cable troughs are categorized into signal cable troughs and power cable troughs.
Signal cables and power cables are routed in different cable troughs to separate strong-current
cables from weak-current cables.

Figure 3-11 600 mm cable trough

(1) Bracket (2) Supporting plate


(3) Partition plate (4) Position for the smart ETH gateway

3.1.9 (Optional) Cable Tray


Cable trays are used to route cables across two rows of cabinets in the smart module. If two
rows of cabinets are deployed, route strong-current and weak-current cables over the control
skylight at either end of the rows preferentially. If there are more than 24 cabinets, install one

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

cable tray on the top of end cabinets for routing power cables as there are many cables to be
routed.
A cable tray is 2.5 m long.

Figure 3-12 Cable tray

(1) Cable ladder support (2) Cable ladder

3.1.10 (Optional) Adaptive Frame


To meet requirements for cabinet height in different scenarios, top frames can be installed to
ensure that all cabinets in the smart module have the same height.

Table 3-5 Adaptive frame specifications

Component Width Depth Height Remarks


(mm) (mm) (mm)
Smart cooling product top 600 1200 200 Adapts to 2200 mm
frame high cabinets.

3.2 Power Supply and Distribution System


Features
 The smart module uses an intelligent integrated N+1 or 2N power supply and
distribution system.
 The power distribution branch of the integrated power supply and distribution system
can detect current, voltage, active power, electricity, and temperature.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.2.1 Power Supply and Distribution System for Smart Module B


N+1 System Power Distribution Diagram

Figure 3-13 N+1 system power distribution diagram (precision PDC)

Figure 3-14 N+1 system power distribution diagram (new main way)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

2N System Power Distribution Diagram

Figure 3-15 2N physical isolation system power distribution diagram (precision PDC)

Figure 3-16 2N non-physical isolation system power distribution diagram (precision PDC)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-17 2N system power distribution diagram (new main way)

3.2.2 Precision PDC


The precision PDC provides the following features:
 Modular design, facilitating capacity expansion and backup
 Compatible with cabinets of low to high power density
This section uses the full configuration with three output modules as an example.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-18 Appearance of a precision PDC with single input (2000 mm high)

(1) Indicators (2) MCCB input circuit


breaker
(3) Surge protective device (SPD) and SPD circuit (4) Monitoring board 1
breaker
(5) Monitoring board 4 (6) Monitoring board 2
(7) Monitoring board 5 (8) MCB output circuit breaker
(9) Monitoring board 3 (10) Monitoring board 6

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-19 Appearance of a precision PDC with single input (2200 mm high)

(1) Indicators (2) MCCB input circuit


breaker
(3) Surge protective device (SPD) and SPD circuit (4) Monitoring board 1
breaker
(5) Monitoring board 4 (6) Monitoring board 2
(7) Monitoring board 5 (8) MCB output circuit breaker
(9) Monitoring board 3 (10) Monitoring board 6

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-20 Appearance of a precision PDC with single input (2500 mm high)

(1) Indicators (2) MCCB input circuit


breaker
(3) Surge protective device (SPD) and SPD circuit (4) Monitoring board 1
breaker
(5) Monitoring board 4 (6) Monitoring board 2
(7) Monitoring board 5 (8) MCB output circuit breaker
(9) Monitoring board 3 (10) Monitoring board 6

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-21 Appearance of a precision PDC with dual inputs (2000 mm high)

(1) Indicators of route I (2) Indicators of route II


(3) Input circuit breaker of route I (4) Input circuit breaker of route II
(5) SPD and SPD circuit breaker of route I (6) SPD and SPD circuit breaker of route II
(7) Monitoring board 1 (8) Monitoring board 4
(9) Output circuit breaker of route I (10) Output circuit breaker of route II
(11) Monitoring board 2 (12) Monitoring board 5
(13) Monitoring board 3 (14) Monitoring board 6

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-22 Appearance of a precision PDC with dual inputs (2200 mm high)

(1) Indicators of route I (2) Indicators of route II


(3) Input circuit breaker of route I (4) Input circuit breaker of route II
(5) SPD and SPD circuit breaker of route I (6) SPD and SPD circuit breaker of route II
(7) Monitoring board 1 (8) Monitoring board 4
(9) Output circuit breaker of route I (10) Output circuit breaker of route II
(11) Monitoring board 2 (12) Monitoring board 5
(13) Monitoring board 3 (14) Monitoring board 6

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-23 Appearance of a precision PDC with dual inputs (2500 mm high)

(1) Indicators of route I (2) Indicators of route II


(3) Input circuit breaker of route I (4) Input circuit breaker of route II
(5) SPD and SPD circuit breaker of route I (6) SPD and SPD circuit breaker of route II
(7) Monitoring board 1 (8) Monitoring board 4
(9) Output circuit breaker of route I (10) Output circuit breaker of route II
(11) Monitoring board 2 (12) Monitoring board 5
(13) Monitoring board 3 (14) Monitoring board 6

Table 3-6 Technical specifications

Item Specifications
H x W x D (mm) 2000 x 600 x 1200, 2200 x 600 x 1200, 2500 x 600 x 1200
Weight (kg) < 450
Rated operating voltage (V) 208/220/380/400/415
Rated insulation voltage (V) 500
Rated frequency (Hz) 50/60
Rated operating current (A) 630/400/250/160

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Enclosure protection level IP20
Output switch Single- or three-phase 16 A/20 A/32 A/40 A/63 A;
maximum: 144 single-phase routes or 48 three-phase routes
Surge protection Class C SPD in standard configuration
Cable routing Routed in and out from the top
Certification CCC, CE, TLC
Environmental friendliness RoHS, REACH
Overvoltage level II
Operating temperature –5°C to +40°C
Relative humidity 5%–95%, non-condensing
Altitude ≤ 2000 m (If the altitude exceeds 2000 m, the device is
derated according to GB/T3859.2-93.)

3.2.3 New Main Way


Table 3-7 Features

Feature Description
High efficiency, Space saving: saves the IT cabinet space.
economical, and rapid
delivery Easy maintenance: short maintenance duration, less than 10
minutes for replacing a single power distribution unit.
High scalability: Busbar trunking units can be added. Each
busbar trunking unit connects to one power distribution unit.
Long lifespan: over 35 years
Safe, reliable, and High reliability: uses a foolproof structure with installation
flexible O&M position marks and spacing measures.
Easy O&M: can be easily maintained as the new main way is
highly reliable and allows users to replace power distribution
units.
Intelligent monitoring Easy to network through an FE port to implement
and flexible management teleindication, telemetering, and teleadjusting.
Flexible to manage and monitor the power usage effectiveness
(PUE) and maintenance.
Intelligently measures and monitors parameters such as
electricity, current, voltage, power factor, total active power,
total apparent power, total reactive power, and neutral wire
current.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-8 Technical specifications

Item Technical Specifications


System type TN-S supports three-phase five-wire input.
Rated operating voltage (Un) 380 V AC/400 V AC/415 V AC
Overvoltage type II
Rated operating current (In) at 40°C 250 A/400 A
Output switch Six 1-pole 40 A MCBs
Rated frequency 50 Hz/60 Hz
External communications port RJ45
Protection level IP30
Cabling mode Routed in from the end

3.2.4 PDU2000
Figure 3-24 Full-height PDU2000

Table 3-9 PDU2000 specifications

PDU2000 Type PDU2000 Model PDU2000 Output Port


Basic type PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19
PDU2000-16-3PH-24/6-B3 24 x C13 + 6 x C19
PDU2000-32-3PH-12/9-B2 12 x C13 + 9 x C19
PDU2000-32-1PH-24/6-B2 24 x C13 + 6 x C19
PDU2000-16-3PH-30/6-B3 30 x C13 + 6 x C19
PDU2000-32-3PH-24/9-B1 24 x C13 + 9 x C19
PDU2000-32-1PH-20/4-B10 20 x GB 10 A + 4 x GB 16 A
PDU2000-16-3PH-24/6-B4 24 x GB 10 A + 6 x GB 16 A
PDU2000-32-3PH-12/9-B3 12 x GB 10 A + 9 x GB 16 A

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.3 Cooling System


3.3.1 NetCol5000-C Positioning
With the rapid development of data centers, power consumption of core equipment in a
traditional equipment room has risen from 3–5 kW per cabinet to 6–10 kW per cabinet. In the
meantime, the design specifications of data centers have evolved, so have the environment
requirements for data centers (for example, the return air temperature and the inlet chilled
water temperature have risen).
Traditional air cooled cooling systems or half-sized/normal-temperature chilled water systems
are facing severe challenges of heat dissipation and energy conservation, and cannot meet the
requirements of new-generation data centers. Newly-developed in-row smart cooling products
are able to solve the issue of heat dissipation caused by high-density deployment, applicable
to new-generation data centers with the design of high return air temperatures and high inlet
water temperatures, and lower the cooling power consumption and the power usage
effectiveness (PUE) value of data centers. Thanks to good compatibility with standard
cabinets, they can be combined with standard cabinets, implementing the designs and
applications of modular data centers.

3.3.2 NetCol5000-C Features


Efficient
 The highly efficient EC fan saves more than 30% of energy than a common fan.
 Intelligent differential pressure control (optional): Saves energy compared with the
control mode of a normal fan.
 Wet film humidifier (optional): Lowers water quality requirements and supports a long
replacement interval, and saves energy by over 95% compared with a traditional
electrode humidifier.

Reliable
 Teamwork control: Enables smart cooling products to work in turn to avoid competitive
operating and supports dynamic cooling capacity allocation and backup of the main
control system.
 Dual power supplies: When the active power supply fails, the standby power supply
takes over automatically. When the active power supply is recovered, the power supply is
automatically switched back to the active power supply.
 Supports a wide range of input voltages to adapt to poor power grids.
 Intelligent differential pressure control (optional): Solves the issue of hot spots due to
insufficient air volume to improve reliability.

Simple
 Real-time display: The cooling capacity, air volume, power, and fan speed can be
displayed in real time on the control panel, which helps O&M personnel grasp the
running status of smart cooling products.
 Professional diagnosis system: Common alarms and faults can be located intelligently.
The intelligent and highly efficient system lowers skill requirements, simplify O&M, and
reduce O&M time.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 Startup wizard: A startup wizard is provided to guide operators through the


commissioning process. The smart cooling product running data is collected
automatically, which helps O&M personnel evaluate the status of the key components of
the smart cooling product, shortens the startup commissioning duration, simplifies the
startup commissioning, and reduces the commissioning costs.
 Automatic fault diagnosis: Automatically identifies the root cause when a fault occurs
and intelligently excludes irrelevant fault causes. This function helps O&M personnel
perform quick maintenance, greatly simplifying O&M and reducing the troubleshooting
time.
 Health management: Forecasts the life of key components and prompts for component
replacement. The function allows operators to know the life span status of core
components so that they can formulate an O&M strategy in advance.

3.3.3 NetCol5000-C Components


3.3.3.1 NetCol5000-C Cooling Components

Figure 3-25 NetCol5000-C Appearance (300 mm wide)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-26 NetCol5000-C Appearance (600 mm wide)

The smart cooling product consists of the heat exchanger, chilled water valve, electronically
commutated (EC) fan, air filter, wet film humidifier (optional), and micro differential pressure
sensor (optional).
 Heat exchanger
The I-type finned-tube exchanger with a high cooling efficiency adopts the synergy field
principle and computational fluid dynamics (CFD) to optimize the flow path design,
which greatly improves the heat exchange efficiency.
 Chilled water valve
The chilled water valve, also known as the chilled water proportional integral regulating
valve, features incremental proportional-integral-derivative (PID) control with precise
adjustment and accurate control.
 EC fan
− The axial fan comes from a high-end brand and provides high reliability and a long
service life.
− The highly efficient EC fan saves more than 30% of energy than a common fan.
− You can view the power and speed status as well as obtain fault information in real
time over the LCD, allowing you to view the status and locate a fault.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 Air filter
The G4 (optional F5) air filter meets requirements for equipment room cleanliness.
 Wet film humidifier
− The wet film humidifier has low water quality requirements and high environment
adaptability. In most cases, tap water can be used without special water treatment.
− The wet film humidifier has a simple structure and is easy to remove, clean, and
maintain.
− The wet film humidifier quickly starts and generates huge humidification capacity.
− The wet film humidifier consumes less than over 95% of energy compared with a
traditional electrode humidifier.
 Micro differential pressure sensor
Intelligent differential pressure control (optional): Saves energy compared with the
control mode of a normal fan.

3.3.3.2 NetCol5000-C Controller


3.3.3.2.1 Appearance and Ports

Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 3-27
shows the position of the indicator. Table 3-10 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.

Figure 3-27 Display panel

(1) Indicator (2) Display panel

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-10 Indicator and buzzer status description

Alarm Status Indicator Buzzer


The device is operating properly, or a Green No buzzing
warning is generated.
There is an unacknowledged major alarm. Yellow Intermittent buzzing
There is an unacknowledged critical alarm. Red Constant buzzing

Ports

Figure 3-28 Controller side ports

Table 3-11 Ports

No. Name Note


1 MUS05A Reserved
2 FE (fast Ethernet) communications port
3 CAN communications port for the main control board and LCD
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to the
smart cooling product over the Service Expert app.
Obtain the initial startup password during deployment.
View or obtain the running information about the smart
cooling product during preventive maintenance.
(Applicable to V200R001C20 and later versions)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

No. Name Note


NOTE
Only Huawei service engineers or authorized service engineers are
allowed to use the WiFi module. To ensure security, remove the WiFi
module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade software.
6 RST restart switch for the display
7 SD Reserved
8 SW1-4 Dual in-line package (DIP) switch on LCD

3.3.3.2.2 Functions and Features

Functions
 Single unit control: Each smart cooling product has an independent control system, LCD,
humidifier, and T/H sensor to ensure its normal operating and high-precision operating.
The controller provides logic control over components in each smart cooling product to
meet the indoor temperature and humidity requirements.
 Display and operations: The 7-inch touchscreen of the controller allows you to set
parameters for the device and query the device status.
 The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the unit
− Teleindication: startup/shutdown, overvoltage/undervoltage, supply water
overtemperature/undertemperature, return air overtemperature/undertemperature,
return air overhumidity/underhumidity, air filter normal/blocked, and fan
normal/fault
− Teleadjust: smart cooling product startup/shutdown
− Teleadjusting: temperature, humidity, and alarm threshold
 Teamwork control: Up to 32 smart cooling products can be networked for teamwork.
When multiple smart cooling products work cooperatively, heat load is optimally
distributed to reduce power consumption and backup is provided to improve reliability.
− Backup: When a smart cooling product in the group is faulty, the backup smart
cooling product starts to operate automatically to improve the reliability of the
smart cooling product system.
− Rotation: Each smart cooling product enters the backup mode periodically.
− On-demand operation: The number of operating smart cooling products varies
depending on the thermal load in the equipment room to meet requirements
promptly, eliminate hot spots, and save energy.
− Anti-competitive running: A mechanism is adopted to prevent the smart cooling
products in the same equipment room operating in opposite status to save energy.
 Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management software (NetEco, ECC, app, and Web) provided
by Huawei.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 A large space is available for recording and storing fault alarm data, and 1500 historical
alarms can be stored.
 Access logs can be traced back. At least 1000 historical login and setting records can be
stored.
 The monitoring system displays 30 days' temperature and humidity in colored curves.
O&M personnel can view the unit operating status onsite.
 A comprehensive power monitoring function is provided. Faults such as overvoltage,
undervoltage, mains power failure, high frequency, and low frequency are diagnosed and
appropriate alarms are reported and recorded. Automatic protection, recovery, and restart
are also provided.
 The embedded wizard commissioning program guides the operator through the startup
commissioning. The controller automatically collects or instructs the operator to collect
the operating data produced in the process, and analyzes the commissioning result
automatically. This ensures the commissioning quality, simplifies the startup
commissioning, and shortens the commissioning duration.
 The embedded professional fault diagnosis system automatically locates the fault cause
and instructs the operator to rectify the fault. This simplifies fault handling and improves
efficiency.
 The controller displays the current cooling load rate and recommended optimal water
temperature (intelligently calculated to meet current load requirements), which helps
lower the power consumption of chillers.

Features
 The controller provides a touchscreen with a user-friendly interface.
 The controller is highly precise and responsive.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification upon the first startup is required to ensure that the smart cooling
product is started after valid authentication to avoid quality or security issues caused by
unauthorized startup.
 The LCD displays the margin of cooling capacity at the moment so that you can improve
the operating efficiency of the equipment room.
 The controller protects the smart cooling product against overvoltage, undervoltage,
abnormal power failure, and water leakage, which ensures the reliable operation of the
system.
 The cooling capacity, air volume, as well as the operating status and runtime of each
component in the smart cooling product are displayed on the LCD in real time.
 The controller provides a professional fault locating system that automatically displays
the root cause and maintenance policy for the fault, facilitating maintenance.
 The controller provides abundant external ports such as FE ports, CAN ports, RS485
ports, and USB ports that are protected by a security mechanism. These ports flexibly
meet the communication requirements and feature good electrical isolation (signal
terminals will not break down or flash over within 1 minute at a 500 V DC voltage to
ground).
 The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the NetEco.
 The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 If the indoor temperature is out of the normal range, an audible and visible alarm signal
is sent automatically.
 Fans can be maintained without power-off so that the normal operations of other fans
will not be affected.

3.3.3.3 NetCol5000-C Monitoring System


The monitoring system provides logic control, data collection, control demand delivering,
alarm reporting, data storage, user right management, and teamwork control functions.
The smart cooling product can interwork with the customer's monitoring system over an
RS485 port or FE port on the monitoring system. If RS485 connection is used, the
Modbus-RTU protocol is supported. If FE connection is used, the Modbus-TCP and SNMP
protocols are supported. Key smart cooling product parameters, including but not limited to
the temperatures and humidity of the inlet and outlet air, power supply status and operating
status of the smart cooling product, fan status, and alarms, can be uploaded to the monitoring
system.
Up to 32 smart cooling products can be connected over a controller area network (CAN) for
teamwork to save energy and extend the service life. Any smart cooling product can be set as
the master unit. The following figure shows the monitoring system network diagram.

Figure 3-29 FE teamwork network diagram

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-30 FE monitoring network diagram

Figure 3-31 Northbound RS485 monitoring network diagram

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-32 CAN teamwork network diagram

3.3.4 NetCol5000-C Operating Conditions


Pipe Ports

Table 3-12 Pipe ports of NetCol5000-C030&032

Item Description
Water outlet pipe G 1 in. port with inner threads
Water inlet pipe G 1 in. port with inner threads
(Optional) Humidifier water inlet G 1/2 in. port with inner threads
pipe
Forcible drainpipe Water pump port with an outer diameter of 9.8 mm
Automatic drainpipe BSPP 1/2 in. port with inner threads

Table 3-13 Pipe ports of NetCol5000-C 65 kW & 80 kW

Item Description

Water outlet pipe G 1–1/2 in. port with inner threads


Water inlet pipe G 1–1/2 in. port with inner threads
(Optional) Humidifier water inlet G 1/2 in. port with inner threads
pipe
Forcible drainpipe Water pump port with an outer diameter of 9.8 mm
Automatic drainpipe BSPP 1/2 in. port with inner threads

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Installation Requirements

Table 3-14 Installation requirements

Item Description
Room door  2000 mm high: width ≥ 1.2 m, height ≥ 2.3 m, the cabinet
may topple over in a short time.
 2200 mm high: width ≥ 1.2 m, height ≥ 2.5 m, the cabinet
may topple over in a short time.
 2500 mm high: width ≥ 1.2 m, height ≥ 2.8 m, the cabinet
may topple over in a short time.
Floor Floor bearing capacity ≥ 530 kg/m2
Floor height ≥ 300 mm
Pipe routing Bottom pipe routing
Cabling mode Top cabling
Drainage requirements Automatic drainage
Power distribution Leakage circuit breakers are not used for the main power
route. If leakage circuit breakers are required by the customer
or by local regulations, use the residual current circuit breakers
(RCCBs) that are not sensitive to the single-phase DC pulses
and transient current pulses.

Operating Specifications

Table 3-15 Operating specifications

Item Specifications
Operating ambient temperature 4–55°C
Operating humidity 5%–95% RH
Inlet water temperature of chilled 7–20°C (water, glycol solution)
water or glycol solution
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m: normal use; 1000–4000 m: derated
Temperature adjustment range Return air: 18–45°C
Supply air: 15–35°C
Temperature adjustment precision ±1°C
Humidity adjustment range 20%–80% RH
Humidity adjustment precision ±5% RH

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Air outlet static pressure  NetCol5000-C0300&032: 0–20 Pa
 NetCol5000-C065&080: 0–50 Pa

3.3.5 NetCol5000-C Technical Specifications


Table 3-16 Technical specifications of NetCol5000-C030

Item NetCol5000-C030H90D0/ NetCol5000-C030H9HD0


NetCol5000-C030H90E0 /NetCol5000-C030H9HE0

Power system 220–240 V AC, 1 PH, 50/60 Hz


Number of fans 6
Cooling capacity (kW) 30a
Air volume (m3/h) 5000
Humidification No Yes
Humidification capacity 0 1.5
(kg/h)
External dimensions (H x W 2000 x 300 x 1200
x D, mm)
Air filter level G4
a: The return air dry-bulb temperature / wet-bulb temperature is 37°C/ 21.2°C, the inlet /
outlet temperature of chilled water is 10°C/ 15°C.

Table 3-17 Technical specifications of NetCol5000-C032

Item NetCol5000-C032H90D0 NetCol5000-C032H9HD0

Power system 220–240 V AC, 1 PH, 50/60 Hz


Number of fans 6
Cooling capacity (kW) 32a
Air volume (m3/h) 5400
Humidification No Yes
Humidification capacity 0 1.5
(kg/h)
External dimensions (H x W 2200 x 300 x 1200
x D, mm)
Air filter level G4

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item NetCol5000-C032H90D0 NetCol5000-C032H9HD0


a: The return air dry-bulb temperature / wet-bulb temperature is 37°C/ 21.2°C, the inlet /
outlet temperature of chilled water is 10°C/ 15°C.

Table 3-18 Technical specifications of NetCol5000-C065

Item NetCol5000-C065H9B202 NetCol5000-C065H9B202


0030E2 W030E2

Power system 220–240 V AC, 1 PH, 50/60 Hz


Number of fans 10
Cooling capacity (kW) 65
Air volume (m3/h) 10000
Water flow (m3/h) 11.9
Water pressure drop (kPa) 100
Humidification No Yes
Humidification capacity 0 3
(kg/h)
Maximum operating current 15
(A)
Recommended upstream 32
circuit breaker (A)
External dimensions (H x W 2000 x 600 x 1200
x D, mm)
Air filter level G4
Net weight/Gross weight 200/228 202/230
(kg)
Note: Rated working conditions are that the return air temperature is 37°C; the return air
relative humidity is 24%; the supply/return water temperatures are 10°C/15°C respectively;
and the static pressure outside the smart cooling product is 0 Pa.

Table 3-19 Technical specifications of NetCol5000-C080

Item NetCol5000-C080H9B202 NetCol5000-C080H9B202


W020D4 0020D4

Power system 220–240 V AC, 1 PH, 50/60 Hz


Number of fans 12
Cooling capacity (kW) 80

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item NetCol5000-C080H9B202 NetCol5000-C080H9B202


W020D4 0020D4

Air volume (m3/h) 12000


Water flow (m3/h) 14
Water pressure drop (kPa) 100
Humidification No Yes
Humidification capacity 0 3
(kg/h)
Maximum operating current 17
(A)
Recommended upstream 32
circuit breaker (A)
External dimensions (H x W 2500 x 600 x 1200
x D, mm)
Air filter level G4
Net weight/Gross weight 238/268 240/270
(kg)
Note: Rated working conditions are that the return air temperature is 37°C; the return air
relative humidity is 24%; the supply/return water temperatures are 10°C/15°C respectively;
and the static pressure outside the smart cooling product is 0 Pa.

3.4 Management System


Table 3-20 Management system configurations

Function ECC800 ECC800 NetEco


WebUI App

Work order management No No Yes


Energy efficiency management No No Yes
PUE statistics Yes Yes Yes
Capacity management Yes Yes Yes
Generating alarms for SNMP northbound Yes No Yes
equipment
Monitoring data for SNMP northbound Yes No Yes
equipment
Mobile app O&M Yes Yes Yes

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Function ECC800 ECC800 NetEco


WebUI App
Monitoring data/alarms for power supply Yes Yes Yes
and distribution equipment
Monitoring data/alarms for cooling Yes Yes Yes
equipment
Monitoring data/alarms for environment Yes Yes Yes
equipment
Monitoring data/alarms for fire No No Yes
extinguishing equipment
Access control management Yes Yes Yes
Intelligent lighting Yes Yes Yes
View presetting Yes Yes No
(manually
drag)
Alarm notification by SMS or email Alarm No Optional
notification
by SMS
(optional)
Alarm
notification
by email (yes)
Log recording Yes Yes Yes
Management range A single A single Multiple
smart module smart module smart
modules
Configuration principle Mandatory Optional Optional

3.4.1 System Description


The management system consists of the management software and other components. It
implements data collection and management for various processes and infrastructure of the
smart module.
The ECC800 provides the real-time status, alarms, and configuration information about the
equipment inside the smart module for management. It also provides a graphical user
interface (GUI) for ease of operating and maintaining equipment inside the smart module.
With a flexible structure and modular design, the NetEco can manage infrastructure of a
single smart module or multiple smart modules in different areas in a centralized manner.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-33 Management system inside the smart module (precision PDC)

Figure 3-34 Management system inside the smart module (new main way)

The smart module provides the WiFi and RF_Z wireless networking functions. The mobile
app can be connected by wireless networking. Certain southbound components (such as the

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

skylight actuator, AC actuator, multi-functional sensor, and access actuator) can be connected
by RF_Z wireless networking.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system can monitor the following equipment:
 Power equipment, including precision smart cooling products, precision PDCs, and new
main ways
 Environment monitoring equipment, including multi-functional sensors (smoke,
temperature, and humidity sensors) and water sensors
 Video equipment, including cameras and network video recorders VCN
 Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
 Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.

3.4.2 Server
Tecal RH2288 V2 Server
The Tecal RH2288 V2 rack server (RH2288 V2 for short) of Huawei features large-capacity
and high-performance. It serves as the monitoring host of the NetEco and is responsible for
data processing and analysis.
The server is a standard 2 U rack server, and supports standard rack mounting.

Figure 3-35 RH2288 V2 server

The RH2288 V2 server has the following features:


 The server has powerful computing, storage, and expansion capabilities.
 The server can be flexibly configured with value-added components to provide diverse
functions.

Table 3-21 RH2288 V2 technical specifications

Item Specifications
Equipment 2 U, H x W x D: 87.5 mm x 447 mm x 740 mm
Can be installed in a standard cabinet that is 19
inches wide and 1000 mm deep or deeper

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Main board CPU One or two
CPU model Intel®Xeon® E5-2600 (Romely-EP) series 4C/6C/8C
processor; maximum configuration: 135 W processor
of 3.3 GHz dominant frequency and the L3 cache of
20 MB for a CPU
Memory 24 DIMMs slots, supports RDIMM/LRDIMM
memory of DDR3, a maximum of 768 GB
Hard drive Supports eight 2.5-inch 6 Gbit/s hot-swappable
SAS/SATA/SSD hard drives, or twelve 3.5-inch 6
Gbit/s hot-swappable SAS/SATA hard drives and
two 2.5-inch built-in 6 Gbit/s hot-swappable
SAS/SATA/SSD hard drives.
Expansion Supports six expansion slots for PCIe 3.0 cards: one
slot for PCIe3.0X16, four slots for PCIe3.0X8, and
one dedicated slot for RAID.

3.4.3 ECC800
The ECC800 consists of two power supply units (PSUs) and an ECC800 main control module.
It monitors the equipment and environment in the smart module.

Figure 3-36 ECC800 controller (front view)

(1) PSU (2) PSU (3) Status (4) 3G/4G


indicator antenna port
(5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW
and LAN_1–LAN_2) input ports antenna port button
(9) DO_1–2 dry contact outputs (10) RS485 port (11) Default (12) USB
(COM1–4/12 V) button port
(13) ECC800 main control
module

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-37 ECC800 controller (rear view)

(1) 53.5VDC_OUT1 (2) 53.5VDC_OUT2 (3) AC_INPUT1


(4) AC_INPUT2

Table 3-22 ECC800 technical specifications

Item Specifications

Power input  Two AC inputs


 Rated operating voltage: 200–240 V AC or 100–120 V
AC
 Rated operating frequency: 50 Hz/60 Hz
Power output  Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)
 Output power of two power supplies: 2000 W (176–300
V AC); 940 W (linear derating at 85–175 V AC)
 Output power of a single power supply: 1000 W
(176–300 V AC); 470 W (linear derating at 85–175 V
AC)
FE port expansion Supports two WAN ports and two LAN ports with the
10/100M communications rate
RS485 serial port  Four RS485 ports with the default communications rate
expansion of 9600 bit/s
 Each port provides 12 V DC power with the rated current
of 450 mA
AI/DI expansion (RJ45)  Supports six AI/DI ports to connect to smoke detectors,
water sensors, and temperature sensors
 Each port provides 12 V DC power with the rated current
of 85 mA
DO expansion (RJ45) Two DO ports, both supporting active and passive DO
 Supports passive (dry contact) DO port with contact point
capacity of 20 W, maximum withstand voltage of 60 V
DC, and rated current of 500 mA.
 Supports the active DO port with an output voltage of 12
V DC and output current of 450 mA.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Wireless communication Wireless communication that complies with IEEE802.15.4
3G (optional) Supports 3G (WCDMA) communication and is compatible
with 2G (GSM) communication. A standard SIM card slot is
provided
NOTE
The prerequisite for using a SIM card is that the site has signal
coverage.

USB  After installing the WiFi module, connect the WiFi


module to the ECC800 using the app on the mobile phone
or tablet computer to view the basic information about the
smart module, such as layout, resources, energy
efficiency, environment, and alarms.
 Insert a USB flash drive to export historical data, device
data, fault information, and configuration files, and
import or export the device configuration data and
historical data.
Button  SW: wireless network pairing button
 Default: button for restoring the default IP address

Table 3-23 Indicators on the ECC800 main control module

Indicator Color Name Status Description

RUN Green Module running Steady on The power supply is


status indicator normal, the program is
being loaded, or WiFi
WPS is pairing.
Off The power supply fails.
Blinking at long The software runs
intervals properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s), or
the ECC800 registers
with the NetEco
successfully.
Blinking at short The ECC800 does not
intervals register with the NetEco
(the indicator blinks at 4
Hz, on for 0.125s and
then off for 0.125s).
ALM Red Alarm indicator Steady on A system failure alarm is
generated.
Off The system is normal.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


3G Green 3G status Steady on The 3G module is
indicator powered on.
Off The 3G module stops
running, or no 3G module
is configured.
Blinking at long The 3G module succeeds
intervals in dial-up (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at short The 3G module registers
intervals with the operator network
successfully (the
indicator blinks at 4 Hz,
on for 0.125s and then off
for 0.125s).
RF_Z Green Communication Steady on No network parameters
status indicator exist, or a network is to
be created.
Blinking at long A network is being set
intervals up, and no node access is
allowed (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at super A network is set up, and
short intervals node access is allowed
(the indicator blinks at 10
Hz, on for 0.05s and then
off for 0.05s).

Table 3-24 PSU indicator description

Indicator Color Name Status Description


Green Power Steady on The PSU has a power
indicator input.
Off The PSU has no power
input or is faulty.
Blinking at long Querying is in progress
intervals (the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).
Blinking at short The application program is
intervals being loaded (the indicator
blinks at 4 Hz, on for
0.125s and then off for
0.125s).

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


Yellow Alarm Steady on The PSU has generated a
indicator prewarning indicating that
power will be limited due
to ambient
overtemperature, or a
protection shutdown alarm
due to ambient
overtemperature or
undertemperature.
Power input overvoltage or
undervoltage protection
Reverse DC input polarity
Slight current imbalance
Output overvoltage
Hibernating
Off No alarm is generated.
Blinking at long The PSU fails to
intervals communicate (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Red Fault Steady on The PSU locks out due to
indicator output overvoltage.
The PSU delivers no output
due to an internal fault.
Off The PSU is running
properly.

Table 3-25 Wireless network pairing and IP address reset buttons

Name Function Operation Description Indicator Status


Description

SW Wireless In non-wireless network (802.15.4) The RF_Z indicator


network pairing mode, press and hold down is blinking at super
(802.15.4) the button for 1.2s to 5s to enter the short intervals.
pairing wireless network pairing mode.
In wireless network (802.15.4) The RF_Z indicator
pairing mode, press and hold down is blinking at long
the button for 1.2s to 5s to exit the intervals.
pairing mode; or the system
automatically exits the pairing mode
after 30 minutes without pressing
the button.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Name Function Operation Description Indicator Status


Description
Press and hold down the button for The RF_Z indicator
more than 6s to clear network is on.
parameters.
WiFi pairing In non-WiFi pairing mode, press the  When the system
button button for less than 1.2s to enter the enters the pairing
WiFi pairing mode. mode, the RUN
indicator is
steady on.
 After pairing
succeeds, the
RUN indicator
blinks just as
before WiFi
pairing.
 If pairing does
not succeed in 3
minutes, the RUN
indicator blinks
just as before
WiFi pairing.
Default IP address reset Press and hold down the button for None
3s. Then the IP address for the
ECC800 WAN_1 port will restore
to the default address 192.168.1.10.

3.4.4 Video System


The video surveillance subsystem consists of the camera and VCN (a network video recorder)
and implements real-time monitoring, video storage, and video playback.

3.4.4.1 IP Camera
The IPC6325-WD-VR IP camera (IPC6325 camera for short) is a two-megapixel wide
dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-38 IPC6325 camera

Table 3-26 IPC6325 camera technical specifications

Item Specifications
Image sensor 1/2.7" two-megapixel progressive scan CMOS
Lowest illuminance  Color: 0.01 lux (F1.4, AGC ON)
 Black and white: 0.004 lux (F1.4, AGC ON)
0 lux (infrared enabled)
Wide dynamic range 120 dB
Focal length 2.8–12 mm manual zoom, 4.3x optical zoom
Video coding format H.265/H.264/MJPEG
Maximum resolution 1920 x 1080
Intelligent video analysis Supports tripwire detection, loitering detection, intrusion
detection, abandoned object detection, removed object
detection, target color recognition, classifications of
people and vehicles, and metadata backhaul.
Power supply PoE (802.3at/af), 24 V AC±25%, 24 V DC±25%, 12 V
DC±25% (polarity-insensitive DC power supply),
applicable to DC/AC adapter and PoE hot backup
Protection level IP66; complying with IEC 60529
Vandal-proof class IK10; complying with IEC 62262

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.4.4.2 VCN500

Figure 3-39 VCN500

Table 3-27 VCN500 performance specifications

Item Specifications
Video input A VCN500 supports the access from a maximum of 32
cameras and the maximum access bandwidth of 160 Mbit/s.
Video transfer A VCN500 supports the video transfer from 32 cameras or of
160 Mbit/s.
Storage A VCN500 supports the storage access from a maximum of
32 cameras and the maximum storage access bandwidth of
160 Mbit/s.
Video playback and A VCN500 supports video playback and download of 32
download cameras or 160 Mbit/s.

Table 3-28 VCN500 hardware specifications

Item Specifications

Hard drive slot Twelve 3.5-inch hard drive slots


Hard drive type and Twelve 4 TB SATA hard drives
quantity NOTE
The VCN500 supports hard drives at enterprise and monitoring
levels.

RAID control card The VCN500 does not have a RAID control card on its
mainboard.
CPU type and quantity 1 x 1 GHz, maximum 10 MB cache
Memory capacity 2 GB
I/O port Two service network ports, with RJ45 connectors and
LNK/ACT indicators
Power parameters Single power supply only
Maximum PSU power: 250 W

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
AC power input voltage range: 100–240 V AC
AC power frequency range: 50–60 Hz
Weight (full configuration) ≤ 20 kg
Typical power 40 W
consumption (excluding
hard drives)
Maximum power 70 W
consumption (excluding
hard drives)
Typical power 170 W
consumption (including
monitoring hard drives)
Maximum power 215 W
consumption (including
monitoring hard drives)
Typical power 200 W
consumption (including
enterprise hard drives)
Maximum power 250 W
consumption (including
enterprise hard drives)
Dimensions (H x W x D) 86.1 mm x 447.0 mm x 470.0 mm

3.4.5 Skylight Actuator


The skylight actuator controls the rotating skylight on the aisle containment of the smart
module through the alarm linkage information from the equipment room fire extinguishing
system or the control information from the upper host. The skylight actuator supports E-labels
and wireless networking (802.15.4).

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-40 Skylight actuator

(1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor
magnetic lock DO window open button DI input port input port
output port input port
(5) BLINK button (6) Status indicator (7) Address DIP (8) COM1 RS485
switch port
(9) COM2 RS485 (10) PoE port (11) 48 V power
port port

Table 3-29 Skylight actuator technical specifications

Item Specifications
Power input 36–60 V DC input voltage, Phoenix terminal
PoE port  FE communication with the rate of 10/100M
 36–60 V DC power input
Wireless One wireless port that complies with IEEE802.15.4, mutual
communication backup with FE communication
AI/DI port Two AI/DI ports for detecting equipment room fire
extinguishing linkage signals; smoke detection signals also
supported
DO output One 12 V DC power output for controlling the skylight magnetic
lock; driving six skylight magnetic locks simultaneously
DI input One DI input port for connecting to the skylight open button
BLINK button  Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network and
start networking.
 Hold down the button for more than 6s to clear network
parameters.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Address DIP switch 4-pin address DIP switch
E-label Supported

Table 3-30 Skylight actuator indicator description

Indicator Color Name Status Description

Power Green Power input Steady on The power input is normal.


status indicator
Off There is no power input.
RUN Green Operating status Off The power is abnormal or the
indicator board program is loading.
Blinking at The skylight actuator has
long intervals successfully registered with
the ECC800 and the software
runs properly (blinking at 0.5
Hz, on for 1s and then off for
1s).
Blinking at The communication is
short intervals disconnected or the skylight
actuator fails to register with
the ECC800 (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Blinking The indicator blinks at super
short intervals (blinking at 10
Hz, on for 0.05s and then off
for 0.05s) for 0.5s, and then
turns off for 0.5s. The cycle
lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm is
generated.
Off No system alarm is generated.
RF_Z Green Communication Steady on No network parameters exist,
status indicator or a network is to be created.
Blinking at A network is being set up, and
long intervals no node access is allowed (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s
and then off for 0.05s).

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


Blinking The skylight actuator is
intermittently searching for a network (the
at super short indicator blinks at super short
intervals intervals for 0.5s and then
turns off for 0.5s).

Table 3-31 LOCK/GND/BUTTON/GND port pin definitions

Item Description

LOCK/GND pin sequence LOCK 12V_OUT


GND GND
BUTTON/GND pin sequence BUTTON DI3
GND GND

3.4.6 Access Control System


3.4.6.1 Access Actuator
The access actuator is the control component for the aisle door in a smart module. It connects
to the ECC800-Pro controller over FE port, wireless networking (802.15.4). It opens the
magnetic lock by detecting the card swiping information of the card reader, door open button
information, and fire linkage information. It has access right management, access event record,
and alarm record functions.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-41 Access actuator

(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry (11) AI/DI_1 dry (12) LOCK/GND/GATE/COM door
contact (Reserved port contact (Reserved port status or magnetic lock port
for linkage control or for exit button)
third-party fire
extinguishing system
dry contacts)

Specifications

Table 3-32 Access actuator technical specifications

Item Specifications

Power input  DC input: Terminal, with input voltage of 36–60 V DC


 POE input: One POE port that complies with
IEEE802.3at.
POE port FE communication, 10/100M communications rate
Wireless communication One wireless communication port that complies with
IEEE802.15.4, mutual backup with FE communication
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit
button

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
DO/DI port  One 12 V DC power output that controls magnetic
locks, terminal
 One DI input port for connecting to the door status
switch
RS485 serial port expansion Two RS485 ports (one route) with the default
communications rate of 9600 bit/s, physical port cascading
supported (reserved function)
Wiegand interface Two Wiegand interfaces, 12 V DC card reader operating
power output; two routes of card readers (non-fingerprint
readers) can operate at the same time.
BLINK button  Press the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a
network and start networking.
 Hold down the button for more than 10 seconds to clear
network parameters.
Address DIP switch 4-pin address DIP switch
E-label Supported

Indicators

Table 3-33 Access actuator indicator description

Indicator Color Name Status


PWR Green Power input status  Steady on: The power input is normal.
indicator  Off: There is no power input.
RUN Green Communication  Off: The power is abnormal or the
status indicator board program is loading.
 Blinking at long intervals: The access
actuator successfully registers with the
ECC800-Pro and the software runs
properly (the indicator blinks at 0.5 Hz,
on for 1s and then off for 1s).
 Blinking at short intervals: The
communication is disconnected or the
access actuator fails to register with the
ECC800-Pro (the indicator blinks at 4
Hz, on for 0.125s and then off for
0.125s).
 Blinking: The indicator blinks at super
short intervals for 0.5s (blinking at 10
Hz, on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The cycle
lasts for 5s.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status


ALM Red Alarm indicator  Steady on: A system failure alarm is
generated.
 Off: No system alarm is generated.
RF_Z Green Wireless  Steady on: No network parameters
communication exist, or a network is to be created.
status indicator  Blinking at long intervals: A network
is set up, and no node access is allowed
(the indicator blinks at 0.5 Hz, on for
1s and then off for 1s).
 Blinking at super short intervals: A
network is set up, and node access is
allowed (the indicator blinks at 10 Hz,
on for 0.05s and then off for 0.05s).
 Blinking intermittently at super short
intervals: The access actuator is
searching for a network (the indicator
blinks at super short intervals for 0.5s
and then turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 3-34 lists the LOCK/GND/GATE/COM port pin definitions.

Table 3-34 LOCK/GND/GATE/COM port pin definitions

Item Description
LOCK/GND (control magnetic locks) pin sequence LOCK 12V_OUT
GND GND
GATE/COM (door status) pin sequence GATE DI1
COM COM

3.4.6.2 (Optional) Aisle Access Control System


The aisle access control system is used in an aisle containment. It monitors and collects data
for devices and personnel moving into or out of the aisle containment. Diverse access control
devices such as the fingerprint and card reader with a keypad, fingerprint and card reader, and
card reader with a keypad are supported.
 The access control system applies to the equipment room, aisle containment, and cabinet
doors.
 The access control system consists of an access actuator, fingerprint reader with a
keypad, magnetic lock, and exit button.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 The access control system is configured with an emergency button that can disconnect
the power supply to the magnetic lock to open the door.

Fingerprint and Card Reader with a Keypad

Figure 3-42 Fingerprint and card reader with a keypad

Table 3-35 Specifications of the fingerprint and card reader with a keypad

Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12V DC±15%
Rated operating current 300mA±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status  Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
 Fingerprint collection: The red indicator for the
fingerprint reader is on.
 Unauthorized fingerprint collection: The buzzer
sounds twice, and the red and blue indicators blink
twice.
 Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
 Card swiping: The buzzer sounds once, and the red
and blue indicators blink once.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Fingerprint and Card Reader

Figure 3-43 Fingerprint and card reader

Table 3-36 Specifications of the fingerprint and card reader

Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Operating voltage Rated voltage: 12 V DC ±5%
Operating current Rated current: 300 mA ±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Working status  Standby: The blue indicator is on, and the green
indicator for the fingerprint reader is steady on.
 Fingerprint collection: The red indicator for the
fingerprint reader is on.
 Unauthorized fingerprint collection: The buzzer
sounds twice, and the red and blue indicators blink
twice.
 Authorized fingerprint collection: The buzzer sounds
once, and the red and blue indicators blink once.
 Card swiping: The buzzer sounds once, and the red
and blue indicators blink once.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Card Reader with a Keypad

Figure 3-44 Card reader with a keypad

Table 3-37 Specifications of the card reader with a keypad

Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current 80 mA, dynamic operating current
(card swiping, key pressing) 150 mA, minimum input
current 12 V DC/300 mA
Communications mode Wiegand communications port

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Magnetic Lock

Figure 3-45 Double door magnetic lock

Figure 3-46 Single door magnetic lock

Figure 3-47 Magnetic lock for a sliding door

3.4.6.3 (Optional) Cabinet Access Control System


The cabinet door access control system applies to cabinets in the aisle containment to ensure
data and device security.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Cabinet Electronic Lock

Figure 3-48 Cabinet electronic lock

Table 3-38 Cabinet electronic lock specifications

Item Specifications
Rated input voltage 12V DC
Rated current 200–300 mA
Unlock mode Power on to unlock
Card type supported IC card
Mechanically unlock Supported

Features:
 An IC card can be used after being authorized using software.
 An IC card can be authorized for one lock or all locks.
 Door opening information is recorded through a network.
 The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
 The system supports remote door opening.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

(Optional) Mechanical Code Lock

Figure 3-49 Cabinet code lock

Functions and features


 The cabinet door can be opened with only the key and without the password.
 The cabinet door can be opened with only the password and without the key.
 The user can set a password.
 A password should only contain three digits.
 If a user forgot the password, he can reset it.

3.4.7 (Optional) Water Sensor


A water sensor monitors the leak water on the floor in real time. When water intrusion is
found, the water sensor generates an audible alarm and delivers dry contact signals to report
the alarm.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-50 Water sensor and water detection cable

Table 3-39 Water sensor technical specifications

Item Specifications

Operating voltage 12 V DC (9–16 V DC)


Output when no liquid exists Closed
Output when liquid exists Open
Insulation resistance > 500 megohms
Operating environment –20°C to +70°C, 10%–80% RH
(non-condensing)
Storage environment –40°C to +80°C, 10%–80% RH
(non-condensing)
Default length of the water detection cable 5m
Extensibility The water detection cable can be connected
to a quick-connect terminal and extended
flexibly to a maximum of 50 m.
Water detection cable reliability The water detection cable cannot be
installed on a metal surface.
Reliability Failure rate: 800 fits
Power consumption <1W

3.4.8 (Optional) Smoke Detector


Smoke detectors are used to detect smoke in an aisle containment.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-51 Smoke detector

Table 3-40 Smoke detector technical specifications

Item Specifications
Operating voltage 9–16 V DC
Quiescent current < 8 mA
Alarm current < 35 mA
Output mode Relay output
Output contact capacity 3 A 120 V AC or 3 A 24 V DC
Operating temperature –10°C to +50°C
Ambient humidity ≤ 95% RH
External dimensions Diameter: 112 mm; height: 41 mm

3.4.9 (Optional) Temperature Sensor


Figure 3-52 Temperature sensor

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-41 Temperature sensor specifications

Item Specifications
Temperature measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 10–16 V DC
Storage temperature –40°C to +70°C

3.4.10 Temperature and Humidity Sensor


Figure 3-53 Appearance

Table 3-42 Temperature and humidity sensor specifications

Item Specifications
Measurement range –20°C to +70°C
Measurement precision ±1°C
Operating temperature –10°C to +55°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +70°C

3.4.11 Multi-functional Sensor


A multi-functional sensor integrates the smoke sensor and temperature and humidity sensor
and can connect to the ECC800 controller system over PoE or wireless communication.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-54 Multi-functional sensor

Table 3-43 Multi-functional sensor technical specifications

Item Specifications
Temperature monitoring –40°C to +80°C, precision ≤ ±0.5°C (0–50°C)
Humidity monitoring 0–100% RH, precision ≤ ±5% RH (25°C, 20%–80% RH)
Smoke monitoring Complies with Ul217. The smoke sensor generates an
alarm when testing 3.2% weak dust for each foot.
PoE port One PoE port that complies with IEEE802.3AT
RS485 port Reserved
DI input One DI input port, 12 V DC power input
BLINK button Wireless communication:
 Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network
and start networking.
 Hold down the button for more than 6s to clear
network parameters.
Smoke sensor test button Supported
E-label Supported

Table 3-44 Indicators on the multi-functional sensor

Indicator Color Name Status Description

RUN Green Module running Steady on The power supply is normal.


status indicator
Off The power supply fails.
Blinking at The multi-functional sensor
long intervals has successfully registered
with the ECC800 and the
software runs properly
(blinking at 0.5 Hz, on for 1s
and then off for 1s).

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


Blinking at The multi-functional sensor
short intervals fails to register with the
ECC800 or the
communication is
disconnected (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Blinking The indicator blinks at super
short intervals (blinking at
10 Hz, on for 0.05s and then
off for 0.05s) for 0.5s, and
then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm or
smoke alarm is generated.
Off No system alarm is
generated.
RF_Z Green Communication Steady on No network parameters exist,
status indicator or a network is to be created.
Blinking at A network is being set up,
long intervals and no node access is
allowed (the indicator blinks
at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at A network is set up, and
super short node access is allowed (the
intervals indicator blinks at 10 Hz, on
for 0.05s and then off for
0.05s).
Blinking The multi-functional sensor
intermittently is searching for a network
at super short (the indicator blinks at super
intervals short intervals for 0.5s and
then turns off for 0.5s).

3.4.12 Rack Environment Unit


The rack environment unit is used to collect and control environmental data for IT cabinets in
the smart module.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-55 Rack environment unit

(1) Ground port (2) 48 V DC power (3) PoE port (4) COM1/12V port
input port
(5) COM2/12V port (6) COM3 port (7) COM4 port (8) NTC1–3 ports
(9) NTC4–6 ports (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) BLINK button (15) Status indicator

Table 3-45 Technical specifications for the rack environment unit

Item Specifications
Power input  DC input: Phoenix terminal, with an input voltage
range of 36–60 V DC
 PoE power supply: 36–60 V DC power input
12 V power output Two 12 V DC power outputs with the rated output current
of 250 mA
FE port FE communication with the rate of 10/100M
RS485 serial port expansion  Four RS485 ports with the default communications
rate of 9600 bit/s
 Among the four RS485 ports, two support 12 V DC
power output with the rated current of 400 mA.
 The other two are isolated, with the default
communications rate of 9600 bit/s, and do not support
power output.
AI/DI input Two active 12 V DC, 200 mA (rated) AI/DI input ports
Temperature sensor port Provides two RJ45 ports to connect to six temperature
sensors, each RJ45 port connecting to three temperature
sensors.
BLINK button Supports the blinking function.

Table 3-46 Indicators on the rack environment unit

Indicator Color Name Status Description

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


PWR Green Power input Steady on The power input is normal.
status indicator
Off There is no power input.
RUN Green Module Off The power is abnormal or the board
running status program is loading.
indicator
Blinking The software runs properly (the
at long indicator blinks at 0.5 Hz, on for 1s
intervals and then off for 1s).
Blinking PoE communication fails (the
at short indicator blinks at 4 Hz, on for
intervals 0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals (blinking at 10 Hz, on for
0.05s and then off for 0.05s) for
0.5s, and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm is generated.
Off No system alarm is generated.

3.4.13 Smart ETH Gateway


The smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800 and can be flexibly deployed in the smart module.

Figure 3-56 Smart ETH gateway

(1) PWR_IN (2) FE_1 cascading (3) PoE_1–2 ports (4) PoE_3–4 ports
cascading power port signal port
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-47 Technical specifications for a smart ETH gateway

Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power output  PWR_OUT D-type power output terminal, for power cascading,
output voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, Phoenix terminal, output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M
communication rate, for the cascading between smart ETH gateways
and the communication with the host
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 45–55 V DC of power output, complying with
IEEE802.3at
BLINK button If you press the BLINK button, the RUN indicator blinks
intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 10s.

Table 3-48 Indicators on the smart ETH gateway

Indicator Color Name Status Description

PWR Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

RUN Green Module Off The power supply fails.


running
status Blinking at The smart ETH gateway has
indicator long intervals successfully registered with the
ECC800 and the software runs
properly (blinking at 0.5 Hz, on for
1s and then off for 1s).
Blinking at The smart ETH gateway has failed
short to register with the ECC800
intervals (blinking at 4 Hz, on for 0.125s and
then off for 0.125s).
Blinking The indicator blinks at super short
intervals (blinking at 10 Hz, on for
0.05s and then off for 0.05s) for
0.5s, and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.4.14 WiFi Converter


The WiFi converter is used in the smart module to convert PoE signals into WiFi signals for
communicating with devices such as the PAD and mobile phone.

Figure 3-57 WiFi converter

(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset button (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port

Table 3-49 WiFi converter technical specifications

Item Specifications
Power input  DC input: Phoenix terminal, with input voltage of 36–60 V DC
 PoE power supply: 36–60 V DC power input
WiFi function  2.4 GHz frequency, two antennas, supporting eight STA
connections, 50 m WiFi coverage (no blockage)
 Supports the WPS button.
PoE port One PoE port, complying with IEEE802.3AT, 25.5 W
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter.
WPS button Support fast WiFi access by WPS

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

WPS function: When the WiFi is enabled, if you choose Advanced settings > WPS connection on the
WLAN of the intelligent device (such as a mobile phone and PAD) and press the WPS button on the
WiFi converter at the same time, the intelligent device will quickly connect to the WiFi hotspot of the
smart module.

Table 3-50 WiFi converter indicator description

Indicator Color Name Status Description


RUN Green Module Steady on The power supply is normal.
running
status Off The power supply fails.
indicator
Blinking at The WiFi converter has successfully
long registered with the ECC800 and the
intervals software runs properly (blinking at
0.5 Hz, on for 1s and then off for
1s).
Blinking at The WiFi converter fails to register
short with the ECC800 or the
intervals communication is disconnected (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.
WiFi Green WiFi status Steady on The WiFi converter is powered on
indicator but there is no data communication.
Blinking Data communication is in progress.
WPS Green WPS mode Off The WPS is normal.
indicator
Blinking WPS matching mode. If the
matching fails, the WPS indicator
turns off after blinking for 2
minutes. If the matching is
successful, the WPS indicator turns
off.

3.4.15 Alarm Beacon


The alarm beacon is installed outside an aisle containment. When fire or smoke is detected in
the smart module, the alarm beacon generates an audible alarm and blinks to inform operators
of fire and safety risks.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-58 Alarm beacon

Table 3-51 Alarm beacon structural specifications

Item Specifications
Dimensions (L x W x H) 130 mm x 75 mm x 55 mm
Installation requirements Installed on a wall
Protection level IP50
Environment protection requirements RoHS, Reach
Mean time between failures (MTBF) ≥ 100,000 hours

Table 3-52 Alarm beacon technical specifications

Item Specifications

Power input RJ45 port; supported input voltage 9–16 V DC; operating
current ≤ 400 mA
Acoustic pressure ≥ 100±3 dB/30 cm
Working duration ≥ 45 min

3.4.16 (Optional) LAN Switch


Figure 3-59 S5320 LAN switch

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Table 3-53 S5320 LAN switch specifications

Item Specifications
External dimensions (H x W x D) 44.4 mm x 442 mm x 420 mm
Maximum power (full configuration) 913 W (power consumption: 173 W; PoE:
740 W)
Weight ≤ 8 kg
DC input voltage Rated voltage: –48 V DC to –60 V DC
Voltage range: –36 V DC to –72 V DC
AC input voltage Rated voltage: 100–240 V AC
Voltage range: 90–264 V AC
Temperature  Operating temperature: 0°C to +50°C
NOTE
When the altitude ranges from 1800 m to 5000
m, the highest temperature decreases by 1°C for
each additional 220 m.
 Storage temperature: –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude  Non-PoE device:
− With DC power: 0–2000 m
− With AC power: 0–5000 m
 PoE device: 0–5000 m

3.4.17 PAD
The PAD allows wireless access to the data center facility management system. You can
monitor the equipment in the data center and environmental parameters in real time over the
app.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-60 PAD

Table 3-54 PAD structural specifications

Item Specifications
Dimensions (L x W x H) 248.5 mm x 150 mm x 8.3 mm
Weight About 433 g

Table 3-55 PAD technical specifications

Item Specifications
Touchscreen 9.6-inch, 1280 x 800 IPS full view, IPS screen, and capacitive
five-point touch
Processor MSM8916, quad-core A53, 1.2 GHz integrated chip
WLAN 802.11a/b/g/[email protected] GHz & 5 GHz
Storage  ROM: 16 GB
 Memory: 2 GB LPDDR3
 Extension card: microSD, a maximum of 64 GB supported
Button/Port  Power and volume buttons
 3.5 mm stereo headphone port
 Micro SD card port
 Micro-USB port that supports charging and data
synchronization with a PC
Battery  Material: Li-polymer
 Capacity: 4800 mAh
 WiFi connection/Web page browse time: about 6.5 hours
 Power adapter charge time: about 6 hours
Operating system Android 4.4 (KitKat) + EMUI 3.0

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.5 Cable Management System


Cables inside cabinets are sorted by cable managers, cable rings, and cable trays. Cable
managers route cables horizontally, cable rings on the cabinet side route cables vertically, and
cable trays route cables from the cabinet front to cabinet rear.

Cable Manager
A cable manager is used to manage cables inside a cabinet horizontally.

Figure 3-61 Cable manager

Table 3-56 1 U cable manager specifications

Dimensions (H x W x D) Weight Space Occupied


43.6 mm x 482.6 mm x 91 mm 0.56 kg 1U

Cable Ring
A cable ring is installed on a side post in the cabinet to secure vertically routed cables.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-62 Cable ring

Table 3-57 Cable ring specifications

Name Dimensions (H x W x D) Weight


Standard cable ring 55 mm x 48 mm x 188.6 mm 0.163 kg
Small cable ring 55 mm x 48 mm x 44 mm 0.096 kg

Cable Tray
A cable tray is used for forward and backward cabling. It uses mounting ears to facilitate
device installation.

Figure 3-63 Cable tray

Table 3-58 Cable tray specifications

Dimensions (H x W x D) Weight Space Occupied

43.6 mm x 482.6 mm x 250 mm 1.89 kg 1U

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.6 Lighting System


The lighting system is composed of AC actuators and aisle lights. They can be configured
based on site requirements.

3.6.1 AC Actuator
The AC actuator is used in a smart module to control the lighting inside the smart module by
receiving commands from the access control system or host, infrared linkage information
(disabled by default), or signals from the light button. It also provides a charging port for the
pad. The AC actuator can connect to the ECC800 controller by wireless networking
(802.15.4).

Figure 3-64 AC actuator

(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicators
(5) BLINK button (6) AI/DI dry (7) COM1–2 RS485
contact port

Table 3-59 AC actuator technical specifications

Item Specifications

Power input One AC input, 90–240 V AC


Power output Two AC outputs, 90–240 V AC, maximum current 5 A

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Wireless communication One wireless communication port, complying with
IEEE802.15.4
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI detection One AI/DI dry contact connects to the lighting switch, and
the other one is reserved.
BLINK button  Press the button for less than 1s to start blinking.
 Hold down the button for 1–5s to search for a network
and start networking.
 Hold down the button for more than 6s to clear network
parameters.

Table 3-60 AC actuator indicator description

Indicator Color Name Status Description


Power Green Power status Steady on The power input is normal.
indicator
Off There is no power input.
RUN Green Operating status Off The power is abnormal or
indicator the board program is
loading.
Blinking at long The AC actuator has
intervals successfully registered with
the ECC800 and the
software runs properly
(blinking at 0.5 Hz, on for
1s and then off for 1s).
Blinking at short The communication is
intervals disconnected or the AC
actuator fails to register
with the ECC800 (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking The indicator blinks at
super short intervals
(blinking at 10 Hz, on for
0.05s and then off for
0.05s) for 0.5s, and then
turns off for 0.5s. The cycle
lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm is
generated.
Off No system alarm is
generated.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Indicator Color Name Status Description


RF_Z Green Communication Steady on No network parameters
status indicator exist, or a network is to be
created.
Blinking at long A network is being set up,
intervals and no node access is
allowed (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at super A network is set up, and
short intervals node access is allowed (the
indicator blinks at 10 Hz,
on for 0.05s and then off
for 0.05s).
Blinking The AC actuator is
intermittently at searching for a network
super short (the indicator blinks at
intervals super short intervals for
0.5s and then turns off for
0.5s).

3.6.2 Aisle Light


Light emitting diode (LED) lights are used for lighting in an aisle. The lights are installed on
the top at the two sides of the aisle.

Figure 3-65 LED light

Table 3-61 LED light technical specifications

Item Specifications

Installation mode Ceiling installation


Light base requirement The light base and light are integrated.
Protection level IP20
Electrical insulation class CLASS I
Standards compliance IEC 60598

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Item Specifications
Rated operating voltage 220–240 V AC (working normally in the
range of 198 V AC to 264 V AC)
Light color Daylight color
Luminous flux ≥ 500 lm
Power 9W

3.7 Surge Protection and Grounding System


The surge protection and grounding system of the smart module consists of the surge
protection solution and grounding solution.

3.7.1 Surge Protection Solution


Surge protection modules are installed in the precision PDC.

3.7.2 Grounding Solution


Each cabinet in the smart module connects to the ground grid nearby using ground cables with
the minimum cross-sectional area of 16 mm2.
Use 100 mm x 0.3 mm copper foils or 25 mm2 braided copper strips for the equipotential
bonding grid, and use 30 mm x 3 mm red copper strips for the equipotential bonding bar
based on the customer's configurations.

Figure 3-66 M-shaped/grid grounding (single-bar) solution diagram

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-67 M-shaped/grid grounding (dual-bar) solution diagram

The new main way connects to the ground grid nearby over the ground point on the general input unit.

3.8 Integrated Cabling System


The integrated cabling system of the smart module includes cable routing devices and cables.

3.8.1 Cable Trough


Cable troughs are installed on the top of cabinets for routing cables. There are two types of
cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDC and one network cabinet, power
cables need to be routed to the other end of the module through the control skylight on the top
of the PDC while signal cables need to be routed to the other end of the module through the
control skylight on the top of the network cabinet.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-68 Cable routes through cable troughs

(1) Network cabinet (2) Optical fiber (3) Signal cable


(4) PDC (5) Power cable

If the distance between two modules is 1200 mm, power cables need to be routed to the other
module through the cable trays on the top of the PDC while signal cables need to be routed to
the other module through the cable trays on the top of the network cabinet.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

Figure 3-69 Cable routes between modules

(1) Power cable (2) Network cable (signal cable) (3) Optical fiber

3.8.2 Cable Routes for a Dual-Row Aisle Containment (New Main


Way)

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 88


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

 Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.
 Power cables are first connected to the general input unit in the smart module.

Figure 3-70 Routing power and signal cables (new main way)

(1) General input unit (2) Power distribution unit (3) Network cabinet
(4) Power cables (5) Signal cables

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 89


FusionModule5000 Smart Modular Data Center
Product Description 3 System Architecture

3.8.3 Cables
Power Cables
The power cables include power cables to the precision PDC, smart cooling product,
PDU2000, and others.

Ground Cables
The ground cables include ground cables to the PDU8000, smart cooling product, and IT
cabinet.

Monitoring Cables
The monitoring cables include monitoring cables to the smart cooling product, precision PDC,
video devices, and access control devices, cables in the network cabinet, and various sensor
cables.

Cables to the Fire Extinguishing Auxiliary Components


Cables to the fire extinguishing auxiliary components include cables to the alarm beacon and
skylight actuator.

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 90


FusionModule5000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
AC alternate current

D
DC direct current

E
EC electronic commutation
ECC energy control center
ETH Ethernet

F
FE fast Ethernet

I
IC integrated circuit
IT Internet technology

L
LCD liquid crystal display
LED light emitting diode

M
MTBF mean time between failures

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 91


FusionModule5000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

MTTR mean time to repair

N
NTC negative temperature coefficient

P
PDC power distribution cabinet
PDU power distribution unit
PE protective earthing
PoE power over Ethernet
PUE power usage effectiveness

S
SD secure digital memory
SIM subscriber identity module
SNMP Simple Network Management Protocol

U
USB Universal Series Bus

V
VCN video cloud node

W
WiFi wireless fidelity

Issue 04 (2020-01-14) Copyright © Huawei Technologies Co., Ltd. 92