NEC CHAPTER 2 QUIZ With Answers
NEC CHAPTER 2 QUIZ With Answers
QUIZ
NEC CHAPTER 2
1. If the branch circuit rating is more than …………., the lamp holders
connected to it should be of the heavy duty type.
• 40 Amp
• 25 Amp
• 20 Amp
• 45 Amp
Refer: NEC 210.23 (B) Any occupancy other than dwelling unit
• 10 Amp
• 15 Amp
• 20 Amp
• 25 Amp
4. What will the branch circuit calculated load for a single 12 KW electric
range in a dwelling unit?
• 12 KW
• 8 KW
• 15 KW
• 6 KW
5. What is the maximum continuous load that can be connected to 240 volts
20 ampere branch circuit?
• 20 Amp
• 16 Amp
• 10 Amp
• 14 Amp
The continuous load should have conductors rated 125 % above the connected load.
The maximum permitted load = 20 / 1.25 = 16 amperes
• 10 Awg
• 14 Awg
• 12 Awg
• 8 Awg
• 20 Amp
• 10 Amp
• 30 Amp
• 15 Amp
8. A 2400 watts electric motor is connected to 240 volts single phase supply
2 wire circuit. What is the minimum size TW conductor that is required to
carry the load?
• 14 Awg
• 12 Awg
• 10 Awg
• 8 Awg
Current = P /E = 2400 / 240 = 10 amperes
Refer: NEC 424.3 (B)
Motor should be considered as continuous load
Refer : NEC 210.20(A)
Over current device should be 125% of continuous loads
over current device rating = 10 * 1.25 = 12.5 amperes
Refer: NEC 310.15 (B) (16) 14 AWG
• True
• False
10. The lighting system protection ground terminals shall be bonded to which
of the following grounding electrode system?
• Neutral Conductor
• Secondary Conductor
• Ungrounded Conductor
12. In a single phase electrical system the size of the largest ungrounded
service entrance aluminum conductor is 1/0 AWG, which of the following is
the size of the grounding conductor?
• Aluminum 6 Awg
• Aluminum 4 Awg
• Copper 2 Awg
• Copper 6 Awg
13. Grounding in electrical system limits the high current and thus reduces the
damage.
• True
• False
14. In a single raceway the size of the grounded conductor shall not be larger
than the ungrounded conductor in the raceway.
• True
• False
15. In a single phase three wire electrical system, the middle conductor of a 3-
wire should be which of the following?
• Grounded
• Ungrounded
• Hot conductor
16. Over current protection is not required at the point where the wire size is
not over 25 feet.
• False
• True
• 1/10
• 1/8
• 1/5
• 1/12
18. The ampacity of the feeder tap conductors not less than 10 ft shall not be
less than the rating of its terminating device.
• True
• False
19. The branch circuit rated circuit breaker is marked for use with No 18 AWG
and supplies a continuous load of 5.6 ampere, which of the following over
current protection amperage that can be used?
• 10 Amp
• 7 Amp
• 20 Amp
• 15 Amp
• True
• False
21. What is the smallest rating plug fuse that is used for residential 120 volts
branch circuit?
• 12 Amp
• 20 Amp
• 18 Amp
• 15 Amp
Refer: NEC 240.6 (A) 15 Amps
The standard fuse ratings are 15,20,25,30 amperes, so 15 amperes is the smallest fuse
rating.
23. A multi wire branch circuit may supply only ………….. if it is protected by
fuses.
24. The allowable ampere rating of bus conductor is 48 amperes. What is the
maximum allowable rating of over current device?
• 70 Amp
• 50 Amp
• 40 Amp
• 60 Amp
48 amperes rating is not a standard fuse rating. So next higher standard rating 50
amperes can be taken.
25. What is the maximum voltage applied to branch circuits that are connected
to luminaries in dwelling unit?
• 480 V
• 120 V
• 240 V
• 150 V
• True
• False
27. What is the minimum heavy duty lamp holders that are permitted on 20
ampere branch circuit operated at 120 volts?
• 2
• 1
• 3
• 4
As the load is continuous, the minimum branch circuit rating = 600 * 1.25 = 725 amperes
Total volt-ampere rating of 120 volts 20 ampere branch circuit = 120 * 20 = 2400 volt-
ampere
the minimum number permitted per branch circuit is 2400 / 725 = 3.2 = 3.
Refer: NEC 215 (B) (1) less than the sum of name plate ratings of transformer
29. Which of the following is the amperage of the branch circuit additionally
required for bathroom outlets?
• 20 Amp
• 15 Amp
• 25 Amp
• 10 Amp
• True
• False
• 600 V
• 277 V
• Above 1kV
• 120 V
32. Utilization equipment connected by cord and plug type shall not exceed
…………….. Percentage of branch circuit rating.
• 95
• 90
• 70
• 80
33. What is the minimum feeder or service load for cloth dryers in a dwelling
unit?
• 6500 Watt
• 5000 Watt
• 2500 Watt
• 4000 Watt
35. As per NEC what is the minimum general lighting load that is used for
branch circuit and feeder/Service calculations of a single family dwelling
unit?
36. For branch circuits above 600 V, The ampacity of branch-circuit conductors
shall not be less than ____ of the designed potential load of utilization
equipment which will be operated simultaneously.
• 125 %
• 75 %
• 150 %
• 100 %
37. In dwelling units other than Kitchen, 125-volt, single-phase, 15- and 20-
ampere receptacles installed within ______ of the outside edge of the sink
shall provided with GFCI.
• 8 feet
• 10 feet
• 6 feet
• 9 feet
• True
• False
Refer: NEC Code 210.9 False
• True
• False
• True
• False
41. Branch circuits installed for the purpose of lighting, central alarm, and
signal for public or common areas of multifamily dwelling can be supplied
from equipment that supplies an individual dwelling unit
• True
• False
42. Voltage in In the guest rooms supplied by Branch circuits shall not exceed
__ volts between the conductors supplying luminaries
• 120 V
• 277 V
• 600 V
• 180 V
43. Receptacles outlets shall not be considered as per the required number of
receptacle outlets unless the installed receptacles located _____ inches of
wall
• 18
• 20
• 22
• 16
Refer: NEC 210.52(A)(3) 18
44. Which of the Following Statement is Correct:
(1) Fluorescent lighting branch circuit ratings generally will not be more
than 20A
(2) A Heavy Duty Lamp-holders shall have a rating of not less than 750
watts for ad medium type
• (1) is Correct
• (2) is Correct
• Both (1) and (2) are Correct
• Neither (1) nor (2) is Correct
45. According to NEC Code, reasonable efficiency can be achieved if the total
sum of voltage drop of branch circuit plus feeder is within ______ of the
rated voltage
• 10 %
• 3%
• 6%
• 5%
• True
• False
Refer NEC Code 215.12(A) Both (1) and (2) are true
48. Which of the following methods are permitted to act as identification
means for ungrounded feeder conductors in premises wiring:
Refer NEC Code 215.12 (C) Color Coding, Marking Tape and Tagging
• 450 V
• 1 KV
• 277 V
• 600 V
50. Feeder having voltage rating between 150V to ground and 600V phase to
phase which are solidly grounded to wye connected electrical system and
having disconnect rating 1000A and above shall be provided with GFP
Equipment
• True
• False
• True
• False
52. A floor receptacle may be required if a balcony handrail is longer than ____
• 6 ft
• 9 ft
• 3 ft
• 12 ft
• True
• False
55. AC Electrical systems having voltage rating between 50V and 1000V used
exclusively to supply industrial electric furnaces for melting, refining, and
tempering shall not be grounded:
• True
• False
• 10 AWG, 8 AWG
• 8 AWG. 6 AWG
• 8 AWG. 4 AWG
• 6 AWG. 8 AWG
• True
• False
59. If a single rod, pipe, or plate grounding electrode has a resistance to earth
of ___ or less, the supplemental electrode shall not be required. Refer:
• 20 Ohm
• 25 Ohm
• 30 Ohm
• 15 Ohm
• True
• False
61. If practicable, rod, pipe, and plate electrodes shall be embedded above
permanent moisture level.
• True
• False
• 6 Mtr
• 8 Mtr
• 5 Mtr
• 7 Mtr
• True
• False
64. Each plate electrode permitted for grounding shall expose not less than
___ of surface to exterior soil:
• 2 ft
• 2.5 ft
• 1.5 ft
• 3 ft
65. The maximum continuous operating voltage of the surge arrester shall be
___ voltage of the system.
• Phase-to-ground
• Phase-to-phase
• Phase-to-neutral
• Phase only
66. The rating of a surge arrester shall be less than the maximum continuous
operating voltage available at the point of application.
• True
• False
67. In a single raceway the size of the grounded conductor shall not be larger
than the ungrounded conductor in the raceway.
• True
• False
• True
• False
69. Type ___ shall be permitted to be installed on the load side of branch-
circuit overcurrent protection up to the equipment served.
• 1 SPDs
• 2 SPDs
• 3 SPDs
• All of the above
70. Conductors shall have a vertical clearance of not less than ___ above the
roof surface.
• 2.4 m
• 2.5 m
• 2.6 m
• 2.7 m
• Article 210
• Article 215
• Article 220
• Article 225
• True
• False
Refer: NEC code 240.5 (B) (2) 20-ampere circuits — 18 AWG, up to 15 m (50 ft) of run length
and 50-ampere circuits — 12 AWG and larger
• True
• False