General ROTAMETER RAKD

Variable Area Flowmeter


Specifications
GS 01R01B30-00E-E

The short-tube Rotameter is used for measurement of low


flow rates of liquids and gases. Its special application is in
turbulent, opaque or aggressive mediums and under high
pressure.
The instrument is mounted in a vertical pipeline with flow
direction upwards and the flow is indicated by a guided
magnetic float inside the conical metal tube, which transmits
its position to the indicator. The correct flow can be then read
on the scale.

FEATURES
• Different process connections like internal threads and
flanges
• Available with control valve (horizontal connection) or
without valve (vertical connection)
• All wetted parts of stainless steel ASTM 316Ti (1.4571)
• Measuring accuracy acc. to standard VDI/VDE 3513
sheet 2 (qG = 50 %) at calibration conditions
• Round, industrial standardized stainless steel housing
with degree of protection IP 66/67
• Light, guided floats resulting in low pressure loss and
stable float movement Rotameter RAKD without valve
• Max. flow range water: 1 to 250 l/h (0.265 to 66 gph)
• Max. flow range air: 40 to 8000 l/h at +20 °C, 1 bar abs
(1.4 to 282.5 cfh at 68 °F, 14.5 psi)
• Turndown ratio: 10:1
• Flow controller up to a maximum flow range of 100 l/h
(26.4 gph) water resp. 3250 l/h (114.8 cfh) air
• Electronic µP-controlled transmitter with linearized output
• Electrical connection by fast connection technique
(Quickon)
• Limit switches, also available as “fail-safe” version
• Connection of common transformer isolated barriers and
transmitter power supplies possible
• Suitable for hazardous area applications
• FMEDA report available for SIL application

Contents
Features page 1
Standard Specifications page 2
Hazardous Area Specifications page 5
Temperature Specification page 8
Installation and Planning Hints page 9
Model Specifications page 10
Options page 12
Dimensions page 13
Types of Process Connections page 16
Installation Lengths depending on Process page 16
Connection Type and Size Tube RAKD with valve
Weights page 16

Rota Yokogawa GmbH & Co. KG GS 01R01B30-00E-E


Rheinstr. 8 ©Copyright June 2004 (RYG)
D-79664 Wehr 15th edition, July 2020 (RYG)
Germany
2

STANDARD SPECIFICATIONS Installation:


• Installation position: vertical
RoHS Directive 2011/65/EU, 2015/863/EU: • Flow direction: upwards
RoHS conform according to EN IEC 63000 • Face to face length: 125 mm, with flange 250 mm
(4.92 in., with flange 9.84 in.)
Weight:
MEASURING TUBE See table 8 and 9
Materials of wetted parts:
• Stainless steel ASTM 316Ti (1.4571)
• Other materials on request MECHANICAL INDICATOR, type -T
• Process connections: high grade SS Measuring principle
• With flange: PTFE gasket The indication is made by magnetic coupling of a magnet
• With valve: PCTFE seat or silver seat, PTFE gasket enclosed in the float and a magnet in the indication unit,
Fluids to be measured: which follows the movements of the float.
Liquid or gas
Scale:
Measuring range:
Standard: removable aluminum plate with printed scale
See pages 9 to 11
The measureable flow rates are depending from density (double scale as option)
and viscosity of the fluid. To find the fluid specific Indicator housing:
measuring range please use the Yokogawa Sizing • Material: Stainless steel AISI304 (1.4301)
Software: www.FlowConfigurator.com • Degree of Protection: IP66/67
Measuring turndown ratio: Process and ambient temperature:
10:1 The dependency of the process temperature from the
Process connections: ambient temperature is shown in fig. 2.
• Inner thread: ¼ - 18 NPT; ⅜ -18 NPT Transportation and storage condition:
G ¼; G ⅜; Rp ¼ -40 °C to +110 °C (-40 °F to 230 °F)
• Cutting ring: 6 mm; 8 mm; 10 mm; 12 mm
• Cutting ring (Swagelok): 6 mm; 8 mm; 10 mm; 12 mm
• Nozzle: 6 mm; 8 mm ELECTRONIC TRANSMITTER, type -E
• Flange (screwed in): Temperature range:
• Acc. to EN 1092-1: -25 °C to +65 °C (-13 °F to 149 °F)
DN15 and DN25, PN40; Transportation and storage condition:
• Acc. to ASME B 16.5: -40 °C to +70 °C (-40 °F to 158 °F)
½ in. and 1 in. Class 150, Class 300 Process and ambient temperature:
• Stainless steel AISI 316Ti The dependency of the process temperature from the
Gasket PTFE ambient temperature is shown in fig. 2.
Process pressure:
Power supply:
Depends on process connection; see model code
14 to 30 V DC
Viscosity limit:
Load resistance:
max. 6 mPas recommended
Process temperature: (U − 14 V) / 20 mA, max. 500 Ω
• Without valve: -25 °C to +250 °C (-13 to 482 °F) Analog output:
• With valve: -25 °C to +150 °C (-13 to 302 °F) 4 to 20 mA
See also fig. 2. Linearity:
Lower temperatures on request. ± 0.25 % of 20 mA
Measurement accuracy: Hysteresis:
Acc. to standard VDI/VDE 3513 sheet 2 (qG = 50 %) 4 % ± 0.15 % of 20 mA
Repeatability:
± 0.16 % of 20 mA
Accuracy specification Influence of power supply:
± 0.1 % of 20 mA
± 25 % Temp. coefficient of analog output:
± 4 %, qG =50 % ± 0.5 % / 10 °C of 20 mA
± 20 % AC-part of analog output:
± 0.15 % of 20 mA
± 15 % Long time stability:
Error

± 0.2 % / year
± 10 % Maximum output current:
21.5 mA
±5% Output current in case of failure:
≤ 3.6 mA (NAMUR NE 43)
0%
Response time (99 %):
0% 20 % 40 % 60 % 80 % 100 %
Approx. 1 s
Flow Quickon connector:
• Cable diameter: 4 to 6 mm (0.16 to 0.24 in.)
Calibration conditions: • Cable cross-section: 0.34 to 0.75 mm2
• Water, 1 to 2 bar, 15 °C to 25 °C (59 °F to 77 °F) (0.0002 to 0.03 in.2)
• Air, 18 °C to 25 °C (64 °F to 77 °F ), atmospheric pressure Pulse output, option /CP:
Electronic switch with galvanic isolation, acc. to
EN 60947-5-6
• Pulse length: 200 ms
• Max. frequency: 4 Hz

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
3

Electromagnetic compatibility (EMC): HYSTERESIS OF LIMIT SWITCHES


• EN 61326-1: Class A, Table 2 Min-contact and Max-contact:
• EN 61326-2-3 • Pointer movement: ≈ 0.8 mm (0.03 in.)
• Approval for Morocco: • Float movement: ≈ 0.8 mm (0.03 in.)
Rotameter RAKD complies with the provisions of the Minimum distance between 2 limit switches:
Moroccan Regulations: ≈ 8 mm (0.3 in.)
- EN 61326 1
- EN 61326 2 3
Logo shown on the name plate (scale)
POWER SUPPLY FOR LIMIT SWITCHES, option /W
Type:
Acc. to EN 60947-5-6
POWER SUPPLY FOR ELECTRONIC TRANSMITTER, • KFA5-SR2-Ex*.W (115 V AC); * = 1 or 2
option /UT • KFA6-SR2-Ex*.W (230 V AC); * = 1 or 2
Type: • KFD2-SR2-Ex*.W (24 V DC); * = 1 or 2
Power supply with galvanically separated input and output Fail-safe
RN221N-B1 • KFD2-SH-Ex1 (24 V DC), 1 channel
Supply voltage: Power supply:
20 to 250 V DC / AC 50/60 Hz • 230 V AC ± 10 %, 45 to 65 Hz
Maximum load: • 115 V AC ± 10 %, 45 to 65 Hz
700 Ω • 24 V DC ± 25 %
Output signal: Relay output:
4 to 20 mA 1 or 2 potential-free change over contact(s)
Switching capacity:
Max. 250 V AC, max. 2 A
ELECTRICAL CONNECTION, indicator type -E Note:
Type: If fail-safe limit switch option /K6 or /K7 is ordered, for power
• Quickon supply option /W4E must be selected.
• M12, option /A29, /A30 If fail-safe limit switch option /K8 is ordered, for power supply
Cable diameter: option /W4F must be selected.
4 to 6 mm (0.16 to 0.24 in.)
Maximum cross section of core:
Ø 0.34 to 0.75 mm2 (0.0002 to 0.03 in.2) SWITCHING LEVELS FOR LIMIT SWITCHES
Table 1 Min, Max, Min-Max, Min-Min and Max-Max-contact
as standard version
LIMIT SWITCHES IN STANDARD VERSION,
option /K1 to /K3 Option /K1 Option /K2 Option /K3
Type: Signal Signal Signal
Inductive proximity switch SC2-N0 acc. to EN 60947-5-6 Function Pointer
SC2-N0 SC2-N0 SC2-N0
Nominal voltage:
8 V DC above LV ---- 1 mA 1 mA
MAX
below LV ---- 3 mA 3 mA
Output signal:
≤ 1 mA or ≥ 3 mA
Signal Signal Signal
Function Pointer
SC2-N0 SC2-N0 SC2-N0
LIMIT SWITCHES IN FAIL-SAFE VERSION,
above LV 3 mA ---- 3 mA
option /K6 to /K8 MIN
below LV 1 mA ---- 1 mA
Type:
Inductive proximity switch SJ2-SN acc. EN 60947-5-6 Note: LV = Limit Value
Nominal voltage:
8 V DC
Output signal: Table 2  Min, Max and Min-Max-contact as fail-safe
≤ 1 mA or ≥ 3 mA version
Option /K6 Option /K7 Option /K8

Signal Signal Signal


ELECTRICAL CONNECTION, option /K1 to /K8 Function Pointer
Type: SJ2-SN SJ2-SN SJ2-SN
• Quickon above LV ---- 1 mA 1 mA
• M12 (option /A29, /A30) MAX below LV ---- 3 mA 3 mA
Cable diameter: fail-safe ---- 1 mA 1 mA
4 to 6 mm (0.16 to 0.24 in.)
Maximum cross section of core: Signal Signal Signal
Function Pointer
Ø 0.34 to 0.75 mm2 (0.0002 to 0.03 in.2) SJ2-SN SJ2-SN SJ2-SN
above LV 3 mA ---- 3 mA
MIN below LV 1 mA ---- 1 mA
fail-safe 1 mA ---- 1 mA
Note: LV = Limit Value

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
4

FLOW CONTROLLER, option /R1 and /R3 FOLLOWING IEC 61508


Flow controller for constant flow in case of variations in RAKD with local indicator and standard or fail-safe limit
process pressure. switches
These are no valves to reduce the pressure. (RAKD-SS--TNNN/K1 to K8):
• Flow Controller /R1 for liquids and gases Suitable for application in safety functions up to and
The regulator keeps the flow rate constant in case of a including SIL1.
variable inlet pressure and constant back pressure. For RAKD with valve and controller with local indicator and
gases the process conditions are based on the outlet standard or fail-safe limit switches
conditions. The inlet pressure should be minimum
(RAKD-SS-V-TNNN/R/K1 to K8):
400 mbar larger than the outlet pressure (see Fig.1).
Suitable for application in safety functions up to and
• Flow Controller /R3 for gases with fluctuations of the
outlet pressure and constant inlet pressure. The process including SIL1.
conditions are the inlet conditions. Details see FMEDA report.
The inlet pressure should be minimum 400 mbar (5.8 psi)
larger than the outlet pressure.
Max. liquid flow: 100 l/h (26.4 gph) FOLLOWING ISO 13849-1
Max. gas flow: 3250 l/h (858.56 gph) Safety Metrics available for:
Max. pressure: 25 bar (362.6 psi) RAKD with local indicator and standard or fail-safe limit
Temperature range: -20 °C to +80 °C (-4 °F to 176 °F) switches
Table 3 Materials: (RAKD-SS--TNNN/K1 to K8)
Housing Diaphragm Springs
RAKD with valve and controller with local indicator and
standard or fail-safe limit switches
/R1 or /R3 CrNi-Steel PTFE CrNi-Steel
(RAKD-SS-V-TNNN/R/K1 to K8)
Details see FMEDA report.

flow 6
APPROVALS IN EAEU AND CIS COUNTRIES
flow 5 Eurasian Conformity (EAC)
Flow in l/h, air at 20 °C, backpressure 1 bar

1000
RAKD complies to applicable Technical Regulations valid in
flow 4 EAEU countries Russia, Belarus, Kazakhstan, Armenia and
Kyrgyzstan (option /VE).
flow 3
• TR CU 004
• TR CU 020
100
flow 2 • TR CU 012 can be added for hazardous area applications
(options /GS1, /GC1)
flow 1
Pattern Approval certificate of Measuring Instruments
RAKD has Pattern Approval certificates and is registered as a
measuring instrument in Kazakhstan, Uzbekistan and Russia.
10 • Option /QR2 for Kazakhstan
0 1 2 3
Prepressure in barg
• Option /QR3 for Uzbekistan
• Option /VR for Russia
1000
flow 6
Flow in gph, air at 68 °F, backpressure 14.7 psi

flow 5

flow 4
100
flow 3

flow 2

flow 1
10

1
0 10 20 30 40 50
Prepressure in psi

Fig. 1 Control characteristic for /R1


The above curves show the control characteristic of the
inlet flow regulator /R1 with air for 6 different flowrates, each
with fixed valve position, back pressure 1 bar (14.5 psi) (atmo-
sphere conditions).
As it can be seen for the smallest flowrate, the regulation
works best from 0.4 bar (5.8 psi) to 3 bar (43.5 psi) (or more)
inlet pressure change, for the largest flowrate from 0.9 bar
(13 psi) to 3 bar (43.5 psi) (or more).

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
5

HAZARDOUS AREA SPECIFICATIONS Intrinsically safe RAKD with ATEX-approval for use
in zone 2, option /KS3
HAZARDOUS AREA APPROVALS FOR Explosion proof:
INTRINSICALLY SAFE RAKD Ex ic IIC T6...T4 Gc
Entity parameter:
Intrinsically safe with ATEX-approval, option /KS1 See table 4
Certificate: Temperature specification:
See table 5
KEMA 00ATEX 1037X
Explosion proof:
Ex ia IIC T6...T4 Gb Intrinsically safe RAKD with IECEx-approval,
Entity parameter: option /ES1
Table 4 Certificate:
IS Ana- Pulse Limit switch IECEx DEK 12.0003X
parame- log out- Type 2 Type 3 Type 2 Type 3 Explosion proof:
ter output put /K1 to /K1 to /K6 to /K6 to Ex ia IIC T6...T4 Gb
/K3 /K3 /K8 /K8 Entity parameter:
Ui in V 30 16 16 16 16 16 See table 4
Temperature specification:
Ii in mA 100 20 25 52 25 52
See table 5
Pi in mW 750 64 64 169 64 169 For the configurations where a transmitter is combined with
Li in mH 0.73 0 0.15 0.15 0.1 0.1
limit switches, the temperature class is determined by the most
restrictive combinations of maximum ambient temperature and
Ci in nF 2.4 0 150 150 30 30 maximum process temperature. Description of limit switch type
2 and 3 see IECEx certificates from Pepperl & Fuchs:
• IECEx PTB 11.0091X (SC2-NO) for /K1 to /K3
Temperature specification: • IECEx PTB 11.0092X (SJ2-SN) for /K6 to /K8
Table 5
Configuration Max. Max. Temperature
ambient process tem- class Intrinsically safe RAKD with NEPSI-approval (China),
temperature perature option /NS1
Certificate:
65 °C 65 °C
(149 °F) (149 °F)
GYJ20.1089X
T6 Explosion proof:
50 °C 80 °C
Transmitter (122 °F) (176 °F)
Ex ia IIC T4~T6 Gb
4 to 20 mA / Max. Tamb.:
Pulse 45 °C 100 °C
(113 °F) (212 °F)
T5 +65 °C (149 °F)
Limit switches:
38 °C 135 °C
(100 °F) (267 °F)
T4 Option /K1 to /K8
Entity parameter:
65 °C 65 °C
(149 °F) (149 °F)
T6 See table 4
Temperature specification:
80 °C 80 °C
(176 °F) (176 °F)
See table 5
T5
Limit switches 59 °C 100 °C
type 2 (138 °F) (212 °F)
Intrinsically safe RAKD with PESO-approval (India),
100 °C 100 °C
(212 °F) (212 °F)
option /Q11 with /KS1
T4 Same data as ATEX-certified type, option /KS1.
73 °C 135 °C
Certificate:
(163 °F) (275 °F)
PESO Ref. No.: P420770/1
23 °C 65 °C
T6 Explosion proof:
(149 °F) (149 °F)
Ex ia IIC T6...T4 Gb
37 °C 80 °C
Temperature specification:
(73 °F) (176 °F)
T5 See table 5
34 °C 100 °C
Limit switches (93 °F) (212 °F)
type 3 57 °C 80 °C
Intrinsically safe RAKD with KOSHA-approval (Korea),
(134 °F) (176 °F)
Option /ES1 with /KC
54 °C 100 °C
T4 Same data as for IECEx certification, option /ES1.
(129 °F) (212 °F)
Certificate:
48 °C 135 °C 12-AV4BO-0522X
(118 °F) (275 °F)
Explosion proof:
Ex ia IIC T6...T4
For the configurations where a transmitter is combined with Limit switches:
limit switches, the temperature class is determined by the Option /K1 to /K8
most restrictive combinations of maximum ambient temperature Temperature specification:
and maximum process temperature. See table 5
Description of limit switch type 2 and 3 see ATEX certificates
from Pepperl & Fuchs:
• PTB 99 ATEX 2219X (SC2-NO) for /K1 to /K3
• PTB 00 ATEX 2049X (SJ2-SN) for /K6 to /K8

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
6

Intrinsically safe RAKD with KOSHA-approval (Korea), HAZARDOUS AREA APPROVALS FOR COMPLETE
Option /KS1 with /KC MECHANICAL RAKD
Same data as for ATEX certification, option /KS1.
Certificate: ATEX registrated RAKD, option /KC1
12-AV4BO-0720X Archive No.:
Explosion proof: IBExU 137/15
Ex ia IIC T6...T4 Explosion proof:
Limit switches:
• II2G Ex h IIC TX Gb
Option /K1 to /K8
Temperature specification: • II2D Ex h IIIC TX°C Db
See table 5 Max. surface temperature:
TX°C: max. surface temperature determined by the
process temperature
Intrinsically safe RAKD with EAC-approval (Russia, Ambient temperature:
Belarus, Kazakhstan, Armenia and Kyrgyzstan), -25 °C to +80 °C (-4 °F bis 176 °F)
option /GS1 Max. process temperature
For indicator type -E and limit switches
• Without valve: +250 °C (482 °F)
Certificate:
RU С-DЕ.AA87.В.00398/20 • With valve: +150 °C (302 °F)
Explosion proof:
1Ex ia IIC T6...T4 Gb X
Limit switches: RAKD with EAC-approval, option /GC1
Option /K1 to /K8
Approval:
Entity parameter:
RU С-DЕ.AA87.В.00398/20
See table 4
Temperature specification: Explosion proof:
See table 5 • II Gb c IIC T** X
• III Db c IIIC T**°C X
Max. surface temperature:
Intrinsically safe with Taiwan Safety Mark T**°C: corresponding process temperature
Registration Document: Ambient temperature:
ML041200703XN3 -25 °C to +80 °C (-4 °F bis 176 °F)
Option /ES1 must be selected. Max. process temperature:
Same data as IECEx-certified type (/ES1). • Without valve: +250 °C (482 °F)
For export to Taiwan please contact your Yokogawa • With valve: +150 °C (302 °F)
representative in Taiwan to receive the Taiwan Safety Mark.

Intrinsically safe RAKD with ECAS-approval (UAE)


Same data as for IECEx certification, option /ES1.
Certificate:
20-04-10408 / E20-04-000728

HAZARDOUS AREA APPROVALS FOR


INTRINSICALLY SAFE LIMIT SWITCHES

Intrinsically safe and dust proof limit switches with


ATEX-approval for indicator type -T, option /K1 to
/K8 with /KS2
Certificate:
• PTB 99 ATEX 2219X (SC2-N0)
• PTB 00 ATEX 2049X (SJ2-SN)
Explosion proof:
• Ex ia IIC T6...T1 Gb, II 2G
• Ex ia IIIC T135 °C Da, II 1D
• Ex ib IIIC T135 °C Db, II 2D
Entity parameter:
See certificate

Intrinsically safe or nonincendive limit switches


with FM-approval for indicator type -T, option /K1 to
/K8 with /FS1
Explosion proof:
• IS: Cl. I, II, III, Div. 1, Gp. ABCDEFG, T6, Ta = +60 °C,
• Nl: Cl. I, Div. 2, Gp. ABCD, T5, Ta = +50 °C
Cl. II, Div. 1, Gp. EFG
Cl. III, Div. 1
Entity parameter:
• See FM-control drawing 116-0165 for IS
• See FM-control drawing 116-0155 for Nl
GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
7

POWER SUPPLIES FOR INTRINSICALLY SAFE


COMPONENTS
Power Supply for the intrinsically safe electronic
transmitter, option /UT
Type:
Power supply with galvanically separated input and output
RN221N-B1
Certificate:
• ATEX: PTB00ATEX 2018
• Other certificates available on request.
Supply voltage:
20 to 250 V DC/AC 50/60 Hz
Maximum load impedance:
700 Ω
Output signal:
4 to 20 mA
Control circuit:
Intrinsically safe [Ex ia] IIC; group II; category (1)GD
Entity parameters: ­
See certificate

Power supply for intrinsically safe limit switches,


option /W
Type:
Acc. to EN 60947-5-6
• KFA5-SR2-Ex*.W (115 V AC),* = 1 or 2
• KFA6-SR2-Ex*.W (230 V AC),* = 1 or 2
• KFD2-SR2-Ex*.W (24 V DC),* = 1 or 2
Fail-safe
• KFD2-SH-Ex1 (24 V DC), 1 channel
Approvals:
• KFA5-SR2-Ex*.W: ATEX: PTB 00 ATEX 2081
FM: ID 3011578
IECEx: PTB11.0031
EAC: RU С-DE.EX01.В.00102/19
NEPSI: GYJ17.1283
• KFA6-SR2-Ex*.W: ATEX: PTB 00 ATEX 2081
FM: ID 3011578
IECEx: PTB11.0031
EAC: RU С-DE.EX01.В.00102/19
NEPSI: GYJ17.1283
• KFD2-SR2-Ex*.W: ATEX: PTB 00 ATEX 2080
FM: ID 3011578
IECEx: PTB11.0034
EAC: RU С-DE.EX01.В.00102/19
NEPSI: GYJ17.1283
• KFD2-SH-Ex1: ATEX: PTB 00 ATEX 2042
EAC: RU С-DE.EX01.В.00102/19
Control circuit (ATEX):
[Ex ia] IIC; group II; category (1)GD
Entity parameter:
See certificate

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
8

TEMPERATURE SPECIFICATION

Tamb in °F
68 86 104 122 140 158 176

245 473

220 428

195 383

Tprocess in °F
170 338
Tprocess in °C

145 293

120 248

95 203

Tp w/o valve
70 158
Tp with valve
Tp with limit switches
45 Tp with electronic transmier 113

20 68
20 30 40 50 60 70 80
Tamb in °C

Fig. 2 Maximum allowed process temperature depending on ambient temperature

For units with explosion proof certification the temperature limits according the certificate of conformity must be regarded (see also
table 5).
The minimum ambient temperature is -25 °C (-13 °F). Lower temperatures on request.

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
9

PLANNING AND INSTALLATION HINTS


• The user is responsible for the use of the flowmeters with regard to suitability and intended use.

• The actual process pressure must be lower as the specified pressure limits.

• Make sure that the wetted parts are resistant to the process fluid.

• Ambient- and process temperature must be between the specified temperature limits.

• If dirt accumulation is to be expected, we recommend to install a bypass pipe.

• To avoid float bouncing in case of gas application notice the recommendations of VDI/VDE 3513 Sheet 3.

• To avoid mutual magnetic influence in case of paralleldesign of several Rotameters please make sure that the distance
between the tube middle axes is at least 300 mm. The distance to other ferromagnetic materials should be at least 250 mm.

• Avoid static magnetic fields next to the Rotameter.

Specify the following when ordering:


Standard:
• Model, suffix and option code
• Flow conditions
• Temperature
• Pressure
• Viscosity (see viscosity limit)
• Density

For gases:
• Cross reference of the scale
• Option /B: customer specific markings

For your special application please use the Yokogawa Sizing Software www.FlowConfigurator.com.

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
10

MODEL SPECIFICATIONS
RAKD are available with valve or without valve. For a RAKD with valve, the flow inlet will be from the rear (see fig. 6). For a RAKD
without valve, the flow inlet will be from the bottom (see fig. 3). On the following pages you will be able to configure the matching
model for your application.

RAKD without valve


1 to 250 l/h (0.26 to 66 gph) water or 40 to 8000 l/h (1.4 to 282.5 cfh) air at 1 bar and 20 °C (14.5 psi and 68 °F)
Model Process connection Description Restrictions
RAKD01 -D4 EN flange DN15 PN40, dimensions + facing acc. to EN 1092 Form B1
-A1 ASME flange ½ in. class 150, dimension and facing acc. to ASME B 16.5
-A2 ASME flange ½ in. class 300, dimension and facing acc. to ASME B 16.5
RAKD02 -D4 EN flange DN25 PN40, dimensions + facing acc. to EN 1092 Form B1
-A1 ASME flange 1 in. class 150, dimension and facing acc. to ASME B 16.5
-A2 ASME flange 1 in. class 300, dimension and facing acc. to ASME B 16.5
RAKD41 -G6 Internal thread, G ¼, PN100 Not with cone 52, 53
-G7 Internal thread, G ¼, PN160 Not with cone 52, 53
-T6 Internal thread, ¼- 18 NPT, PN100 Not with cone 52, 53
-T7 Internal thread, ¼ - 18 NPT, PN160 Not with cone 52, 53
RAKD42 -G6 Internal thread, G ⅜, PN100 Only with cone 52, 53
-G7 Internal thread, G ⅜, PN160 Only with cone 52, 53
-T6 Internal thread, ⅜ - 18 NPT, PN100 Only with cone 52, 53
-T7 Internal thread, ⅜ - 18 NPT, PN160 Only with cone 52, 53
RAKD53 -C6 Cutting ring for 6 mm outer diameter tubes, PN100 Not with cone 52, 53
-C7 Cutting ring for 6 mm outer diameter tubes, PN160 Not with cone 52, 53
-P1 Nozzle for flexible hoses, inner diamenter 6 mm, PN10 Not with cone 52, 53
-W6 Swagelok for 6 mm outer diameter tubes, PN100 Not with cone 52, 53
-W7 Swagelok for 6 mm outer diameter tubes, PN160 Not with cone 52, 53
RAKD54 -C6 Cutting ring for 8 mm outer diameter tubes, PN100 Not with cone 52, 53
-C7 Cutting ring for 8 mm outer diameter tubes, PN160 Not with cone 52, 53
-P1 Nozzle for flexible hoses, inner diamenter 8 mm, PN10 Not with cone 52, 53
-W6 Swagelok for 8 mm outer diameter tubes, PN100 Not with cone 52, 53
-W7 Swagelok for 8 mm outer diameter tubes, PN160 Not with cone 52, 53
RAKD55 -C6 Cutting ring for 10 mm outer diameter tubes, PN100 Not with cone 52, 53
-C7 Cutting ring for 10 mm outer diameter tubes, PN160 Not with cone 52, 53
-W6 Swagelok for 10 mm outer diameter tubes, PN100 Not with cone 52, 53
-W7 Swagelok for 10 mm outer diameter tubes, PN160 Not with cone 52, 53
RAKD56 -C6 Cutting ring for 12 mm outer diameter tubes, PN100
-C7 Cutting ring for 12 mm outer diameter tubes, PN160
-W6 Swagelok for 12 mm outer diameter tubes, PN100
-W7 Swagelok for 12 mm outer diameter tubes, PN160
Material SS 1.4571/ AISI 316 TI, P1: 1.4408
Cone -31 Max flow water: 1 l/h (0.264 gph ), air: 40 l/h (1.4 cfh), dp: 6 mbar
-32 Max flow water: 1.6 l/h (0.42 gph), air: 60 l/h (2.1 cfh), dp: 6 mbar
-33 Max flow water: 2.5 l/h (0.66 gph), air: 100 l/h (3.5 cfh), dp: 6 mbar
-34 Max flow water: 4 l/h (1.1 gph), air: 150 l/h (5.3 cfh), dp: 6 mbar
-37 Max flow water: 6 l/h (1.58 gph), air: 200 l/h (7.1 cfh), dp: 6 mbar
-41 Max flow water: 10 l/h (2.6 gph), air: 325 l/h (11.5 cfh), dp: 8 mbar
-42 Max flow water: 16 l/h (4.2 gph), air: 500 l/h (17.7 cfh), dp: 8 mbar
-43 Max flow water: 25 l/h (6.6 gph), air: 800 l/h (28.3 cfh), dp: 8 mbar
-44 Max flow water: 40 l/h (10.6 gph), air: 1400 l/h (49.4 cfh), dp: 11 mbar
-47 Max flow water: 60 l/h (15.8 gph), air: 2000 l/h (70.3 cfh), dp: 11 mbar
-51 Max flow water: 100 l/h (26.4 gph), air: 3250 l/h (114.8 cfh), dp: 11 mbar
-52 Max flow water: 160 l/h (42 gph), air: 5000 l/h (176.6 cfh), dp: 13 mbar
-53 Max flow water: 250 l/h (66 gph), air: 8000 l/h (282.5 cfh), dp: 13 mbar
Valve nnn Without valve Mandatory
Indicator -T Mechanical indicator
-E Indicator with electronic transmitter
Housing type 80 Stainless steel housing
Power supply nnn Without power supply Only for indicator T
424 24V DC, 2 wire, 4 to 20 mA Only for indicator E

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
11

RAKD with valve


1 to 250 l/h (0.264 to 66 gph) water or 40 to 8000 l/h air (10.6 to 2113 gph ) at 1 bar and 20 °C (14.5 psi and 68 °F)
Model Process connection Description Restrictions
RAKD41 -R3 Internal thread, R ¼, PN25 Only with controller
-T3 Internal thread, ¼ - 18 NPT, PN25 Only with controller
-G4 Internal thread, G ¼, PN40 Not with controller
-G6 Internal thread, G ¼, PN100 Not with controller
-T4 Internal thread, ¼ - 18 NPT, PN40 Not with controller
-T6 Internal thread, ¼- 18 NPT, PN100 Not with controller
RAKD53 -P1 Nozzle for flexible hoses inner diamenter 6 mm, PN10
-C3 Cutting ring for 6 mm outer diameter tubes, PN25 Only with controller
-W3 Swagelok for 6 mm outer diameter tubes, PN25 Only with controller
-C4 Cutting ring for 6 mm outer diameter tubes, PN40 Not with controller
-C6 Cutting ring for 6 mm outer diameter tubes, PN100 Not with controller
-W4 Swagelok for 6 mm outer diameter tubes, PN40 Not with controller
-W6 Swagelok for 6 mm outer diameter tubes, PN100 Not with controller
RAKD54 -P1 Nozzle for flexible hoses inner diamenter 8 mm, PN10
-C3 Cutting ring for 8 mm outer diameter tubes, PN25 Only with controller
-W3 Swagelok for 8 mm outer diameter tubes, PN25 Only with controller
-C4 Cutting ring for 8 mm outer diameter tubes, PN40 Not with controller
-C6 Cutting ring for 8 mm outer diameter tubes, PN100 Not with controller
-W4 Swagelok for 8 mm outer diameter tubes, PN40 Not with controller
-W6 Swagelok for 8 mm outer diameter tubes, PN100 Not with controller
RAKD55 -C3 Cutting ring for 10 mm outer diameter tubes, PN25 Only with controller
-W3 Swagelok for 10 mm outer diameter tubes, PN25 Only with controller
-C4 Cutting ring for 10 mm outer diameter tubes, PN40 Not with controller
-C6 Cutting ring for 10 mm outer diameter tubes, PN100 Not with controller
-W4 Swagelok for 10 mm outer diameter tubes, PN40 Not with controller
-W6 Swagelok for 10 mm outer diameter tubes, PN100 Not with controller
RAKD56 -C3 Cutting ring for 12 mm outer diameter tubes, PN25 Only with controller
-W3 Swagelok for 12 mm outer diameter tubes, PN25 Only with controller
-C4 Cutting ring for 12 mm outer diameter tubes, PN40 Not with controller
-C6 Cutting ring for 12 mm outer diameter tubes, PN100 Not with controller
-W4 Swagelok for 12 mm outer diameter tubes, PN40 Not with controller
-W6 Swagelok for 12 mm outer diameter tubes, PN100 Not with controller
Material SS 1.4571/ AISI 316 TI, P1: 1.4408
Cone -31 Max flow water: 1 l/h (0.264 gph ), air: 40 l/h (1.4 cfh), dp: 6 mbar
-32 Max flow water: 1.6 l/h (0.42 gph), air: 60 l/h (2.1 cfh), dp: 6 mbar
-33 Max flow water: 2.5 l/h (0.66 gph), air: 100 l/h (3.5 cfh), dp: 6 mbar
-34 Max flow water: 4 l/h (1.1 gph), air: 150 l/h (5.3 cfh), dp: 6 mbar
-37 Max flow water: 6 l/h (1.58 gph), air: 200 l/h (7.1 cfh), dp: 6 mbar
-41 Max flow water: 10 l/h (2.6 gph), air: 325 l/h (11.5 cfh), dp: 8 mbar
-42 Max flow water: 16 l/h (4.2 gph), air: 500 l/h (17.7 cfh), dp: 8 mbar
-43 Max flow water: 25 l/h (6.6 gph), air: 800 l/h (28.3 cfh), dp: 8 mbar
-44 Max flow water: 40 l/h (10.6 gph), air: 1400 l/h (49.4 cfh), dp: 11 mbar
-47 Max flow water: 60 l/h (15.8 gph), air: 2000 l/h (70.3 cfh), dp: 11 mbar
-51 Max flow water: 100 l/h (26.4 gph), air: 3250 l/h (114.8 cfh), dp: 11 mbar
-52 Max flow water: 160 l/h (42 gph), air: 5000 l/h (176.6 cfh), dp: 13 mbar Not with controller
-53 Max flow water: 250 l/h (66 gph), air: 8000 l/h (282.5 cfh), dp: 13 mbar Not with controller
Valve VSE inlet valve, PTFE gasket, silver seat
VPE inlet valve, PTFE gasket, PCTFE seat
VSA outlet valve, PTFE gasket, silver seat
VPA outlet valve, PTFE gasket, PCTFE seat
Indicator -T Mechanical indicator
-E Indicator with electronic transmitter
Housing type 80 Stainless steel housing
Power supply nnn Without power supply Only for indicator T
424 24V DC, 2 wire, 4 to 20 mA only for indicator E

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
12

OPTIONS
Options Option Description Restriction
code
Indicator /A12 US-engineering units Only for indicator type E
/A29 M12-connector acc. to IEC 61076-2-101 Only for indicator type E or T with limit switches
/A30 M12-connector with plug connector acc. IEC 61076-2-101 Only for indicator type E or T with limit switches
Marking /B1 Tag plate (SS) fixed by wire and customer specified tag number on Plate 9x40 mm (0.35x1.57 in.); max. 45 digits
scale
/B4 Neutral version Not with /VR, /VE, not with hazardous area approval
/B10 Percentage scale
/BG With customer specified tag number on scale Max. 30 digits
/BD Dual Scale The current output is adjusted to the conditions of
the first scale.
Limit switches /K1 MIN-contact
/K2 MAX-contact
/K3 MIN-MAX-contact, MIN-MIN-contact, MAX-MAX-contact Only for indicator type T
/K6 MIN-contact fail-safe version
/K7 MAX-contact fail-safe version
/K8 MIN-MAX-contact fail-safe version Only for indicator type T
Pulse output /CP Pulse output, acc. EN 60947-5-6 Only for indicator type E; not with limit switches
Hazardous area /KS1 ATEX intrinsically safe “ia”; Not for indicator type T without limit switches
approvals in combination with /KC: KOSHA intrinsically safe “ia” (Korea)
/KS2 ATEX gas and dust proof limit switches, category 2G 1D Only for indicator type T with limit switches
/KS3 ATEX intrinsically safe “ic” Not for indicator type T without limit switches
/ES1 IECEx intrinsically safe “ia”; Not for indicator type T without limit switches;
in combination with /KC: KOSHA intrinsically safe “a” (Korea)
/FS1 FM intrinsically safe / non incendive limit switches (USA) For indicator type T only with limit switches
/NS1 NEPSI intrinsically safe approval (China) Not for indicator type T without limit switches;
only with /CN
/GS1 EAC-Ex intrinsically safe “ia” Not for indicator type T without limit switches;
only with /VE or /VR
/KC1 ATEX non-electrical type Only for indicator type T without limit switches
/GC1 EAC-Ex non-electrical type Only for indicator type T without limit switches;
only with /VE or /VR
Country-specific /VE EAC-mark for EAEU countries Not with /Q11, not with /B4
delivery /VR EAC-mark and Pattern Approval marking for Russia Not with /Q11, not with /B4
/KC KC-mark for Korea Not with /Q11, not with /B4, for explosion proof see
/KS1 or /ES1
/CN China RoHS mark Not with /Q11, not with /B4
Country-specific /QR2 Primary verification certificate and Pattern Approval valid in Kazakhstan See page 4, only with /VE or /VR, not with /B4
application /QR3 Primary verification certificate and Pattern Approval valid in Uzbekistan See page 4, only with /VE or /VR, not with /B4
/Q11 PESO intrinsically safe “ia” Only with option /KS1
Test and certificates /H1 Oil + fat free for wetted surfaces acc. Yokogawa specification Not for /R1 and /R3
/PP Pressure test report measuring system
/P2 Certificate of Compliance with the order acc. to EN 10204: 2004-2.1
/P3 As /P2 +Test report acc. to EN 10204: 2004-2.2
/P6 Material certificate acc. to EN 10204: 2004-3.1 Only for tube, connection heads, screw sealing plug
/PM1 PMI test (1 test point: metering tube) Only for models without valve, not with D4, A1, A2
/PM4 PMI test (4 test points: metering tube, connection heads, sealing plug) Only for models with valve
/PM5 PMI test (5 test points: metering tube, connection pieces, slip on flanges) Only for models with process connection D4, A1, A2
Accessories /QC Colored caps for valve knob (red, blue, yellow, green) Only with valve, not with /NS1
/QSA Float shock absorber
Controller /R1 Flow regulator for alternating pre-pressure Only for process connection R3, T3, C3, W3, P1;
only with valve
/R3 Flow regulator for alternating back-pressure Only for process connection R3, T3, C3, W3, P1;
only with valve
Power supply for /UT RN221N-B1, 20 to 250V DC/AC, Ex i Only for indicator type E in standard and ATEX
electronic transmitter
Power supply for /W1A KFA5-SR2-Ex1.W / 115 V AC, 1 channel Only for limit switches /K1, /K2, /K3 or /CP
limit switches (trans- /W1B KFA5-SR2-Ex2.W / 115 V AC, 2 channel Only for limit switches /K1, /K2, /K3
mitter relay) /W2A KFA6-SR2-Ex1.W / 230 V AC, 1 channel Only for limit switches /K1, /K2, /K3 or /CP
/W2B KFA6-SR2-Ex2.W / 230 V AC, 2 channel Only for limit switches /K1, /K2, /K3
/W4A KFD2-SR2-Ex1.W / 24 V DC, 1 channel Only for limit switches /K1, /K2, /K3 or /CP
/W4B KFD2-SR2-Ex2.W / 24 V DC, 2 channel Only for limit switches /K1, /K2, /K3
/W4E KFD2-SH-Ex1 / 24 V DC, 1 channel, fail-safe Only for limit switches /K6, /K7
/W4F 2x KFD2-SH-Ex1 / 24 V DC, 1 channel, fail-safe Only for limit switches /K8
Instruction manuals /IEn Quantity of instruction manuals in English n = 1 to 9 selectable *)
/IDn Quantity of instruction manuals in German n = 1 to 9 selectable *)
Special order /Z Special design, must be specified separately.
If /Z is selected, several Suffix of Model-Suffix Code can be changed
to Z.
*)
If no instruction manual is selected, only a DVD with instruction manuals is shipped with the flowmeter

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
13

DIMENSIONS
Note: The dimensions a, b, c, L1, L2 and L3 are listed in table 6 and 7.

)
3.98 Ø
1.2( 101
10 .2
Ø (3.
98

Flange EN DN25 PN40

Flange ASME 1/2 - 300


Flange EN DN15 PN40

Flange ASME 1/2 - 150


)

approx. 250 (9.84)

Flange ASME 1 - 300


Flange ASME 1 - 150
125 (4.92)
L1

Cutting ring

Fig. 3 Version without valve, dimensions in mm (in.) Fig. 4 Version with flange connection,
dimensions in mm (in.)

50 (1.96)
a

Additional bore for fixing.


For the bore please use no ferritic
(magnetic) material
Ø 101.2 (3.98)

3)
(0.2
Ø6

9 (0.35)

Fig. 5 Back view with mounting bores, dimensions in mm (in.)

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
14

Ø
10 28 (1.1) 50 (1.96)
1.2
(3

b
.9
8)

155.5 (6.12)

125 (4.92)

L2 60 (2.36)

Cutting ring

Fig. 6 Version with inlet valve, dimensions in mm (in.)

L2 60 (2.36)
Ø
10
1.2
(3

b
.9
8)

155.5 (6.12)

125 (4.92)

28 (1.1) 50 (1.96)

Cutting ring

Fig. 7 Version with outlet valve, dimensions in mm (in.)

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa
15

125 (4.92)

163 (6.42)
Ø 70 (2.75)

Cutting ring

approx. 113 (4.45) approx. 60 (2.36)

G or NPT thread approx. 135 (5.31)

Fig. 8 Version with inlet valve and inlet controller, dimensions in mm (in.)

G or NPT thread approx. 135 (5.31)


approx. 113 (4.45) approx. 60 (2.36)

Ø 70 (2.75)
125 (4.92)

163 (6.42)

Cutting ring

Fig. 9 Version with outlet valve and back pressure controller, dimensions in mm (in.)

All Rights Reserved. Copyright © 2004, Rota Yokogawa GS 01R01B30-00E-E 15th edition, July 01, 2020-00
16

TYPES OF PROCESS CONNECTIONS


Table 6
Size a b c
Cone 31 to 51 52 to 53 31 to 53 31 to 51
G¼ G⅜ G¼ G¼
Thread
¼ -18 NPT ⅜ -18 NPT ¼ -18 NPT ¼ -18 NPT

INSTALLATION LENGTHS DEPENDING ON PROCESS CONNECTION TYPE AND SIZE


Table 7
L1 L2 L3
Process connection Size Cone 31 to 51 Cone 52 to 53 Cone 31 to 53 Cone 31 to 51
6 (0.24) 178 (7.01) - 54.5 (2.15) 164 (6.46)
8 (0.31) 172 (6.77) - 51.5 (2.03) 161 (6.34)
Cutting ring
10 (0.39) -
174 (6.85) 52.5 (2.07) 162 (6.38)
12 (0.47) 174 (6.85)
6 (0.24)
Nozzle 182 (7.17) - 56.5 (2.22) 166 (6.54)
8 (0.31)
6 (0.24) 178 (7.01) - 54.5 (2.15) 164 (6.46)
8 (0.31) 172 (6.77) - 51.5 (2.03) 161 (6.34)
Swagelok
10 (0.39) -
174 (6.85) 52.5 (2.07) 162 (6.38)
12 (0.47) 177 (6.97)
dimensions in mm (in.)

WEIGHTS
Table 8
Without flanges:
Without valve With valve With controller
Weight approx. 600 (1.32) approx. 1000 (2.20) approx. 1800 (3.97)
weight in g (lbs)

Table 9
With flanges:
Flange DN15 PN40 DN25 PN40 ASME ½ in. ASME ½ in. ASME 1 in. ASME 1 in.
class 150 class 300 class 150 class 300
Weight approx. 2480 (5.47) approx. 3760 (8.29) approx. 1800 (3.97) approx. 2300 (5.07) approx. 3000 (6.61) approx. 4200 (5.29)
weight in g (lbs)

Rotameter® is a trademark of Rota Yokogawa GmbH & Co. KG, a subsidiary of Yokogawa Electric Corporation, Japan.
In the United Kingdom RotameterTM is a trademark of Emerson Electric Co.
All other company and product names mentioned in this document are trade names, trademarks or registered trademarks of their
respective companies. In this document, trademarks or registered trademarks are not marked with ™ or ®.

Manufacturer:

ROTA YOKOGAWA GmbH & Co. KG


Rheinstr. 8
D-79664 Wehr
GERMANY

For the actual manufacturing location of your device refer to the model code and/or serial number.

GS 01R01B30-00E-E 15th edition, July 01, 2020-00 All Rights Reserved. Copyright © 2004, Rota Yokogawa