Refrigeration Piping
Refrigeration Piping
Refrigeration Piping
32-3009-03 3
Application
Guide
General Information B — Oil return must always be consid- 3 – There is no direct penalty for pres-
ered since some oil is continually being sure drop in a liquid line provided
The four prime considerations in design- circulated with the refrigerant and must that 100% liquid is being delivered
ing a refrigerant piping system are: be returned to the compressor. If the to the expansion device, and that
A – System Reliability recommended suction line sizes are the liquid pressure available to the
B – Oil Return used, no oil return problems should be expansion device is adequate to
encountered with split systems and no produce the required refrigerant
C – Friction Losses (Pressure Drop) traps are recommended. flow. Pressure drop or gain due to
D – Cost vertical lift must be added to the friction
C — Pressure drop or friction losses are loss in liquid lines to determine the total
A — The piping system can affect important from a performance stand- pressure drop. The acceptable pressure
system reliability in a number of ways: point. The following general statements drop in the liquid line for equipment
• Oversized liquid lines significantly point out the effects of pressure drop in through 10 tons is 35 PSI for R-22 sys-
increase the amount of refrigerant the various components of the refriger- tems and 50 PSI for R-410A systems.
in the system, and thus creating the ant piping system.
potential for slugging, oil dilution, D — Cost is an obvious consideration
or other damage to the compressor. 1 – Pressure drop in the suction line and dictates that the smallest tubing
reduces system capacity significantly possible be used that will result in a
• Undersized liquid lines and the and increases power consumption per system with acceptable friction losses.
associated “flashing” of refrigerant ton. The most generally accepted value
causes starving of the evaporator coil. for pressure drop in a suction line is a The following pages cover the selection
The results can be significant loss in pressure drop equivalent to 2°F (approx. of liquid lines and suction lines for split
capacity, frosted evaporator coil, high 3 PSI with R-22 in the air conditioning heat pump and cooling systems.
superheat etc. range of evaporating temperatures or
approx. 5 PSI for R-410A). As tubing runs It is recommended that the user read
• Oversized suction lines will result become longer, it is inevitable that the all of Chapter I in order to better under-
in refrigerant velocities too low to ASHRAE recommendation will be stand the Tables, Charts, etc.
provide adequate oil return to the exceeded, at times. This trade-off, of
compressor. somewhat greater suction line losses, See the Index for a complete listing,
for adequate oil return is an absolute including page number, for all tables,
• Undersized suction lines reduce must, in order to preserve system charts, etc.
capacity and efficiency and contribute reliability.
to high superheat. All installations must conform to any
2 – Pressure drop in hot gas lines re- codes or regulations applying at the
• Excessive refrigerant line length duces system capacity to a somewhat site. The Safety Code for Mechanical
reduces system capacity and effi- lesser degree and increases power Refrigeration, ASA-B-9-1 and the Code
ciency, as well as system reliability consumption to a slightly lesser degree for Refrigeration Piping, ASA-B31.5
(excessive refrigerant charge). than does pressure drop in suction lines. should serve as your guide toward a
Keep refrigerant lines as short as Since the only hot gas lines we are con- safe piping system.
conditions permit! cerned with are in heat pump systems
where they also serve as suction lines,
we will treat them as suction lines. (See
Chapter III in this manual for information
on hot gas lines for hot gas bypass.)
4 32-3009-03
Application
Guide
CHAPTER I must be avoided. However, it prevails The saturation pressure for R-22 at 110°F
only when outdoor temperatures are is approx. 226 PSIG Substracting 226
Refrigerant Piping relatively cool and under conditions PSIG from the 260 PSIG condensing
when air conditioning for most residen- pressure, gives us a difference of 34 PSI.
tial applications is not required. While this pressure difference is 1 PSI
Liquid Lines for
less than the 35 PSI obtained with the
Split Cooling and Any situation such as an unusually long 125°F example used in earlier versions
liquid line or a large difference in eleva-
Heat Pump Systems tion between the indoor and outdoor
of this manual, we will continue to use
35 PSI as the maximum liquid line pres-
The purpose of the liquid line is to sections may require consideration as sure drop. (A drop in liquid line tempera-
convey liquid refrigerant from the con- discussed further below. ture of 1/3°F by natural cooling, will
denser to the expansion device such as
provide the needed 1 PSI.)
the expansion valve or FCCV Accutron.TM The flashing of refrigerant to gas will
The expansion device in turn throttles occur if the refrigerant absorbs heat Note that the above mentioned tempera-
the refrigerant from the high side pres- in the liquid line so that it is no longer tures of 120°F and 110°F represent pres-
sure as it exists at the entrance to the subcooled or if its pressure is reduced sures of 418 PSIG and 365 PSIG with
device to the relatively low evaporator below the saturation pressure corre- R-410A, a difference of 53 PSI. For the
pressure. The high side pressure varies sponding to its temperature. present, we will limit R-410A liquid line
through a wide range with the cooling pressure drop to 50 PSI.
load and the outdoor temperature. The Normally, the liquid line temperature is The foregoing has shown how to
expansion device has to handle this above that of the surrounding ambient figure the liquid line pressure drop
situation and the fact that a particular so there is no “flashing” as a result of and indicated that the heat loss to the
pressure drop is required to produce temperature rise and usually there is surroundings help to maintain adequate
the flow through the liquid line is not enough cooling of the refrigerant to subcooling. The amount of refrigerant
especially critical providing two compensate for the fact that the pressure in the system governs the amount of
conditions exist. gradually drops to maintain flow. In spe- subcooling of the liquid as it leaves
cial cases where the liquid line is run the condenser. The appropriate installa-
The first condition is that the liquid line through hot attics or other heat sources tion and charging instructions should
transports the refrigerant completely as the liquid line should be insulated. be followed.
liquid and not allow the refrigerant to
flash partly into gas. This requires that Table “C,” page 10, lists the equivalent With regard to whether adequate head
the liquid temperature be lower than the length of fittings, which must be added pressure is available at the expansion
temperature which causes refrigerant to to the linear length of the tubing to device to give the required flow, note
vaporize at the pressure prevailing lo- obtain the equivalent length of the line. that an unusually high pressure drop in
cally in the tube, that is, the refrigerant a liquid line due to long lengths or large
must be subcooled throughout the The pressure loss due to vertical lift differences in elevation, has the same
length of the liquid line. (evaporator above the condenser) de- effect as a reduced head pressure due
pends on the difference in level between to cooler outdoor temperatures entering
The second condition is that the pres- the metering device and condenser (or the air cooled condenser. Typically each
sure and amount of subcooling at the receiver) and on the density of the refrig- additional 10 PSI drop in pressure in the
entrance to the expansion device must erant. At normal liquid line temperatures liquid line means that the minimum out-
be adequate for the device to pass the with R-22 the static pressure drop will be door temperature at which the system
required flow into the evaporator to 0.50 PSI per foot of lift (.43 PSI per foot will perform satisfactorily is raised by
suit the cooling load condition. If not, with R-410A). 3 degrees. Allowance for this is signifi-
the evaporator is starved for refrigerant. cant only for unusual applications
This may cause one part to freeze ice As an example, consider an air-cooled where cooling is required at low outdoor
and gradually choke off the indoor air- R-22 system with 95°F air entering the temperatures. Performance for such
flow even though other parts of the condenser, the condensing temperature conditions is published in the Product
evaporator are warm for lack of refriger- is 120°F (approx. 260 PSI). Manual and is based on 25 feet of line as
ant. When the evaporator is starved, the After being subcooled in the condenser, used for Standard Ratings. For marginal
reduced cooling effect reduces the head the liquid R-22 leaves the condenser at applications where a Head Pressure
pressure in the condenser and through- 110°F. Assuming the pressure at the Control accessory is under consider-
out the liquid line, which tends still fur- condenser outlet is the same as the con- ation, the effect of liquid line pressure
ther to reduce the refrigerant flow. This densing pressure of approx. 260 PSIG, drop should be considered.
inadequate head pressure situation the liquid R-22 has been subcooled 10°F.
32-3009-03 5
Application
Guide
Note that equivalent lengths are used • Suction Line Selection – pages 8, 9
when calculating pressure drops. Actual and 10
(linear) lengths are used when calculat- • Refrigerant Piping Limits – page 11
ing pounds of R-22 in a line set. (An
elbow contains about the same amount • Piping Accessories for Scroll and
of R-22 as does the same length of Reciprocating Compressors – page 12
straight tubing.) • Tubing Hints – page 13
Table “C,” page 10, lists equivalent • Air Conditioning Formulas – page 14
lengths for elbows, etc. for pressure
drop calculations. • R-410A Refrigerant – pages 15, 16
and 17
In addition to friction loss, any pres- Note: A worksheet for Manual Calculations is provided
sure drop due to liquid lift must be on page 31.
accounted for (.5 PSI per foot of lift
for R-22 systems, .43 PSI per foot
with R-410A).
6 32-3009-03
Application
Guide
Table “A”
Liquid Line Selection Table For R-22 Systems
Maximum Allowable Liquid Line Pressure Drop .................................................................................................. = 35 PSI
Subtract .5 PSI for each foot of Liquid Lift (if any) ......................................................................................................
Do Not Exceed this value when selecting Liquid Line. ...............................................................................................
Pressure Drop (PSI)
Total Equivalent Length
Tube Rated
O.D. BTUH 20' 40' 60' 80' 100' 120' 140' 160' 180' 200' 220' 240'
15000 4.3 8.7 13.0 17.4 21.7 26.0 30.4 34.7 — — — —
1/4" 18000 6.0 12.0 18.1 24.1 30.1 — — — — — — —
24000 10.2 20.3 30.5 — — — — — — — — —
15000 1.1 2.3 3.4 4.6 5.7 6.8 8.0 9.1 10.3 11.4 12.5 13.7
18000 1.6 3.2 4.7 6.3 7.9 9.5 11.1 12.6 14.2 15.8 17.4 19.0
5/16" 24000 2.7 5.3 8.0 10.6 13.3 16.0 18.6 21.3 23.9 26.6 29.3 31.9
30000 4.0 8.0 11.9 15.9 19.9 23.9 27.9 31.8 — — — —
36000 5.5 11.1 16.6 22.2 27.7 33.2 — — — — — —
42000 7.3 14.6 22.0 29.3 — — — — — — — —
18000 .6 1.1 1.7 2.2 2.8 3.4 3.9 4.5 5.0 5.6 6.2 6.7
24000 .9 1.9 2.8 3.8 4.7 5.6 6.6 7.5 8.5 9.4 10.3 11.3
30000 1.4 2.8 4.2 5.6 7.0 8.4 9.8 11.2 12.6 14.0 15.4 16.8
3/8" 36000 1.9 3.9 5.8 7.8 9.7 11.6 13.6 15.5 17.5 19.4 21.3 23.3
42000 2.6 5.1 7.7 10.2 12.8 15.4 17.9 20.5 23.0 25.6 28.2 30.7
48000 3.3 6.5 9.8 13.0 16.3 19.6 22.8 26.1 29.3 32.6 — —
60000 4.9 9.8 14.7 19.6 24.5 29.4 34.3 — — — — —
72000 6.8 13.7 20.5 27.4 34.2 — — — — — — —
36000 .4 .8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8
42000 .5 1.0 1.6 2.1 2.6 3.1 3.6 4.2 4.7 5.2 5.7 6.2
48000 .7 1.3 2.0 2.6 3.3 4.0 4.6 5.3 5.9 6.6 7.3 7.9
1/2" 60000 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0
72000 1.4 2.8 4.1 5.5 6.9 8.3 9.7 11.0 12.4 13.8 15.2 16.6
90000 2.1 4.2 6.2 8.3 10.4 12.5 14.6 16.6 18.7 20.8 22.9 25.0
120000 3.5 7.0 10.5 14.0 17.5 21.0 24.5 28.8 31.5 35.0 — —
90000 .6 1.2 1.9 2.5 3.1 3.7 4.3 5.0 5.6 6.2 6.8 7.4
5/8"
120000 1.1 2.1 3.2 4.2 5.3 6.4 7.4 8.5 9.5 10.6 11.7 12.7
Note 1: A blank space indicates a pressure drop of more than 35 PSI.
Note 2: Other existing sources of pressure drop such as solenoid valves, etc. must be accounted for.
Note 3: A vertical run with a heat pump system always results in a liquid lift (heating or cooling).
Note 4: The smallest liquid line diameter that results in a total liquid line pressure drop of 35 PSI or less results in the most reliable system (fewer pounds of R-22).
32-3009-03 7
Application
Guide
Suction Lines for do not. These compressors are provided improper mixing of hot gas and
with special piping which allows oil lev- desuperheating liquid may result
Split Cooling and els in the two compressors to equalize.) in slugging of liquid refrigerant.
Heat Pump Systems
Do not use evaporator pressure regulat- Do not tape or otherwise fasten liquid
Suction lines must return refrigerant lines and suction lines together unless
ing valves (EPR valves) or similar throt-
vapor and oil from the evaporator to there is insulation between them. The
tling valves in the suction line. Hermetic
the compressor during operation of the resultant heat exchange would increase
compressors depend on suction gases
system, but should not allow oil or liquid suction gas superheat and may cause
for cooling and as the EPR valve throttles
refrigerant to be returned as slugs at any overheating of the hermetic compressor.
time, because of the danger of broken down to maintain a constant evaporator
pressure, the quantity of suction gas (See Tubing Hints on page 13.)
compressor valves, oil dilution, etc.
returning to the compressor is reduced
and its superheat is increased. The only Suction lines must be insulated to pre-
Never attempt to operate two hermetic vent condensation and vapor sealed
compressors with a common suction type of capacity modulation recom-
mended (other than multiple units) is a on the outside to prevent a build-up
line. It is impossible to return oil to each of moisture in the insulation.
compressor at precisely the same rate hot gas by-pass system properly applied
as it is being pumped. As a result, one so as to keep suction gas superheat It is advisable to avoid running
compressor will eventually run low on within normal limits, and provide proper refrigerant lines underground
oil in its sump and proper lubrication velocity through the evaporator and whenever possible. If it is absolutely
is no longer possible. Each hermetic suction lifts (if any) for adequate oil necessary to run refrigerant lines under-
compressor must have its own separate return. ground, they must be run in 6" P.V.C.
refrigerant system. conduit. (See Figure 1 below.)
High superheat will result in improper
(Our two compressor systems may cooling of the hermetic compressor,
appear to violate this rule, but they while excessively low superheat or
Figure 1
Underground Conduit
(For Underground Refrigerant Lines)
45° Ells
No Joints In Copper
6" PVC Pipe Schedule 40 Within The Conduit
Use 45° elbows to facilitate pulling the conduit is critical. Some installers install
tubing through the conduit. The purpose a drain in the lower parts of the conduit.
of the conduit is to keep water away Bear in mind, that if the water table rises
from the refrigerant lines. Careful seal- above the drain, water may be forced
ing, where the lines enter and leave the into the conduit.
8 32-3009-03
Application
Guide
About Suction Lines 3 – Increase the indoor airflow some- the compressor is equipped with sump
what, within the 350 to 450 CFM per ton heat, in order to bring the system up to
and Pressure Drops limits. (Some latent capacity will be lost.) current requirements.)
ASHRAE recommends that suction line 4 – Select a different equipment
pressure drop be limited to a pressure combination that provides the The Dilemma:
corresponding to 2°F (approx. 3.0 PSI needed capacity. Suppose that a service man is attempt-
with R-22). This is usually not a problem
ing to check the refrigerant charge in
with line sets of 100 eq. ft. or less. The pressure drop values show in Table the existing 2-1/2 ton system, with 5/16"
“B” are not required in order to select a – 5/8" O.D. refrigerant lines, mentioned
A quick look at the pressure drop per suction line. They are provided for your
100 ft. listed in Table “B” reveals that above (F.C.C.V. flow control). He is using
information only. One example of their the superheat method and, based on the
using the largest allowable suction line use might be to evaluate an existing
diameter for each tonnage results in a existing indoor and outdoor conditions,
system. For instance, careful measure- has determined that 10° superheat, at
pressure drop of less than 3 PSI per ments of an existing 2-1/2 ton system,
100 eq. ft. in all cases, except the 1 ton the outdoor unit is required.
installed with a 5/16" liquid line and
system (3.3 PSI). 5/8" suction reveal the following: 110 His compound gauge indicates 63 PSIG
linear ft., 8 short radius elbows. The or 36° evaporating temperature. Adding
Obviously, if line sets exceed 100 eq. ft. equivalent length, 110 + (8 x 5.7*)
significantly, there will be cases where 10° to the 36° tells him that he should
= 155.6 ft. (*from Table “C” page 10). try for a 46° suction line temperature,
the suction line pressure drop exceeds 155.6 ft. x 12.7/100 = approx. 19.8 PSI
3.0 PSI. (This is a price we must pay for right? Wrong in this case!
suction line pressure drop (more than six
long line sets.) times the ASHRAE recommendation). His actual evaporating pressure is
In those cases, where long tubing 63 PSIG plus 19.8 PSI pressure drop,
The approx. 20% loss in capacity tells or approx. 83 PSIG (49° plus.) The
runs result in higher suction line us that our 2-1/2 ton system is delivering
pressure drops than desired, do not desired suction line temperature = 59°.
2 tons. This 20% loss in capacity, to- Attempting to charge to the 46° suction
use a suction line diameter larger than gether with a 10% loss in efficiency,
those listed in Table “B,” page 10, line temperature would undoubtedly
makes a very strong case for replacing result in a severe overcharge. The
for the system tonnage. To do so the line set with a properly sized line set.
would result in refrigerant velocities extreme pressure drop not only resulted
too low to ensure oil return. in very substantial losses in capacity and
Assuming that the 5/8" O.D. suction efficiency, but could easily be the cause
line is to be replaced with a 7/8" O.D. of a severe overcharge (and possibly a
The net capacities indicated in Table “B” suction line, and the installer was able
for the various equivalent lengths show compressor failure).
to reduce the number of elbows to six
that there is approx. 1% loss in capacity (long radius) elbows: the equivalent
for each 1.0 PSI of pressure drop. (Effi- Always select one of the suction line
length = 110 + (6 x 5.3) or 141.8 ft., sizes listed in Table “B” for the nominal
ciency losses are approx. .5% per PSI 2.0 PSI/100 ft. (from Table “B”) x
of pressure drop.) tonnage of your system. Oil return will
141.8/100 = approx. 2.8 PSI suction line be assured with any of the listed sizes.
pressure drop. The lowest possible capacity losses
If the net capacity, indicated for the
calculated equivalent length, falls a consistent with adequate oil return are
The 30000 BTUH system will now deliver afforded by the largest tube size listed.
little short of your requirement (and approx. 29500 BTUH (140 eq. ft. value).
you have selected the largest allowable Short tubing runs may provide accept-
The loss in efficiency is now less than able losses with a smaller tube size.
tube diameter) one of the following 1%, which will be reflected in the
hints may remedy the situation: Net capacities are listed for all approved
owner’s electric bill (favorably). sizes for equivalent lengths up to 240 ft.
1 – Move the outdoor unit closer,
if possible. (The installer, when replacing the
2 – Use as few elbows as possible, and undersized refrigerant lines, should
use long radius elbows to reduce the convert the indoor unit to expansion
equivalent length. valve flow control and make sure that
32-3009-03 9
Application
Guide
Table “B”
Allowable Suction Line Diameters and Net Capacities
Tube Nominal P.D. Net Capacity For Equivalent Length
Nom. Size Capacity Per
Tons (In.) (25 Ft.) 100 Ft. 40 60 80 100 120 140 160 180 200 220 240
1.0 1/2 14685 11.7 14425 14080 13735 13390 13045 — — — — — —
5/8 15000 3.3 14925 14825 14725 14625 14525 14425 14325 14225 14125 14025 13925
1.5 5/8 18000 4.7 17875 17705 17535 17365 17195 17025 16855 16685 16515 16345 16175
3/4 19305 1.8 19255 19185 19115 19045 18975 18905 18835 18765 18695 18625 18555
5/8 23695 8.1 23405 23020 22635 22250 21865 21480 21095 20710 — — —
2.0 3/4 24000 3.0 23890 23745 23600 23455 23310 23165 23020 22875 22730 22585 22440
7/8 24100 1.3 24055 23990 23925 23860 23795 23730 23665 23600 23535 23470 23405
5/8 29370 12.7 28810 28665 27320 26575 25830 — — — — — —
2.5 3/4 30000 4.6 29795 29520 29245 28970 28695 28420 28145 27870 27595 27320 27045
7/8 30195 2.0 30105 29985 29865 29745 29625 29505 29385 29265 29145 29025 28905
3.0 3/4 35670 6.5 35320 34855 34390 33925 33460 32995 32530 32065 31600 31135 30670
7/8 36000 2.8 35850 35650 35456 35250 35050 34850 34650 34450 34250 34050 33850
3/4 41475 8.8 40930 40200 39470 38740 38010 37280 36550 35820 — — —
3.5 7/8 42000 3.8 41760 41440 41120 40800 40480 40160 39840 39520 39200 38880 38560
1-1/8 42295 1.0 42230 42145 42060 41975 41890 41805 41720 41635 41550 41465 41380
4.0 7/8 47570 4.9 47220 46755 46290 45825 45360 44895 44430 43965 43500 43035 42570
1-1/8 48000 1.3 47905 47780 47655 47530 47405 47280 47155 47030 46905 46780 46655
7/8 59175 7.5 58510 57620 56730 55840 54950 54060 53170 52280 51390 — —
5.0 1-1/8 60000 2.0 59820 59580 59340 59100 58860 58620 58380 58140 57900 57660 57420
1-3/8 60195 .7 60130 60045 59960 59875 59790 59705 59620 59535 59450 59365 59280
6.0 1-1/8 72000 2.8 71700 71295 70890 70485 70080 69675 69270 68865 68460 68055 67650
1-3/8 72325 1.0 72215 72070 71925 71780 71635 71490 71345 71200 71055 70910 70765
1-1/8 89390 4.2 88825 88075 87325 86575 85825 85075 84325 83575 82825 82075 81325
7.5 1-3/8 90000 1.5 89795 89525 89255 88985 88715 88445 88175 87905 87635 87365 87095
1-5/8 90205 .6 90125 90015 89905 89795 89685 89575 89465 89355 89245 89135 89025
1-1/8 118560 7.4 117245 115490 113785 111980 110225 108470 106715 104960 103205 101450 —
10.0 1-3/8 120000 2.6 119230 118905 118280 117655 117030 116405 115780 115135 114530 113905 113280
1-5/8 120450 1.1 120250 119985 119720 119455 119190 118925 118660 118395 118130 117865 117600
Note 1: Shaded values = more than 10% capacity loss.
Note 2: Blank space = more than 15% capacity loss.
10 32-3009-03
Application
Guide
Piping Limits
1. Compressor Protection
A. Suction line accumulators are no longer required (on 1 through 10 ton systems).
B. Protect reciprocating compressors as follows:
• Up to 80 linear feet of rated tube sizes: OK as shipped.
• Over 80 linear feet , or oversized lines: Apply sump heat1 and TXV indoor metering device.13
C. Protect Scroll compressors as follows:
• Up to 12 lbs. R-22 system charge2: OK as shipped.
• 10.5 lbs. for R-410A.
• Over 12 lbs. R-22 system charge2: Apply sump heat and TXV indoor metering device.1
D. Liquid line solenoid valves (straight cooling systems only):*
Cycle solenoid valve with compressor (no pump down).
• If compressor is above the indoor unit, locate the liquid line solenoid valve near the indoor unit.
• If compressor is below the indoor unit, locate the liquid line solenoid valve within 25 ft. of compressor.
Note: If pump down is desired, a discharge check valve must be installed in the discharge line. (Locate the liquid line solenoid valve near the indoor unit.)
* Liquid line solenoid valves are not required with TXV systems.
5. R-410A Systems
A. Maximum linear length = 200 ft.
B. Maximum linear liquid lift = 60 ft.
C. Maximum linear suction lift = 200 ft.
6. Traps
A. Traps are not recommended.
Notes:
1 If not factory furnished.
2 System charge = nameplate charge, plus tubing allowance (See page 12 for Tubing Allowance).
3 If a non-bleed TXV is applied to a single phase Reciprocating compressor system, a hard start kit will be required (not required with Scroll compressor systems).
4 Pub. No. 32-3312-01 (Windows® based) computer software contains complete piping data, including high rise systems, R-410A, pressure drops, net capacity,
system charge, tube sizes, etc.
32-3009-03 11
Application
Guide
Application Requirements Liquid lifts up to 60 linear ft. Suction line accumulator is not required
Systems within the limits indicated Suction lifts up to 200 linear ft. on 1 through 10 tons.
above, or systems beyond those limits
This includes R-410A systems (recom- Do not apply pump down cycle, unless
which are equipped with compressor
mended line sizes only), but does not discharge check valve has been applied.
sump heat and indoor TXV refrigerant
include two compressor systems which (See page 11.)
control, are O.K. for:
are limited to 80 linear ft. and to lifts
Linear Lengths up to 200 ft.
(liquid or suction) of up to 25 linear ft.
12 32-3009-03
Application
Guide
Figure 3 Figure 2
Thermal Bulb Location Typical Straight Cooling System
(Outdoor Unit Above Indoor Unit)
LIQUID LINE
Figure 4
Tubing Hints
SUCTION LINE
LARGER THAN 7/8"
STRAP HANGER
SADDLE
SADDLE SUPPORT
32-3009-03 13
Figure 5
NO V No V
Infiltration or Ventilation CFMo 2. CFMo = 2. CFMo =
60 min./hr. 60 min./hr.
Total Heat (HT) Btuh 5. HT = CFMT x 4.5 x (h1 – h2) = Btuh 6. HT = CFMT x 4.5 x (h2 – h1) = Btuh
Sensible Heat (HS) Btuh 7. HS = CFMT x 1.08 x (T1 – T2) = Btuh 8. HS = CFMT x 1.08 x (T2 – T1) = Btuh
Latent Heat (HL) Btuh 9. HL = CFMT x .68 x (W1 – W2) = Btuh 10. HL = CFMT x .68 x (W2 – W1) = Btuh
CFMo CFMo
Entering Air Temperature (T1) °F. D.B. 11. T1 = t1 + x (t2 – t1) = °F.D.B. 1 12. T1 = t1 – x (t1 – t2) = °F.D.B. 2
CFMT CFMT
(Mixed Air)
1 If duct heat gain is a factor, add to T1: 2 If duct heat loss is a factor, subtract from T1:
Duct Heat Gain (Btuh) Duct Heat Loss (Btuh)
CFMT x 1.08 CFMT x 1.08
Btu/lb. HT HT
Enthalpy – Leaving Air (h2) 17. h2 = h1 – = Btu/lb. dry air 18. h2 = h1 + = Btu/lb. dry air
dry air CFMT x 4.5 CFMT x 4.5
19. Refer to Enthalpy Table and read W.B. temperature 20. Refer to Enthalpy Table and read W.B. temperature
Leaving Air W.B. Temperature °F.W.B.
corresponding to enthalpy of leaving air (h2) (see #17). corresponding to enthalpy of leaving air (h2) (see #18).
Heat Required to Evaporate
Water Vapor Added to Btuh 21. HL = CFMo x .68 (W3 – Wo) = Btuh 22. HL = CFMo x .68 (W3 – Wo) = Btuh
Ventilation Air
Excess Latent Capacity
HL loss Btuh (see #22)
Humidification Requirements
Lbs.
water/hr.
23.
( Moisture )
Make up = of System x % Run Time
1060 Btu/lb.
= lbs./hr.
(
24. Make up =
Moisture ) 1060 Btu/lb.
= lbs./hr.
* See Enthalpy of air (Total Heat Content of Air) Table for exact values.
14 32-3009-03
Application
Guide
32-3009-03 15
Application
Guide
Example
Given: Rated system capacity = 42000 BTUH, 68 linear ft., 4 long radius elbows (no solenoid valve or other source of
pressure drop): 20 ft. liquid lift.
Step #1 20 x .43 = 8.6 PSI pressure drop due to liquid lift. 50 minus 8.6 = 41.4 PSI available for friction loss.
Step #2 68 + (4 x 3.2) = 80.8 eq. ft. (See Table “C,” page 10, for equivalent lengths.)
Step #3 Referring to Table A-R, we find that 80 ft. of 5/16" liquid line, (42,000 BTUH) = 30.7 PSI pressure drop.
(Well within our 41.4 PSI limit.)
16 32-3009-03
Application
Guide
32-3009-03 17
Application
Guide
CHAPTER II umes of vapor, as well as substantially heat exchange capacity to provide the
reducing the capacity of the metering required additional subcooling for
High Rise Heat Pump device because of the mixture of vapor systems up through 10 tons (and is
Applications and liquid it would be forced to handle. rated for both R-22 or R-410A).
(R-22 and R-410A) It is not unusual for high rise systems It should be noted that although the
The demand for greater vertical separa- to operate with total liquid line pressure heat exchanger used with the high rise
tion for the indoor and outdoor sections drops in excess of 100 PSI (R-22) with no system is designed as a suction to liquid
of heat pump systems, over the years, “flashing” (even higher with R-410A.) heat exchanger, it is not used in that
has lead to the development of the high manner. (Suction gas is not routed
rise system. Until this time, the maxi- As mentioned earlier, the (windows) through the heat exchanger.) Instead,
mum allowable liquid lift for R-22 sys- computer piping program will call for the normal liquid flow is through the
tems was approximately 60 ft. The 60 ft. the subcooler when ever it is required, suction side of the heat exchanger. A
lift resulted in a pressure drop (60 x .5) size the capillary tube and call for any small portion of the liquid is fed through
of 30 PSI, which left only 5 PSI of the other required accessories. The rest of the capillary tube to the other side of the
allowable 35 PSI for friction loss. Some- this chapter is designed to help the sys- heat exchanger where it is evaporated
what higher liquid lifts can be tolerated tem designer who does not have access to chill the liquid R-22 the required
with R-410A systems, because the to the computer program to apply the number of degrees. A 3/8" O.D. suction
allowable (total) liquid line pressure high rise system. line (insulated) is run from the heat
drop for R-410A systems is 50 PSI, also exchanger (located at the bottom of
The heat exchanger used with the high the liquid lift) to the common suction
the loss for each foot of liquid lift is .43
rise system (refrigeration research line of the outdoor unit (between the
PSI versus .50 PSI for R-22.
#H-100, or Heat-X 3/4 HP) has sufficient switch-over valve and the compressor).
However, when liquid lifts become high
enough to produce a total liquid line
pressure drop (lift + friction) of over
35 PSI with R-22 systems or 50 PSI with Table “D”
R-410A systems, the high rise system
with subcooler will be required. Subcooling Heat Exchangers
The high rise system is to be applied to
heat pump systems only, and only on
systems where the outdoor unit is above ➤
the indoor unit. The indoor unit must
utilize expansion valve flow control.
18 32-3009-03
Application
Guide
The 3/8" O.D. suction line is teed into the Figure 7 (below) indicates the hook-up door units. Note that there are now three
top of a horizontal common suction line, for the heat exchanger and capillary connecting lines between the indoor and
or into the side of a vertical common tube. The heat exchanger is to be located outdoor units (liquid line, gas line and a
suction line, thus preventing the drain- at the bottom of the liquid lift (near the 3⁄8” insulated suction line) running from
age of oil down the 3/8" O.D. tube. indoor unit). the heat exchanger to the common suc-
Figure 8, page 20, shows the piping tion line (between the switchover valve
The fact that a small portion of the liquid hook-up between the indoor and out- and the compressor).
R-22, being circulated, is diverted to the
heat exchanger, and boiled to a vapor,
has no effect on system capacity. While a
slightly reduced quantity of liquid R-22 is
delivered to the system evaporator, each Figure 7
pound contains less heat, because of the
additional subcooling and the net cool- Piping Detail – Heat Exchanger
ing effect is the same. So what have we
accomplished? We have delivered 100%
liquid to the system expansion valve, in
spite of liquid line pressure drops of 100
PSI or more.
The heat exchanger and capillary tube
are to be purchased at your local parts
wholesaler.
Table “D,” page 18, provides a picture To liquid line
and dimensional information for the connection at
heat exchanger. outdoor unit Insulated 3/8" line.
Tee into common suction
Note that the heat pump indoor unit line, between S.O.V. and
Refrigeration Research H-100 or
Large connection
to minimize
pressure drop
Small connection
32-3009-03 19
Application
Guide
Figure 8
High Lift Heat Pump Piping Schematic (Outdoor Unit above Air Handler)
Sub-Cooler
Sub-Cooler
Capillary
Air Handler with
TXV Expansion Valve Coil
Air Handler
20 32-3009-03
Application
Guide
32-3009-03 21
Application
Guide
CHAPTER III 4 – Unusually high latent loads, which The remainder of the chapter will cover
require very low evaporator tempera- the field application of hot gas bypass,
Hot Gas Bypass tures, must limit capacity at reduced including, bypass valve selection (siz-
(Capacity Modulation) load or reduced outdoor temperatures. ing), sizing of the hot gas line, and infor-
(Evaporator coils may frost.) mation on accessories, such as solenoid
valves, auxiliary side connectors, etc.
Introduction 5 – Fluctuating loads which may lead to
excessive short cycling of equipment. Some of the concerns which will be
Why Capacity Modulation? covered are:
The typical residential cooling system How Can We Modulate
performs reasonably well, with a simple • Oil return
System Capacity?
on/off control (system thermostat). Introducing the hot gas at the evaporator
1 – The application of multiple systems,
inlet (side port distributor, or, auxiliary
While cooling loads vary considerably whenever practical, results in capacity
side connector), ensures adequate refrig-
from design conditions, to mild weather modulation, without sacrificing effi-
erant velocity for oil entrainment,
cooling, the changes are usually gradual. ciency, and should be the first consider-
through the evaporator, and any
Solar and internal loads as well as the ation. (Multiple systems also have the
suction lifts.
flywheel effect of the home and furnish- inherent advantage of not “putting all
ings tend to keep short cycling of the your eggs in one basket,” in the event of • Proper superheat in suction gas
system, in mild weather, within accept- a system failure.) If very precise control to compressor
able limits. Humidity control suffers of capacity modulation is required, hot
somewhat during mild weather, but gas bypass can be applied to the first The refrigerant metering device must
with a carefully sized system, it is stage system. An example of this could be a thermostatic expansion valve. The
usually tolerable. be two five ton systems matched with a valve will automatically compensate for
dual circuited 10 ton air handler. Apply- the highly superheated hot gas, and pro-
Loads, which vary more dramatically, ing hot gas bypass to the first stage sys- vide normally superheated suction gas
and over shorter periods of time, how- tem, only, provides modulation from to the compressor (thus preventing
ever, will often require some means of 10 tons to near 5 tons when both stages compressor overheating or slugging).
capacity modulation in order to: are called for. When first stage, only, is
called for, modulation is from 5 tons to • Undersizing of bypass valve
• Provide better humidity control near zero.
• Provide better temperature control Select a valve capable of bypassing the
• Reduce short cycling problems 2 – Cylinder unloading. This method maximum required, at the existing con-
of capacity modulation is very effective ditions, at the time of the minimum load.
• Avoid frosting of evaporator coils on larger systems (factory applied). The (Design load minus minimum load =
industry has found that cylinder unload- required bypass.) If the system is signifi-
Some examples of loads requiring
ing is not cost-effective on systems of cantly oversized, system capacity minus
capacity modulation are:
10 tons capacity or less. minimum load = required bypass.
1 – High percentages of outside air.
3 – Hot gas bypass. Hot gas bypass, Allow for pressure drops through the
The current emphasis on improving properly applied, provides very precise sideport distributor, or auxiliary side
indoor air quality often leads to high capacity modulation with a moderate connector, hot gas line, solenoid
outside air percentages. Code require- loss in efficiency. (Some energy is ex- valve, etc.
ments, or high exhaust requirements pended in pumping the bypassed gas
are also contributors. It is generally through the system, which provides no (An oversized bypass valve presents
accepted, that outside air percentages cooling effect.) no problem, since it is a modulating
greater than 25% require capacity type valve, and will open only as far
For applications where cylinder unload- as is required. To maintain the desired
modulation.
ing is not available, hot gas bypass is evaporator pressure.) If more bypass is
2 – On/off type loads such as lighting, undoubtedly the method of choice, if the required than is available from a single
industrial processes, etc. can result in application of multiple systems is not valve, two valves can be piped in paral-
wide variations in loads. practical. (Hot gas bypass can be com- lel. (Adjust both valves to open at the
bined with multiple systems to provide same pressure.)
3 – Special applications requiring very even more precise modulation.)
close control of humidity, temperature,
or both.
22 32-3009-03
Application
Guide
Low head pressure problems are likely Operation – Hot Gas the valve to the limit of its stroke. The
to occur with hot gas bypass applica- Bypass Valve amount of pressure change required to
tions due to: move the valve from the closed position
The hot gas bypass regulator or dis-
to its rated open position varies with
1 – Operation at low outdoor ambients charge bypass valve automatically re-
the refrigerant used and the minimum
sponds to changes in suction pressure.
evaporator temperature desired. Most
2 – The bypassed gas bypasses the When the refrigerant evaporating pres-
manufacturers’ valve capacity ratings
condenser, further reducing head pres- sure is above the bypass valve setting,
are based on a 6°F change in suction
sure. (The published low ambient limit the valve remains closed. When the
temperature (approximately 9 PSI for
does not apply when hot gas bypass is cooling load drops, the suction pressure
R-22). In other words, a 6°F change in
utilized.) The application of a head pres- drops below the bypass valve setting
evaporator refrigerant temperature is
sure control is highly recommended. and the valve begins to open, bypassing
required to move the valve from the
a portion of the hot gas directly into the
fully closed position to the rated open
low side, thereby, maintaining the com-
position or from the rated open position
pressor suction pressure at a relatively
Hot Gas Bypass high level. The amount of valve opening
to the fully closed position. This same
valve would be able to open further if
The purpose of a hot gas bypass system is proportional to the change in the suc-
an 8°F or a 10°F change in evaporator
is to artificially load the compressor tion pressure, thereby, providing capac-
refrigerant temperature, which results
upon a decrease in evaporator load for ity modulation. Capacity reduction over
in a lower leaving air temperature,
one or more of the following reasons: a wide range is possible with proper
could be tolerated.
selection of the components. This is
• Prevent operation of the compressor shown in the sample problem. (See Note 1: The values given in manufactures’ catalogs are valve
capacities – not system capacities.
at excessively low suction pressures. page 23)
Note 2: Use of discharge bypass valves alone will not main-
This could cause compressor short tain adequate head pressure for proper operation under low
cycling, resulting in temperature and If the suction pressure continues to drop outdoors ambient operating conditions (below 50 – 55°F).*
humidity control variation. below the valve setting, the valve contin- It will be necessary to use an approved low ambient control-
ling device to maintain adequate high side pressure under
ues to open until the limit of its stroke is low ambient operating conditions. If bypassing 50% or more,
• Prevent a significant drop in evapora- reached. Most applications cannot toler- head pressure control is a must.
tor temperature where reasonably ate sufficient pressure change to open
constant conditions must be main-
tained. This is often necessary for
precise temperature control.
Figure 9
• Prevent frosting of the evaporator coil
causing serious loss of capacity be- Recommended Piping Hook-Up for Hot Gas Bypass
cause of restricted airflow, and
potential damage to the compressor.
32-3009-03 23
Application
Guide
The cutaway view (below) of a typical Application • Locate the bypass valve close to the
sporlan hot gas bypass valve illustrates compressor to avoid the accumula-
its construction. Figure #9 indicates the only recom- tion of significant amounts of liquid
mended piping hook up for hot gas by- refrigerant in the hot gas line when
When evaporator pressure (sensed pass applied to Trane U.P.G. products. not bypassing.
through the external equalizer line) falls Introducing the hot gas at the inlet to the
evaporator provides proper refrigerant • Externally equalized bypass valves
below the setpoint of the valve, spring are a must.
pressure against the diaphragm over- velocity for oil return through the evapo-
comes evaporator pressure and begins rator and suction lifts, if present (regard- • Adjustable bypass valves are recom-
to move the piston off its seat. This al- less of the amount being bypassed). mended.
lows the high pressure, hot gas to flow Good mixing of the bypassed gas with • Do not apply evaporator pressure
through the valve to maintain low side the evaporating refrigerant takes place regulating valves to Trane D.P.G.
pressure. When evaporator pressure and the system expansion valve com- products (Trane or American
has fallen approx. 9 PSI (R-22) below pensates for the added superheat. Standard).
the setpoint, the valve will be open to
its rated position. This hook-up does require either a side-
port distributor or an auxiliary side con-
When evaporator pressure rises above nector. In some cases, depending on the Heat Pump Systems
the setpoint, it forces the valve closed. size of the original distributor and the When applying hot gas bypass to a heat
required amount of bypass, a larger pump system:
distributor could be required.
A — The hot gas bypass valve inlet must
An externally equalized bypass valve is be connected to the discharge line be-
recommended for all applications. tween the compressor and the
switchover valve.
Bypass valves should be sized gener-
ously, in order to accommodate pressure B — A hot gas solenoid valve must be
drops in the hot gas line, etc. installed upstream of the bypass valve,
Figure 10 and wired so that it opens in the cooling
A hand valve installed upstream of the mode only.
bypass valve facilitates pump down for
Typical Sporlan Hot Gas service operations. The bypass valve C — Low head pressure problems
Bypass Valve must be installed close to the tee in the during bypass may occur, requiring
discharge line, to prevent the accumula- some means of head pressure control.
tion of liquid R-22 in the hot gas line
when not bypassing. External equalizer D — If a 24 volt solenoid valve is used,
lines should be connected approxi- be sure that adequate transformer
mately 6" downstream of the TXV capacity is available.
Thermal Bulb. (The hot gas bypass
valve external equalizer can be con- E — Apply multiple systems whenever
nected to the suction line near the out- possible, to achieve capacity modula-
door unit if desired.) tion.
24 32-3009-03
Application
Guide
Selecting The Hot Gas very often, require the application of tions. Table “E” is based on the amount
a head pressure control device. (tons) of bypass required.
Bypass Valve
Pressure drops in the hot gas line, Chart “X,” page 24, can be used to calcu-
The bypass valve must be capable of
solenoid valve (if used), side-port dis- late the pressure drop in the hot gas line,
bypassing the difference between the
tributor (or auxiliary side connector if desired.
design load and the anticipated mini-
mum load (at the conditions existing plus distributor), all tend to reduce the Table “F” below, lists information on
when the minimum load occurs). capacity of the hot gas bypass valve. Sporlan Bypass Valves. (The selections
(Size it generously.) in Table “F,” assume a 26°F evaporating
Anticipated lower head pressures at temperature, and 80°F condensing tem-
the minimum load conditions (further Table “E” provides a simple method, for perature, for the minimum load condi-
aggravated by the fact that the bypassed the selection of a hot gas bypass valve, tions.) The adjustment range of 0 to
gas is bypassing the condenser) will and the hot gas line, for average condi- 80 PSIG is recommended for R-22.
Table “E”
Quick Selection Table For Hot Gas Bypass Valves
R-22 Refrigerant
Amount of Bypass Required
(Design Load Minus Minimum Load)
0 – 2 Tons 2.5 – 4 Tons 4.5 – 8 Tons 8.5 – 10 Tons
Sporlan Sporlan Sporlan Sporlan
Hot Gas Bypass Valve ADRSE-2 ADRPE-3 ADRHE-6 DRHE-6
(or Equiv.) (or Equiv.) (or Equiv.) (or Equiv.)
Recommended
Hot Gas Line O.D.
Up to 50 Eq. Ft. 1/2" O.D. 5/8" O.D. 3/4" O.D. 7/8" O.D.
51 to 100 Eq. Ft. 1/2" O.D. 5/8" O.D. 7/8" O.D. 7/8" O.D.
Table “F”
Discharge Bypass Valve Capacities – Tons
Capacities based on 6°F evaporator temperature change from closed to rated opening, discharge temperature 30°F above isentropic compression, 25°F
superheat at the compressor, 0° subcooling, and includes both the hot gas bypassed and liquid refrigerant for desuperheating, regardless of whether the
liquid is fed through the system thermostatic expansion valve or an auxiliary desuperheating thermostatic expansion valve.
Minimum Allowable Evaporator Temperature At The Reduced Load – °F
ADRS–2 0/30 — — — — — — — — — 2.93 3.77 4.73 2.82 3.63 4.57 2.72 3.51 4.42
ADRSE–2 0/80 2.65 3.40 4.26 2.69 3.45 4.34 2.71 3.48 4.37 2.88 3.70 4.66 — — — — — —
22 ADRP–3 0/30 — — — — — — — — — 5.56 7.16 9.00 5.61 7.23 9.10 5.47 7.06 8.90
ADRPE–3 0/80 4.50 5.78 7.25 4.72 6.06 7.61 4.80 6.17 7.75 5.24 6.73 8.47 — — — — — —
0/30 — — — — — — — — — 10.5 13.5 17.0 10.6 13.7 17.2 10.3 13.3 16.7
ADRHE–6
0/80 6.89 8.84 11.1 7.46 9.58 12.0 7.68 9.87 12.4 8.12 11.4 14.4 — — — — — —
Adjustable “Remote Bulb” Models
12 25/35 5.51 7.11 8.96 4.86 6.26 7.89
These models are recommended for air conditioning
22 DRHE–6 55/70 14.3 19.0 24.0 12.7 16.4 20.6
temperature ranges only.
134a 25/35 7.03 9.26 11.9 6.06 7.98 10.2
502 65/80 13.9 18.2 22.6 12.6 15.8 19.4
32-3009-03 25
Chart “J”
Pressure Drop in R-22 Vapor Lines
5 Tons of Bypass with a 7/8" O.D. Hot
Gas Line = 5.4 PSI/100' Pressure Drop.
PRESSURE DROP — PSI / 100 FT.
0.1 .2 .3 .4 .5 .6 .7 .8 .9 1.0 2 3 4 5 6 7 8 9 10
80°
L
R
PE
PO
TY
VA
D
D
D
D
°F
OD
OD
OD
OD
OD
OD
OD
OD
OD
20
"O
"O
"O
"O
N
R
/8"
/8"
/8"
/8"
/8"
/8"
/8"
/8"
O
/8"
P
1
1
1/2
5/8
3/4
7/8
ED
-
-
4-1
2-1
VA
2-5
1-3
3
3-5
5
1-1
1-5
BAS
ED
)
T
Guide
(°F
RA
P.
TU
M
A
TE
)S
D.
(°F
N
O
P.
26
C
EM
S
AP
E
V
N
E
LI
E
G
Application
R
E
N
HA
LI
ISC
N
D
IO
CT
SU
0 10 20 30 40 50 0 0 0 0
–4 –3 –2 –1
0
–5
0
–6
1 2 3 4 5 10 20 30 50 100 200 300 500 1000 2000 3000 5000 10,000 20,000 30,000
FLOW RATE — LB / MIN
32-3009-03
Application
Guide
Figures 11 and 12 on this page and 13 a 26° evaporating temperature (9.46 x Figure 11
on page 26 provide information on .95 = approx. 9.0 tons). The above values
accessories for hot gas bypass applica- are based on a 10 PSI pressure drop Auxiliary Side Connectors
tions, plus capacity multipliers for eva- across the solenoid valve. If no more
porating temperature changes other than a 5 PSI pressure drop across the ASC
than the standard 6°. (See Figure 12.) solenoid valve can be tolerated, its Distributor Connection Sizes (Inches)
capacity is 6.77 x .95 or approx. 6.4 tons Type ASC Type Inlet Outlet Auxiliary
Figure 11 lists compatible distributor/ of bypass. (Selecting a hot gas bypass Number Number ODM ODF ODF
auxiliary side connector combinations, valve with some excess capacity, would 1620, 1622 ASC-5-4 5/8 5/8 1/2
complete with fitting sizes. (O.D.M. = allow us to use the 10 PSI valve.) The 1112, 1113 ASC-7-4 7/8 7/8 1/2
outside diameter, male and O.D.F. = solenoid valve’s capacity would be 1115, 1116 ASC-9-5 1-1/8 1-1/8 5/8
outside diameter, female.) derated somewhat more, assuming a 1117, 1126 ASC-11-7 1-3/8 1-3/8 7/8
Figure 12 lists bypass valve capacity condensing temperature of 80° on a 1125, 1127
ASC-13-9 1-5/8 1-5/8 1-1/8
multipliers for evaporating temperature mild day. (The Table in Figure 13 is based 1143
changes, other than 6°F. Note that the on a 100° condensing temperature.)
capacity multiplier for a 2°F evaporating Figure 14, page 27, lists capacities for
change is .70 (26° evaporating tempera- liquid line solenoid valves. (Do not con- Figure 12
ture). A 26° refrigerant evaporating fuse Figure 14 with Figure 13, which
temperature, with normal airflows’ covers hot gas solenoid valves.) Much
Capacity Multipliers
will result in a coil surface temperature larger port sizes are required to handle
above 32°F. (Frosting should not occur.) For Evaporator Temperature Changes
R-22 vapor. Other Than 6°F Nominal Change
Figure 13 lists capacities of hot gas sole- Evaporator Evaporator Temperature °F
The circled values in Figure 14 indicate
noid valves. Hot gas solenoid valves are that the ME9S230 (or 240) liquid line Temp.
not usually required on straight cooling Change Refrigerant 40 26 20 0 and
solenoid valve has a capacity of 8 tons °F Below
applications, since pump down is not at a 3 PSI pressure drop across the valve
normally permitted. (The hot gas sole- 12 & 134a 0.65 0.65 0.65
(R-22). 2° 0.65
noid valve is required on heat pump 22 & 502 0.72 0.70 0.70
applications, however, in order to dis- Could we use this solenoid valve on a 4°
12 & 134a 0.80 0.80 0.80
0.74
able the hot gas bypass during the 10 ton system? The answer is yes, if the 22 & 502 0.87 0.85 0.85
heating mode.) 4.7 PSI pressure drop does not result 12 & 134a 1.11 1.11 1.11
8° 1.09
in a total liquid line pressure drop of 22 & 502 1.17 1.15 1.11
Note that a ME19S250 (or 270) hot gas over 35 PSI (3.0 PSIG x (10/8)2 = 4.7 PSI). 12 & 134A 1.22 1.20 1.19
solenoid valve (R-22) has a capacity of 10° 1.11
22 & 502 1.34 1.27 1.25
9.46 tons x a correction factor of .95 for
32-3009-03 27
Application
Guide
Figure 13
Hot Gas Solenoid Valve Capacities – Tons
Capacities based on 100°F condensing temperature, isentropic compression plus 50°F, 40°F evaporator and 65°F suction gas.
For other evaporator conditions use the multipliers in the table below.
Valve Type Refrigerants
12 22 134a 502
“E” Series
“A” & “B” Extended Connections Pressure Drop Across Valve Port – PSI
Series Connections Inches 5 10 5 10 5 10 5 10
A3F1 — 1/4 SAE
0.26 0.35 0.37 0.51 0.31 0.42 0.30 0.42
A3S1 — 1/4 or 3/8 ODF
— E5S120 1/4 ODF
0.61 0.84 0.88 1.22 0.74 1.00 0.72 1.00
— E5S130 3/8 ODF
MB6F1 — 3/8 SAE
MB6S1 ME6S130 3/8 ODF 1.01 1.43 1.51 2.10 1.27 1.74 1.30 1.70
MB6S1 ME6S140 1/2 ODF
MB9F2 — 3/8 SAE
— ME9S230 3/8 ODF 1.50 0.21 2.17 3.04 1.80 2.50 1.80 2.50
MB9S2 ME9S240 1/2 ODF
MB10F2 — 1/2 SAE
— ME10S240 1/2 ODF 2.30 3.20 3.37 4.69 2.80 3.90 2.80 3.80
MB10S2 ME10S250 5/8 ODF
MB14S2 ME14S250 5/8 ODF 3.20 4.40 4.58 6.40 3.80 5.30 3.80 5.30
MB19S2 ME19S250 5/8 ODF
4.70 6.50 6.77 9.46 5.70 7.90 5.70 8.00
MB25S2 ME19S270 7/8 ODF
MB25S2 ME25S270 7/8 ODF
7.50 10.5 10.8 15.1 9.10 12.7 8.90 12.5
MB25S2 ME25S290 1-1/8 ODF
Correction Factors
For evaporator temperatures at the reduced load condition
Evaporator
Temperature °F 40° 26° 20° 0° -20° -40°
Multiplier 1.00 .95 .93 .87 .81 .75
28 32-3009-03
Application
Guide
Figure 14
Liquid Line Solenoid Valve Capacity Selection Table
Type Number Tons of Refrigeration
“E” Series
“A” & “B” Extended Pressure Drop – PSI
Series Connections
Port
With Manual Lift Stem Connections Size 1 2 3
Normally Closed (Inches) (Inches) 12 22 134a 502 12 22 134a 502 12 22 134a 502
A3P1 — — — 3/8 NPT Female
A3F1 — — — 1/4 SAE Flare
.101 0.7 0.9 0.8 0.6 1.0 1.3 1.2 0.8 1.2 1.6 1.5 1.0
A3S1 — E3S120 — 1/4 ODF Solder
A3S1 — E3S130 — 3/8 ODF Solder
— — E5S120 — 1/4 ODF Solder
.150 1.2 1.6 1.5 1.1 1.8 2.3 2.1 1.5 2.2 2.8 2.6 1.9
— — E5S130 — 3/8 ODF Solder
— MB6P1 — — 3/8 NPT Female
— MB6F1 — — 3/8 SAE Flare
3/16 2.2 2.9 2.7 1.9 3.1 4.0 3.8 2.6 3.8 4.9 4.6 3.2
— MB6S1 — ME6S130 3/8 ODF Solder
— MB6S1 — ME6S140 1/2 ODF Solder
— MB9P2 — — 3/8 NPT Female
— MB9F2 — — 3/8 SAE Flare
9/32 3.6 4.7 4.4 3.0 5.1 6.6 6.2 4.3 6.2 8.0 7.5 5.2
— — — ME9S230 3/8 ODF Solder
— MB9S2 — ME9S240 1/2 ODF Solder
32-3009-03 29
Application
Guide
30 32-3009-03
Refrigerant Pipe Sizing
Worksheet
Project Application
________________________________________ Outdoor Model ____________________________________
Address Guide
________________________________________ Indoor Model ____________________________________
________________________________________ A.R.I. Capacity ____________________________________
■ Cooling ■ Heat Pump
Piping Runs
Liquid line fittings/accessories equivalent total = (b) ________ ft Gas line fittings/accessories equivalent total = (x) ________ ft
100
= 100
=
32-3009-03 31
Standard Piping Size Oversized Piping
Nominal
Tonnage #/Min
ARI (1)
Capacity Gas
Pipe Size
Liquid
Application
Pressure Drops(1)
Gas Liquid
Lbs. R-22 (100 ft.)
Gas Liquid Gas
Pipe Size
Liquid
Pressure Drops(1)
Gas Liquid
Lbs. R-22 (100 ft.)
Gas Liquid
(100 ft.) (100 ft.) (100 ft.) (100 ft.)
32 32-3009-03
Application
Guide
Notes
32-3009-03 33
Application
Guide
Notes
34 32-3009-03
Application
Guide
Notes
32-3009-03 35
Literature Order Number
File No. Pub. No. 32-3009-03 7/00
Supersedes Pub. No. 32-3009-02 1/00
Stocking Location P.I. (L)
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change
design and specifications without notice.