Conductivity controller
Committed to process automation solutions

Datasheet

SUP-TDS210-B

1
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

The model SUP-TDS210-B is used for the conductive measurement/control of electrolytic conductivity,
resistivity or the TDS value.Conductivity is a function of ion concentration, ionic charge, and ion mobility.
Ions in water conduct current when an electrical potential is applied across electrodes immersed in the
solution. A controller system consists of a microprocessor-based controller and a conductivity probe.

4 Electrode cells (K=0.01,0.1,1.0 and 10.0)can be connected to the device. Temperature serves as the
second input variable, measured by a NTC10K/ PT1000 probe. Depending on the measured variable, it is
therefore possible to implement specific, automatic temperature compensation.

All adjustments to the current outputs, alarm relays, and calibration of the conductivity and temperature
inputs can be made using the controller's membrane keypad.

Features

■ Direct change over to ■ IP54 water resistant and corrosion proof


■ - Conductivity (µS/cm ) enclosure
■ Using the setup program: user-friendly
■ - Resistivity ( MΩ x cm)
programming
■ - TDS measurement (ppm )
■ RS485 communication
■ Automatic temperature compensation
■ Relay output
■ 4-20 mA Isolated Output
■ Large LCD display with background lighting

Applications

■ Reverse Osmosis ■ Food Processing ■ Printing ■ Medical


■ Process Control ■ Plating ■ Aquaculture ■ Boilers
■ Seawater Desalination ■ Power Plants ■ Agriculture ■ Cooling Towers
■ Waste Treatment ■ Laboratories ■ Environmental Studies

Benefits

■ Affordable
■ Ease of Operation
■ Low Maintenance
■ Ensures Product Quality

2
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

Parameter

Screen size 2.8 inch


Overall dimension: 100mm*100mm*150mm(H*W*D)
Dimension
Cutout dimension:92.5mm*92.5mm(H*W)
Weight 0.65Kg
Ingress protection IP54
Measure variables EC/ TDS/ Resistivity
0.01electrode:0.02 ~ 20.00μS/cm
0.1electrode:0.20 ~ 200.0μS/cm
1.0electrode:2.00 ~ 2000μS/cm
10.0electrode:0.02 ~ 20.00mS/cm
Measure range for extended range controller:
Measure range
0.01electrode:0.20 ~ 200.0μS/cm
0.1electrode:2.00 ~ 2000μS/cm
0.1electrode:0.02 ~ 20.0mS/cm
10.0electrode:0.20 ~ 200.0mS/cm
Temperature range:-10 ~130℃
NTC10K/PT1000
Temperature compensation
Temperature compensation:manual/automatic

EC/TDS/Resistivity: ±1%FS
Accuracy NTC10K: (-10~5℃) ±2℃;(5~60℃) ±0.2℃;(60~130℃) ±2℃
PT1000: (-10~5℃) ±2℃;(5~130℃) ±0.2℃

Isolated 4-20mA output


Output
maximum loop is 750Ω,±0.2%FS
Communication protocol MODBUS-RTU RS485
Alarm relay Pickup/Breakaway AC250V/3A
Relative humidity 10 ~ 85%RH(No condensation)
Operating temperature 0 ~ 60℃
Power supply 220VAC±10% 50Hz/60Hz
Temperature:-15 ~ 65℃
Storage conditions
Relative humidity:5 ~ 95%RH(No condensation)

3
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

Electrode

K=0.01 electrode K=0.1 electrode K=1.0 electrode K=10.0 electrode

Suitable for pure water Suitable for drinking water Suitable for rive raw Suitable for sewage waste
ultrapure water testing testing water testing testing

The device offers a far wider dynamic range on the input side, the range must be matched to the operating
range of the cell

Cell Material Length Diameter Hole size Thread Recommended/practical


constant measuring span(depending
(K) on the conductivity cell)
0.01 Stainless steel 77mm 13mm 6mm 0.02 ~ 20 µs/cm
0.1 Stainless steel 59mm 13mm 6mm 0.20 ~ 200.0µs/cm
1.0 Stainless steel 59mm 13.5mm 6mm 2.00 ~ 2000µs/cm
10.0 Polysulfone 60.5mm 23.3mm 6mm 0.10 ~ 20 ms/cm

Example

A measurement is to be carried out in the 10 µS/cm to 10 µS/cm range. A conductivity cell with
the cell constant K = 0.1 1 is chosen.

Note

When electrode works with SUP-TDS210-B (0-20,000us/cm)


Measuring span = 20,000 µs/cm x cell constant (K)

4
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

Display

SUP-TDS210-B conductivity controller

1. Temperature:Compensation temperature
2. Analog output:Analog output
3. Measured value:Real-time measurements value
4. High alarm:High alarm
5. Low alarm:Low alarm

TDS monitor page EC monitor page

Resistivity monitor page

5
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

Sign Name of the key Function description


Enter the MENU on the “monitoring page”
1. MENU
Exit the MENU on the “menu page”
Check related warning status on the “monitoring page”;
2. EXIT Return to previous level page in the up& down level page
linked to “menu page”
Enter the menu under “monitoring interface”
RIGHT
Exit the menu under “monitoring interface”
3.
Relevant menu is selected under the “menu interface”
DOWN
Relevant numerical value is modified under the setup status

Enter the sub-menu or confirm modification on the “menu


4. ENTER
Page”

Wiring

■ ECL1:Measuring terminal of the electrode and PT1000 connect here


■ B:Temperature compensation terminal B,
■ ECL2:Reference terminal of the electrode
NTC10K and PT1000 connect here
■ NC:Unidentified
■ C:Temperature compensation terminal C,
■ A:Temperature compensation terminal A,NTC10K
PT1000 three-wire temperature grounding,

6
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China
Tel: 86-15158063876 E-mail: [email protected]
www.supmea.com

PT1000 two-wire need to be short-connected to ■ COM:high alarm common


TEMPB, not NTC10K.
■ LO:Low alarm normally open relay
■ 485A+:RS485 communication interface A+
■ L:Low alarm normally closed relay
■ 485B-:RS485 communication interface B-
■ COM:low alarm common
■ I+:4-20mA output end+
■ N:AC220V neutral wire
■ I-:4-20mA output end -
■ PE:earth wire
■ HO:High alarm normally open relay
■ L:AC220V live wire
■ HC:High alarm normally closed relay

Ordering Code

Conductivity controller

SUP-TDS210-B Model Description

R1 0-2000 μS/cm
Range
R2 0-20000 μS/cm
K1 K=0.01 0.02 ~ 20.00μS/cm
K2 K=0.1 0.20 ~ 200.0μS/cm
Cell constant
K3 K=1.0 2.00 ~ 2000μS/cm
K4 K=10.0 0.02 ~ 20.00mS/cm
L1 5M
L2 10M
Cable length L3 15M
L4 20M
L5 Other Length
Signal output S1 4-20mA RS485
Relay A1 Two (high and low)
V1 220VAC
Power supply
V2 110VAC

7
Add : 5th floor, Building 4, Singapore Hangzhou
Science Technology Park, Hangzhou Economic
Development Area, 310018, Hangzhou, China