Manual Meter Chint Three-Phase
Manual Meter Chint Three-Phase
Manual
ZTY0.464.1267
1. Brief Introduction
DTSU666 and DTSU666-CT three phase Smart meter (Din-rail) (hereinafter referred to as the
“instrument”) is designed based on power monitoring and energy metering demands for electric power
instrument combining measurement and communication function, mainly applied into the
measurement and display for the electric parameters in the electric circuit including three voltage,
three current, active power, reactive power, frequency, positive& negative energy, four-quadrant
energy, etc. Adopting the standard DIN35mm din rail mounting and modular design, it is characterized
with small volume, easy installation and easy networking, widely applied into the internal energy
monitoring and assessment for industrial and mining enterprises, hotels, schools, large public
buildings.
The meter is intended to be installed in a Mechanical Environment ‘M1’, with Shock and
Directive.
Complied standards:
EN 50470-1:2007 Electricity metering equipment (a.c.) - Part 1 general requirements, tests and
MODUS-RTU protocol.
DTSU666 and DTSU666-CT three phase Smart meter
ZTY0.464.1267
(Din-rail)
Operation manual Page 2, Total 18
1) Characterized with positive and reverse active power, combined active power, combined
reactive power, four quadrant reactive power metering and storage function with combination mode
3) Adopting the standard DIN35mm din rail mounting and modular design, it is characterized with
Atmospheric pressure: 63.0kPa~106.0kPa( altitude 4km and below), excepting the requirements
2. Working Principle
The instrument are composed of high accurately integrated circuit specially for measurement
(ASIC) and managing MCU, memory chip, RS485 communication module, etc.
DTSU666 and DTSU666-CT three phase Smart meter
ZTY0.464.1267
(Din-rail)
Operation manual Page 3, Total 18
The special metering integrated circuit (ASIC) integrated six load two order ∑-△ type of A/D
conversion, please take the digital signal processing measured by the voltage circuit as well as all the
power, energy, effective values, power factor and frequency. This metering chip can measure the active
power, reactive power, apparent power, active energy, reactive power, apparent energy of each phase
and combined phase, and at the same time measuring current, voltage effective values, power factor,
phase angle, frequency and other parameters, entirely satisfying the needs of power meter. The chip
provides an SPI interface, convenient for metering parameters as well as parameter calibration between
Table 2 The limit value of the active percentage error of meters on balanced load
3.2.1. Starting
DTSU666 and DTSU666-CT three phase Smart meter
ZTY0.464.1267
(Din-rail)
Operation manual Page 5, Total 18
Under the power factor of 1.0 and started current, the instrument can be started and continuously
measure (for multiple phase instrument, it will bring balanced load). If the instrument is designed
based on measurement for dual directional energy, then it is applicable for each direction of energy.
When the voltage is applied with no current flowing in the current circuit, the test output of the
For this test, the current circuit shall be open-circuit and a voltage of 115 % of the reference
600 106
Δt [min] for meters of class 0.5S or 1
k m U n I max
480 106
Δt [min] for meters of class 2
k m U n I max
k is the number of pulses emitted by the output device of the meter per kilovarhour(imp/kW⋅h);
m is the number of measuring elements;
Un is the reference voltage in volts;
Imax is the maximum current in amperes.
4. Main function
From the displayed interface, the electrical parameter and energy data are all primary side data
(that is, the multiplied by current and voltage ratios). The energy measuring value will be displayed
Figure 2 display
=1.100kW
Combined
phase
Phase B voltage
6 15 power
=220.1V
factor
PFt=0.500
phase A
Phase C voltage power
7 16
=220.2V factor
PFa=1.000
Phase B
Phase A current power
8 17
=5.000A factor
PFb=0.500
phase C
Phase B current power
9 18
=5.001A factor
PFc=-0.500
4.2. Programming function
Button description: “SET” button represents “confirmation”, or “cursor shift” (when input digits),
“ESC” button represents “exit”, “→” button represents “add”. The input code is (default 701).
”is Exit the programming operation interface or switch to the character interface from digit modification
interface, add from the beginning after setting the digit to the maximum value.
Characterized with a RS485 communication interface, the baud rate can be changed between
Factory default communication parameter is ModBus-RTU protocol, the baud rate is 9600bps,
with the calibration bit and stop bit to be n.1, and the instrument address to be 1. The following table
is the common ModBus protocol address table, can be asked for specified communication protocol
negative number:capacitive)
(Invalid for three phase three phase) (×0.001)
B phase power factor(positive number:inductive, float
202EH PFb negative number:capacitive) 2 R
(Invalid for three phase three phase) (×0.001)
C phase power factor(positive number:inductive, float
2030H PFc negative number:capacitive) 2 R
(Invalid for three phase three phase) (×0.001)
2044H Freq Frequency, Unit Hz(×0.01Hz) float 2 R
Power primary side data
101EH ImpEp (current)positive total active energy(kWh) float 2 R
1028H ExpEp (current)negative total active energy(kWh) float 2 R
Note : Single-precision floating poin(float)t adopts standard IEEE754 format, total 32 bit(4 word). The
single-precision floating point mode is assumed to be ABCD(high type in the front, low byte
behind).
The horizontal axis of the measurement plane represents the current vector I (fixed on the
horizontal axis), and the instantaneous voltage vector is used to represent the current power transmission.
Compared with the current vector I, it has phase angleφ. The counter-clockwise direction φangle is
positive.
Output active power Output reactive power
- +
Input reactive power
II I
+ S
Q
Output
Output reactive
reactive power
power φ
I
P
- III IV
Figure 7 current cable terminal (Conductor Cross-sectional Area Range ≤16 mm2 )
When unpacking the carton, if the shell has obvious signs caused by severe impact or falling, please
After the instrument being removed from the packing box, it should be placed on a flat and safe
plane, facing up, not overlaying for more than five layers. If not installed or used in a short time, the
electric meter shall be packed and placed to the original packing box for storage.
The waterproof and dustproof rating of the front panel of the Meter is IP51,it shall be used in the
If the model No or configuration in the original packing box is not in accordance with the
requirement, please contact with the supplier. While, if the inner package or shell has been damaged
after removing the instrument from the packing box, please do not install, power on the instrument,
6.2.2. Installation
It requires experienced electrician or professional personnel to install it and you must read this
operation manual. During the installation, if the shell has obvious damage or marks caused by violent
impact or falling, please do not install it or power on and contact with the supplier as soon as possible.
2-------UA (Phase A voltage input terminal) 5 -------UB (Phase B voltage input terminal)
8-------UC (Phase C voltage input terminal) 10-------UN (Phase N voltage input terminal)
DTSU666 and DTSU666-CT three phase Smart meter
ZTY0.464.1267
(Din-rail)
Operation manual Page 15, Total 18
Current signal:
Auxiliary function
When transporting and unpacking the products, please confirm they are not severely impacted,
transporting and storing based on Transportation, basic environmental conditions and testing methods
The instrument and accessories shall be stored in the dry and ventilated places, to avoid humidity
and corrosive gas erosion, with the limited environmental temperature for storage to be -40℃~+70℃
We guarantee free reparation and change for the multi-meter if found any unconformity with the
standard, under circumstance of that the users fully comply with this instructions and complete seal after
Dear clients,
Please assist us: when the product life is end, to protect our environment, please recycle the product or
components, while for the materials that cannot be recycled, please also deal with it in a proper way. Really appreciate
Zip Code:325603
Telephone:0577-62877777
Fax:0577-62891577
Email:ztyb@chint.com
No.:ZTY0.464.1267V4