1.INFORMATION ABOUT AMF 25
DESCRIPTION :
InteliLite AMF 25 meets all possible requirements for
AMF applications, including modem control, user
configuration and full gen-set monitoring and protection.
Ersin ERDALI 3
1.INFORMATION ABOUT AMF 25
GENERAL OUTLOOK AND BENEFITS :
Less wiring and components.
Integrated solution.
Less engineering and programming.
Perfect performance.
Ersin ERDALI 4
1.INFORMATION ABOUT AMF 25
GENERAL FEATURES - 1:
Support of engines equipped with Electronic Control
Unit (J1939 interface).
Comprehensive diagnostic messages; SPN/FMI codes;
KWP2000 support.
Automatic or manual start/stop of the gen-set.
Push buttons for simple control, lamp test.
Graphic back-lit LCD display 128x64 pixels.
6 LED indicators.
Parameters adjustable on keyboard or PC.
Mains measurements (50/60 Hz): U1-U3, Hz.
Generator measurements (50/60 Hz): U1-U3, I1-I3, Hz,
kW, kVAR, kWh.
Selectable protections alarm/shutdown.
Ersin ERDALI 5
1.INFORMATION ABOUT AMF 25
GENERAL FEATURES - 2:
Configurable analog inputs.
Battery voltage, engine speed (pick-up)
measurement.
Configurable programmable binary inputs and
outputs.
Warm-up and cooling functions.
Generator C.B. and Mains C.B. control with
feedback and return timer.
RS232 interface (AT-LINK CONV cable is necessary
for IL-AMF 20).
Modem communication support
Dimensions 180x120 mm (front panel).
Sealed to IP65.
Ersin ERDALI 6
1.INFORMATION ABOUT AMF 25
PROTECTION FEATURES :
3 Phase Generator protections :
• Over/under voltage
• Over/under frequency
• Current/voltage asymmetry
• Overcurrent/overload
Ersin ERDALI 7
1.INFORMATION ABOUT AMF 25
TECHNICAL FEATURES :
Supply Voltage : Max. voltage indication :
8-36 V DC 290 VAC (phase-neutral)
Ersin ERDALI 8
2.BUTTONS VE LEDS
1-2 MODE : Selection for generator process mode (Off, Man., Aut, Test).
3 Horn Reset : Squelch the horn.
4 Fault Reset : Reset information of fault and alarm .
5 Start : Start generator.
6 Stop : Stop generator.
7 MCB on/off : On or off main switch by manual.
8 GCB on/off : On or off generator switch by manual.
9 Page : There are 2 pages to select menu.
10 Up Arrow : Selection for function, enhencement parameter degrees.
11 Down Arrow : Selection for function, reduction parameter degrees.
12 Enter : Saving degrees which it has set before.
Ersin ERDALI 9
2.BUTTONS VE LEDS
13. MAINS PRESENT : GREEN LED is on, if mains is present and within limits.
14. MAINS FAILURE : RED LED starts flashing when the mains failure occurs and
gen-set does not run, goes to steady light when the gen-set starts and goes off
when the mains restores.
15. GEN VOLTAGE PRESENT : GREEN LED is on, if gen. voltage is present and
within limits.
16. GEN-SET FAILURE : RED LED starts flashing when gen-set failure occurs.
After FAULT RESET button is pressed, goes to steady light (if an alarm is still
active) or is off (if no alarm is active).
17. GCB ON : GREEN LED is on, if GCB is closed. Driven by the feedback signal.
18. MCB ON : GREEN LED is on, if MCB is closed. Driven by the feedback signal.
Ersin ERDALI 10
3. SCREENS DESCRIPTION
1
2
3
4
5
6
7
8
1. Operation mode of the gen-set
2. Indication of active access lock, Remote OFF or Remote TEST
L and alarm !
3. Status of the gen-set
4. Actual condition
5. Power factor
6. RPM of the gen-set
7. Timer - event s counting time (e.g. prestart, cooling, etc.)
8. Active power
Ersin ERDALI 11
3. SCREENS DESCRIPTION
Name of Parameter
Password
Basic settings
Engine Params
Engine Protect
Gener Protect
Automains Fail
Sensors Spec
IOM/PTM Module
Ersin ERDALI 12
3. SCREENS DESCRIPTION
Password :
EnterPassword :
Password is a four-digit number. Password enables change of
relevant protected set points Use ↑ or ↓ keys to set and ENTER
key to enter the password.
ChangePassword :
Use ↑ or ↓ keys to set and ENTER key to change the password.
Hint :
At first the Password has to be entered before the new Password
can be changed.
Ersin ERDALI 13
3. SCREENS DESCRIPTION
Basic settings :
Vm PT ratio [/1]
Gen-set name Mains potential transformers ratio.
Nomin power [kW] Step: 0,1 V / V
Nominal power of the generator Range: 0,1 – 500,0 V / V
Step: 1kW Nomin voltage [V]
Range: 1 – 4000 kW Phase to neutral
Nomin current [ A ] Step: 1V
Step: 1 A Range: 100 – 300
Range: 1 - 5000 A Nominal freq [Hz]
CT Ratio [/5A] Step: 1Hz
Gen-set phases current transformers ratio. Range: 45 – 65 Hz
Step: 1 A Gear teeth [-]
Range: 1 – 5000 A / 5A Step: 1
PT ratio [/1] Range: 0 – 500
Gen-set potential transformers ratio. Nominal RPM [RPM]
Step: 0,1 V / V Step: 1RPM
Range: 0,1 – 500,0 V / V Range: 100 – 4000 RPM
Ersin ERDALI 14
3. SCREENS DESCRIPTION
Engine Params :
Starting RPM [%] CrnkFail pause [s]
“Firing” speed when iL controller stops Pause between crank attempts.
cranking (starter goes OFF). Step: 1s
Step: 1% of nominal RPM Range: 5 – 60 s
Range: 5 – 50 %
Starting POil [Bar] Crank attemps [-]
When reached controller stops Max number of crank attempts.
cranking Step: 1
(starter goes OFF). Range: 1 – 10
Ersin ERDALI 16
3. SCREENS DESCRIPTION
Engine Protect :
Eng prot del [s] AnlInp1 level2 [ Bar]
During the start of the gen-set, some engine Shutdown threshold level for ANALOG
protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the Protection
INPUT 1
del time. The time starts after reaching Start RPM.
Step: 0,1 bar
Range: -100 – AnlInp1 level1
Step: 1s
Range: 0 – 300 s AnlInp1 del [s]
Horn timeout [s]
Delay for ANALOG INPUT 1
Step: 1 s
Range: 0 – 180 s
Max time limit of horn sounding. Set to zero if
you want to leave the output HORN open.
Step: 1s AnlInp2 level1 [ ]
Range: 0 – 600 s Warning threshold level for ANALOG
Overspeed [%]
INPUT 2
Step: 1 °C
Range: -100 – Anlinp2 level2
Threshold for over speed protection
Step: 1% of nominal RPM
Range: 100 – 150% AnlInp2 level2 [ ]
AnlInp1 level1 [ Bar] Shutdown threshold level for ANALOG
Warning threshold level for ANALOG INPUT 1 INPUT 2
Step: 0,1 bar Step: 1 °C
Range: AnlInp1 level2 – 10000 Range: AnlInp2 level1 – 10000
Ersin ERDALI 17
3. SCREENS DESCRIPTION
Engine Protect :
AnlInp2 del [s] Batt undervolt [V]
Delay for ANALOG INPUT 2 alarm. Warning threshold for low battery voltage.
Step: 1 s Step: 0,1 V
Range: 0 – 180 s Range: 8V – Batt overvolt
AnlInp3 level1 [ ] Batt overvolt [V]
Warning threshold level for ANALOG INPUT 3 Warning threshold for high battery
Step: 1 % voltage.
Range: AnlInp3 level2 – 10000 Step: 0,1 V
AnlInp3 level2 [ ] Range: Batt undervolt – 40 V
Shutdown threshold level for ANALOG INPUT 3 Batt volt del [s]
Step: 1 % Delay for low battery voltage alarm.
Range: -100 – AnlInp3 level1 Step: 1s
Range: 0 – 600 s
AnlInp3 del [s]
Delay for ANALOG INPUT 3 NextServTime [h]
Step: 1 s Counts down when engine running. If
Range: 0 – 180 s reaches zero, an alarm appears.
Step: 1h
Range: 0 – 65535h
Ersin ERDALI 18
3. SCREENS DESCRIPTION
Gener Protect :
Overload [%] Curr unbal del [s]
Threshold for generator overload (in % of Delay for generator current unbalance
Nominal power) Step: 0.1 s
Step: 1% of Nominal power Range: 0 – 60.0 s
Range: 0 – 200%
Gen >V Sd [%]
Overload del [s] Threshold for generator overvoltage. All
Delay for generator overload alarm. three phases are checked. Maximum
Step: 0.1s out of three is used.
Range: 0 – 60.0 s Step: 1% of Nominal voltage
Range: Gen <V – 200%
Ishort [ % ]
Shutdown occurs when short circuit limit Ishort
Gen <V Sd [%]
limit is reached.
Step: 1 % of Nominal current
Threshold for generator undervoltage.
All three phases are checked. Minimum
Range: 100 - 500 %
out of three is used.
Curr unbal [%] Step: 1% of Nominal voltage
Threshold for generator current asymmetric Range: 0% – Gen >V
(unbalance).
Step: 1% of Nominal current
Range: 1 – 200% of Nominal current
Ersin ERDALI 19
3. SCREENS DESCRIPTION
Gener Protect :
Gen V del [s] Gen >f [%]
Delay for generator undervoltage and Threshold for generator phase L3
overvoltage alarm overfrequency.
Step: 0.1s Step: 0.1% of Nominal frequency
Range: 0 – 60 s Range: Gen <f – 200.0%
Ersin ERDALI 20
4. OPERATION MODES
On AUT mode, we can not attend generator and main circuit breaker
by manual.
OPERATION MODES
Ersin ERDALI 21
4. OPERATION MODES
OFF MODE :
Ersin ERDALI 22
4. OPERATION MODES
MAN MODE :
START : starts the gen-set.
GCB ON/OFF :
• The controller closes GCB to dead bus.
• The controller opens GCB when closed.
• If the generator voltage is out of the limits, the controller does not to
respond to the GCB ON/OFF
MCB ON/OFF :
• The controller closes MCB to dead bus.
• The controller opens MCB when closed.
STOP : stops the gen-set.
Ersin ERDALI 23
4. OPERATION MODES
AUTO MODE :
Ersin ERDALI 24
4. OPERATION MODES
TEST MODE :
Ersin ERDALI 25
5. ELECTRICAL CONNECTIONS
Terminals :
Ersin ERDALI 26
5. ELECTRICAL CONNECTIONS
Wiring Diagram :
Ersin ERDALI 27
5. ELECTRICAL CONNECTIONS
INPUTS AND OUTPUTS :
Ersin ERDALI 28
5. ELECTRICAL CONNECTIONS
Binary Inputs :
BI1 GCB feedback
BI2 MCB feedback
BI3 Emergency stop
BI4 Access lock
BI5 Remote OFF
BI6 Remote TEST
BI7 Sprinkler
GCB feedback ;
Use this input for indication, whether the generator circuit breaker is open or
closed. If the feedback is not used, connect this input to the output GCB
CLOSE/OPEN
MCB feedback ;
This input indicate, whether the gen-sets group operate in parallel to mains
(MCB FEEDBACK is closed) or parallel isolated (MCB FEEDBACK is open) .
Emergency stop ;
If the input is opened, shut down is immediately activated. Input is inverted
(normally closed).
Ersin ERDALI 29
5. ELECTRICAL CONNECTIONS
Binary Inputs :
Sprinkler ;
If the input is closed all alarms are disabled except the binary input
EMERGENCY STOP and "engine overspeed protection".
Access lock ;
If the input is closed, no setpoints can be adjusted from controller front panel
and gen-set mode (OFF-MAN-AUT-TEST) cannot be changed.
Remote OFF ;
If closed, iL is switched to OFF mode (there are four modes OFF-MAN-AUT-
TEST). When opens controller is switched back to previous mode.
Remote TEST ;
If closed, iL is switched to TEST mode (there are four modes OFF-MAN-
AUT-TEST). When opens controller is switched back to previous mode.
Remote MAN ;
If the input is active, MAN mode is forced to the controller independently on
the position of the MODE selector. If another of „remote“ inputs is active,
then the Remote MAN input has the lowest priority.
Ersin ERDALI 30
5. ELECTRICAL CONNECTIONS
Binary Inputs :
RemControlLock ;
If the input is active, setpoints writing or command sending from the external
terminal is disabled.
Emergency manual ;
If the input is activated the controller behaves like when switched to OFF
mode. Opens all binary outputs. There is one exception – Stop solenoid
doesn’t activate on this transition.
TestOnLoad ;
Affects the behaviour in TEST mode. When input is closed, the controller
automatically transfers load from the mains to the genset. Setpoint
AutoMainsFail: Ret from test must be set to MANUAL. Load is automatically
transferred back to the mains when any genset shut down protection
activates.
Start button ;
Binary input has the same function as Start button on the InteliLite front
panel. It is active in MAN mode only.
Ersin ERDALI 31
5. ELECTRICAL CONNECTIONS
Binary Inputs :
Stop button ;
Binary input has the same function as Stop button on the InteliLite front
panel. It is active in MAN mode only.
FaultResButton ;
Binary input has the same function as Fault reset button on the InteliLite
front panel.
HornResButton ;
Binary input has the same function as Horn reset button on the InteliLite
front panel.
GCB button ;
Binary input has the same function as GCB button on the InteliLite front
panel. It is active in MAN mode only.
MCB button ;
Binary input has the same function as MCB button on the InteliLite front
panel. It is active in MAN mode only.
Ersin ERDALI 32
5. ELECTRICAL CONNECTIONS
Binary outputs :
BO1 Starter (relay output)
BO2 Fuel solenoid (relay output)
BO3 GCB close/open
BO4 MCB close/open
BO5 Prestart
BO6 Read to Load
BO7 Alarm
Starter ;
The closed relay energizes the starter motor.
The relay opens if:
• the “firing” speed is reached or
• maximum time of cranking is exceeded or
• request to stop comes up
Ersin ERDALI 33
5. ELECTRICAL CONNECTIONS
Binary outputs :
Fuel solenoid ;
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
•Emergency stop comes or
•Cooled gen-set is stopped or
•in pause between repeated starts
Ignition ;
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens
after stopping of the engine or in pause during repeated start.
Prestart ;
The output closes prior to the engine start (Prestart) and opens when START
RPM speed is reached. During repeated crank attempts the output is closed
too. The output could be used for pre-glow, pre-heat or prelubrication.
Ready to load ;
The output is closed if genset is running and all electric values are in limits no
alarm is active - it is possible to close GCB or it is already closed. The output
opens during cooling state.
Ersin ERDALI 34
5. ELECTRICAL CONNECTIONS
Binary outputs :
Alarm ;
The output closes if any alarm comes up or the gen-set malfunctions.
The output opens if FAULT RESET is pressed.
The output closes again if a new fault comes up.
Horn ;
The output closes if any alarm comes up or the gen-set malfunctions
The output opens if FAULT RESET is pressed or HORN RESET is pressed
or Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Vgen fail ;
The output closes if the generator over/under voltage alarm or voltage
asymmetry alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed
fgen fail ;
Output closes if the generator over/under frequency alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed
Ersin ERDALI 35
5. ELECTRICAL CONNECTIONS
Binary outputs :
Vmains fail ;
The output closes if the mains over/under voltage alarm or voltage
asymmetry alarm activates. The output opens, if alarm is not active and
FAULT RESET is pressed
fmains fail ;
Output closes if the mains over/under frequency alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
Overload ;
Output closes if the generator overload alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed
Stop fail ;
Output closes when the engine have to be stopped, but speed or frequency
or voltage or oil pressure is detected. This protection goes active 60s after
stop command. With start goes this protection inactive. The output opens, if
alarm is not active and FAULT RESET is pressed
Overspeed ;
Output closes if the gen-set overspeed alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed
Ersin ERDALI 36
5. ELECTRICAL CONNECTIONS
Binary outputs :
Underspeed ;
Output closes if the gen-set underspeed alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed.
Start fail ;
Output closes after the gen-set start-up fails. The output opens, if alarm is
not active and FAULT RESET is pressed.
Overcurrent ;
Output closes if the generator over current or current unbalance or short
current alarm activates. The output opens, if Alarm is not active and FAULT
RESET is pressed.
Battery flat ;
Output closes when iL preforms reset during start procedure (probably due to
weak battery). The output opens, if alarm is not active and FAULT RESET is
pressed.
V batt failed ;
Output closes when battery over/under voltage warning appears. The output
opens, if alarm is not active and FAULT RESET is pressed.
Ersin ERDALI 37
5. ELECTRICAL CONNECTIONS
Binary outputs :
OilPress ;
Output closes if the oil pressure shutdown alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed.
OilPressWrn ;
Output closes if the oil pressure warning alarm activates. The output opens,
if alarm is not active and FAULT RESET is pressed
WaterTemp ;
Output closes if the water temperature shutdown alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
WaterTempWrn ;
Output closes if the water temperature warning alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
FuelLevel ;
Output closes if the Fuel level shutdown alarm activates.
FuelLevelWrn ;
Output closes if the Fuel level warning alarm activates.
Ersin ERDALI 38
5. ELECTRICAL CONNECTIONS
Binary outputs :
Running ;
Output closes if the engine is in Running state.
OFF mode ;
The output is closed, if OFF mode is selected.
MAN mode ;
The output is closed, if MAN mode is selected.
AUT mode ;
The output is closed, if AUT mode is selected.
TEST mode ;
The output is closed, if TEST mode is selected.
The output opens, if Alarm is not active and FAULT RESET is pressed.
ChrgAlternFail ;
Output closes if gen-set is running and D+ input not energized. The output
opens, if alarm is not active and FAULT RESET is pressed.
ServiceTime ;
Output closes if the ServiceTime alarm activates.
Ersin ERDALI 39
5. ELECTRICAL CONNECTIONS
Analog inputs :
Oil press ;
Oil pressure analog input. Default range 0 to 10.0 bars.
Water temp ;
Water temperature analog input. Default range 0 to 100 °C.
Fuel level ;
Fuel level analog input. Default VDO sensor 0-180R = 0-100%
Ersin ERDALI 40
AMF 25 TRAINING FINISHED