N2 Requirement

1) The document provides guidance on inert gas blanketing requirements for a storage tank to prevent flashback. 2) The required nitrogen flow rate for the tank, which is 1.6 m3 in volume, is 6.56 Nm3/hr. 3) The required volume of reserve inert gas for the tank is 0.191637 m3 at operating conditions.

Uploaded by

sandesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
759 views2 pages

N2 Requirement

1) The document provides guidance on inert gas blanketing requirements for a storage tank to prevent flashback. 2) The required nitrogen flow rate for the tank, which is 1.6 m3 in volume, is 6.56 Nm3/hr. 3) The required volume of reserve inert gas for the tank is 0.191637 m3 at operating conditions.

Uploaded by

sandesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

API 2000 - SEVENTH EDITION, MARCH 2014

ANNEXURE - F , "Guidance for Inert gas inert gas blanketing of tanks for flash back protection"

LEVEL - 3 (No additional protection against flame propagation from outside to the inside of tank is required)

Required flow rate

Volume of reserve inert gas

Tank Dimensions:
Dia = 1
Height = 2
Slope of cone roof = 5 1
Site Latitude = 21 °
In Flow rate = 0 m3/hr
Out Flow Rate = 1.2 m3/hr
Operating Pressure = 101.325 kPag
Operating Temperature = 47 °C
wall thickness of insulation lin 0.00E+00 m
inside heat transfer co-efficient h 1 W/(m2.K)
thermal conductivity of insulation λin 1 W/(m.K)
Reduction factor for insulation Rin 1.000
C Factor for Lattitude = 6.5
Tank Volume Vtk 1.60 m3
Out flow rate Vpe 2.05 Nm3/hr

Required Nitrogen flow rate = 6.56 Nm3/hr 45.90

Volume of reserve inert gas = 0.191637 m3 @ 101.325 kPag, 65°C


Volume of reserve inert gas = 0.025135 m 3
@ 600 kPag, 25°C

Required Outbrething flowrate = 0.487662 Am3/h Air


Required Outbrething flowrate for PVRV = 0.416036 Nm3/hr Air
Required vaccum capacity for PVRV = 6.331697 Nm3/hr of Air
Required Outbrething flowrate for SAPCV = 0.430895 Nm3/hr of N2

Emergency Relieving
Reference API 2000 : Section 3.3.3.3 : Fire Relief Requirements

Considering hexane
Wetted surface area 631.7115 m2 631.7115 m2
Q 4,129,700 W 208.2
F 0.15 1
L 1519000 j/kg 334900 j/kg
T 338.15 K 288.75 K
M 30.33 86.17

q 1234.486 41200.84 6427.331


Table 1 — Y-factor for various latitudes
Latitude Y-factor
Below 42° 0.32
Between 42° and 58° 0.25
Above 58° 0.2

Table 2 — C-factors
Latitude C-factor for various conditions
Vapour pressure
Hexane or similar
Higher than hexane, or unknown
Average storage temperature °C
°C <25 ≥25 <25 ≥25

Below 42° 4 6.5 6.5 6.5


Between 42° and 58° 3 5 5 5
Above 58° 2.5 4 4 4