Controller/Programmer: Specification Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

2404

2408
MODELS

Controller/Programmer
Specification Sheet
● High stability control The 2404/2408 is a versatile, high stability temperature or process
controller, with self and adaptive tuning, in 1/4 DIN and 1/8 DIN sizes. It
● Up to twenty comes with a standard 8 segment setpoint programmer, with options for
programs one, four or twenty programs of 16 segments each.

● 16 segments It has a modular hardware construction which accommodates a wide range


of plug-in modules. It will accept up to three I/O modules and two
● Heating and cooling communication modules. Two digital inputs and an optional alarm relay are
● Customisable included as part of the fixed hardware build. The hardware is configurable
for heating, cooling, alarms and other functions. A transmitter power
operation
supply option is available, as is a 5 or 10V transducer supply option. The
● Heater current 2404/2408 is fully configurable on-site.
display
The 16 segment programmer can have up to 8 programmable outputs
● Multiple alarms on a which can be set in each segment to trigger external events. The two digital
single output inputs can be used to run, hold and reset the program. Parallel operation
of several programmers can be performed with synchronisation chosen at
● DC retransmission the end of any desired segments.

● Digital
communications Precise control
An advanced PID control algorithm gives stable ‘Straight-line’ control of the
- Modbus RTU process. A one-shot tuner is provided to set up the initial PID values and to
calculate the overshoot inhibition parameters. In addition an adaptive tuner
- Profibus DP network
will handle processes with continually changing characteristics. On
- DeviceNet® network electrically heated loads, power feedback is used to stabilise the output
power and hence the controlled temperature against supply voltage
fluctuations. Dedicated cooling algorithms ensure optimum control of fan,
water and oil cooled systems.

Universal input
A universal input circuit with an advanced analogue to digital convertor
samples the input at 9Hz and continuously corrects it for drift. This gives
high stability and rapid response to process changes. High noise immunity
is achieved by rejection of 50/60Hz pick-up and other sources of noise.
Sensor diagnostics are also provided. The input will accept all standard
thermocouples, the Pt100 resistance thermometer and linear millivolts,
milliamps or DC volts.

•EUROTHERM ® FLEXIBLE SOLUTIONS•


Customisable operation SPECIFICATION
A custom LED display provides a bright, clear display of the process General
value and setpoint. Tactile push buttons ensure positive operation. Environmental performance
Dedicated buttons provide for auto/manual and program run/hold Temperature limits Operation: 0 to 55°C
capabilities. Access to other parameters is simple and easy to Storage: -10 to 70°C
understand and can be customised to present only those parameters Humidity limits Operation: 5 to 90% RH non condensing
that need to be viewed or adjusted. All other parameters are locked Storage: 5 to 90% RH non condensing
away under password protection. Panel sealing: IP65
Altitude: <2000 metres
Atmospheres: Not suitable for use in explosive or
Alarms corrosive atmosphere
Electromagnetic compatibility (EMC)
Up to four alarms can be combined onto a single output. They can be Emissions and immunity: BS EN61326
full scale high or low, deviation from setpoint, rate of change or load
Suitable for domestic, commercial and light industrial as well as heavy
failure alarms. Alarm messages are flashed on the main display. Alarms
industrial. (Domestic/light (Class B) emissions. Industrial environmental
can be configured as latching or non-latching and also as ‘blocking’ immunity.
type alarms which means they will become active only after they have
Under industrial immunity conditions the instrument will not deviate by
first entered a safe state. more than an additional amount equal to the published tolerance.

Electrical safety
Digital communications BS EN61010 Installation cat. II; Pollution degree 2
2404/2408 controllers are available with a wide range of INSTALLATION CATEGORY II
communications options. EIA485 2 wire, EIA232, EIA422 4 wire. The rated impulse voltage for equipment on nominal 230V mains is 2500V.
Profibus DP or Eurotherm® proprietary PDS communications modules
are available, offering Modbus RTU, Profibus DP (24xxf), DeviceNet, POLLUTION DEGREE 2
Normally, only non-conductive pollution occurs. Occasionally, however, a
Eurotherm Bisynch or PDSIO protocols.
temporary conductivity caused by condensation shall be expected

Physical
iTools configuration editor Panel mounting 2408: 1/8 DIN
Although 2404/2408 controllers are easily and fully configurable via 2404: 1/4 DIN
the front panel, iTools configuration software offers an easy to use PC Weight 2408: 440g max.
configuration tool. 2404: 670g max.
iTools has the built-in ability to save or clone instrument Panel cut-out dims. 2408: 45W x 92Hmm (-0.0 +0.8)
configurations ensuring full back up of any engineering effort. 2404: 92W x 92Hmm (-0.0 +0.8)
Panel depth Both: 148mm
Operator interface
Type: Dual 7 segment LED up to 2 decimal places
Display 2408: Upper 12mm
Lower 10mm
2404: Upper 21mm
Lower 10mm
Status beacons: OP1, OP2, SP2, REM
Status indicators: Auto, manual, run, hold
Access levels: Operator, full access, Edit,
config. Password protected
Power requirements
Supply voltage: 85 to 264Vac,
48 to 62 Hz,
2404 16W max.
2408 13W max.
24Vac, -15%, +10%
24Vdc, -15% +20% ±5% ripple voltage
OPC Scope Inrush current
OPC Scope is a separate utility that allows trending, data logging and High Voltage (VH): 30A duration <100μS
Dynamic Data Exchange (DDE). It is an OPC explorer program that can Low Voltage (VL): 15A duration <100μS
connect to any OPC server that is in the Windows registry. Approvals
CE, cUL listed (file E57766), Gost
Suitable for use in Nadcap and
AMS2750D applications under System
Accuracy Test calibration conditions

Communications
No of ports: 2 modules can be fitted
Slot allocation: PDSIO remote setpoint or retransmission
J comms port
Serial communications option
Protocols: Modbus RTU Slave
Profibus DP (24XXf only)
EI-Bisync (818 style mnemonics)
Isolation: 264Vac, double insulated
Transmission standard: EIA232, EIA485, CAN (DeviceNet), Profibus
(24XXf only)

Both data logging and trending are available and the user can trend
and view live data, with a scaleable time axis between 1 minute and 1
month. This utility also offers a Historical Review mode and data can
be logged onto the PC hard disk, from which it may be retrieved and
analysed in an Excel spreadsheet.
Main process variable input DC Input module (Isolated)
Calibration accuracy: <±0.2% of reading ±1LSD Calibration accuracy: <±0.2% of reading ±1LSD
Sample rate: 9Hz (110ms) Sample rate: 9Hz (110ms)
Isolation: 264Vac double insulation Isolation: 264Vac double insulation
Input filter: Off to 999.9. Default 1.6s Input filter: Off to 999.9. Default 1.6s
Zero offset: User adjustable over full range Zero offset: User adjustable over full range
User calibration: 2-point gain & offset User calibration: 2-point gain & offset
Functions: Includes process input, remote setpoint, Functions: Includes process input, remote setpoint,
power limit power limit
Thermocouple Thermocouple
Range: -100mV to +100mV Range: -100mV to +100mV
Types: K, J, N, R, S, B, L, T, C, PL2, custom Types: K, J, N, R, S, B, L, T, C, PL2, custom
Resolution (μV): <3.3μV @ 1.6s filter time Resolution (μV): <3.3μV @ 1.6s filter time
Effective resolution: 15.9 bits Effective resolution: 15.9 bits
Linearisation accuracy: <0.2% of reading Linearisation accuracy: <0.2% of reading
Cold junction compensation: >30:1 rejection of ambient change Cold junction compensation: >30:1 rejection of ambient change
External reference of 0°C, 45°C and 50°C External reference of 0°C, 45°C and 50°C
Cold junction accuracy: <±1°C at 25°C ambient Cold junction accuracy: <±1°C at 25°C ambient
Resistance thermometer Resistance thermometer
Range: 0-400Ω (-200°C to +850°C) Range: 0-400Ω (-200°C to +850°C)
Resistance thermometer types: 3-wire Pt100 DIN 43760 Resistance thermometer types: 3-wire Pt100 DIN 43760
Resolution (°C): <±0.08°C with 1.6sec filter Resolution (°C): <±0.08°C with 1.6sec filter
Effective resolution: 13.7 bits Effective resolution: 13.7 bits
Linearity error: <0.033% (best fit straight line) Linearity error: <0.033% (best fit straight line)
Calibration error: <±(0.4°C + 0.15% of reading in °C) Calibration error: <±(0.4°C + 0.15% of reading in °C)
Drift with temperature: <±(0.015°C + 0.005% of reading in °C) Drift with temperature: <±(0.015°C + 0.005% of reading in °C)
per °C per °C
Common mode rejection: <0.000085°C/V (maximum of 264Vrms) Common mode rejection: <0.000085°C/V (maximum of 264Vrms)
Series mode rejection: <0.240°C/V (maximum of 280mV pk-pk) Series mode rejection: <0.240°C/V (maximum of 280mV pk-pk)
Lead resistance: 0Ω to 22Ω, matched lead resistance Lead resistance: 0Ω to 22Ω, matched lead resistance
Input impedance: 100MΩ Input impedance: 100MΩ
Bulb current: 300μA Bulb current: 300μA
100mV range 100mV range
Range: -100mV to +100mV Range: -100mV to +100mV
Resolution (μV): <3.3μV with 1.6s filter time Resolution (μV): <3.3μV with 1.6s filter time
Effective resolution: 15.9 bits Effective resolution: 15.9 bits
Linearity error: <0.033% (best fit straight line) Linearity error: <0.033% (best fit straight line)
Calibration error: <±10μV, ± 0.2% of measurement at 25°C Calibration error: <±10μV, ± 0.2% of measurement at 25°C
Drift with temperature: <±0.2μV + 0.004% of reading per °C Drift with temperature: <±0.2μV + 0.004% of reading per °C
Common mode rejection: >146dB (maximum of 264Vrms) Common mode rejection: >146dB (maximum of 264Vrms)
Series mode rejection: >90dB (maximum of 280mV pk-pk) Series mode rejection: >90dB (maximum of 280mV pk-pk)
Input impedance: >100MΩ Input impedance: >100MΩ
10 Volts range 10 Volts range
Range: 0V to +10.0V Range: -3.0V to +10.0V
Resolution (μV): <300μV with 1.6sec filter Resolution (μV): <300μV with 1.6sec filter
Effective resolution: 15.4 bits Effective resolution: 15.4 bits
Linearity error: <0.033% (best fit straight line) Linearity error: <0.033% (best fit straight line)
Calibration error: <±(0.4°C + 0.15% of reading in °C) Calibration error: <±(0.4°C + 0.15% of reading in °C)
Drift with temperature: <± 0.1mV + 0.02% of reading per °C Drift with temperature: <± 0.1mV + 0.02% of reading per °C
Common mode rejection: >145dB (maximum of 264Vrms) Common mode rejection: >145dB (maximum of 264Vrms)
Series mode rejection: >92dB (maximum of 5V pk-pk) Series mode rejection: >92dB (maximum of 5V pk-pk)
Input impedance: >69kΩ Input impedance: >69kΩ

Notes Potentiometer input


(1) Calibration accuracy quoted over full ambient operating range and for all Type: Single channel
input linearisation types Resistance: 100Ω to 15kΩ
(2) Contact Eurotherm for details of availability of custom downloads for Excitation: 0.5Vdc supplied by module
alternative sensors Isolation: 264Vac double insulation
Functions: Includes valve position and remote
Digital input (LA and LB) setpoint
Isolation: Not isolated from each other. 264Vac
double insulation from the PSU and Analogue control output
communication Type: Single channel
Input Rating: 0-20mA <600Ω
Rating Voltage level: Closed 0 to <11Vdc 0-10Vdc >500Ω
Open >13 to 24Vdc Accuracy: ±2.5%
Contact closure: Open >28kΩ Resolution: 10 bits
Closed <100Ω Isolation: 264Vac double insulation
Functions: Includes program control, alarm
acknowledge, SP2 select, manual, keylock, Analogue retransmission output
RSP select, standby Type: Single channel
Rating: 0-20mA <600Ω
AA Relay 0-10Vdc >500Ω
Type: Form C (changeover) Accuracy: ±0.5%
Rating: Min 1mA @ 1Vdc, Max 2A @ 264Vac resistive Resolution: 11 bits
1,000,000 operations with external snubber Isolation: 264Vac double insulation
Isolation: 264Vac double insulation
Functions: Alarms, events, status
Logic input modules Transmitter PSU module
Module types: Triple contact closure, triple logic level Type: Single channel
Isolation: No channel isolation. 264Vac double Isolation: 264Vac double insulation
insulation from other modules and system Rating: 24Vdc @ 20mA
Rating: Voltage Level: Open -3 to 5Vdc @ <-0.4mA
Closed 10.8 to 30Vdc @ 2.5mA Transducer PSU module
Contact closure: Open >28kΩ Type: Single channel
Closed <100Ω Isolation: 264Vac double insulation
Functions: Includes program control, alarm acknowledge, Bridge voltage: Software selectable 5Vdc or 10Vdc
SP2 select, manual, keylock, RSP select, Bridge resistance: 300Ω to 15kΩ
standby Internal shunt resistor: 30.1Ω @0.25%, used for calibration of
350Ω bridge at 80%
Logic output modules
Module types: Single channel, triple channel Software features
Isolation: No channel isolation. 264Vac double Control loop
insulation from other modules and system Control types: PID, OnOff, VP, Dual VP
Rating Single: 12Vdc @ 24mA, source Cooling types: Linear, fan, oil, water
Triple: 12Vdc @ 9mA, source Modes: Auto, manual, forced manual
Functions: Includes control outputs, alarms, events, Overshoot inhibition: High and low cutbacks
status Number of PID sets: 2, selectable on PV
Control options: Supply voltage compensation, feedforward,
Relay modules output tracking, OP power limiting, SBR safe
Module types: Single channel Form A, Single channel output
Form C, dual channel Form A Setpoint options: Remote SP with trim, SP rate limit, 2nd
Isolation: 264Vac double insulation Setpoint, tracking modes
Rating: Min 100mA @ 12Vdc, Max 2A @ 264Vac Setpoint programmer
resistive Program function: Standard 1, 8 segment
Min 400,000 (max load) operations with Optional 1, 4 or 20, 16 segment
external snubber Events: 8 with 16 segment programmer
Functions: Includes control outputs, alarms, events, Segment types: Ramp rate, Ramp time, dwell, call, step
status Digital inputs: Run, Hold, Reset, RunHold, RunReset,
ResetRun, Adv Seg, Skip Seg
Triac modules Servo action: Process value, setpoint
Module types: Single channel, dual channel Power failure modes: Continue, ramp, reset
Isolation: 264Vac double insulation Other functions: Holdback, inputs
Rating: <1A @ 30-264Vac resistive Process alarms
Functions: Includes control outputs, alarms, events, Number: 4
status Type: High, low, devhi, devlo, devband
Latching: None, auto, manual, event
Other features: Blocking

Isolation diagram

Live
2400 Isolated modules

Rectification

Power
Neutral supply
2400 Isolated modules
circuits

Y μP &
Functional earth system
circuits 2400 Isolated modules

Communications
(H module)
PSU mounted
PV Input/Logic IO/
Non isolated modules
PDS input 264Vac
PDS retransmission
(J module) Double
(J module) Insulated
PDSIO load diagnostics
Supply
PDSIO (Pulse Density Signalling I/O) is a major innovation in the
2404/2408. When used in combination with a Eurotherm TE10 solid
state relay (SSR), it allows the logic output of a 2404/2408 to transmit
the power demand signal and simultaneously read back load fault
alarms. These alarms will be flashed as messages on the controller PDSIO 2-wire
Connection
front panel.
Two alarm conditions will be detected, either SSR failure indicating an
open or short circuit condition in the SSR and heater circuit failure
indicating either fuse failure, heater open circuit or line supply absent.

(PDS Heater Break Detect) Heater

PDSIO master setpoint transmission Master Setpoint Generator


PDSIO can be used to digitally transmit the setpoint profile to a
number of slave Series 2000 controllers.
If any slave zone departs from the required setpoint by more than a
pre-settable amount, a signal grom any slave can be transmitted back PDSIO Master
Setpoint Transmission
to the master causing the program to freeze until the error is
corrected. Digital accuracy is preserved using PDSIO. Slave
Controllers

(PDS Output)

Rear terminal connections


2408 (PDS Input) (PDS Input)

Low voltage supply


HA
1A

Line
24
L

85 to 264V ac 20 to 29V
I/O Module 1

ac/dc
HB
1B

Neutral
24

Isolated Logic Output


+ A

Triple Contact Input


10V A + A NO A A NO A + A A
DC Remote Input

Transmitter PSU
Comms 1

24V
HC
1C

Earth Earth In A
Not in slots 1 or 2

DC Retrans

Dual Relay
B +
Not in slot 1

Not in slot 1
B - B B B B B B
Relay

Dig in 1

Triac
C C In B 0V
HD
1D

D8

C NO C +
+ C C C C C C
Dig in 2 In C
2A

HE

LB

- +
- D D D D D C D D
Com D
I/O Module 2

Common
2B

HF

LC

NO A + A
Potentiometer Input

A + A A A

Triple Logic Input


Change Over Relay

Transducer PSU
In A EXC+
AA
2C

JA

Not in slot 1

DC Output
Not in slot 3

Dual Triac
B B + B
B - B B
+0.5V In B EXC-
2D

Alarm
AB
JB

+
Relay C C C C C C
Wiper NC In C CAL+
Comms 2
3A

AC
JC

+
0V D D D D Com D CAL-D
I/O Module 3
3B

JD

VI

+ + A
Triple Logic Output
A
Dual Logic + Relay
V+
3C

+ Out A
JE

RTD PV - B + B
Out B
3D

V–
JF

– + C
C
Out C
D -
D
Com

2404 + A
Dual Logic + Triac

- B

Low voltage supply C


D
4A

Line
HA
1A

24
L

85 to 264V ac 20 to 29V
Module 1

ac/dc
4B

HB
1B

Neutral
N

24
Comms 1
4C

Earth
HC
1C

Earth
Dig in 1
4D

HD
1D

D8

Dig in 2
5A

2A

HE

LB

Common
5B

2B

HF

LC
Module 2
5C

AA
2C

JA

Alarm
5D

2D

AB
JB

Relay
Comms 2
6A

3A

AC
JC
Module 3
6B

3B

JD

VI
6C

V+
3C

+
JE

RTD PV
6D

3D

V–
JF


Hardware coding

Model Supply Alarm 10amp


Function Module 1 Module 2 Module 3 Comms 1 Comms 2 Manual
Number Voltage Relay Output

Omit
for 2408

Model Number Module 1 Module 2 Module 3 10amp Output


Panel size XX Not fitted XX Not fitted XX Not fitted XX Not fitted
2408 48x96mm Relay: 2-pin Relay: 2-pin Relay: 2-pin
2404 96x96mm R2 Fitted unconfigured R2 Fitted unconfigured R2 Fitted unconfigured
Profibus units RH Heating output RC Cooling output Relay: change over
2408f 48x96mm RU Valve raise output RW Valve lower output R4 Fitted unconfigured
Comms 1
2404f 96x96mm Relay: change over Relay: change over PO Program event 4
R4 Fitted unconfigured R4 Fitted unconfigured (note 7) XX Not fitted
YH Heating output YC Cooling output PE Program END output 2 wire, EIA485
RP Valve raise (note 6) RL Valve lower(note 6) Or alarm 3 from table A Y2 Fitted unconfigured
Function (2408) Or alarm 1 from table A PO Program event 1 Logic: (Non-isolated) YM Modbus protocol
Logic: (Non-isolated) (note 7) L2 Fitted unconfigured YE EI-Bisynch
PID control L2 Fitted unconfigured PE Program END output Logic: (Isolated) protocol (note 1)
CC Controller only LH Heating output Or alarm 2 from table A LO Single logic OP EIA232
CG 1x 8 seg Prog M1 PDS Heater break Dual relay Triac A2 Fitted unconfigured
CP 1x16 seg Prog detect (note 2) RR Fitted unconfigured T2 Fitted unconfigured AM Modbus protocol
P4 4x16 seg Prog M2 PDS Current PP Program events 1 & 2 Dual relay AE EI-Bisynch
CM 20x16 seg Prog monitoring (note 3) (note 7) RR Fitted unconfigured protocol (note 1)
2408

(note 1) Logic: (Isolated) Logic: (Non-isolated) PP Program event 4 & 5 4 wire EIA422
On/Off Control LO Single logic OP L2 Fitted unconfigured (note 7) F2 Fitted unconfigured
NF Controller only Triac LC Cooling output Digital I/O (unconfig’d) FM Modbus protocol
NG 1x8 seg Prog T2 Fitted unconfigured Logic: (Isolated) TK Triple contact input FE EI-Bisynch
NP 1x16 seg Prog TH Heating output LO Single logic OP TL Triple logic input protocol (note 1)
N4 4x16 seg Prog TU Valve raise output Triac TP Triple logic output PDS Output
NM 20x16 seg Prog DC control (Isolated) T2 Fitted unconfigured Power supply M7 Fitted unconfigured
(note 1) D4 Fitted unconfigured TC Cooling output MS 24Vdc transmitter PT PV retrans
Motorised valve control H6 0-20mA heating TW Valve lower output DC remote input TS Setpoint retrans
VC Valve positioner H7 4-20mA heating DC control (Isolated) D5 Fitted unconfigured OT Output retrans
VG 1x8 seg Prog H8 0-5V heating D4 Fitted unconfigured W2 4-20mA setpoint Profibus Module
VP 1x16 seg Prog H9 1-5V heating C6 0-20mA cooling W5 0-10V setpoint PB Profibus (note 6)
V4 4x16 seg Prog HZ 0-10V heating C7 4-20mA cooling WP Second PV input DeviceNet
VM 20x16 seg Prog Digital I/O (unconfig’d) C8 0-5V cooling DC retran. (Isolated) DN DeviceNet
(note 1) TK Triple contact input C9 1-5V cooling Select from Table B
TL Triple logic input CZ 0-10V cooling Potentiometer input
TP Triple logic output Digital I/O (unconfig’d) VU Fitted unconfigured
Dual relay TK Triple contact input VS Valve position feedback Comms 2
Function (2404) RR Fitted unconfigured TL Triple logic input VR Setpoint input
RD Heat + cool TP Triple logic output XX Not fitted
PID control RM VP raise & lower OPs Power supply PDS Input
CC Controller only Dual triac MS 24Vdc transmitter M6 Fitted unconfigured
CG 1x 8 seg Prog TT Fitted unconfigured DC retran. (Isolated) Alarm relay RS Setpoint input
CP 1x16 seg Prog TD Heat + cool Select from Table B PDS Output
P4 4x16 seg Prog TM VP raise & lower OPs Potentiometer input XX Not fitted M7 Fitted unconfigured
CM 20x16 seg Prog Logic+relay VU Fitted unconfigured Alarm 4 relay PT PV retrans
2404

(note 1) LR Fitted unconfigured VS Valve position feedback RF Fitted unconfigured TS Setpoint retrans
On/Off Control LD Heat + cool VR Setpoint input Table A alarm options plus: OT Output retrans
NF Controller only QC Mode 2 + cool Transducer PS RA Rate of change alarm
NG 1x8 seg Prog Logic+triac G3 5Vdc transducer PSU PDS Alarms
NP 1x16 seg Prog LT Fitted unconfigured G5 10Vdc transducer PSU LF Heater break detect
N4 4x16 seg Prog GD Heat & cool HF Current monitoring Manual
NM 20x16 seg Prog QD Mode 2 + cool Table B: DC retransmission heater break
(note 1) Transducer PS D6 Fitted unconfigured SF Current monitoring
Motorised valve control XXX No manual
G3 5Vdc transducer PSU First character SSR failure
VC Valve positioner ENG English
G5 10Vdc transducer PSU V- PV retrans PO Program event 7
VG 1x 8 seg Prog FRA French
S- Setpoint retrans (note 7)
VP 1x16 seg Prog Table A: alarm codes GER German
O- Output retrans PE Program END output
V4 4x16 seg Prog FH High alarm NED Dutch
Z- Error retrans
VM 20x16 seg Prog FL Low alarm SPA Spanish
Second character
(note 1) DB Dev. band alarm SWE Swedish
-1 0-20mA
DL Dev. low alarm ITA Italian
-2 4-20mA
DH Dev. high alarm -3 0-5V
-4 1-5V
Supply Voltage -5 0-10V

VH 85-264Vac
VL 20-29Vac/dc

2404/2408 Accessories

Handbook HA025132
Communications handbook HA026230
Profibus DP handbook HA026290
2.49Ω precision resistor SUB24/2R49.1
Sensor Setpoint Setpoint Display Digital Digital Options
Input Min Max Units Input 1 Input 2 Control Power Cooling Buttons Program

note 4 note 4

Setpoint Setpoint Display Units Digital Input 1 & 2 Options


Sensor Input
Min Max
C Celsius XX Disabled Control action
Standard Sensor Inputs Min °C Max F Fahrenheit AM Manual select XX Reverse acting (standard)
J J Thermocouple K Kelvin SR Remote SP select DP Direct acting
-210 1200
K K Thermocouple X Linear input S2 Second setpoint Power feedback
-200 1372
T T Thermocouple EH Integral hold XX Enabled on logic, relay &
-200 400
L L Thermocouple AC Alarm acknowledge triac heating
-200 900
N N Thermocouple-Nicrosil/Nisil RP SP rate limit enabled PD Feedback disabled
-250 1300
R R Thermocouple-Pt/Pt13%Rh RN Run program Cooling options
-50 1700
S S Thermocouple-Pt/Pt10%Rh HO Hold program XX Linear cooling
-50 1768
B B Thermocouple-Pt/Pt30%Rh -6%Rh RE Reset program CF Fan cooling
0 1820
P Platinel II Thermocouple RH Run/hold prog CW Water cooling
0 1369
Z RTD/PT100 DIN 43760 KL Keylock CL Oil cooling
-200 850
Factory Downloaded Input NT Run/Reset CO On/Off cooling
Min °C Max
C C Thermocouple - W5%Re/W26%Re (Hoskins) TN Reset/Run Front panel buttons
0 2319
D D Thermocouple - W3%Re/W25%Re HB Program holdback XX Enabled
0 2399
E E Thermocouple P2 Second PID MD Auto/manual disabled
-250 1000
1 Ni/Ni18%Mo Thermocouple ST One shot tune enable MR Auto/man & run/hold
0 1399
2 Pt20%Rh/Pt40%Rh Thermocouple AT Adaptive tune enable disabled
0 1870
3 W/W26%Re (Englehard) Thermocouple FA Select full access level RD Run/hold disabled
0 2000
4 W/W26%Re (Hoskins) Thermocouple RB Simulates UP button Programmer time units
0 2010
5 W5%Re/W26%Re (Engelhard) Thermocouple LB Simulates DOWN button XX Dwell & ramp in mins
10 2300
6 W5%Re/W26%Re (Bucose) Thermocouple SB Simulates SCROLL button HD Dwell time in hours
0 2000
7 Pt10%Rh/Pt40%Rh Thermocouple PB Simulates PAGE button HR Ramp rate in units/hrs
200 1800
8 Exergen K80 I.R. pyrometer B1 Least sig. BCD digit HT Ramp/dwell hours
-45 650
Process Inputs (Scaled to setpoint min and max) B2 2nd BCD digit
Min °C Max
F -100 to +100mV linear B3 3rd BCD digit
-1999 9999
Y 0 to 20mA linear (note 4) B4 4th BCD digit
-1999 9999
A 4 to 20mA linear (note 4) B5 5th BCD digit
-1999 9999
W 0 to 5Vdc linear B6 Most significant digit
-1999 9999
G 1 to 5Vdc linear SY Standby-all O/Ps OFF
-1999 9999
V 0 to 10Vdc linear SC Prog synchronisation
-1999 9999
SG Skip segment
(without changing SP)
PV Select PV2
AG Advance to end of
Note 1. segment(& step to target SP)
Not available with profibus controllers M5 CTX (mode 5) Input 2 only
Note 2.
PDS heater break detect will transmit the power demand to a TE10S Solid State Relay and
read back a heater break alarm.

Note 3.
PDS current monitoring will transmit the power demand signal to a TE10S Solid State
Relay and read back load current and open and short circuit alarms.

Note 4.
Setpoint limits: Include the decimal position required in the displayed value. Up to one for
temperature inputs, up to two for process inputs.

Note 5.
An external 1% current sense resistor is supplied as standard. If greater accuracy is required,
a 0.1% 2.49Ω can be ordered as
part no. SUB2K/249R.1.

Note 6
Only available with Profibus controller.

Note 7.
Not available with 8 segment programmer

Example ordering code


2408 - CC - VH - LH - RC - FL - FH - YM - TS - K - 0 - 1000 - C - AM - S2 - XX - XX - XX - MD - XX
2408, PID Controller, 85 to 264Vac, Logic heating, Relay cooling, Low alarm relay, High alarm relay,
RS485, Modbus comms, PDSIO setpoint retrans, Type K thermocouple, 0 to1000°C, Auto/manual select,
2nd setpoint select, Manual button disabled.
Dimensional details
2404 2408 2404/08
48mm
(1.89in) 161mm
96mm
(3.78in) (6.3in)

96mm 96mm
(3.78in) (3.78in)

150mm
(5.9in)
Panel cut-out

-0.0 -0.0 -0.0 -0.0


92mm +0.8 92mm 45mm +0.6 92mm
+0.8 +0.8

Eurotherm: International sales and service


Understanding and providing local support is a key part of Eurotherm's business. Complementing worldwide Eurotherm offices are a whole
range of partners and a comprehensive technical support team… to ensure you get a service you will want to go back to.
AUSTRALIA Sydney FRANCE Lyon IRELAND Dublin SPAIN Madrid
Eurotherm Pty. Ltd. Eurotherm Automation SA Eurotherm Ireland Limited Eurotherm España SA
T (+61 2) 9838 0099 T (+33 478) 664500 T (+353 1) 4691800 T (+34 91) 6616001
F (+61 2) 9838 9288 F (+33 478) 352490 F (+353 1) 4691300 F (+34 91) 6619093
E [email protected] E [email protected] E [email protected] E [email protected]
AUSTRIA Vienna GERMANY Limburg ITALY Como SWEDEN Malmo
Eurotherm GmbH Eurotherm Deutschland GmbH Eurotherm S.r.l Eurotherm AB
T (+43 1) 7987601 T (+49 6431) 2980 T (+39 31) 975111 T (+46 40) 384500
F (+43 1) 7987605 F (+49 6431) 298119 F (+39 31) 977512 F (+46 40) 384545
E [email protected] E [email protected] E [email protected] E [email protected]
BELGIUM & LUXEMBOURG Moha HONG KONG & CHINA KOREA Seoul SWITZERLAND Wollerau
Eurotherm S.A/N.V. Eurotherm Limited North Point Eurotherm Korea Limited Eurotherm Produkte (Schweiz) AG
T (+32) 85 274080 T (+85 2) 28733826 T (+82 31) 2738507 T (+41 44) 7871040
F (+32) 85 274081 F (+85 2) 28700148 F (+82 31) 2738508 F (+41 44) 7871044
E [email protected] E [email protected] E [email protected] E [email protected]
BRAZIL Campinas-SP Guangzhou Office NETHERLANDS Alphen a/d Rijn UNITED KINGDOM Worthing
Eurotherm Ltda. T (+86 20) 8755 5099 Eurotherm B.V. Eurotherm Limited
T (+5519) 3707 5333 F (+86 20) 8755 5831 T (+31 172) 411752 T (+44 1903) 268500
F (+5519) 3707 5345 E [email protected] F (+31 172) 417260 F (+44 1903) 265982
E [email protected] Beijing Office E [email protected] E [email protected]
T (+86 10) 6567 8506 www.eurotherm.co.uk
DENMARK Copenhagen F (+86 10) 6567 8509 NORWAY Oslo
Eurotherm Danmark AS E [email protected] Eurotherm A/S U.S.A. Leesburg VA
T (+45 70) 234670 T (+47 67) 592170 Eurotherm Inc.
F (+45 70) 234660 Shanghai Office F (+47 67) 118301 T (+1 703) 443 0000
E [email protected] T (+86 21) 6145 1188 E [email protected] F (+1 703) 669 1300
F (+86 21) 6145 1187 E [email protected]
FINLAND Abo E [email protected] POLAND Katowice
www.eurotherm.com
Eurotherm Finland Invensys Eurotherm Sp z o.o.
INDIA Chennai ED53
T (+358) 22506030 T (+48 32) 2185100
F (+358) 22503201 Eurotherm India Limited F (+48 32) 2177171
E [email protected] T (+91 44) 24961129 E [email protected]
F (+91 44) 24961831
E [email protected]

© Copyright Eurotherm Limited 2007


Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates.
All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system
other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice.
The information in this document is given in good faith, but is intended for guidance only.
Printed on
Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
recycled paper
Part No. HA026553 Issue 4 2408, 2404 Specification Sheet in England 01.07