AMF 25 For Lion Rock

Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

TRAINING DEPARTMENT

COMAP AMF 25 CONTROL


MODULE TRAINING
Ersin ERDALI
October 2007
INCLUDES OF
INCLUDES OF AMF
AMF 25
25 CONTROL
CONTROL MODULE
MODULE TRAINING
TRAINING

1. INFORMATION ABOUT AMF 25


2. BUTTONS AND LEDS
3. SCREENS DESCRIPTION
4. OPERATION MODES
5. ELECTRICAL CONNECTIONS

Ersin ERDALI 2
1.INFORMATION ABOUT AMF 25
DESCRIPTION :
 InteliLite AMF 25 meets all possible requirements for
AMF applications, including modem control, user
configuration and full gen-set monitoring and protection.

 InteliLite controller is equipped with a powerful graphic


display. Icons, symbols and bar graphs for intuitive
operation together with high functionality set new
standards in gen-set control.

 AMF 25 is also available, allowing the display to work in


tepmperature between -20°C and +70°C.

Ersin ERDALI 3
1.INFORMATION ABOUT AMF 25
GENERAL OUTLOOK AND BENEFITS :
 Less wiring and components.
 Integrated solution.
 Less engineering and programming.
 Perfect performance.

Ersin ERDALI 4
1.INFORMATION ABOUT AMF 25
GENERAL FEATURES - 1:
 Support of engines equipped with Electronic Control
Unit (J1939 interface).
 Comprehensive diagnostic messages; SPN/FMI codes;
KWP2000 support.
 Automatic or manual start/stop of the gen-set.
 Push buttons for simple control, lamp test.
 Graphic back-lit LCD display 128x64 pixels.
 6 LED indicators.
 Parameters adjustable on keyboard or PC.
 Mains measurements (50/60 Hz): U1-U3, Hz.
 Generator measurements (50/60 Hz): U1-U3, I1-I3, Hz,
kW, kVAR, kWh.
 Selectable protections alarm/shutdown.
Ersin ERDALI 5
1.INFORMATION ABOUT AMF 25
GENERAL FEATURES - 2:
 Configurable analog inputs.
 Battery voltage, engine speed (pick-up)
measurement.
 Configurable programmable binary inputs and
outputs.
 Warm-up and cooling functions.
 Generator C.B. and Mains C.B. control with
feedback and return timer.
 RS232 interface (AT-LINK CONV cable is necessary
for IL-AMF 20).
 Modem communication support
 Dimensions 180x120 mm (front panel).
 Sealed to IP65.
Ersin ERDALI 6
1.INFORMATION ABOUT AMF 25
PROTECTION FEATURES :
 3 Phase Generator protections :
• Over/under voltage
• Over/under frequency
• Current/voltage asymmetry
• Overcurrent/overload

 3 Phase Mains Protections :


• Over/under frequency
• Over/under voltage
• Voltage asymmetry

Ersin ERDALI 7
1.INFORMATION ABOUT AMF 25
TECHNICAL FEATURES :
 Supply Voltage :  Max. voltage indication :
 8-36 V DC  290 VAC (phase-neutral)

 Standards :  MPU input frequency :


 EMC (Comformaty of electromagnetic ),  4 Hz-10 kHz
 LVD (Low Voltage Degree).
MPU input voltage :
 Dimension :  6-50 V
 180x120x55 mm
 Input current :
 Weight :  5 A (from current transf.)
 800 gr
 Voltage indication :
 Frequency :  231 VAC (phase-neutral),
 50-60 Hz  400 VAC (phase-phase)

Ersin ERDALI 8
2.BUTTONS VE LEDS

1-2 MODE : Selection for generator process mode (Off, Man., Aut, Test).
3 Horn Reset : Squelch the horn.
4 Fault Reset : Reset information of fault and alarm .
5 Start : Start generator.
6 Stop : Stop generator.
7 MCB on/off : On or off main switch by manual.
8 GCB on/off : On or off generator switch by manual.
9 Page : There are 2 pages to select menu.
10 Up Arrow : Selection for function, enhencement parameter degrees.
11 Down Arrow : Selection for function, reduction parameter degrees.
12 Enter : Saving degrees which it has set before.
Ersin ERDALI 9
2.BUTTONS VE LEDS

13. MAINS PRESENT : GREEN LED is on, if mains is present and within limits.
14. MAINS FAILURE : RED LED starts flashing when the mains failure occurs and
gen-set does not run, goes to steady light when the gen-set starts and goes off
when the mains restores.
15. GEN VOLTAGE PRESENT : GREEN LED is on, if gen. voltage is present and
within limits.
16. GEN-SET FAILURE : RED LED starts flashing when gen-set failure occurs.
After FAULT RESET button is pressed, goes to steady light (if an alarm is still
active) or is off (if no alarm is active).
17. GCB ON : GREEN LED is on, if GCB is closed. Driven by the feedback signal.
18. MCB ON : GREEN LED is on, if MCB is closed. Driven by the feedback signal.
Ersin ERDALI 10
3. SCREENS DESCRIPTION
1

2
3
4
5
6
7

8
1. Operation mode of the gen-set
2. Indication of active access lock, Remote OFF or Remote TEST
L and alarm !
3. Status of the gen-set
4. Actual condition
5. Power factor
6. RPM of the gen-set
7. Timer - event s counting time (e.g. prestart, cooling, etc.)
8. Active power
Ersin ERDALI 11
3. SCREENS DESCRIPTION

Name of Parameter
Password
Basic settings
Engine Params
Engine Protect
Gener Protect
Automains Fail
Sensors Spec
IOM/PTM Module

Ersin ERDALI 12
3. SCREENS DESCRIPTION
 Password :

 EnterPassword :
Password is a four-digit number. Password enables change of
relevant protected set points Use ↑ or ↓ keys to set and ENTER
key to enter the password.

 ChangePassword :
Use ↑ or ↓ keys to set and ENTER key to change the password.

 Hint :
At first the Password has to be entered before the new Password
can be changed.

Ersin ERDALI 13
3. SCREENS DESCRIPTION
 Basic settings :
 Vm PT ratio [/1]
 Gen-set name Mains potential transformers ratio.
 Nomin power [kW] Step: 0,1 V / V
Nominal power of the generator Range: 0,1 – 500,0 V / V
Step: 1kW  Nomin voltage [V]
Range: 1 – 4000 kW Phase to neutral
 Nomin current [ A ] Step: 1V
Step: 1 A Range: 100 – 300
Range: 1 - 5000 A  Nominal freq [Hz]
 CT Ratio [/5A] Step: 1Hz
Gen-set phases current transformers ratio. Range: 45 – 65 Hz
Step: 1 A  Gear teeth [-]
Range: 1 – 5000 A / 5A Step: 1
 PT ratio [/1] Range: 0 – 500
Gen-set potential transformers ratio.  Nominal RPM [RPM]
Step: 0,1 V / V Step: 1RPM
Range: 0,1 – 500,0 V / V Range: 100 – 4000 RPM
Ersin ERDALI 14
3. SCREENS DESCRIPTION
 Engine Params :
 Starting RPM [%]  CrnkFail pause [s]
“Firing” speed when iL controller stops Pause between crank attempts.
cranking (starter goes OFF). Step: 1s
Step: 1% of nominal RPM Range: 5 – 60 s
Range: 5 – 50 %
 Starting POil [Bar]  Crank attemps [-]
When reached controller stops Max number of crank attempts.
cranking Step: 1
(starter goes OFF). Range: 1 – 10

 Idle time [s]


Step: 0,1 bar
Range: -10,0 – 1000,0
Idle time delay starts when RPM exceeds
 Prestart time [s] Start RPM .
Time of closing of the PRE-START output Step: 1 s
prior to the engine start. Range: 0 – 600 s
Step: 1s
Range: 0 – 600 s  Min stab time [s]
Minimum time after reaching of defined
 MaxCrank time [s] level of RPM to the closing GCB.
Maximum time limit of cranking. Step: 1s
Step: 1s Range: 0 – 300 s
Range: 1 – 60 s
Ersin ERDALI 15
3. SCREENS DESCRIPTION
 Engine Params :
 Max stab time [s]  Cooling time [s]
Maximum time after start to get proper voltage Runtime of the unloaded gen-set to cool
level of the generator. the engine before stop.
Step: 1s Step: 1s
Range: 0 – 300 s Range: 0 – 3600 s

 Stop time [s]


Under normal conditions the engine must  Fuel solenoid [ DIESEL / GAS ]
certainly stop within this period. The period Determines behavior of the Binary output
starts by issuing stop command. FUEL SOLENOID.
Step: 1s
Range: 0 – 600 s

 Cooling speed [ NOMINAL / IDLE ]


Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.
NOMINAL : Cooling is executed at Nominal speed and generator protections are active.
IDLE: Cooling is executed at Idle speed and generator protections are switched off.

Ersin ERDALI 16
3. SCREENS DESCRIPTION
 Engine Protect :
 Eng prot del [s]  AnlInp1 level2 [ Bar]
During the start of the gen-set, some engine Shutdown threshold level for ANALOG
protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the Protection
INPUT 1
del time. The time starts after reaching Start RPM.
Step: 0,1 bar
Range: -100 – AnlInp1 level1
Step: 1s
Range: 0 – 300 s  AnlInp1 del [s]
 Horn timeout [s]
Delay for ANALOG INPUT 1
Step: 1 s
Range: 0 – 180 s
Max time limit of horn sounding. Set to zero if
you want to leave the output HORN open.
Step: 1s  AnlInp2 level1 [ ]
Range: 0 – 600 s Warning threshold level for ANALOG
 Overspeed [%]
INPUT 2
Step: 1 °C
Range: -100 – Anlinp2 level2
Threshold for over speed protection
Step: 1% of nominal RPM
Range: 100 – 150%  AnlInp2 level2 [ ]
 AnlInp1 level1 [ Bar] Shutdown threshold level for ANALOG
Warning threshold level for ANALOG INPUT 1 INPUT 2
Step: 0,1 bar Step: 1 °C
Range: AnlInp1 level2 – 10000 Range: AnlInp2 level1 – 10000
Ersin ERDALI 17
3. SCREENS DESCRIPTION
 Engine Protect :
 AnlInp2 del [s]  Batt undervolt [V]
Delay for ANALOG INPUT 2 alarm. Warning threshold for low battery voltage.
Step: 1 s Step: 0,1 V
Range: 0 – 180 s Range: 8V – Batt overvolt
 AnlInp3 level1 [ ]  Batt overvolt [V]
Warning threshold level for ANALOG INPUT 3 Warning threshold for high battery
Step: 1 % voltage.
Range: AnlInp3 level2 – 10000 Step: 0,1 V
 AnlInp3 level2 [ ] Range: Batt undervolt – 40 V
Shutdown threshold level for ANALOG INPUT 3  Batt volt del [s]
Step: 1 % Delay for low battery voltage alarm.
Range: -100 – AnlInp3 level1 Step: 1s
Range: 0 – 600 s
 AnlInp3 del [s]
Delay for ANALOG INPUT 3  NextServTime [h]
Step: 1 s Counts down when engine running. If
Range: 0 – 180 s reaches zero, an alarm appears.
Step: 1h
Range: 0 – 65535h

Ersin ERDALI 18
3. SCREENS DESCRIPTION
 Gener Protect :
 Overload [%]  Curr unbal del [s]
Threshold for generator overload (in % of Delay for generator current unbalance
Nominal power) Step: 0.1 s
Step: 1% of Nominal power Range: 0 – 60.0 s
Range: 0 – 200%
 Gen >V Sd [%]
 Overload del [s] Threshold for generator overvoltage. All
Delay for generator overload alarm. three phases are checked. Maximum
Step: 0.1s out of three is used.
Range: 0 – 60.0 s Step: 1% of Nominal voltage
Range: Gen <V – 200%
 Ishort [ % ]
Shutdown occurs when short circuit limit Ishort
 Gen <V Sd [%]
limit is reached.
Step: 1 % of Nominal current
Threshold for generator undervoltage.
All three phases are checked. Minimum
Range: 100 - 500 %
out of three is used.
 Curr unbal [%] Step: 1% of Nominal voltage
Threshold for generator current asymmetric Range: 0% – Gen >V
(unbalance).
Step: 1% of Nominal current
Range: 1 – 200% of Nominal current
Ersin ERDALI 19
3. SCREENS DESCRIPTION
 Gener Protect :
 Gen V del [s]  Gen >f [%]
Delay for generator undervoltage and Threshold for generator phase L3
overvoltage alarm overfrequency.
Step: 0.1s Step: 0.1% of Nominal frequency
Range: 0 – 60 s Range: Gen <f – 200.0%

 Volt unbal [%]  Gen <f [%]


Threshold for generator voltage Threshold for generator phase L3
unbalance alarm. underfrequency.
Step: 1% of Nominal voltage Step: 0.1% of Nominal frequency
Range: 0 – 100% of Nominal voltage Range: 0.0 – Gen >f of Nominal
frequency
 Volt unbal del [s]
Delay for generator voltage unbalance  Gen f del [s]
alarm. Delay for generator underfrequency
Step: 0.1s and overfrequency alarm.
Range: 0 – 60.0 s
Step: 0.1s
Range: 0 – 60.0 s

Ersin ERDALI 20
4. OPERATION MODES
 On AUT mode, we can not attend generator and main circuit breaker
by manual.

 On MAN mode We can attend generator and main circuit breaker by


manual. Before switching the circuit breaker voltage and frequency
have to be suitable rating. AMF 25 has got elecrical lock to stop
switching both circuit breaker.

OPERATION MODES

Ersin ERDALI 21
4. OPERATION MODES
 OFF MODE :

 No start of the gen-set is possible. Outputs STARTER, GCB


CLOSE/OPEN and FUEL SOLENOID are not energized.
 No reaction if buttons START,STOP,GCB ON/OFF, MCB ON/OFF are
pressed.
 When power-cut comes, MCB CLOSE/OPEN opens. After mains
returns, MCB CLOSE/OPEN closes with MCB close del.

Ersin ERDALI 22
4. OPERATION MODES
 MAN MODE :
START : starts the gen-set.
GCB ON/OFF :
• The controller closes GCB to dead bus.
• The controller opens GCB when closed.
• If the generator voltage is out of the limits, the controller does not to
respond to the GCB ON/OFF
MCB ON/OFF :
• The controller closes MCB to dead bus.
• The controller opens MCB when closed.
STOP : stops the gen-set.

Ersin ERDALI 23
4. OPERATION MODES
 AUTO MODE :

The controller does not respond to buttons START, STOP, MCB


ON/OFF, GCB ON/OFF. Engine start/stop request is evaluated form
Mains failure/return.

Ersin ERDALI 24
4. OPERATION MODES
 TEST MODE :

The genset starts automatically and is always running in TEST mode.

The controller does not respond to GCB ON/OFF , STOP, START.


The load is automatically transferred back to the mains when any
genset shut down protection activates.

Ersin ERDALI 25
5. ELECTRICAL CONNECTIONS
 Terminals :

Ersin ERDALI 26
5. ELECTRICAL CONNECTIONS
 Wiring Diagram :

Ersin ERDALI 27
5. ELECTRICAL CONNECTIONS
 INPUTS AND OUTPUTS :

Ersin ERDALI 28
5. ELECTRICAL CONNECTIONS
 Binary Inputs :
BI1 GCB feedback
BI2 MCB feedback
BI3 Emergency stop
BI4 Access lock
BI5 Remote OFF
BI6 Remote TEST
BI7 Sprinkler

GCB feedback ;
Use this input for indication, whether the generator circuit breaker is open or
closed. If the feedback is not used, connect this input to the output GCB
CLOSE/OPEN
MCB feedback ;
This input indicate, whether the gen-sets group operate in parallel to mains
(MCB FEEDBACK is closed) or parallel isolated (MCB FEEDBACK is open) .
Emergency stop ;
If the input is opened, shut down is immediately activated. Input is inverted
(normally closed).
Ersin ERDALI 29
5. ELECTRICAL CONNECTIONS
 Binary Inputs :

Sprinkler ;
If the input is closed all alarms are disabled except the binary input
EMERGENCY STOP and "engine overspeed protection".
Access lock ;
If the input is closed, no setpoints can be adjusted from controller front panel
and gen-set mode (OFF-MAN-AUT-TEST) cannot be changed.
Remote OFF ;
If closed, iL is switched to OFF mode (there are four modes OFF-MAN-AUT-
TEST). When opens controller is switched back to previous mode.
Remote TEST ;
If closed, iL is switched to TEST mode (there are four modes OFF-MAN-
AUT-TEST). When opens controller is switched back to previous mode.
Remote MAN ;
If the input is active, MAN mode is forced to the controller independently on
the position of the MODE selector. If another of „remote“ inputs is active,
then the Remote MAN input has the lowest priority.

Ersin ERDALI 30
5. ELECTRICAL CONNECTIONS
 Binary Inputs :

RemControlLock ;
If the input is active, setpoints writing or command sending from the external
terminal is disabled.
Emergency manual ;
If the input is activated the controller behaves like when switched to OFF
mode. Opens all binary outputs. There is one exception – Stop solenoid
doesn’t activate on this transition.
TestOnLoad ;
Affects the behaviour in TEST mode. When input is closed, the controller
automatically transfers load from the mains to the genset. Setpoint
AutoMainsFail: Ret from test must be set to MANUAL. Load is automatically
transferred back to the mains when any genset shut down protection
activates.
Start button ;
Binary input has the same function as Start button on the InteliLite front
panel. It is active in MAN mode only.

Ersin ERDALI 31
5. ELECTRICAL CONNECTIONS
 Binary Inputs :

Stop button ;
Binary input has the same function as Stop button on the InteliLite front
panel. It is active in MAN mode only.
FaultResButton ;
Binary input has the same function as Fault reset button on the InteliLite
front panel.
HornResButton ;
Binary input has the same function as Horn reset button on the InteliLite
front panel.
GCB button ;
Binary input has the same function as GCB button on the InteliLite front
panel. It is active in MAN mode only.
MCB button ;
Binary input has the same function as MCB button on the InteliLite front
panel. It is active in MAN mode only.

Ersin ERDALI 32
5. ELECTRICAL CONNECTIONS
 Binary outputs :
BO1 Starter (relay output)
BO2 Fuel solenoid (relay output)
BO3 GCB close/open
BO4 MCB close/open
BO5 Prestart
BO6 Read to Load
BO7 Alarm

Starter ;
The closed relay energizes the starter motor.
The relay opens if:
• the “firing” speed is reached or
• maximum time of cranking is exceeded or
• request to stop comes up

Ersin ERDALI 33
5. ELECTRICAL CONNECTIONS
 Binary outputs :
Fuel solenoid ;
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
•Emergency stop comes or
•Cooled gen-set is stopped or
•in pause between repeated starts
Ignition ;
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens
after stopping of the engine or in pause during repeated start.
Prestart ;
The output closes prior to the engine start (Prestart) and opens when START
RPM speed is reached. During repeated crank attempts the output is closed
too. The output could be used for pre-glow, pre-heat or prelubrication.
Ready to load ;
The output is closed if genset is running and all electric values are in limits no
alarm is active - it is possible to close GCB or it is already closed. The output
opens during cooling state.
Ersin ERDALI 34
5. ELECTRICAL CONNECTIONS
 Binary outputs :
Alarm ;
The output closes if any alarm comes up or the gen-set malfunctions.
The output opens if FAULT RESET is pressed.
The output closes again if a new fault comes up.
Horn ;
The output closes if any alarm comes up or the gen-set malfunctions
The output opens if FAULT RESET is pressed or HORN RESET is pressed
or Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Vgen fail ;
The output closes if the generator over/under voltage alarm or voltage
asymmetry alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed
fgen fail ;
Output closes if the generator over/under frequency alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed

Ersin ERDALI 35
5. ELECTRICAL CONNECTIONS
 Binary outputs :
Vmains fail ;
The output closes if the mains over/under voltage alarm or voltage
asymmetry alarm activates. The output opens, if alarm is not active and
FAULT RESET is pressed
fmains fail ;
Output closes if the mains over/under frequency alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
Overload ;
Output closes if the generator overload alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed
Stop fail ;
Output closes when the engine have to be stopped, but speed or frequency
or voltage or oil pressure is detected. This protection goes active 60s after
stop command. With start goes this protection inactive. The output opens, if
alarm is not active and FAULT RESET is pressed
Overspeed ;
Output closes if the gen-set overspeed alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed
Ersin ERDALI 36
5. ELECTRICAL CONNECTIONS
 Binary outputs :
Underspeed ;
Output closes if the gen-set underspeed alarm activates. The output opens, if
alarm is not active and FAULT RESET is pressed.
Start fail ;
Output closes after the gen-set start-up fails. The output opens, if alarm is
not active and FAULT RESET is pressed.
Overcurrent ;
Output closes if the generator over current or current unbalance or short
current alarm activates. The output opens, if Alarm is not active and FAULT
RESET is pressed.
Battery flat ;
Output closes when iL preforms reset during start procedure (probably due to
weak battery). The output opens, if alarm is not active and FAULT RESET is
pressed.
V batt failed ;
Output closes when battery over/under voltage warning appears. The output
opens, if alarm is not active and FAULT RESET is pressed.
Ersin ERDALI 37
5. ELECTRICAL CONNECTIONS
 Binary outputs :
OilPress ;
Output closes if the oil pressure shutdown alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed.
OilPressWrn ;
Output closes if the oil pressure warning alarm activates. The output opens,
if alarm is not active and FAULT RESET is pressed
WaterTemp ;
Output closes if the water temperature shutdown alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
WaterTempWrn ;
Output closes if the water temperature warning alarm activates. The output
opens, if alarm is not active and FAULT RESET is pressed
FuelLevel ;
Output closes if the Fuel level shutdown alarm activates.
FuelLevelWrn ;
Output closes if the Fuel level warning alarm activates.

Ersin ERDALI 38
5. ELECTRICAL CONNECTIONS
 Binary outputs :
Running ;
Output closes if the engine is in Running state.
OFF mode ;
The output is closed, if OFF mode is selected.
MAN mode ;
The output is closed, if MAN mode is selected.
AUT mode ;
The output is closed, if AUT mode is selected.
TEST mode ;
The output is closed, if TEST mode is selected.
The output opens, if Alarm is not active and FAULT RESET is pressed.
ChrgAlternFail ;
Output closes if gen-set is running and D+ input not energized. The output
opens, if alarm is not active and FAULT RESET is pressed.
ServiceTime ;
Output closes if the ServiceTime alarm activates.

Ersin ERDALI 39
5. ELECTRICAL CONNECTIONS
 Analog inputs :
Oil press ;
Oil pressure analog input. Default range 0 to 10.0 bars.
Water temp ;
Water temperature analog input. Default range 0 to 100 °C.
Fuel level ;
Fuel level analog input. Default VDO sensor 0-180R = 0-100%

Ersin ERDALI 40
AMF 25 TRAINING FINISHED

THANKS

QUESTIONS

ANSWERS
Ersin ERDALI 41