Fault Location in Power Transformers During Impulse Tests
Fault Location in Power Transformers During Impulse Tests
Abstract: In this paper we present a new approach to detect, and transferred to an adjacent winding, the tank current or the
investigate the feasibility of locating winding faults with also voltage transferred to a non-tested winding. In its simplest
determining the percentage of short within windings of power form a test arrangement would consist of Marx generator
transformers.There has not been much emphasis on methods of with an arrangement for conducting an impulse test
assessing the extent of failure and in the estimation of the location
of failure during such tests. However, this is a very important chopped on the tail, a voltage divider, a current shunt and
aspect since all faults involving non self-restoring insulation are measuring cables that connect to a recording device as in
destructive in nature and hence have to be necessarily rectified. Fig.1. Traditionally the voltage and supplementary
In case of failure. of a transformer during an impulse test, oscillograms have been recorded on analog impulse
manufacturers have to untank the winding in order to locate the oscilloscopes whose specifications are laid in IEC 790.
fault. Often the destructive 1-minutepower Frequency test is done Here we suggest an important technique for analysis based
in order to visually locate the fault. It would be appropriate to on digital recording.
develop a method for fault location so that results are available
prior to the untanking of the transformer. In principle, the absence of significant difference
This paper discusses methods for fault location based on a between voltage and current transient records constitutes
frequency domain approach. Windings of a transformer behaviour evidence that insulation has withstood the test inspite of
at very high frequency, is essentially that of a capacitive ladder their long usage. The impulse testing is to demarcate the
network. At lower frequency standing wave behaviour is presence of insulation faults and the measurement of
obtained. Based on a choice of filters, the appropriate behaviour parameters.
of the winding during a fault can be studied. In this work, we
develop methods for fault location based on simulations on layer With the advent of digital recorder in the high voltage
windings using a circuit simulation model. The results are environment the requirements of digitizer for impulse
validated experimentally on a specially constructed layer winding. measurement are specified in IEC 1083. A perusal of the
Keywords Transformer, High frequency , Impulse test , Signal standard show that a recording device should have the
Processing ,Transfer function following features for transformer testing.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.
~
Malewski [3] used a 'diac' across the section for elucidating The experimental simulation to verify the above study
certain features of the transfer function mctliod. was doric os is shown in Fig. 1.
FFT (i)
The transfer function approach is T.F ...
-20
FFr (VI
m
w
Since the initial simulation is being done with a standard -40
Lightning impulse voltage constant, firther analysis has
been equivalently done with current spect" only. The
spectral changes are compared for faulted and unfaulted
simulations and analyzed. Analysis was done with respect
to fault identification and measurement of parameters of
measured signal. I .
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.
I
W i t h fault
g .0008 The transfer h c t i o n is computed based on a 3 db cut off
U
“4 of 250 kHz as suggested by Dcgeneff [SI who suggested
$ .0006 that lumped parameter model need be valid upto 50 lcHz for
a
ul a lightning wave and 250 Wz for a chopped wave. The
dl
-0004 analysis considered for the Abetti coil LIS energized by a
U4
Marx circuit is presented with computation of
:
‘0,
.0002 corresponding spectra with simulating winding section
fauln. The design of antialiasing filter is L I ~ S ObaNed on B e
I
CI
0 .5 10 15 20 25 30 fact that filler must have a monotonic response [6].A study
f/2(KHz) of filter application identified that with a Butter worth
digital highpass filter of order 22 and Hamming window
Fig.4. Transfer function with and without fault function, high frequency signals could be identified as in
shown in Fig.6. with the proposed algorithm of transfer
L1
function evaluation as shown in Fig.7
iorvfimn
dcvidmI shun!
60 JB a! SOMhz
f l u . -
%
--
60dB at 500 Khz
Fig.5. Model equivalent of Abetti Coil
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.
C,n = Surge capacitance of coil
U = Amplitude of signal
I 1
60
0 area Vs 0 Winding - ___
50
40
p0
-2 0
10
0'
- :.
0 10 20 30 40 50 60 70
8 Winding
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.
a=4; 2 u s e c c h o p
a=4; 6usec c h o p
Fig.11. Magnitude irariation of fault (a) Percentagevariation of first three
rcsonant frequencies (b) Percentage variation with respect to magnitude of
short cuircuit faull
V. CONCLUSION
220
II/ a=4;1.2/50 US L.I.
method proposed in this paper is used to estimate the
location of fault within windings as a shin in resonant
frequency. The principle emphasis of the location of fault
and percentage of fault during impulse testing was done
using fkquency spectrum on the basis of the parameters
descnied The choice of low pass filter prior to fmt
resonant m u e n c y was used to determine the magnitude of
fault. The results presented h m simulation and
experimental study illustrates this as a reliable method of
location of faults in transformer windings.
V. REFERENCES
rp
”[ 0.2 0.4 0.6 0.8 A-
1. R. Malewski, et.aI, “Five years of monitoring the
P e r c e n t i l e l e n g t h (x/l) impulse test of power transformer with digital
recorders and the transfer function method”, CIGRE,
Fiy.10. Percmlile variation of first threc nsonanl Trqxluccics ( f ~fz.
. 0) August 1992, pp 12-20 I .
along length of winding 2. Heller and Veverka. B, Surge phenomena in electrical
machines, London, Lliffe books.
3. R. Malewski and B. Powlin, “Digital monitoring
technique for HV impulse tests”, IEEE Trans. PAS.
vol. 104,no.ll,April 1985,pp 3108-3116.
4. RC. Degeneff, “A general method of dettrmining
resonance in transformer winding”, IEEE Trans on
PAS, vol. 96,110.2, September 1977, pp. 423430.
5. K. C.DcycncT1; ct.el., “A Methcxl Tor reduced order
transformer model for system studies from detailed
lumped parameter models”, IEEE Trans. Power
Delivery, vol. 7,no. 2, 1992, pp. 649-655.
m V. Jayashankar, et.al., “A new paradigm for the
6.
’“I 0 10 20 30 40 50 60 70 80
impulse testing of power transformers”, third
conference and workshop on EHV technology,
Pig.1l.a. N PAU~T Ban&dore, India, 1995.
Resonance frequency : &-First, B-Second 7. Pritindra, Chowdhuri, Electromagnetic Transients in
C-Third Power Systems, Chapter 12, John Wiley and SOIIS,
1996.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.
APPENDIX I
C, =8.5 x 10-"f
& =2.1 x 1o"n
s -22.m
M1-2 = 13.537 mH
M 1-3 =6.23 I d
M1-4 -3.379mH
M1-5 -1.987mH
M 1-6 = 1.242mH
M1-7 =0.817mH
M 1-8 t0.560mH
M1-9 10.398mH
M1-10 ~0.292mH
L11 =28.998 mH
c, =3 . 4 ~ 10"*f
- 1 . 6 5 ~105Q
APPENDIX 11
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on December 28,2022 at 20:18:27 UTC from IEEE Xplore. Restrictions apply.