The UV flame detectors are designed for use with Siemens burner controls, for
the supervision of gas or oil flames.
The QRA and this Data Sheet are intended for use by OEMs which integrate the
flame detectors in their products.
The flame detectors are used for the supervision of gas flames, yellow- or blue-burning
oil flames and for ignition spark proving.
Flame detector For use with burner control type Operating mode
QRA2, QRA10 LGB2 / LGB4 with AGQ1 Intermittent
LFL
LFE1
LFE10
LMG with AGQ2
LME21 / LME22 / LME39 with AGQ3 / LME7
LMV2 / LMV3
LMV5 with AGQ1
QRA53, QRA55 LGK16 Continuous
LGI16 operation
QRA73, QRA75 LMV5 Continuous
LME75 operation
Warning notes
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before carrying out any work on the flame detector, isolate the power supply
completely (all-polar disconnection). Check the power supply with a suitable
voltage test and secure the power supply against being switched on again
unintentionally.
If not observed, there is a risk of electric shock hazard.
Ensure protection against electric shock hazard by providing adequate protection
for the terminals. If this is not observed, there is a risk of electric shock
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state. If this is not observed, there is a
risk of electric shock
Halogen lamps, welding equipment, special lamps or ignition sparks may produce
sufficient radiation for the detector’s UV cell to ignite. X-rays and gamma radiation
can also generate erroneous flame signals. If this is not observed, there is a risk
of loss of safety functions
Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage. If this is not observed,
there is a risk of loss of safety functions and a risk of electric shock
2/19
Ensure that the relevant national safety regulations are complied with
Tightening torque for QRA2 housing screws: Max. 0.3 Nm
Installation notes
Always run the detector cable separate from other cables, especially from high-voltage
ignition cables, while observing the greatest possible distance.
3/19
Trouble-free burner operation is ensured only when the intensity of UV radiation at the
detector’s location is high enough for the detector’s UV cell to ignite during each half
wave. The intensity of UV radiation at the detector’s location is checked through
measurement of the detector current
Legend 1) Connection of micro-ammeter across AGQ1 / AGQ2 / AGQ3 adapter and flame detector
2) Only in combination with QRA2M and QRA10M
A Viewing angle
M Micro-ammeter (DC), internal resistance 5000
C Electrolytic capacitor 100...470 µF, DC 10...25 V
Note!
The KF8832 flame detector current measuring device must not be used in continuous
operation!
4/19
LME75
QRA7 LME75 connection assignment:
X10-05 pin 3 PE
X10-05 pin 4 N
X10-05 pin 5 L
Ri > 10 M
0...10 V
Certificates
Note!
Only in connection with burner controls!
ISO 9001:2015
ISO 14001:2015
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
Service notes
Use the KF8832 service unit for short periods of time only.
Disposal notes
The flame detector contains electrical and electronic components and must not be
disposed of together with domestic waste. Local and currently valid legislation must be
observed.
5/19
Flame detectors QRA2 Plastic housing metalized to prevent static charging caused by the air flow from the fan.
For mounting direct on the burner. The detectors can be supplied with or without
securing flange (version 4 241 8855 0/4 241 8898 0) and clamp (refer to «Type
summary»).
Flame detectors QRA10 Die-cast aluminum housing with a mounting coupling D and connection facility for
cooling air. The housing of this detector has a bayonet fitting which allows it to be
secured either directly to the mounting coupling D or to the AGG06 glass holder. The
mounting coupling D can be screwed to a viewing tube or to the AGG07 ball head. The
Pg cable gland can be removed and replaced, if some other detector cable shall be
used.
Flame detectors QRA5, The detector’s UV cell is located behind a swiveling shutter at the front end of the
QRA7 detector tube which is flanged to the housing. A quartz-glass window protects the tube
and the shutter against dirt. The detector’s housing accommodates a stepper motor to
drive the shutter and the electronics to control the shutter. QRA5 series E and G differ
with regard to the closing interval of the orifice. Using the AGG16.C adapter, this flame
detectors can be mounted either directly on the burner, on a viewing tube or on a
combustion chamber viewing hole.
Connecting cable For the electrical connection of the flame detector QRA53 and QRA55.
AGM19
Connecting cable For the electrical connection of the flame detector QRA7.
AGM23
Connecting cable For the electrical connection of the flame detector QRA7, USA version.
AGM23U
Note!
Applications in the USA are only possible with AGM23U.
Mounting coupling D Using the bayonet fitting, the mounting coupling D can be attached either to the
AGG06, the AGG16.C or the QRA10 flame detector. The mounting coupling D is
supplied with the QRA10 or AGG16.C.
Adapter AGG16.C Adapter AGG16.C for QRA5 and QRA7 made from die-cast aluminum, including
mounting coupling D, which is fixed to the housing with a bayonet fitting.
QRA5... / QRA7...
7712m17/0116
6/19
Quartz-glass lens AGG03 with spring washer and O-ring for increasing the sensitivity.
AGG03
Heat insulation glass AGG02 with spring washer and O-ring. This heat insulation glass is required on
AGG02 applications where the temperature at the flame detector exceeds 80 °C. The AGG02
extends the life cycle of the UV cell.
Glass and quartz-glass The glass and quartz-glass lens holder AGG06 serves for holding the AGG03 lens and
lens holder AGG06 the AGG02 heat insulation glass. The AGG06 also allows various combinations of lens,
heat insulation glass and mounting coupling D. When using the lens and the heat
insulation glass, the AGG06 with the lens must be mounted as close as possible to the
flame detector.
AGG16.C
AGG02
AGG06
AGG03
7712z07/0403
AGG06
Correct Wrong
AGG06 has a bayonet fitting with which it is attached either to the housing of the
AGG16.C or to the housing of the QRA10 and the 1 mounting coupling D. By undoing
the bayonet fittings on both sides, the AGG06 glass holder(s) can be easily detached
from the combination of QRA10 or AGG16.C and QRA53 or QRA55. This facilitates
straightforward cleaning of the glass or lens without having to remove them from the
AGG06 glass holder. The intermediate rings are used for the smooth running of the
bayonet fittings, especially where – after removal of the flame detector – the hole to the
combustion chamber serves as a viewing tube. By fitting the intermediate ring to the
appropriate bayonet connection, the combination can be undone where required by
rotating the housing of the QRA10 or AGG16.C
Note!
AGG02 or AGG03 can also be fitted in the mounting coupling D of the AGG16.C or
the QRA10.
Nipple AGG05 1 in. nipple AGG05 for connecting the mounting coupling D to the AGG07 ball head.
7/19
Ball head AGG07 AGG07 with 1 in. internal thread. Connection on AGG05 and for use with the mounting
coupling D and AGG06. The AGG07 is used for mounting on a rigid surface, such as
the boiler wall. It facilitates optimum adjustment of the viewing angle.
Accessories
combinations
AGG16.C
AGG03
AGG06
AGG02
AGG06
AGG05
7712z05/0403
AGG07
8/19
When ordering, please give type references according to the Type summary.
Flame detectors
1) With heat-resistant housing for ambient temperatures up to 200 °C (short-time, up to a few seconds)
Note
Mounting instructions for replacing the spare UV cell, refer to 4 319 9513 0
(M7712.5)!
Note
Mounting instructions for replacing the spare UV cell, refer to 4 319 9506 0
(M7712.1)!
Note
All QRA5s are delivered complete with clamp. The connection requires an AGM19
connection cable (refer to Accessories for QRA5).
9/19
Note!
Mounting Instruction for replacing of spare UV tube, refer to 74 319 0654 0
(M7712.6)!
Note
All QRA7s are delivered complete with clamp. The connection requires an AGM23 /
AGM23U connection cable (refer to Accessories for QRA7).
10/19
Accessories for QRA2 Part For use with Article no. / Part number
and QRA5 and QRA7 Flange rounded ¹) QRA2 BPZ:4 241 8855 0
when ordered as single
Flange straight ²) QRA2 BPZ:4 241 8898 0
items
Clamp ¹) ²) QRA2 BPZ:4 199 8806 0
Clamp for direct mounting QRA5 / QRA7 BPZ:4 199 1034 0
11/19
12/19
General detector data Average life of UV cell Approx. 10,000 hours at max. 50 °C, higher
ambient temperatures reduce considerably
the cell’s life
Perm. combustion chamber pressure
- QRA10 Max. 50 mbar
- QRA10 + AGG03 or AGG02 Max. 500 mbar
Safety class
- QRA2 II
- QRA10 I
- QRA5x.E / QRA5x.G I
- QRA7 I
Degree of protection
- QRA2 IP20
Note!
IP40 conforming to DIN EN 60529
when using adequate cable entries
(e.g. AGG09).
- QRA10 IP54 (IP65 with AGG08)
- QRA5x.E / QRA5x.G IP65
- QRA7 IP65
Mounting position Optional
Weight
- AGG01 Approx. 10 g
- AGG02 Approx. 10 g
- AGG03 Approx. 10 g
- AGG05 Approx. 170 g
- AGG06 Approx. 160 g
- AGG07 Approx. 1330 g
- AGG16.C Approx. 650 g
- QRA2 Approx. 46 g
- QRA10 Approx. 740 g
- QRA10 + AGG03 Approx. 750 g
- QRA5x.E, QRA5x.G Approx. 700 g
- QRA7 Approx. 700 g
Ignition cable (see Technical data for the relevant burner control)
- QRA2 Supplied by customer
Recommended: H05VV-F 2 x 0.75
Observe the application standards!
- QRA10 Supplied by customer
Recommended: H05VV-F 3 x 0.75
Observe the application standards!
- QRA53 / QRA55 Connecting cable AGM19
- QRA73 / QRA75 Connecting cable AGM23
13/19
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, the safety functions are no longer ensured and there will be a
risk of electric shock!
Function
With this type of flame supervision, the UV radiation emitted by gas or oil flames is
used to generate the flame signal. The radiation detector consists of a UV-sensitive cell
with 2 electrodes, which ignite when illuminated with radiation in the 190...270 nm
range of the spectrum, thereby triggering a current in the flame detector circuit. The UV
cell does not respond to glowing firebrick in the combustion chamber, daylight or light
from boiler room illumination.
14/19
Dimensions in mm
QRA2
25...50
7712m16/0414
4 241 8898 0 4 241 8855 0
QRA10
87
SW20
52
66
SW22 120
'' 8
3
R1 ''
7712m02/0997
UV
Pg13,5
65
15/19
Dimensions in mm
QRA5x.E / QRA5x.G
7712m13/0909
12
32
75
124,5 (QRA53...) 64
108
68,5 (QRA55...) 112,1
72
16/19
Dimensions in mm
12
32
75
124,5 (QRA73...)
68,5 (QRA75...) 108 62,1
112,1
72
7712m11/0108
17/19
Dimensions in mm
12
32
75
124,5 (QRA73...)
68,5 (QRA75...) 108 81
112,1
72
7712m12/0108
18/19
Dimensions in mm
40° 30°
7712z08/0111
Accessories
4 199 1034 0
Clamp for direct mounting on the burner or the AGG16.C
46
40
7712m15/0111
60
AGG02 AGG03
24 36
.3
18
R2 R4
R4
7
7
R0.3
25°
R2
30
30
25°
15
15
3
7712m09e/1001 7712m10e/1001