HLIM
HLIM
Model HLIM
Loop Isolator Module
OPERATION The SIEMENS Model HLIM Loop Isolator Module isolates short circuits on FireFinder-
XLS analog loops. By placing devices between HLIMs during installation, a short in
the wiring within that group is disconnected from the rest of the loop. The remainder
of the devices continue
to operate. The HLIM
FRONT BACK
operates in both Class A
and Class B circuits.
Remove all system power before installation, first the battery and then the AC.
INSTALLATION The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the
two input terminals and two output terminals. Line 1 and Line 2 can be either line of
the loop.
Class B (See Figure 2) In Class B wiring each HLIM isolates a branch on the circuit. Note that
a short on the main branch causes the entire loop to fail. To prevent this, mount the
HLIMs at the FireFinder-XLS enclosure and run each branch independently.
Class A Single Loop (See Figure 3) In Class A wiring the HLIMs are wired in series with the loop wiring.
This results in a single continuous loop. If any group in the loop has a short, that
group is lost and a Class A circuit failure results. The FireFinder-XLS displays commu-
nication errors for the devices and a Class A failure for the loop itself.
SWITCHPLATE
4-INCHES SQUARE
(SUPPLIED)
SWITCHPLATE
4-INCHES SQUARE
(SUPPLIED)
Figure 4
Mounting