D1093 DTS0242 en
D1093 DTS0242 en
D1093 DTS0242 en
10 I (A)
Function Diagram:
MODEL D1093S
+1
-4 10 -
Supply 24 Vdc
11 +
Load 12 -
Diag.
15
Fault Out
16
+7
Out 1-B ND Load
-8 13 +
+5 In
14
Out 1-A NE Load
-6
To prevent relay contacts from damaging, connect an external protection (fuse or similar),
chosen according to the relay breaking capacity diagram.
1 3 1 3
5 7 5 7
PLC PLC
Output ON SIL 3 Service Load Output OFF SIL 3 Service Load
24 Vdc Load (not for Safety 0 Vdc Load (not for Safety
Function purpose) Function purpose)
6 8 6 8
Internally Internally
connected connected
2 4 2 4
Contacts 1-5 and 2-6: in normal operation the relay is energized, contacts are Contacts 1-5 and 2-6: the SIL 3 Safety Function is met when the relay is
closed, SIL 3 load is energized. de-energized, contacts are open, SIL 3 load is de-energized.
Contacts 3-7: in normal operation the relay is energized, contact is closed, Service Contacts 3-7: opening of this contact can be used to monitor contacts 1-5 and 2-6.
load (not for Safety Function purpose) is energized. Service load (not for Safety Function purpose) is de-energized.
Contacts 4-8: internally connected, cannot be changed. Contacts 4-8: internally connected, cannot be changed.
+ / AC Contacts 15-16: Voltage free contact for Line and Load Fault detection.
Can be connected in series with other relay units for common
15 monitoring.
Normally closed when there is not Fault condition.
16
Load
- / AC
15
16
Load
- / AC
1 3 1 3
5 7 5 7
PLC PLC
Service Load SIL 3 Service Load SIL 3
Output OFF Output ON
(not for Safety Load (not for Safety Load
0 Vdc 24 Vdc
Function purpose) Function purpose)
6 8 6 8
Internally Internally
connected connected
2 4 2 4
Contacts 1-5 and 2-6: in normal operation the relay is de-energized, contacts are Contacts 1-5 and 2-6: closing of this contact can be used to monitor contacts 3 - 7.
open, Service Load load (not for Safety Function purpose) is de-energized. Service load (not for Safety Function purpose) is energized.
Contacts 3-7: in normal operation the relay is de-energized, contact is open, Contacts 3-7: the SIL 3 Safety Function is met when the relay is energized,
SIL 3 load is de-energized. contacts are closed, SIL 3 load is energized.
Contacts 4-8: internally connected, cannot be changed. Contacts 4-8: internally connected, cannot be changed.
+ / AC Contacts 15-16: Voltage free contact for Line and Load Fault detection.
Can be connected in series with other relay units for common
15 monitoring.
Normally closed when there is not Fault condition.
16
Load
- / AC
15
16
Load
- / AC