Technical Data: Approved Sprinklers For Use With Foam Concentrates
Technical Data: Approved Sprinklers For Use With Foam Concentrates
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
1. DESCRIPTION
Viking Pendent and Upright Foam-Water Sprinklers are non-aspirated foam
discharge devices. Viking Pendent and Upright Foam-Water Sprinklers are FM
Approved and UL Listed in both closed sprinkler (with bulb or fusible element) and
open sprinkler (bulb removed) configurations.
Features:
• Tested and Approved as foam-water sprinklers with specific foam concentrates
(see Performance Data).
• K-factors available: K5.6 (K80.6), K8.0 (K115.2), and K11.2 (K161.3)
2. LISTINGS AND APPROVALS
Viking Foam Water Sprinklers are FM Approved and/or UL Listed as part of a fire
extinguishing system combining designated foam concentrates, bladder tanks and
proportioning devices. Approved and Listed system components can be found at
www.approvalguide.com and https://iq.ulprospector.com.
UL Listed – GFGV.EX27255 (UL162)
3. TECHNICAL DATA
Refer to the applicable sprinkler’s data page for product data.
4. SCOPE OF DELIVERY
Ensure that all components are complete and in good condition. Viking Foam/
Water Sprinklers are supplied boxed with protective shield or cap.
5. AVAILABILITY
Please contact Viking for further information.
Americas:
The Viking Corporation
5150 Beltway SE
Caledonia, MI 49316
Tel.: (800) 968–9501
Fax: 269–818–1680
Technical Services: 1–877–384–5464
[email protected]
6. PRODUCT VARIANTS
Please refer to relevant sprinkler data page.
7. SCOPE OF DELIVERY
Ensure that all components are complete and in good condition. Viking Foam/Water Sprinklers are supplied boxed with protective
shield or cap.
8. INSTALLATION
Refer to appropriate Installation Standards (i.e. NFPA, VdS, LPCB, etc.) and / or applicable FM Global Property Loss Prevention
Data Sheets such as 4-12, Foam Extinguishing Systems.
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
9. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water or Foam/Water Solution flowing through the sprinkler orifice strikes the sprinkler deflector, forming
a uniform spray pattern to extinguish or control the fire.
10. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
WARNING
Any system maintenance or testing that involves placing a control valve or detection system out of service may eliminate the
fire protection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should
be given to employment of a fire patrol in the affected areas.
12. DISPOSAL
At end of use the product described here should be disposed of via the national recycling system.
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
TABLE 1
FM APPROVALS: HYDROCARBONS1
Sprinkler Height Tested3
VIKING Nominal Identification Listed2 Foam Water Discharge Sprinkler
K-factor Minimum Maximum Design Density Density
Foam Number (SIN) Pressure
Concentrate U.S. Metric4 Upright Pendent Ft. m Ft. m gpm/ft2 Lpm/m2 gpm/ft2 Lpm/m2 PSI bar
VK1001
5.6 80.6 -- 6 1.8 24.8 7.6 0.3 12.2 0.3 12.2 29 1.99
VK3001
VK1021
5.6 80.6 -- 6 1.8 20 6.1 0.3 12.2 0.3 12.2 29 1.99
VK3021
VK200
VK204
8.0 115.2 -- 9 2,7 45 13,7 0.4 16,3 0.4 16,3 25 1,72
VK350
VK351
ARK 3%
VK2021
VK2022
8.0 115.2 -- 8.5 2,6 44 13,4 0.3 12,2 0.3 12,2 14 0,97
VK3521
VK3522
VK530
11.2 161.3 -- 9 2,7 45 14 0.4 16,3 0.4 16,3 13 0,89
VK531
VK377
11.2 161.3 -- 6 1.8 25.2 8 0.4 16.3 0.4 16.3 13 0.89
VK536
VK1001
5.6 80.6 -- 6 1.8 24.8 7.6 0.2 8.1 0.3 12.2 13 0.89
VK3001
VK1021
5.6 80.6 -- 6 1.8 44 13.4 0.2 8.1 0.3 12.2 13 0.89
VK3021
VK200
VK204
8.0 115.2 -- 9 2.7 45 13.7 0.3 12.2 0.3 12.2 14 0.96
VK350
USP 3% VK351
VK2021
VK3521
8.0 115.2 -- 8 2.4 44 13.4 0.3 12.2 0.3 12.2 14 0.96
VK3522
VK2022
VK377
11.2 161.3 -- 6 1.8 25.2 8 0.3 12.2 0.3 12.2 7 0.48
VK536
1. This table shows approvals available at the time of printing.
2. Density indicated is minimum application density required per FM5130 Standard for Foam Extinguishing Systems. This density cannot be reduced.
3. The pressure indicated is the minimum starting pressure required for the sprinkler. However, the minimum density shown overrides the minimum starting pressure (de-
pending on head spacing) and cannot be reduced.
4. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
TABLE 2
FM APPROVALS: JET A11
Sprinkler Height Tested3
VIKING Nominal Identification Listed2 Foam Water Discharge Sprinkler
K-factor Minimum Maximum Design Density Density
Foam Number (SIN) Pressure
Concentrate U.S. Metric4 Upright Pendent Ft. m Ft. m gpm/ft2 Lpm/m2 gpm/ft2 Lpm/m2 PSI bar
VK1021,
USP 3% 5.6 80.6 -- 8.5 2.6 44 13.4 0.2 8.1 0.3 12.2 13 0.89
VK3021
1. This table shows approvals available at the time of printing.
2. Density indicated is minimum application density required per FM5130 Standard for Foam Extinguishing Systems. This density cannot be reduced.
3. The pressure indicated is the minimum starting pressure required for the sprinkler. However, the minimum density shown overrides the minimum starting pressure (de-
pending on head spacing) and cannot be reduced.
4. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
TABLE 3
FM APPROVALS: ALCOHOL - IPA1
Sprinkler Height Tested3
Nominal Listed2 Foam
VIKING K-factor Identification Design Density Sprinkler
Number (SIN) Minimum Maximum Pressure
Foam Concentrate
U.S. Metric4 Upright Pendent Ft. m Ft. m gpm/ft2 Lpm/m2 PSI bar
VK1001
5.6 80.6 -- 6 1.8 24.8 7.6 0.3 12.2 29 1.99
VK3001
VK1021
5.6 80.6 -- 6 1.8 24 7.3 0.3 12.2 29 1.99
VK3021
VK200
VK204
8.0 115.2 -- 6.5 2 45 13.7 0.4 16.3 25 1.7
VK350
VK351
ARK 3%
VK2021
VK2022
8.0 115.2 -- 6 1.8 44 13.4 0.3 12.2 14 0.97
VK3521
VK3522
VK377
11.2 161.3 -- 6 1.8 44 13.4 0.4 16.3 13 0.89
VK536
VK530
11.2 161.3 -- 6 1.8 45 13.7 0.4 16.3 13 0.89
VK531
1. This table shows approvals available at the time of printing.
2. Density indicated is minimum application density required per FM5130 Standard for Foam Extinguishing Systems. This density cannot be reduced.
3. The pressure indicated is the minimum starting pressure required for the sprinkler. However, the minimum density shown overrides the minimum starting pressure (de-
pending on head spacing) and cannot be reduced.
4. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
TABLE 4
FM APPROVALS: KETONE - ACETONE1
Sprinkler Height Tested3
Nominal Listed2 Foam
VIKING K-factor Identification Design Density Sprinkler
Number (SIN) Minimum Maximum Pressure
Foam Concentrate
U.S. Metric4 Upright Pendent Ft. m Ft. m gpm/ft2 Lpm/m2 PSI bar
VK1001
5.6 80.6 -- 6 1.8 24.8 7.6 0.3 12.2 29 1.99
VK3001
VK1021
5.6 80.6 -- 6 1.8 24 7.3 0.3 12.2 29 1.99
VK3021
VK200
VK204
8.0 115.2 -- 6.5 2 45 13.7 0.3 12.2 14 0.97
VK350
VK351
ARK 3%
VK2021
VK2022
8.0 115.2 -- 6 1.8 44 13.4 0.3 12.2 14 0.97
VK3521
VK3522
VK530
11.2 161.3 -- 6 1.8 45 13.7 0.3 12.2 7 0.48
VK531
VK377
11.2 161.3 -- 6 1.8 25.2 8 0.3 12.2 7 0.48
VK536
1. This table shows approvals available at the time of printing.
2. Density indicated is minimum application density required per FM5130 Standard for Foam Extinguishing Systems. This density cannot be reduced.
3. The pressure indicated is the minimum starting pressure required for the sprinkler. However, the minimum density shown overrides the minimum starting pressure (de-
pending on head spacing) and cannot be reduced.
4. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
TABLE 5
FM APPROVALS: ETHANOL1
Sprinkler Height Tested3
Nominal Listed2 Foam
VIKING K-factor Identification Design Density Sprinkler
Number (SIN) Minimum Maximum Pressure
Foam Concentrate
U.S. Metric4 Upright Pendent Ft. m Ft. m gpm/ft2 Lpm/m2 PSI bar
VK200
VK204
8.0 115.2 -- 6.5 2 45 13,7 0.3 12.2 14 0.97
VK350
VK351
VK2021
VK2022
8.0 115.2 -- 6.0 1.8 44.8 13.7 0.30 12.2 14 0.97
VK3521
VK3522
ARK 3%
VK530
11.2 161.3 -- 7.7 2.3 20.6 6.3 0.30 12.2 7 0.48
VK531
VK377
11.2 161.3 -- 6.0 1.8 44.8 13.7 0.30 12.2 7 0.48
VK536
APPROVED SPRINKLERS
TECHNICAL DATA FOR USE WITH FOAM
CONCENTRATES
TABLE 6
UL LISTINGS: HYDROCARBON FUELS1
Sprinkler Listed2 Foam
VIKING Nominal K-factor Identification Design Density Tested3 Sprinkler Pressure
Number (SIN)
Foam Concentrate
U.S. Metric4 Upright Pendent gpm/ft2 Lpm/m2 PSI bar
5.6 -- VK3021 0.22 9.0 7 0.48
VK2021
VK2022
8.0 115.2 -- 0.22 9.0 7 0.48
USP5 3% VK3521
VK3522
VK530 VK377
11.2 161.3 VK531 0.32 13 7 0.48
VK536
VK533
1. This table shows approvals available at the time of printing.
2. Density indicated is minimum application density required per FM5130 Standard for Foam Extinguishing Systems. This density cannot be reduced.
3. The pressure indicated is the minimum starting pressure required for the sprinkler. However, the minimum density shown overrides the minimum starting pressure (de-
pending on head spacing) and cannot be reduced.
4. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.