Red 670

Download as pdf or txt
Download as pdf or txt
You are on page 1of 137

Relion® 670 series

Line differential protection RED670 2.1 IEC


Product guide
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Contents

1. Application..................................................................... 3 13. Monitoring................................................................... 39


2. Available functions..........................................................9 14. Metering......................................................................41
3. Differential protection....................................................21 15. Human machine interface............................................42
4. Impedance protection.................................................. 24 16. Basic IED functions..................................................... 42
5. Current protection........................................................ 29 17. Station communication ...............................................42
6. Voltage protection........................................................ 31 18. Remote communication.............................................. 43
7. Frequency protection....................................................32 19. Hardware description.................................................. 43
8. Multipurpose protection................................................32 20. Connection diagrams.................................................. 46
9. Secondary system supervision..................................... 33 21. Technical data.............................................................47
10. Control........................................................................ 33 22. Ordering for customized IED......................................116
11. Scheme communication..............................................35 23. Ordering for pre-configured IED.................................126
12. Logic...........................................................................37 24. Ordering for Accessories........................................... 132

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2015 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1 Issued: December 2015
Revision: -

1. Application The IED can be used in applications with IEC 61850-9-2LE


The IED is used for the protection, control and monitoring of process bus with up to six merging units (MU) depending on
overhead lines and cables in all types of networks. The IED can other functionality included in the IED.
be used from distribution up to the highest voltage levels. It is
suitable for the protection of heavily loaded lines and multi- Each MU has eight analogue channels, normally four currents
terminal lines where the requirement for tripping is one-, two-, and four voltages. Conventional and Merging Unit channels can
and/or three-phase. The IED is also suitable for protection of be mixed freely in the application.
cable feeders to generator block transformers.
If IEC 61850-9-2LE communication is
The phase segregated current differential protection provides interrupt, data from the merging units (MU)
an excellent sensitivity for high resistive faults and gives a after the time for interruption will be
secure phase selection. The availability of six stabilized current incorrect. Both data stored in the IED and
inputs per phase allows use on multi-breaker arrangements in displayed on the local HMI will be corrupt.
three terminal applications or up to five terminal applications For this reason it is important to connect
with single breaker arrangements. The communication signal from respective MU units
between the IEDs involved in the differential scheme is based (SMPLLOST) to the disturbance recorder.
on the IEEE C37.94 standard and can be duplicated for
important installations when required for redundancy reasons. Forcing of binary inputs and outputs is a convenient way to test
Charging current compensation allows high sensitivity also on wiring in substations as well as testing configuration logic in the
long overhead lines and cables. IEDs. Basically it means that all binary inputs and outputs on the
IED I/O modules (BOM, BIM, IOM & SOM) can be forced to
A full scheme distance protection is included to provide
arbitrary values.
independent protection in parallel with the differential scheme in
case of a communication channel failure for the differential Central Account Management is an authentication
scheme. The distance protection then provide protection for infrastructure that offers a secure solution for enforcing access
the entire line including the remote end back up capability either control to IEDs and other systems within a substation. This
in case of a communications failure or via use of an independent incorporates management of user accounts, roles and
communication channel to provide a fully redundant scheme of certificates and the distribution of such, a procedure completely
protection (that is a second main protection scheme). Eight transparent to the user.
channels for intertrip and other binary signals are available in
the communication between the IEDs. The Flexible Product Naming allows the customer to use an
IED-vendor independent 61850 model of the IED. This
A high impedance differential protection can be used to protect customer model will be exposed in all IEC 61850
T-feeders or line reactors. communication, but all other aspects of the IED will remain
unchanged (e.g., names on the local HMI and names in the
The auto-reclose for single-, two- and/or three phase reclosing
tools).
includes priority circuits for multi-breaker arrangements. It co-
operates with the synchronism check function with high-speed The logic is prepared with a graphical tool. The advanced logic
or delayed reclosing. capability allows special applications such as automatic
opening of disconnectors in multi-breaker arrangements,
High set instantaneous phase and earth overcurrent, four step
closing of breaker rings, load transfer logics etc. The graphical
directional or un-directional delayed phase and earth
configuration tool ensures simple and fast testing and
overcurrent, thermal overload and two step under- and
commissioning.
overvoltage functions are examples of the available functions
allowing the user to fulfill any application requirement. A loop testing function allows complete testing including
remote end IED when local IED is set in test mode.
The IED can also be provided with a full control and interlocking
functionality including co-operation with the synchronism Forcing of binary inputs and outputs is a convenient way to test
check function to allow integration of the main or back-up wiring in substations as well as testing configuration logic in the
control. IEDs. Basically it means that all binary inputs and outputs on the
IED I/O modules (BOM, BIM, IOM & SOM) can be forced to
Disturbance recording and fault locator are available to allow
arbitrary values.
independent post-fault analysis after primary disturbances. The
Disturbance recorder will also show remote station currents, as Central Account Management is an authentication
received to this IED, time compensated with measure infrastructure that offers a secure solution for enforcing access
communication time. control to IEDs and other systems within a substation. This
incorporates management of user accounts, roles and
Out of Step function is available to separate power system
sections close to electrical centre at occurring out of step.
ABB 3
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

certificates and the distribution of such, a procedure completely • Single-breaker (double or single bus) with three phase
transparent to the user. tripping (A31)
• Single-breaker (double or single bus) with single phase
The Flexible Product Naming allows the customer to use an tripping (A32)
IED-vendor independent 61850 model of the IED. This • Multi-breaker (one-and a half or ring) with three phase
customer model will be exposed in all IEC 61850 tripping (B31)
communication, but all other aspects of the IED will remain • Multi-breaker (one-and a half or ring) with single phase
unchanged (e.g., names on the local HMI and names in the tripping (B32)
tools). This offers significant flexibility to adapt the IED to the
customers system and standard solution Optional functions are not configured but a maximum
configuration with all optional functions are available as
Communication via optical connections ensures immunity template in the graphical configuration tool. Analog inputs and
against disturbances. binary input/output signals are pre-defined for basic use. Other
signals may be required by each particular application.
Four packages have been defined for following applications:
Add binary I/O boards as required for the application when
ordering.

4 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Description of configuration A31

WA1
RED670 A31 – Single Breaker with Three phase tripping
WA2 12AI (6I+6U)

WA2_VT
QB1 QB2
MET UN
VN MMXU
WA1_VT

MET UN
VN MMXU

94 1→0 79 5(0→1) 25 SC/VC


QA1
SMP PTRC SMB RREC SES RSYN

LINE_CT
50BF 3I>BF 50 3I>> 46 Iub> 26 θ>
CC RBRF PH PIOC BRC PTOC LC PTTR

REM CT

87L 87L 3Id/I>


QB9 LDL PSCH L3C PDIF

MET Usqi MET P/Q 51_67 4(3I>) U>/I<


QC9 V MSQI CV MMXN OC4 PTOC FUF SPVC

DFR/SER DR 21FL FL MET W/Varh MET I MET Isqi


DRP RDRE LMB RFLO ETP MMTR C MMXU C MSQI
LINE_VT

27 2(3U<) 27 3U< 59 2(3U>) MET UN MET U


UV2 PTUV LOV PTUV OV2 PTOV VN MMXU V MMXU

Other Functions available from the function library

87 INd/I 59N 2(U0>) 60 Ud> Control 63 71 52PD PD


CCS SPVC ROV2 PTOV VDC PTOV Q CBAY S SIMG S SIML CC PDSC

Optional Functions
87 Id> 87LT 3Id/I> 87L 3Id/I> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
HZ PDIF LT3C PDIF L6C PDIF LT6C PDIS NS4 PTOC EF PIOC EF4 PTOC SDEPSDE

2(I>/U<) 50STB 3I>STB 60 Ud> 21 21 21 Z<_> 21 Z<


CV GAPC STB PTOC ZCV PSOF VD SPVC FDPS PDIS FMPS PDIS ZD RDIR ZMF PDIS

21 Z< 21 Z< 21 Z< 68 Zpsb 78 Ucos 78 Ucos Zpsl


ZMH PDIS ZMM PDIS ZMQ PDIS ZM RPSB PSP PPAM ZSM GAPC OOS PPAM PSL PSCH

37 P< 32 P> 24 U/f> 81 f> 81 f< 81 df/dt<> 85 85


GUP PDUP GOP PDOP OEX PVPH SA PTOF SA PTUF SA PFRC EC PSCH ECRW PSCH

85 85 3 Control 3 Control 3 Control 3 Control 3 Control


ZC PSCH ZCRW PSCH ZCLC PSCH S CILO S CSWI S XSWI S XCBR Q CRSV

S SCBR

IEC05000842 V4 EN

Figure 1. Configuration diagram for configuration A31

ABB 5
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Description of configuration A32

WA1
RED670 A32 – Single Breaker with Single phase tripping
WA2 12AI (6I+6U)

WA2_VT
QB1 QB2
MET UN
VN MMXU
WA1_VT

MET UN
VN MMXU

94 1→0 79 5(0→1) 25 SC/VC


QA1
SMP PTRC SMB RREC SES RSYN

LINE_CT
52PD PD 50BF 3I>BF 50 3I>> 46 Iub> 26 θ>
CC PDSC CC RBRF PH PIOC BRC PTOC LC PTTR

REM CT

87L 87L 3Id/I>


QB9 LDL PSCH L3C PDIF

MET Usqi MET P/Q 51_67 4(3I>) U>/I<


QC9 V MSQI CV MMXN OC4 PTOC FUF SPVC

DFR/SER DR 21FL FL MET W/Varh MET I MET Isqi


DRP RDRE LMB RFLO ETP MMTR C MMXU C MSQI
LINE_VT

27 2(3U<) 27 3U< 59 2(3U>) MET UN MET U


UV2 PTUV LOV PTUV OV2 PTOV VN MMXU V MMXU

Other Functions available from the function library

87 INd/I 59N 2(U0>) 60 Ud> Control 63 71


CCS SPVC ROV2 PTOV VDC PTOV Q CBAY S SIMG S SIML

Optional Functions
87 Id> 87LT 3Id/I> 87L 3Id/I> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
HZ PDIF LT3C PDIF L6C PDIF LT6C PDIS NS4 PTOC EF PIOC EF4 PTOC SDEPSDE

2(I>/U<) 50STB 3I>STB 60 Ud> 21 21 21 Z<_> 21 Z<


CV GAPC STB PTOC ZCV PSOF VD SPVC FDPS PDIS FMPS PDIS ZD RDIR ZMF PDIS

21 Z< 21 Z< 21 Z< 68 Zpsb 78 Ucos 78 Ucos Zpsl


ZMH PDIS ZMM PDIS ZMQ PDIS ZM RPSB PSP PPAM ZSM GAPC OOS PPAM PSL PSCH

37 P< 32 P> 24 U/f> 81 f> 81 f< 81 df/dt<> 85 85


GUP PDUP GOP PDOP OEX PVPH SA PTOF SA PTUF SA PFRC EC PSCH ECRW PSCH

85 85 3 Control 3 Control 3 Control 3 Control 3 Control


ZC PSCH ZCRW PSCH ZCLC PSCH S CILO S CSWI S XSWI S XCBR Q CRSV

85 85
S SCBR ZC1P PSCH ZC1W PSCH

IEC05000840 V4 EN

Figure 2. Configuration diagram for configuration A32

6 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Description of configuration B31

WA1
RED670 B31: interruptor múltiple con disparo trifásico
12AI (6I+6U)
QB1 WA1_VT

WA1_CT
50BF 3I>BF MET UN
CC RBRF VN MMXU

50BF 3I>BF
WA1_QA1
CC RBRF
REM CT1

REM CT2
WA1_QB6
LINE1_QB9 87L 87L 3Id/I>

LINE1_VT LDL PSCH L6C PDIF Σ

MET Usqi MET P/Q 51_67 4(3I>) U>/I<

QB61 V MSQI CV MMXN OC4 PTOC FUF SPVC

DFR/SER DR 21FL FL MET W/Varh


DRP RDRE LMB RFLO ETP MMTR

TIE_QA1 MET Isqi MET I 46 Iub> 50 3I>> 26 θ>


3I>STB
C MSQI C MMXU BRC PTOC PH PIOC LC PTTR

TIE_CT
MET U MET UN 27 3U< 27 3U< 59 3U>
V MMXU VN MMXU UV2 PTUV LOV PTUV OV2 PTOV
LINE2_VT

MET UN
QB62
WA2_VT VN MMXU

MET UN 94
94 1→0
1→0 79
79 0→1
5(0→1) 25 SC
25 SC/VC
LINE2_QB9 SMP
VN MMXU SMPPTRC
PTRC SMB
SMBRREC
RREC SES
SESRSYN
RSYN

Otras funciones disponibles desde la biblioteca de funciones


87 INd/I 50STB 3I>STB 59N 2(U0>) 60 Ud> 3 Control 63
CCS SPVC STB PTOC ROV2 PTOV VDC PTOV Q CBAY S SIMG

WA2_QB6 71 52PD PD
S SIML CC PDSC

Funciones opcionales
87 Id> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>

WA2_QA1 HZ PDIF LT6C PDIF NS4 PTOC EF PIOC EF4 PTOC SDE PSDE

2(I>/U<) 60 Ud> 21 21 21 Z<_>


CV GAPC ZCV PSOF VD SPVC FDPS PDIS FMPS PDIS ZD RDIR

21 Z< 21 Z< 21 Z< 21 Z< 68 Zpsb 78 Ucos


QB2 ZMF PDIS ZMH PDIS ZMM PDIS ZMQ PDIS ZM RPSB PSP PPAM

WA2 78 Ucos Zpsl 37 P< 32 P> 24 U/f>


ZSM GAPC OOS PPAM PSL PSCH GUP PDUP GOP PDOP OEX PVPH

81 f> 81 f< 81 df/dt<> 85 85 85


SA PTOF SA PTUF SA PFRC EC PSCH ECRW PSCH ZC PSCH

85 3 Control 3 Control 3 Control 3 Control


ZCRW PSCH ZCLC PSCH S CILO S CSWI S XSWI S XCBR

3 Control
Q CRSV S SCBR

IEC05000843 V4 EN

Figure 3. Configuration diagram for configuration B31

ABB 7
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Description of configuration B32

WA1
RED670 B32 – Multi Breaker with Single phase tripping
12AI (6I+6U)
QB1 WA1_VT

WA1_CT
50BF 3I>BF 52PD PD MET UN
CC RBRF CC PDSC VN MMXU

50BF 3I>BF 52PD PD


WA1_QA1
CC RBRF CC PDSC
REM CT1

REM CT2
WA1_QB6
LINE1_QB9 87L 87L 3Id/I>

LINE1_VT LDL PSCH L6C PDIF Σ

MET Usqi MET P/Q 51_67 4(3I>) U>/I<


QB61 V MSQI CV MMXN OC4 PTOC FUF SPVC

DFR/SER DR 21FL FL MET W/Varh


DRP RDRE LMB RFLO ETP MMTR

TIE_QA1 MET Isqi MET I 46 Iub> 50 3I>> 26 θ>


3I>STB
C MSQI C MMXU BRC PTOC PH PIOC LC PTTR

TIE_CT
MET U MET UN 27 3U< 27 3U< 59 3U>
V MMXU VN MMXU UV2 PTUV LOV PTUV OV2 PTOV
LINE2_VT

MET UN
QB62 WA2_VT VN MMXU

MET UN 94
94 1→0
1→0 79
79 0→1
5(0→1) 25 SC
25 SC/VC
LINE2_QB9 SMP
VN MMXU SMPPTRC
PTRC SMB
SMBRREC
RREC SES
SESRSYN
RSYN

Other Functions available from the function library


87 INd/I 50STB 3I>STB 59N 2(U0>) 60 Ud> 3 Control 63
CCS SPVC STB PTOC ROV2 PTOV VDC PTOV Q CBAY S SIMG

WA2_QB6 71
S SIML

Optional Functions
87 Id> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>

WA2_QA1 HZ PDIF LT6C PDIF NS4 PTOC EF PIOC EF4 PTOC SDE PSDE

2(I>/U<) 60 Ud> 21 21 21 Z<_>


CV GAPC ZCV PSOF VD SPVC FDPS PDIS FMPS PDIS ZD RDIR

21 Z< 21 Z< 21 Z< 21 Z< 68 Zpsb 78 Ucos


QB2 ZMF PDIS ZMH PDIS ZMM PDIS ZMQ PDIS ZM RPSB PSP PPAM

WA2 78 Ucos Zpsl 37 P< 32 P> 24 U/f>


ZSM GAPC OOS PPAM PSL PSCH GUP PDUP GOP PDOP OEX PVPH

81 f> 81 f< 81 df/dt<> 85 85 85


SA PTOF SA PTUF SA PFRC EC PSCH ECRW PSCH ZC PSCH

85 3 Control 3 Control 3 Control 3 Control


ZCRW PSCH ZCLC PSCH S CILO S CSWI S XSWI S XCBR

3 Control 85 85
Q CRSV S SCBR ZC1P PSCH ZC1W PSCH

IEC05000841 V4 EN

Figure 4. Configuration diagram for configuration B32

8 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

2. Available functions

Main protection functions

Table 1. Example of quantities

2 = number of basic instances


0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)

ABB 9
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

Differential protection

HZPDIF 87 1Ph high impedance differential protection 0-3 3-A02 3-A02 3-A02 3-A02

REFPDIF 87N Restricted earth fault protection, low impedance 0–2

L3CPDIF 87L Line differential protection, 3 CT sets, 2–3 line ends 1 1 1

L6CPDIF 87L Line differential protection, 6 CT sets, 3–5 line ends 1 1-A04 1 1-A04 1

LT3CPDIF 87LT Line differential protection, 3 CT sets, with inzone 1 1-A05 1-A05
transformers, 2–3 line ends

LT6CPDIF 87LT Line differential protection, 6 CT sets, with inzone 1 1-A06 1-A06 1-A06 1-A06
transformers, 3–5 line ends

LDLPSCH 87L Line differential protection logic 1 1 1 1 1

LDRGFC 11REL Additional security logic for differential protection 0-1

Impedance protection

ZMQPDIS, 21 Distance protection zone, quadrilateral characteristic 0-5 1-B10 1-B10 1-B10 1-B10
ZMQAPDIS 3-B11 3-B11 3-B11 3-B11

ZDRDIR 21D Directional impedance quadrilateral 0-2 1-B11 1-B11 1-B11 1-B11

ZMCPDIS, 21 Distance measuring zone, quadrilateral characteristic 0-5 3-B16 3-B16 3-B16 3-B16
ZMCAPDIS for series compensated lines

ZDSRDIR 21D Directional impedance quadrilateral, including series 0-2 1-B16 1-B16 1-B16 1-B16
compensation

FDPSPDIS 21 Phase selection, quadrilateral characteristic with fixed 0-2 1-B11 1-B11 1-B11 1-B11
angle 1-B16 1-B16 1-B16 1-B16

ZMHPDIS 21 Fullscheme distance protection, mho characteristic 0-5 4-B17 4-B17 4-B17 4-B17

ZMMPDIS, 21 Fullscheme distance protection, quadrilateral for 0-5 4-B17 4-B17 4-B17 4-B17
ZMMAPDIS earth faults

ZDMRDIR 21D Directional impedance element for mho characteristic 0-2 1-B17 1-B17 1-B17 1-B17

ZDARDIR Additional distance protection directional function for 0-2 1-B17 1-B17 1-B17 1-B17
earth faults

ZSMGAPC Mho impedance supervision logic 0-1 1-B17 1-B17 1-B17 1-B17

FMPSPDIS 21 Faulty phase identification with load enchroachment 0-2 2-B17 2-B17 2-B17 2-B17

ZMRPDIS, 21 Distance protection zone, quadrilateral characteristic, 0-5


ZMRAPDIS separate settings

FRPSPDIS 21 Phase selection, quadrilateral characteristic with fixed 0-2


angle

ZMFPDIS 21 High speed distance protection 0–1

ZMFCPDIS 21 High speed distance protection for series 0–1 1-B19 1-B19 1-B19 1-B19
compensated lines

ZMRPSB 68 Power swing detection 0-1 1-B11 1-B11 1-B11 1-B11


1-B16 1-B16 1-B16 1-B16

PSLPSCH Power swing logic 0-1 1-B03 1-B03 1-B03 1-B03

10 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

PSPPPAM 78 Pole slip/out-of-step protection 0-1 1-B22 1-B22 1-B22 1-B22

OOSPPAM 78 Out-of-step protection 0–1 1-B22 1-B22 1-B22 1-B22

ZCVPSOF Automatic switch onto fault logic, voltage and current 0-1 1-B11 1-B11 1-B11 1-B11
based 1-B16 1-B16 1-B16 1-B16
1-B17 1-B17 1-B17 1-B17

PPLPHIZ Phase preference logic 0-1 1-B04

ABB 11
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Back-up protection functions

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

Current protection

PHPIOC 50 Instantaneous phase overcurrent 0-3 1 1 1 1


protection

OC4PTOC 51_671) Four step phase overcurrent protection 0-3 1 1 1 1

EFPIOC 50N Instantaneous residual overcurrent 0-1 1-C24 1-C24 1-C24 1-C24
protection

EF4PTOC 51N Four step residual overcurrent protection 0-3 1-C24 1-C24 1-C24 1-C24
67N2)

NS4PTOC 46I2 Four step directional negative phase 0-2 1-C24 1-C24 1-C24 1-C24
sequence overcurrent protection

SDEPSDE 67N Sensitive directional residual overcurrent 0-1 1-C16 1-C16 1-C16 1-C16
and power protection

LCPTTR 26 Thermal overload protection, one time 0–2 1 1 1 1


constant, Celsius

LFPTTR 26 Thermal overload protection, one time 0–2 1 1 1 1


constant, Fahrenheit

CCRBRF 50BF Breaker failure protection 0-2 1 2 1 2

STBPTOC 50STB Stub protection 0-2 1-B11 1B 1-B11 1B


1-B11 1-B11

CCPDSC 52PD Pole discordance protection 0-2 1 2 1 2

GUPPDUP 37 Directional underpower protection 0-2 1-C17 1-C17 1-C17 1-C17

GOPPDOP 32 Directional overpower protection 0-2 1-C17 1-C17 1-C17 1-C17

BRCPTOC 46 Broken conductor check 1 1 1 1 1

VRPVOC 51V Voltage restrained overcurrent protection 0-3

Voltage protection

UV2PTUV 27 Two step undervoltage protection 0-2 1 1 1 1

OV2PTOV 59 Two step overvoltage protection 0-2 1 1 1 1

OEXPVPH 24 Overexcitation protection 0-1 1-D03 1-D03 1-D03 1-D03

VDCPTOV 60 Voltage differential protection 0-2 2 2 2 2

LOVPTUV 27 Loss of voltage check 1 1 1 1 1

PAPGAPC 27 Radial feeder protection 0–1

Frequency protection

SAPTUF 81 Underfrequency protection 0-6 2-E02 2-E02 2-E02 2-E02

SAPTOF 81 Overfrequency protection 0-6 2-E02 2-E02 2-E02 2-E02

SAPFRC 81 Rate-of-change frequency protection 0-2 2-E02 2-E02 2-E02 2-E02

12 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

Multipurpose protection

CVGAPC General current and voltage protection 0-4 4-F01 4-F01 4-F01 4-F01

General calculation

SMAIHPAC Multipurpose filter 0-6

1) 67 requires voltage
2) 67N requires voltage

ABB 13
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Control and monitoring functions

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670

Control

SESRSYN 25 Synchrocheck, energizing check and synchronizing 0-2 1 2 1 2

SMBRREC 79 Autorecloser 0-4 1 2 1 2


1-H04 2-H05 1-H04 2-H05

APC10 3 Apparatus control for single bay, max 10 apparatuses 0-1 1-H27 1-H27
(1CB) incl. interlocking

APC15 3 Apparatus control for single bay, max 15 apparatuses 0-1 1-H08 1-H08
(2CBs) incl. interlocking

QCBAY Apparatus control 1 1 1 1 1

LOCREM Handling of LRswitch positions 1 1 1 1 1

LOCREMCTRL LHMI control of PSTO 1 1 1 1 1

SLGAPC Logic rotating switch for function selection and LHMI 15 15 15 15 15


presentation

VSGAPC Selector mini switch 20 20 20 20 20

DPGAPC Generic communication function for Double Point 16 16 16 16 16


indication

SPC8GAPC Single point generic control 8 signals 5 5 5 5 5

AUTOBITS AutomationBits, command function for DNP3.0 3 3 3 3 3

SINGLECMD Single command, 16 signals 4 4 4 4 4

I103CMD Function commands for IEC 60870-5-103 1 1 1 1 1

I103GENCMD Function commands generic for IEC 60870-5-103 50 50 50 50 50

I103POSCMD IED commands with position and select for IEC 50 50 50 50 50


60870-5-103

I103POSCMDV IED direct commands with position for IEC 60870-5-103 10 10 10 10 10

I103IEDCMD IED commands for IEC 60870-5-103 1 1 1 1 1

I103USRCMD Function commands user defined for IEC 60870-5-103 1 1 1 1 1

Secondary system
supervision

CCSSPVC 87 Current circuit supervision 0-2 1 2 1 2

FUFSPVC Fuse failure supervision 0-3 3 3 3 3

VDSPVC 60 Fuse failure supervision based on voltage difference 0-3 1-G03 1-G03 1-G03 1-G03

Logic

SMPPTRC 94 Tripping logic 6 6 6 6 6

TMAGAPC Trip matrix logic 12 12 12 12 12

ALMCALH Logic for group alarm 5 5 5 5 5

WRNCALH Logic for group warning 5 5 5 5 5

INDCALH Logic for group indication 5 5 5 5 5

14 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670

AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-280 40-28 40-280 40-28 40-28
LLD, OR, 0 0 0
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR

ANDQT, Configurable logic blocks Q/T (see Table 3) 0–1


INDCOMBSPQT,
INDEXTSPQT,
INVALIDQT,
INVERTERQT,
ORQT,
PULSETIMERQT,
RSMEMORYQT,
SRMEMORYQT,
TIMERSETQT,
XORQT

AND, GATE, INV, Extension logic package (see Table 4) 0–1


LLD, OR,
PULSETIMER,
SLGAPC,
SRMEMORY,
TIMERSET,
VSGAPC, XOR

FXDSIGN Fixed signal function block 1 1 1 1 1

B16I Boolean 16 to Integer conversion 18 18 18 18 18

BTIGAPC Boolean 16 to Integer conversion with Logic Node 16 16 16 16 16


representation

IB16 Integer to Boolean 16 conversion 18 18 18 18 18

ITBGAPC Integer to Boolean 16 conversion with Logic Node 16 16 16 16 16


representation

TEIGAPC Elapsed time integrator with limit transgression and 12 12 12 12 12


overflow supervision

INTCOMP Comparator for integer inputs 12 12 12 12 12

REALCOMP Comparator for real inputs 12 12 12 12 12

Monitoring

CVMMXN, Measurements 6 6 6 6 6
VMMXU, CMSQI,
VMSQI, VNMMXU

CMMXU Measurements 10 10 10 10 10

AISVBAS Function block for service value presentation of secondary 1 1 1 1 1


analog inputs

EVENT Event function 20 20 20 20 20

ABB 15
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670

DRPRDRE, Disturbance report 1 1 1 1 1


A1RADR-
A4RADR,
B1RBDR-B8RBDR

SPGAPC Generic communication function for Single Point indication 64 64 64 64 64

SP16GAPC Generic communication function for Single Point indication 16 16 16 16 16


16 inputs

MVGAPC Generic communication function for Measured Value 24 24 24 24 24

BINSTATREP Logical signal status report 3 3 3 3 3

RANGE_XP Measured value expander block 66 66 66 66 66

SSIMG 63 Gas medium supervision 21 21 21 21 21

SSIML 71 Liquid medium supervision 3 3 3 3 3

SSCBR Circuit breaker monitoring 0-6 3-M13 6-M15 3-M13 6-M15

LMBRFLO Fault locator 1 1 1 1 1

I103MEAS Measurands for IEC 60870-5-103 1 1 1 1 1

I103MEASUSR Measurands user defined signals for IEC 60870-5-103 3 3 3 3 3

I103AR Function status auto-recloser for IEC 60870-5-103 1 1 1 1 1

I103EF Function status earth-fault for IEC 60870-5-103 1 1 1 1 1

I103FLTPROT Function status fault protection for IEC 60870-5-103 1 1 1 1 1

I103IED IED status for IEC 60870-5-103 1 1 1 1 1

I103SUPERV Supervison status for IEC 60870-5-103 1 1 1 1 1

I103USRDEF Status for user defined signals for IEC 60870-5-103 20 20 20 20 20

L4UFCNT Event counter with limit supervision 30 30 30 30 30

TEILGAPC Running hour-meter 9 9 9 9 9

Metering

PCFCNT Pulse-counter logic 16 16 16 16 16

ETPMMTR Function for energy calculation and demand handling 6 6 6 6 6

16 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 2. Total number of instances for basic configurable logic blocks

Basic configurable logic block Total number of instances

AND 280

GATE 40

INV 420

LLD 40

OR 289

PULSETIMER 40

RSMEMORY 40

SRMEMORY 40

TIMERSET 60

XOR 40

Table 3. Total number of instances for configurable logic blocks Q/T

Configurable logic blocks Q/T Total number of instances

ANDQT 120

INDCOMBSPQT 20

INDEXTSPQT 20

INVALIDQT 22

INVERTERQT 120

ORQT 120

PULSETIMERQT 40

RSMEMORYQT 40

SRMEMORYQT 40

TIMERSETQT 40

XORQT 40

Table 4. Total number of instances for extended logic package

Extended configurable logic block Total number of instances

AND 180

GATE 49

INV 180

LLD 49

OR 180

PULSETIMER 59

SLGAPC 74

SRMEMORY 110

TIMERSET 49

VSGAPC 130

XOR 49

ABB 17
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Communication

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

Station communication

LONSPA, SPA SPA communication protocol 1 1 1 1 1

ADE LON communication protocol 1 1 1 1 1

HORZCOMM Network variables via LON 1 1 1 1 1

PROTOCOL Operation selection between SPA and IEC 1 1 1 1 1


60870-5-103 for SLM

RS485PROT Operation selection for RS485 1 1 1 1 1

RS485GEN RS485 1 1 1 1 1

DNPGEN DNP3.0 communication general protocol 1 1 1 1 1

DNPGENTCP DNP3.0 communication general TCP protocol 1 1 1 1 1

CHSERRS485 DNP3.0 for EIA-485 communication protocol 1 1 1 1 1

CH1TCP, CH2TCP, DNP3.0 for TCP/IP communication protocol 1 1 1 1 1


CH3TCP, CH4TCP

CHSEROPT DNP3.0 for TCP/IP and EIA-485 1 1 1 1 1


communication protocol

MST1TCP, DNP3.0 for serial communication protocol 1 1 1 1 1


MST2TCP,
MST3TCP,
MST4TCP

DNPFREC DNP3.0 fault records for TCP/IP and EIA-485 1 1 1 1 1


communication protocol

IEC 61850-8-1 Parameter setting function for IEC 61850 1 1 1 1 1

GOOSEINTLKRCV Horizontal communication via GOOSE for 59 59 59 59 59


interlocking

GOOSEBINRCV GOOSE binary receive 16 16 16 16 16

GOOSEDPRCV GOOSE function block to receive a double 64 64 64 64 64


point value

GOOSEINTRCV GOOSE function block to receive an integer 32 32 32 32 32


value

GOOSEMVRCV GOOSE function block to receive a measurand 60 60 60 60 60


value

GOOSESPRCV GOOSE function block to receive a single point 64 64 64 64 64


value

MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND

FRONT, LANABI, Ethernet configuration of links 1 1 1 1 1


LANAB, LANCDI,
LANCD

GATEWAY Ethernet configuration of link one 1 1 1 1 1

18 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IEC 61850 ANSI Function description Line Differential

RED670 (B31)

RED670 (B32)
RED670 (A31)

RED670 (A32)
RED670
(Customized)

OPTICAL103 IEC 60870-5-103 Optical serial 1 1 1 1 1


communication

RS485103 IEC 60870-5-103 serial communication for 1 1 1 1 1


RS485

AGSAL Generic security application component 1 1 1 1 1

LD0LLN0 IEC 61850 LD0 LLN0 1 1 1 1 1

SYSLLN0 IEC 61850 SYS LLN0 1 1 1 1 1

LPHD Physical device information 1 1 1 1 1

PCMACCS IED Configuration Protocol 1 1 1 1 1

SECALARM Component for mapping security events on 1 1 1 1 1


protocols such as DNP3 and IEC103

FSTACCS Field service tool access via SPA protocol over 1 1 1 1 1


FSTACCSNA ethernet communication

ACTIVLOG Activity logging parameters 1 1 1 1 1

ALTRK Service Tracking 1 1 1 1 1

SINGLELCCH Single ethernet port link status 1 1 1 1 1

PRPSTATUS Dual ethernet port link status 1 1 1 1 1

Process bus communication IEC 61850-9-2 1)

PRP IEC 62439-3 parallel redundancy protocol 0-1 1-P03 1-P03 1-P03 1-P03

Remote communication

Binary signal transfer receive/transmit 6/36 6/36 6/36 6/36 6/36

Transmission of analog data from LDCM 1 1 1 1 1

Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3

Scheme communication

ZCPSCH 85 Scheme communication logic for distance or 0-1 1-B11 1-B11 1-B11 1-B11
overcurrent protection 1-B16 1-B16 1-B16 1-B16

ZC1PPSCH 85 Phase segregated scheme communication 0-1 1-B05 1-B05


logic for distance protection

ZCRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-B11 1-B11 1-B11 1-B11
distance protection 1-B16 1-B16 1-B16 1-B16

ZC1WPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-B05 1-B05
phase segregated communication

ZCLCPSCH Local acceleration logic 0-1 1-B11 1-B11 1-B11 1-B11

ECPSCH 85 Scheme communication logic for residual 0-1 1-C24 1-C24 1-C24 1-C24
overcurrent protection

ECRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-C24 1-C24 1-C24 1-C24
residual overcurrent protection

DTT Direct transfer trip 0-1

1) Only included for 9-2LE products

ABB 19
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Basic IED functions

Table 5. Basic IED functions

IEC 61850 or function Description


name

INTERRSIG
SELFSUPEVLST Self supervision with internal event list

TIMESYNCHGEN Time synchronization module

BININPUT, SYNCHCAN, Time synchronization


SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA

TIMEZONE Time synchronization

DSTBEGIN, GPS time synchronization module


DSTENABLE, DSTEND

IRIG-B Time synchronization

SETGRPS Number of setting groups

ACTVGRP Parameter setting groups

TESTMODE Test mode functionality

CHNGLCK Change lock function

SMBI Signal matrix for binary inputs

SMBO Signal matrix for binary outputs

SMMI Signal matrix for mA inputs

SMAI1 - SMAI12 Signal matrix for analog inputs

ATHSTAT Authority status

ATHCHCK Authority check

AUTHMAN Authority management

FTPACCS FTP access with password

SPACOMMMAP SPA communication mapping

SPATD Date and time via SPA protocol

DOSFRNT Denial of service, frame rate control for front port

DOSLANAB Denial of service, frame rate control for OEM port AB

DOSLANCD Denial of service, frame rate control for OEM port CD

DOSSCKT Denial of service, socket flow control

GBASVAL Global base values for settings

PRIMVAL Primary system values

ALTMS Time master supervision

ALTIM Time management

MSTSER DNP3.0 for serial communication protocol

PRODINF Product information

RUNTIME IED Runtime Comp

20 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 5. Basic IED functions, continued


IEC 61850 or function Description
name

CAMCONFIG Central account management configuration

CAMSTATUS Central account management status

TOOLINF Tools Information component

SAFEFILECOPY Safe file copy function

Table 6. Local HMI functions

IEC 61850 or function ANSI Description


name

LHMICTRL Local HMI signals

LANGUAGE Local human machine language

SCREEN Local HMI Local human machine screen behavior

FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600


FNKEYMD1–
FNKEYMD5

LEDGEN General LED indication part for LHMI

OPENCLOSE_LED LHMI LEDs for open and close keys

GRP1_LED1– Basic part for CP HW LED indication module


GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

3. Differential protection
Restricted earth-fault protection, low impedance REFPDIF
1Ph High impedance differential protection HZPDIF Restricted earth-fault protection, low-impedance function
The 1Ph High impedance differential protection HZPDIF REFPDIF can be used on all directly or low-impedance earthed
functions can be used when the involved CT cores have the windings. The REFPDIF function provides high sensitivity and
same turns ratio and similar magnetizing characteristics. It high speed tripping as it protects each winding separately and
utilizes an external CT secondary current summation by wiring. thus does not need inrush stabilization.
Actually all CT secondary circuits which are involved in the
differential scheme are connected in parallel. External series The REFPDIF function is a percentage biased function with an
resistor, and a voltage dependent resistor which are both additional zero sequence current directional comparison
mounted externally to the IED, are also required. criterion. This gives excellent sensitivity and stability during
through faults.
The external resistor unit shall be ordered under IED
accessories in the Product Guide. REFPDIF can also protect autotransformers. Five currents are
measured at the most complicated configuration as shown in
HZPDIF can be used to protect tee-feeders or busbars, Figure 5.
reactors, motors, auto-transformers, capacitor banks and so
on. One such function block is used for a high-impedance
restricted earth fault protection. Three such function blocks are
used to form three-phase, phase-segregated differential
protection. Several function block instances (for example, six)
can be available in a single IED.

ABB 21
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

CT CT Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF


YNdx
CT CB CB Line differential protection applies the Kirchhoff's law and
Y d compares the currents entering and leaving the protected
CB CB
multi-terminal circuit, consisting of overhead power lines and
Autotransformer
CT cables. Under the condition that there are no in-line or tap
IED
(shunt) power transformers within the zone of protection, it
offers a phase segregated fundamental frequency current
The most typical CT CB CB CT based differential protection with high sensitivity and provides
application
The most complicated phase selection information for single-pole tripping
application - autotransformer

IEC05000058-2-en.vsd The three-terminal version is used for conventional two-terminal


IEC05000058-2 V1 EN lines with or without a 1½ circuit breaker arrangement in one
end, as well as three-terminal lines with single breaker
Figure 5. Examples of applications of the REFPDIF
arrangements at all terminals.

Protected zone

IED Communication channel IED

IEC05000039-3-en.vsd
IEC05000039 V3 EN

Figure 6. Example of application on a conventional two-terminal line

The six-terminal versions are used for conventional two-


terminal lines with 1½ circuit breaker arrangements in both
ends, as well as multi-terminal lines with up to five terminals.

Protected zone

IED Comm. Channel IED

Comm. Channel Comm. Channel


IED

IEC05000040_2_en.vsd
IEC05000040 V2 EN

Figure 7. Example of application on a three-terminal line with 1½ breaker arrangements

The current differential algorithm provides high sensitivity for A special feature with this function is that applications with
internal faults and it has excellent stability for external faults. small power transformers (rated current less than 50% of the
Current samples from all CTs are exchanged between the IEDs differential current setting IdMin) connected as line taps (that is,
in the line ends (master-master mode) or sent to one IED as shunt power transformers), without measurements of
(master-slave mode) for evaluation. currents in the tap, can be handled. The normal load current is
considered to be negligible, and special measures must be
A restrained dual biased slope evaluation is made where the taken in the event of a short circuit on the LV side of the
bias current is the highest phase current in any line end, giving a transformer. In this application, the tripping of the differential
secure through-fault stability even with heavily saturated CTs. protection can be time-delayed for low differential currents to
In addition to the restrained evaluation, an unrestrained achieve coordination with downstream overcurrent IEDs. The
(instantaneous) high differential current setting can be used for local protection of the small tap power transformer is given the
fast tripping of internal faults with very high currents. time needed to disconnect the faulty transformer.
22 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

A line charging current compensation provides increased


sensitivity of line differential protection.

windings. Both two- and three-winding transformers are


Line differential protection 3 or 6 CT sets, with in-zone correctly represented with vector group compensations made
transformers LT3CPDIF , LT6CPDIF
in the algorithm. The function includes 2nd and 5 th harmonic
Two two-winding power transformers or one three-winding
restraint and zero-sequence current elimination. The phase-
power transformer can be included in the line differential
segregated differential protection with single-pole tripping is
protection zone. In such application, the differential protection
usually not possible in such applications.
is based on the ampere turns balance between the transformer

Protected zone

IED Comm. Channel IED

Comm. Channel Comm. Channel

IED

IEC05000042_2_en.vsd
IEC05000042 V2 EN

Figure 8. Example of application on a three-terminal line with an in-line power transformer in the protection zone

master, and each one of the slave IEDs. The Master-Slave


Analog signal transfer for line differential protection condition for the differential function appears automatically
The line differential protection function can be arranged as a when the setting Operation for the differential function is set to
master-master system or a master-slave system alternatively. Off.
In the former, current samples are exchanged between all IEDs,
and an evaluation is made in each IED. This means that a 64
kbit/s communication channel is needed between every IED It is recommended to use the same firmware
included in the same line differential protection zone. In the version as well as hardware version for a
latter, current samples are sent from all slave IEDs to one specific line differential scheme.
master IED where the evaluation is made, and trip signals are
sent to the remote ends when needed. In this system, a 64
kbit/s communication channel is only needed between the

Protected zone

IED IED

Comm.
Channels

IED IED IED

IEC0500043_2_en.vsd
IEC05000043 V2 EN

Figure 9. Five terminal lines with master-master system

ABB 23
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Protected zone

RED RED
670 670

Comm.
Channels

RED RED RED


670 670 670

en05000044.vsd
IEC05000044 V1 EN

Figure 10. Five terminal line with master-slave system

Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an
each other, must be time coordinated so that the current automatic switchover to a standby link is possible after a preset
differential algorithm can be executed correctly, this is done time.
with the echo method.For applications where transmit and
receive times can differ, the optional built in GPS receivers can
be used

Low voltage criterion takes the phase voltages and phase-to-


Additional security logic for differential protection LDRGFC phase voltages as inputs. It increases the security of protection
Additional security logic for differential protection (LDRGFC) when the three-phase fault occurred on the weak end side.
can help the security of the protection especially when the
communication system is in abnormal status or for example Low current criterion takes the phase currents as inputs and it
when there is unspecified asymmetry in the communication link. increases the dependability during the switch onto fault case of
It helps to reduce the probability for mal-operation of the unloaded line.
protection. LDRGFC is more sensitive than the main protection
logic to always release operation for all faults detected by the The differential function can be allowed to trip as no load is fed
differential function. LDRGFC consists of four sub functions: through the line and protection is not working correctly.

• Phase-to-phase current variation Features:


• Zero sequence current criterion
• Startup element is sensitive enough to detect the
• Low voltage criterion
abnormal status of the protected system
• Low current criterion
• Startup element does not influence the operation speed of
Phase-to-phase current variation takes the current samples as main protection
input and it calculates the variation using the sampling value • Startup element would detect the evolving faults, high
based algorithm. Phase-to-phase current variation function is impedance faults and three phase fault on weak side
major one to fulfill the objectives of the startup element. • It is possible to block the each sub function of startup
element
Zero sequence criterion takes the zero sequence current as • Startup signal has a settable pulse time
input. It increases the security of protection during the high
impedance fault conditions.

4. Impedance protection gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and
Distance measuring zone, quadrilateral characteristic lengths.
ZMQPDIS, ZMQAPDIS
The line distance protection is an up to five (depending on ZMQPDIS together with Phase selection with load
product variant) zone full scheme protection function with three encroachment FDPSPDIS has functionality for load
fault loops for phase-to-phase faults and three fault loops for encroachment, which increases the possibility to detect high
phase-to-earth faults for each of the independent zones. resistive faults on heavily loaded lines, as shown in figure11.
Individual settings for each zone in resistive and reactive reach

24 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

X X

Forward Forward
operation operation

R R

Reverse Reverse
operation operation

en05000034.vsd en05000034.vsd
IEC05000034 V1 EN IEC05000034 V1 EN

Figure 11. Typical quadrilateral distance protection zone with Phase Figure 12. Typical quadrilateral distance protection zone with load
selection with load encroachment function FDPSPDIS encroachment function activated
activated

The independent measurement of impedance for each fault


The independent measurement of impedance for each fault loop together with a sensitive and reliable built in phase
loop together with a sensitive and reliable built-in phase selection makes the function suitable in applications with single
selection makes the function suitable in applications with phase auto-reclosing.
single-phase autoreclosing.
Built-in adaptive load compensation algorithm for the
Built-in adaptive load compensation algorithm prevents quadrilateral function prevents overreaching of zone1 at load
overreaching of zone 1 at load exporting end at phase-to-earth exporting end at phase to earth-faults on heavily loaded power
faults on heavily loaded power lines. lines.

The distance protection zones can operate independently of The distance protection zones can operate, independent of
each other in directional (forward or reverse) or non-directional each other, in directional (forward or reverse) or non-directional
mode. This makes them suitable, together with different mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and communication schemes, for the protection of power lines and
cables in complex network configurations, such as parallel cables in complex network configurations, such as parallel
lines, multi-terminal lines. lines, multi-terminal lines.

Distance measuring zone, quadrilateral characteristic for Phase selection, quadrilateral characteristic with fixed angle
series compensated lines ZMCPDIS, ZMCAPDIS FDPSPDIS
The line distance protection is a five three zone full scheme The operation of transmission networks today is in many cases
protection with three fault loops for phase-to-phase faults and close to the stability limit. Due to environmental considerations,
three fault loops for phase-to-earth fault for each of the the rate of expansion and reinforcement of the power system is
independent zones. Individual settings for each zone resistive reduced, for example, difficulties to get permission to build new
and reactive reach give flexibility for use on overhead lines and power lines. The ability to accurately and reliably classify the
cables of different types and lengths. different types of fault, so that single pole tripping and
autoreclosing can be used plays an important role in this
Quadrilateral characteristic is available.
matter. Phase selection, quadrilateral characteristic with fixed
ZMCPDIS function has functionality for load encroachment angle FDPSPDIS is designed to accurately select the proper
which increases the possibility to detect high resistive faults on fault loop in the distance function dependent on the fault type.
heavily loaded lines.
The heavy load transfer that is common in many transmission
networks may make fault resistance coverage difficult to
achieve. Therefore, FDPSPDIS has a built-in algorithm for load
encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring
zones without interfering with the load.
ABB 25
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

The extensive output signals from the phase selection gives mode (offset). This makes them suitable, together with different
also important information about faulty phase(s), which can be communication schemes, for the protection of power lines and
used for fault analysis. cables in complex network configurations, such as parallel
lines, multi-terminal lines and so on.
A current-based phase selection is also included. The
measuring elements continuously measure three phase The possibility to use the phase-to-earth quadrilateral
currents and the residual current and, compare them with the impedance characteristic together with the mho characteristic
set values. increases the possibility to overcome eventual lack of sensitivity
of the mho element due to the shaping of the curve at remote
Full-scheme distance measuring, Mho characteristic end faults.
ZMHPDIS
The numerical mho line distance protection is a four zone full The integrated control and monitoring functions offer effective
scheme protection for back-up detection of short circuit and solutions for operating and monitoring all types of transmission
earth faults. The numerical mho line distance protection is a and sub-transmission lines.
three zone full scheme protection for back-up detection of short
circuit and earth faults. Full-scheme distance protection, quadrilateral for earth faults
ZMMPDIS, ZMMAPDIS
The line distance protection is an up to five (depending on
The four zones have fully independent measuring and settings, product variant) zone full scheme protection function with three
which gives high flexibility for all types of lines. fault loops for phase-to-earth fault for each of the independent
zones. Individual settings for each zone resistive and reactive
The IED can be used up to the highest voltage levels. It is
reach give flexibility for use on overhead lines and cables of
suitable for the protection of heavily loaded lines and multi-
different types and lengths.
terminal lines where the requirement for tripping is one-, two-
and/or three-pole. The Full-scheme distance protection, quadrilateral for earth
fault functions have functionality for load encroachment, which
The independent measurement of impedance for each fault
increases the possibility to detect high resistive faults on heavily
loop together with a sensitive and reliable phase selection
loaded lines , see Figure 11.
makes the function suitable in applications with single phase
autoreclosing.
X
Built-in selectable zone timer logic is also provided in the
function.
Forward
Adaptive load compensation algorithm prevents overreaching operation
at phase-to-earth faults on heavily loaded power lines, see
Figure 13.

jX
R

Reverse
Operation area Operation area
operation

R
en05000034.vsd
Operation area IEC05000034 V1 EN

Figure 14. Typical quadrilateral distance protection zone with Phase


selection, quadrilateral characteristic with settable angle
No operation area No operation area
function FRPSPDIS activated

IEC07000117-2-en.vsd
IEC07000117 V2 EN
The independent measurement of impedance for each fault
Figure 13. Load encroachment influence on the offset mho
loop together with a sensitive and reliable built in phase
characteristic
selection makes the function suitable in applications with single
phase auto-reclosing.
The distance protection zones can operate, independent of
each other, in directional (forward or reverse) or non-directional
26 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

The distance protection zones can operate, independent of for load encroachment, which increases the possibility to
each other, in directional (forward or reverse) or non-directional detect high resistive faults on heavily loaded lines, as shown in
mode. This makes them suitable, together with different figure 11.
communication schemes, for the protection of power lines and
cables in complex network configurations, such as parallel
lines, multi-terminal lines. X

Directional impedance element for Mho characteristic Forward


ZDMRDIR operation
The phase-to-earth impedance elements can be optionally
supervised by a phase unselective directional function (phase
unselective, because it is based on symmetrical components).

Mho impedance supervision logic ZSMGAPC


The Mho impedance supervision logic (ZSMGAPC) includes R
features for fault inception detection and high SIR detection. It
also includes the functionality for loss of potential logic as well Reverse
as for the pilot channel blocking scheme. operation

ZSMGAPC can mainly be decomposed in two different parts:

1. A fault inception detection logic en05000034.vsd


2. High SIR detection logic IEC05000034 V1 EN

Figure 15. Typical quadrilateral distance protection zone with Phase


selection, quadrilateral characteristic with settable angle
Faulty phase identification with load encroachment FMPSPDIS
function FRPSPDIS activated
The ability to accurately and reliably classify different types of
fault so that single phase tripping and autoreclosing can be
used plays an important roll in today's power systems. The independent measurement of impedance for each fault
loop together with a sensitive and reliable built-in phase
The phase selection function is design to accurately select the
selection makes the function suitable in applications with single
proper fault loop(s) in the distance function dependent on the
pole tripping and autoreclosing.
fault type.
Built-in adaptive load compensation algorithm prevents
The heavy load transfer that is common in many transmission
overreaching of zone 1 at load exporting end at phase-to-earth
networks may in some cases interfere with the distance
faults on heavily loaded power lines.
protection zone reach and cause unwanted operation.
Therefore the function has a built in algorithm for load The distance protection zones can operate, independent of
encroachment, which gives the possibility to enlarge the each other, in directional (forward or reverse) or non-directional
resistive setting of the measuring zones without interfering with mode. This makes them suitable, together with different
the load. communication schemes, for the protection of power lines and
cables in complex network configurations, such as parallel
The output signals from the phase selection function produce
lines, multi-terminal lines and so on.
important information about faulty phase(s), which can be used
for fault analysis as well. Phase selection, quadrilateral characteristic with settable
angle FRPSPDIS
Distance protection zone, quadrilateral characteristic,
The operation of transmission networks today is in many cases
separate settings ZMRPDIS, ZMRAPDIS
close to the stability limit. Due to environmental considerations,
The line distance protection is up to five zone full scheme
the rate of expansion and reinforcement of the power system is
protection with three fault loops for phase-to-phase faults and
reduced for example, difficulties to get permission to build new
three fault loops for phase-to-earth fault for each of the
power lines. The ability to accurately and reliably classify the
independent zones. Individual settings for each zone in resistive
different types of fault, so that single pole tripping and
and reactive reach gives flexibility for use as back-up protection
autoreclosing can be used plays an important role in this
for transformer connected to overhead lines and cables of
matter. The phase selection function is designed to accurately
different types and lengths.
select the proper fault loop in the distance function dependent
Mho alternative quadrilateral characteristic is available. on the fault type.

ZMRPDIS together with Phase selection, quadrilateral The heavy load transfer that is common in many transmission
characteristic with settable angle FRPSPDIS has functionality networks may make fault resistance coverage difficult to

ABB 27
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

achieve. Therefore, the function has a built in algorithm for load can even be decided separate for the phase-to-ground or
encroachment, which gives the possibility to enlarge the phase-to-phase loops. The six zones can operate either
resistive setting of both the phase selection and the measuring independent of each other, or their start can be linked (per
zones without interfering with the load. zone) through the phase selector or the first starting zone. This
can provide fast operate times for evolving faults.
The extensive output signals from the phase selection gives
also important information about faulty phase(s) which can be The operation of the phase-selection is primarily based on a
used for fault analysis. current change criteria (i.e. delta quantities), however there is
also a phase selection criterion operating in parallel which
A current-based phase selection is also included. The bases its operation on voltage and current phasors exclusively.
measuring elements continuously measure three phase Additionally the directional element provides a fast and correct
currents and the residual current and, compare them with the directional decision under difficult operating conditions,
set values. including close-in three-phase faults, simultaneous faults and
faults with only zero-sequence in-feed.
High speed distance protection, quadrilateral and mho
ZMFPDIS During phase-to-earth faults on heavily loaded power lines
The high speed distance protection (ZMFPDIS) provides a sub- there is an adaptive load compensation algorithm that prevents
cycle, down towards a half-cycle operate time. Its six zone, full overreaching of the distance zones in the load exporting end,
scheme protection concept is entirely suitable in applications improving the selectivity of the function. This also reduces
with single-phase autoreclosing. underreach in the importing end.

Each measurement zone is designed with the flexibility to Power swing detection ZMRPSB
operate in either quadrilateral or mho characteristic mode. This Power swings may occur after disconnection of heavy loads or
can even be decided separate for the phase-to-ground or trip of big generation plants.
phase-to-phase loops. The six zones can operate either
independent of each other, or their start can be linked (per Power swing detection function ZMRPSB is used to detect
zone) through the phase selector or the first starting zone. This power swings and initiate block of all distance protection zones.
can provide fast operate times for evolving faults. Occurrence of earth-fault currents during a power swing
inhibits the ZMRPSB function, to allow fault clearance.
The operation of the phase-selection is primarily based on a
current change criteria (i.e. delta quantities), however there is Power swing logic PSLPSCH
also a phase selection criterion operating in parallel which Power Swing Logic (PSLPSCH) is a complementary function to
bases its operation on voltage and current phasors exclusively. Power Swing Detection (ZMRPSB) function. It provides
Additionally the directional element provides a fast and correct possibility for selective tripping of faults on power lines during
directional decision under difficult operating conditions, system oscillations (power swings or pole slips), when the
including close-in three-phase faults, simultaneous faults and distance protection function should normally be blocked. The
faults with only zero-sequence in-feed.During phase-to-earth complete logic consists of two different parts:
faults on heavily loaded power lines there is an adaptive load
compensation algorithm that prevents overreaching of the • Communication and tripping part: provides selective
distance zones in the load exporting end, improving the tripping on the basis of special distance protection zones
selectivity of the function. This also reduces underreach in the and a scheme communication logic, which are not
importing end. blocked during the system oscillations.
• Blocking part: blocks unwanted operation of
Distance zones quad with high speed distance for series instantaneous distance protection zone 1 for oscillations,
compensated networks ZMFCPDIS which are initiated by faults and their clearing on the
The high speed distance protection (ZMCPDIS) provides a sub- adjacent power lines and other primary elements.
cycle, down towards a half-cycle operate time. Its six zone, full
scheme protection concept is entirely suitable in applications
Pole slip protection PSPPPAM
with single-phase autoreclosing.
The situation with pole slip of a generator can be caused by
High speed distance protection ZMFCPDIS is fundamentally different reasons.
the same function as ZMFPDIS but provides more flexibility in
A short circuit may occur in the external power grid, close to the
zone settings to suit more complex applications, such as series
generator. If the fault clearing time is too long, the generator will
compensated lines. In operation for series compensated
accelerate so much, that the synchronism cannot be
networks, the parameters of the directional function are altered
maintained.
to handle voltage reversal.
Undamped oscillations occur in the power system, where
Each measurement zone is designed with the flexibility to
generator groups at different locations, oscillate against each
operate in either quadrilateral or mho characteristic mode. This
28 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

other. If the connection between the generators is too weak the phase, when each group is equipped with current transformers.
magnitude of the oscillations will increase until the angular The protection function performs a simple summation of the
stability is lost. currents of the two channels I3P1 and I3P2.

The operation of a generator having pole slip will give risk of Phase preference logic PPLPHIZ
damages to the generator, shaft and turbine. The optional phase preference logic main purpose is to provide
a selective tripping for cross-country faults in isolated or high
• At each pole slip there will be significant torque impact on impedance-earthed networks.
the generator-turbine shaft.
• In asynchronous operation there will be induction of Automatic switch onto fault logic, voltage and current based
currents in parts of the generator normally not carrying ZCVPSOF
current, thus resulting in increased heating. The Automatic switch onto fault logic (ZCVPSOF) is a function that
consequence can be damages on insulation and stator/ gives an instantaneous trip at closing of breaker onto a fault. A
rotor iron. dead line detection check is provided to activate the function
when the line is dead.
The Pole slip protection (PSPPPAM) function shall detect pole
slip conditions and trip the generator as fast as possible if the
locus of the measured impedance is inside the generator- 5. Current protection
transformer block. If the centre of pole slip is outside in the
Instantaneous phase overcurrent protection PHPIOC
power grid, the first action should be to split the network into
The instantaneous three phase overcurrent function has a low
two parts, after line protection action. If this fails there should be
transient overreach and short tripping time to allow use as a
operation of the generator PSPPPAM in zone 2, to prevent
high set short-circuit protection function.
further damages to the generator, shaft and turbine.
Four-step phase overcurrent protection OC4PTOC
Pole slip protection PSPPPAM
The four step three-phase overcurrent protection function
Sudden events in an electric power system such as large
OC4PTOC has an inverse or definite time delay independent for
changes in load, fault occurrence or fault clearance, can cause
step 1 to 4 separately.
power oscillations referred to as power swings. In a non-
recoverable situation, the power swings become so severe that All IEC and ANSI inverse time characteristics are available
the synchronism is lost, a condition referred to as pole slipping. together with an optional user defined time characteristic.
The main purpose of the pole slip protection (PSPPPAM) is to
detect, evaluate, and take the required action for pole slipping The directional function needs voltage as it is voltage polarized
occurrences in the power system. with memory. The function can be set to be directional or non-
directional independently for each of the steps.
Out-of-step protection OOSPPAM
The out-of-step protection OOSPPAM function in the IED can A second harmonic blocking level can be set for the function
be used for both generator protection and as well for line and can be used to block each step individually.
protection applications.
Instantaneous residual overcurrent protection EFPIOC
The main purpose of the OOSPPAM function is to detect, The Instantaneous residual overcurrent protection EFPIOC has
evaluate, and take the required action during pole slipping a low transient overreach and short tripping times to allow the
occurrences in the power system. use for instantaneous earth-fault protection, with the reach
limited to less than the typical eighty percent of the line at
The OOSPPAM function detects pole slip conditions and trips minimum source impedance. EFPIOC is configured to measure
the generator as fast as possible, after the first pole-slip if the the residual current from the three-phase current inputs and
center of oscillation is found to be in zone 1, which normally can be configured to measure the current from a separate
includes the generator and its step-up power transformer. If the current input.
center of oscillation is found to be further out in the power
system, in zone 2, more than one pole-slip is usually allowed Four step residual overcurrent protection, zero sequence and
before the generator-transformer unit is disconnected. A negative sequence direction EF4PTOC
parameter setting is available to take into account the circuit The four step residual overcurrent protection EF4PTOC has an
breaker opening time. If there are several out-of-step relays in inverse or definite time delay independent for each step.
the power system, then the one which finds the center of
oscillation in its zone 1 should operate first. All IEC and ANSI time-delayed characteristics are available
together with an optional user defined characteristic.
Two current channels I3P1 and I3P2 are available in OOSPPAM
function to allow the direct connection of two groups of three- EF4PTOC can be set directional or non-directional
phase currents; that may be needed for very powerful independently for each of the steps.
generators, with stator windings split into two groups per
ABB 29
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

IDir, UPol and IPol can be independently selected to be either There is also available one nondirectional 3I0 step and one 3U0
zero sequence or negative sequence. overvoltage tripping step.

Second harmonic blocking can be set individually for each step. No specific sensitive current input is needed. SDEPSDE can be
set as low 0.25% of IBase.
EF4PTOC can be used as main protection for phase-to-earth
faults. Thermal overload protection, one time constant LCPTTR/
LFPTTR
EF4PTOC can also be used to provide a system back-up for The increasing utilization of the power system closer to the
example, in the case of the primary protection being out of thermal limits has generated a need of a thermal overload
service due to communication or voltage transformer circuit protection for power lines.
failure.
A thermal overload will often not be detected by other
Directional operation can be combined together with protection functions and the introduction of the thermal
corresponding communication logic in permissive or blocking overload protection can allow the protected circuit to operate
teleprotection scheme. Current reversal and weak-end infeed closer to the thermal limits.
functionality are available as well.
The three-phase current measuring protection has an I2 t
Residual current can be calculated by summing the three phase
characteristic with settable time constant and a thermal
currents or taking the input from neutral CT
memory. The temperature is displayed in either Celsius or
Four step negative sequence overcurrent protection Fahrenheit, depending on whether the function used is LCPTTR
NS4PTOC (Celsius) or LFPTTR (Fahrenheit).
Four step negative sequence overcurrent protection
An alarm level gives early warning to allow operators to take
(NS4PTOC) has an inverse or definite time delay independent
action well before the line is tripped.
for each step separately.
Estimated time to trip before operation, and estimated time to
All IEC and ANSI time delayed characteristics are available
reclose after operation are presented.
together with an optional user defined characteristic.
Breaker failure protection CCRBRF
The directional function is voltage polarized.
Breaker failure protection (CCRBRF) ensures a fast backup
tripping of the surrounding breakers in case the own breaker
NS4PTOC can be set directional or non-directional
fails to open. CCRBRF can be current-based, contact-based or
independently for each of the steps.
an adaptive combination of these two conditions.
NS4PTOC can be used as main protection for unsymmetrical
A current check with extremely short reset time is used as
fault; phase-phase short circuits, phase-phase-earth short
check criterion to achieve high security against inadvertent
circuits and single phase earth faults.
operation.
NS4PTOC can also be used to provide a system backup for
Contact check criteria can be used where the fault current
example, in the case of the primary protection being out of
through the breaker is small.
service due to communication or voltage transformer circuit
failure.
CCRBRF can be single- or three-phase initiated to allow use
with single phase tripping applications. For the three-phase
Directional operation can be combined together with
version of CCRBRF the current criteria can be set to operate
corresponding communication logic in permissive or blocking
only if two out of four for example, two phases or one phase
teleprotection scheme. The same logic as for directional zero
plus the residual current start. This gives a higher security to the
sequence current can be used. Current reversal and weak-end
back-up trip command.
infeed functionality are available.

Sensitive directional residual overcurrent and power CCRBRF function can be programmed to give a single- or
protection SDEPSDE three-phase re-trip of its own breaker to avoid unnecessary
tripping of surrounding breakers at an incorrect initiation due to
In isolated networks or in networks with high impedance
mistakes during testing.
earthing, the earth fault current is significantly smaller than the
short circuit currents. In addition to this, the magnitude of the Stub protection STBPTOC
fault current is almost independent on the fault location in the
When a power line is taken out of service for maintenance and
network. The protection can be selected to use either the
the line disconnector is opened in multi-breaker arrangements
residual current or residual power component 3U0·3I0·cos j,
the voltage transformers will mostly be outside on the
for operating quantity with maintained short circuit capacity.
disconnected part. The primary line distance protection will
thus not be able to operate and must be blocked.
30 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

The stub protection STBPTOC covers the zone between the 6. Voltage protection
current transformers and the open disconnector. The three-
phase instantaneous overcurrent function is released from a Two step undervoltage protection UV2PTUV
normally open, NO (b) auxiliary contact on the line Undervoltages can occur in the power system during faults or
disconnector. abnormal conditions. Two step undervoltage protection
(UV2PTUV) function can be used to open circuit breakers to
Pole discordance protection CCPDSC prepare for system restoration at power outages or as long-
An open phase can cause negative and zero sequence currents time delayed back-up to primary protection.
which cause thermal stress on rotating machines and can
cause unwanted operation of zero sequence or negative UV2PTUV has two voltage steps, each with inverse or definite
sequence current functions. time delay.

Normally the own breaker is tripped to correct such a situation. UV2PTUV has a high reset ratio to allow settings close to
If the situation persists the surrounding breakers should be system service voltage.
tripped to clear the unsymmetrical load situation.
Two step overvoltage protection OV2PTOV
The Pole discordance protection function CCPDSC operates Overvoltages may occur in the power system during abnormal
based on information from auxiliary contacts of the circuit conditions such as sudden power loss, tap changer regulating
breaker for the three phases with additional criteria from failures, and open line ends on long lines.
unsymmetrical phase currents when required.
Two step overvoltage protection (OV2PTOV) function can be
Directional over/underpower protection GOPPDOP/ used to detect open line ends, normally then combined with a
GUPPDUP directional reactive over-power function to supervise the
The directional over-/under-power protection GOPPDOP/ system voltage. When triggered, the function will cause an
GUPPDUP can be used wherever a high/low active, reactive or alarm, switch in reactors, or switch out capacitor banks.
apparent power protection or alarming is required. The
OV2PTOV has two voltage steps, each of them with inverse or
functions can alternatively be used to check the direction of
definite time delayed.
active or reactive power flow in the power system. There are a
number of applications where such functionality is needed. OV2PTOV has a high reset ratio to allow settings close to
Some of them are: system service voltage.

• detection of reversed active power flow Overexcitation protection OEXPVPH


• detection of high reactive power flow When the laminated core of a power transformer or generator is
subjected to a magnetic flux density beyond its design limits,
Each function has two steps with definite time delay.
stray flux will flow into non-laminated components that are not
Broken conductor check BRCPTOC designed to carry flux. This will cause eddy currents to flow.
The main purpose of the function Broken conductor check These eddy currents can cause excessive heating and severe
(BRCPTOC) is the detection of broken conductors on protected damage to insulation and adjacent parts in a relatively short
power lines and cables (series faults). Detection can be used to time. The function has settable inverse operating curves and
give alarm only or trip the line breaker. independent alarm stages.

Voltage-restrained time overcurrent protection VRPVOC Voltage differential protection VDCPTOV


Voltage-restrained time overcurrent protection (VRPVOC) A voltage differential monitoring function is available. It
function can be used as generator backup protection against compares the voltages from two three phase sets of voltage
short-circuits. transformers and has one sensitive alarm step and one trip
step.
The overcurrent protection feature has a settable current level
that can be used either with definite time or inverse time Loss of voltage check LOVPTUV
characteristic. Additionally, it can be voltage controlled/ Loss of voltage check LOVPTUV is suitable for use in networks
restrained. with an automatic system restoration function. LOVPTUV
issues a three-pole trip command to the circuit breaker, if all
One undervoltage step with definite time characteristic is also three phase voltages fall below the set value for a time longer
available within the function in order to provide functionality for than the set time and the circuit breaker remains closed.
overcurrent protection with undervoltage seal-in.
The operation of LOVPTUV is supervised by the fuse failure
supervision FUFSPVC.

ABB 31
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Radial feeder protection PAPGAPC Overfrequency protection SAPTOF


The PAPGAPC function is used to provide protection of radial Overfrequency protection function SAPTOF is applicable in all
feeders having passive loads or weak end in-feed sources. It is situations, where reliable detection of high fundamental power
possible to achieve fast tripping using communication system system frequency is needed.
with remote end or delayed tripping not requiring
communication or upon communication system failure. For fast Overfrequency occurs because of sudden load drops or shunt
tripping, scheme communication is required. Delayed tripping faults in the power network. Close to the generating plant,
does not require scheme communication. generator governor problems can also cause over frequency.

The PAPGAPC function performs phase selection using SAPTOF measures frequency with high accuracy, and is used
measured voltages. Each phase voltage is compared to the mainly for generation shedding and remedial action schemes. It
opposite phase-phase voltage. A phase is deemed to have a is also used as a frequency stage initiating load restoring. A
fault if its phase voltage drops below a settable percentage of definite time delay is provided for operate.
the opposite phase-phase voltage. The phase - phase voltages
SAPTOF is provided with an undervoltage blocking.
include memory. This memory function has a settable time
constant. The operation is based on positive sequence voltage
measurement and requires two phase-phase or three phase-
The voltage-based phase selection is used for both fast and
neutral voltages to be connected. For information about how to
delayed tripping. To achieve fast tripping, scheme
connect analog inputs, refer to Application manual/IED
communication is required. Delayed tripping does not require
application/Analog inputs/Setting guidelines
scheme communication. It is possible to permit delayed
tripping only upon failure of the communications channel by Rate-of-change frequency protection SAPFRC
blocking the delayed tripping logic with a communications The rate-of-change frequency protection function SAPFRC
channel healthy input signal. gives an early indication of a main disturbance in the system.
SAPFRC measures frequency with high accuracy, and can be
On receipt of the communications signal, phase selective
used for generation shedding, load shedding and remedial
outputs for fast tripping are set based on the phase(s) in which
action schemes. SAPFRC can discriminate between a positive
the phase selection function has operated.
or negative change of frequency. A definite time delay is
For delayed tripping, single pole and three pole delays are provided for operate.
separately and independently settable. Furthermore, it is
SAPFRC is provided with an undervoltage blocking. The
possible to enable or disable single pole and three pole delayed
operation is based on positive sequence voltage measurement
tripping. For single phase faults, it is possible to include a
and requires two phase-phase or three phase-neutral voltages
residual current check in the tripping logic. Three pole tripping
to be connected. For information about how to connect analog
is always selected for phase selection on more than one phase.
inputs, refer to Application manual/IED application/Analog
Three pole tripping will also occur if the residual current
inputs/Setting guidelines.
exceeds the set level during fuse failure for a time longer than
the three pole trip delay time.
8. Multipurpose protection

7. Frequency protection General current and voltage protection CVGAPC


The General current and voltage protection (CVGAPC) can be
Underfrequency protection SAPTUF
utilized as a negative sequence current protection detecting
Underfrequency occurs as a result of a lack of generation in the
unsymmetrical conditions such as open phase or
network.
unsymmetrical faults.
Underfrequency protection SAPTUF measures frequency with
CVGAPC can also be used to improve phase selection for high
high accuracy, and is used for load shedding systems, remedial
resistive earth faults, outside the distance protection reach, for
action schemes, gas turbine startup and so on. Separate
the transmission line. Three functions are used, which
definite time delays are provided for operate and restore.
measures the neutral current and each of the three phase
SAPTUF is provided with undervoltage blocking. voltages. This will give an independence from load currents and
this phase selection will be used in conjunction with the
The operation is based on positive sequence voltage detection of the earth fault from the directional earth fault
measurement and requires two phase-phase or three phase- protection function.
neutral voltages to be connected. For information about how to
connect analog inputs, refer to Application manual/IED
application/Analog inputs/Setting guidelines

32 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

practice is more associated with voltage transformer switching


Voltage-restrained time overcurrent protection VRPVOC during station operations.
Voltage-restrained time overcurrent protection (VRPVOC)
function can be used as generator backup protection against Fuse failure supervision VDSPVC
short-circuits. Different protection functions within the protection IED
operates on the basis of measured voltage at the relay point.
The overcurrent protection feature has a settable current level Some example of protection functions are:
that can be used either with definite time or inverse time
characteristic. Additionally, it can be voltage controlled/ • Distance protection function.
restrained. • Undervoltage function.
• Energisation function and voltage check for the weak
One undervoltage step with definite time characteristic is also infeed logic.
available within the function in order to provide functionality for
overcurrent protection with undervoltage seal-in. These functions can operate unintentionally, if a fault occurs in
the secondary circuits between voltage instrument
transformers and the IED. These unintentional operations can
9. Secondary system supervision
be prevented by VDSPVC.
Current circuit supervision CCSSPVC
VDSPVC is designed to detect fuse failures or faults in voltage
Open or short circuited current transformer cores can cause
measurement circuit, based on phase wise comparison of
unwanted operation of many protection functions such as
voltages of main and pilot fused circuits. VDSPVC blocking
differential, earth-fault current and negative-sequence current
output can be configured to block functions that need to be
functions.
blocked in case of faults in the voltage circuit.
Current circuit supervision (CCSSPVC) compares the residual
Multipurpose filter SMAIHPAC
current from a three phase set of current transformer cores with
The multi-purpose filter function block, SMAIHPAC, is arranged
the neutral point current on a separate input taken from another
as a three-phase filter. It has very much the same user interface
set of cores on the current transformer.
(e.g. inputs and outputs) as the standard pre-processing
A detection of a difference indicates a fault in the circuit and is function block SMAI. However the main difference is that it can
used as alarm or to block protection functions expected to give be used to extract any frequency component from the input
inadvertent tripping. signal. Thus it can, for example, be used to build sub-
synchronous resonance protection for synchronous generator.
Fuse failure supervision FUFSPVC
The aim of the fuse failure supervision function FUFSPVC is to
10. Control
block voltage measuring functions at failures in the secondary
circuits between the voltage transformer and the IED in order to Synchrocheck, energizing check, and synchronizing SESRSYN
avoid inadvertent operations that otherwise might occur. The Synchronizing function allows closing of asynchronous
networks at the correct moment including the breaker closing
The fuse failure supervision function basically has three different
time, which improves the network stability.
detection methods, negative sequence and zero sequence
based detection and an additional delta voltage and delta Synchrocheck, energizing check, and synchronizing SESRSYN
current detection. function checks that the voltages on both sides of the circuit
breaker are in synchronism, or with at least one side dead to
The negative sequence detection algorithm is recommended
ensure that closing can be done safely.
for IEDs used in isolated or high-impedance earthed networks.
It is based on the negative-sequence quantities. SESRSYN function includes a built-in voltage selection scheme
for double bus and 1½ breaker or ring busbar arrangements.
The zero sequence detection is recommended for IEDs used in
directly or low impedance earthed networks. It is based on the Manual closing as well as automatic reclosing can be checked
zero sequence measuring quantities. by the function and can have different settings.
The selection of different operation modes is possible by a For systems, which are running asynchronous, a synchronizing
setting parameter in order to take into account the particular function is provided. The main purpose of the synchronizing
earthing of the network. function is to provide controlled closing of circuit breakers when
two asynchronous systems are going to be connected. The
A criterion based on delta current and delta voltage
synchronizing function evaluates voltage difference, phase
measurements can be added to the fuse failure supervision
angle difference, slip frequency and frequency rate of change
function in order to detect a three phase fuse failure, which in
before issuing a controlled closing of the circuit breaker.
Breaker closing time is a parameter setting.
ABB 33
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Autorecloser SMBRREC Interlocking


The autorecloser SMBRREC function provides high-speed The interlocking function blocks the possibility to operate
and/or delayed auto-reclosing for single or multi-breaker primary switching devices, for instance when a disconnector is
applications. under load, in order to prevent material damage and/or
accidental human injury.
Up to five three-phase reclosing attempts can be included by
parameter setting. The first attempt can be single-, two and/or Each apparatus control function has interlocking modules
three phase for single phase or multi-phase faults respectively. included for different switchyard arrangements, where each
function handles interlocking of one bay. The interlocking
Multiple autoreclosing functions are provided for multi-breaker function is distributed to each IED and is not dependent on any
arrangements. A priority circuit allows one circuit breaker to central function. For the station-wide interlocking, the IEDs
close first and the second will only close if the fault proved to be communicate via the system-wide interbay bus (IEC
transient. 61850-8-1) or by using hard wired binary inputs/outputs. The
interlocking conditions depend on the circuit configuration and
Each autoreclosing function is configured to co-operate with
apparatus position status at any given time.
the synchrocheck function.
For easy and safe implementation of the interlocking function,
The autoreclosing function provides high-speed and/or delayed
the IED is delivered with standardized and tested software
three pole autoreclosing.
interlocking modules containing logic for the interlocking
Apparatus control APC conditions. The interlocking conditions can be altered, to meet
The apparatus control functions are used for control and the customer’s specific requirements, by adding configurable
supervision of circuit breakers, disconnectors and earthing logic by means of the graphical configuration tool.
switches within a bay. Permission to operate is given after
Switch controller SCSWI
evaluation of conditions from other functions such as
The Switch controller (SCSWI) initializes and supervises all
interlocking, synchrocheck, operator place selection and
functions to properly select and operate switching primary
external or internal blockings.
apparatuses. The Switch controller may handle and operate on
Apparatus control features: one three-phase device or up to three one-phase devices.
• Select-Execute principle to give high reliability
Circuit breaker SXCBR
• Selection function to prevent simultaneous operation
The purpose of Circuit breaker (SXCBR) is to provide the actual
• Selection and supervision of operator place
status of positions and to perform the control operations, that
• Command supervision
is, pass all the commands to primary apparatuses in the form of
• Block/deblock of operation
circuit breakers via binary output boards and to supervise the
• Block/deblock of updating of position indications
switching operation and position.
• Substitution of position and quality indications
• Overriding of interlocking functions Circuit switch SXSWI
• Overriding of synchrocheck The purpose of Circuit switch (SXSWI) function is to provide the
• Operation counter actual status of positions and to perform the control operations,
• Suppression of mid position that is, pass all the commands to primary apparatuses in the
form of disconnectors or earthing switches via binary output
Two types of command models can be used: boards and to supervise the switching operation and position.
• Direct with normal security
Reservation function QCRSV
• SBO (Select-Before-Operate) with enhanced security
The purpose of the reservation function is primarily to transfer
interlocking information between IEDs in a safe way and to
Normal security means that only the command is evaluated and prevent double operation in a bay, switchyard part, or complete
the resulting position is not supervised. Enhanced security substation.
means that the command is evaluated with an additional
supervision of the status value of the control object. The Reservation input RESIN
command sequence with enhanced security is always The Reservation input (RESIN) function receives the reservation
terminated by a CommandTermination service primitive and an information from other bays. The number of instances is the
AddCause telling if the command was successful or if same as the number of involved bays (up to 60 instances are
something went wrong. available).

Control operation can be performed from the local HMI with Bay control QCBAY
authority control if so defined. The Bay control QCBAY function is used together with Local
remote and local remote control functions to handle the
34 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

selection of the operator place per bay. QCBAY also provides same role as functions GOOSEBINRCV (for IEC 61850) and
blocking functions that can be distributed to different MULTICMDRCV (for LON).
apparatuses within the bay.
Single command, 16 signals
Local remote LOCREM/Local remote control LOCREMCTRL The IEDs can receive commands either from a substation
The signals from the local HMI or from an external local/remote automation system or from the local HMI. The command
switch are connected via the function blocks LOCREM and function block has outputs that can be used, for example, to
LOCREMCTRL to the Bay control QCBAY function block. The control high voltage apparatuses or for other user defined
parameter ControlMode in function block LOCREM is set to functionality.
choose if the switch signals are coming from the local HMI or
from an external hardware switch connected via binary inputs.
11. Scheme communication
Logic rotating switch for function selection and LHMI
Scheme communication logic for distance or overcurrent
presentation SLGAPC
protection ZCPSCH
The logic rotating switch for function selection and LHMI
To achieve instantaneous fault clearance for all line faults,
presentation SLGAPC (or the selector switch function block) is
scheme communication logic is provided. All types of
used to get an enhanced selector switch functionality
communication schemes for permissive underreaching,
compared to the one provided by a hardware selector switch.
permissive overreaching, blocking, delta based blocking,
Hardware selector switches are used extensively by utilities, in
unblocking and intertrip are available.
order to have different functions operating on pre-set values.
Hardware switches are however sources for maintenance The built-in communication module (LDCM) can be used for
issues, lower system reliability and an extended purchase scheme communication signaling when included.
portfolio. The selector switch function eliminates all these
problems. Phase segregated scheme communication logic for distance
protection ZC1PPSCH
Selector mini switch VSGAPC Communication between line ends is used to achieve fault
The Selector mini switch VSGAPC function block is a clearance for all faults on a power line. All possible types of
multipurpose function used for a variety of applications, as a communication schemes for example, permissive underreach,
general purpose switch. permissive overreach and blocking schemes are available. To
manage problems with simultaneous faults on parallel power
VSGAPC can be controlled from the menu or from a symbol on
lines phase segregated communication is needed. This will then
the single line diagram (SLD) on the local HMI.
replace the standard Scheme communication logic for distance
Generic communication function for Double Point indication or Overcurrent protection (ZCPSCH) on important lines where
DPGAPC three communication channels (in each subsystem) are
Generic communication function for Double Point indication available for the distance protection communication.
DPGAPC function block is used to send double indications to
The main purpose of the Phase segregated scheme
other systems, equipment or functions in the substation
communication logic for distance protection (ZC1PPSCH)
through IEC 61850-8-1 or other communication protocols. It is
function is to supplement the distance protection function such
especially used in the interlocking station-wide logics.
that:
Single point generic control 8 signals SPC8GAPC
• fast clearance of faults is also achieved at the line end for
The Single point generic control 8 signals SPC8GAPC function
which the faults are on the part of the line not covered by
block is a collection of 8 single point commands, designed to
its underreaching zone.
bring in commands from REMOTE (SCADA) to those parts of
• correct phase selection can be maintained to support
the logic configuration that do not need extensive command
single-pole tripping for faults occurring anywhere on the
receiving functionality (for example, SCSWI). In this way, simple
entire length of a double circuit line.
commands can be sent directly to the IED outputs, without
confirmation. Confirmation (status) of the result of the To accomplish this, three separate communication channels,
commands is supposed to be achieved by other means, such that is, one per phase, each capable of transmitting a signal in
as binary inputs and SPGAPC function blocks. The commands each direction is required.
can be pulsed or steady with a settable pulse time.
ZC1PPSCH can be completed with the current reversal and
AutomationBits, command function for DNP3.0 AUTOBITS WEI logic for phase segregated communication, when found
AutomationBits function for DNP3 (AUTOBITS) is used within necessary in Blocking and Permissive overreaching schemes.
PCM600 to get into the configuration of the commands coming
through the DNP3 protocol. The AUTOBITS function plays the

ABB 35
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

In the directional scheme, information of the fault current


Current reversal and weak-end infeed logic for distance direction must be transmitted to the other line end. With
protection ZCRWPSCH directional comparison, a short operate time of the protection
The ZCRWPSCH function provides the current reversal and including a channel transmission time, can be achieved. This
weak end infeed logic functions that supplement the standard short operate time enables rapid autoreclosing function after
scheme communication logic. It is not suitable for standalone the fault clearance.
use as it requires inputs from the distance protection functions
and the scheme communications function included within the The communication logic module for directional residual current
terminal. protection enables blocking as well as permissive under/
overreaching, and unblocking schemes. The logic can also be
On detection of a current reversal, the current reversal logic supported by additional logic for weak-end infeed and current
provides an output to block the sending of the teleprotection reversal, included in Current reversal and weak-end infeed logic
signal to the remote end, and to block the permissive tripping at for residual overcurrent protection ECRWPSCH function.
the local end. This blocking condition is maintained long
enough to ensure that no unwanted operation will occur as a Current reversal and weak-end infeed logic for residual
result of the current reversal. overcurrent protection ECRWPSCH
The Current reversal and weak-end infeed logic for residual
On verification of a weak end infeed condition, the weak end overcurrent protection ECRWPSCH is a supplement to Scheme
infeed logic provides an output for sending the received communication logic for residual overcurrent protection
teleprotection signal back to the remote sending end and other ECPSCH.
output(s) for local tripping. For terminals equipped for single-
and two-pole tripping, outputs for the faulted phase(s) are To achieve fast fault clearing for all earth faults on the line, the
provided. Undervoltage detectors are used to detect the faulted directional earth fault protection function can be supported with
phase(s). logic that uses tele-protection channels.

Current reversal and weak-end infeed logic for phase This is why the IEDs have available additions to the scheme
segregated communication ZC1WPSCH communication logic.
Current reversal and weak-end infeed logic for phase
segregated communication (ZC1WPSCH) function is used to If parallel lines are connected to common busbars at both
prevent unwanted operations due to current reversal when terminals, overreaching permissive communication schemes
using permissive overreach protection schemes in application can trip unselectively due to fault current reversal. This
with parallel lines where the overreach from the two ends unwanted tripping affects the healthy line when a fault is cleared
overlaps on the parallel line. on the other line. This lack of security can result in a total loss of
interconnection between the two buses. To avoid this type of
The weak-end infeed logic is used in cases where the apparent disturbance, a fault current reversal logic (transient blocking
power behind the protection can be too low to activate the logic) can be used.
distance protection function. When activated, received carrier
signal together with local undervoltage criteria and no reverse Permissive communication schemes for residual overcurrent
zone operation gives an instantaneous trip. The received signal protection can basically operate only when the protection in the
is also echoed back to accelerate the sending end. remote IED can detect the fault. The detection requires a
sufficient minimum residual fault current, out from this IED. The
Local acceleration logic ZCLCPSCH fault current can be too low due to an opened breaker or high-
To achieve fast clearing of faults on the whole line, when no positive and/or zero-sequence source impedance behind this
communication channel is available, local acceleration logic IED. To overcome these conditions, weak-end infeed (WEI)
ZCLCPSCH can be used. This logic enables fast fault clearing echo logic is used. The weak-end infeed echo is limited to 200
and re-closing during certain conditions, but naturally, it can not ms to avoid channel lockup.
fully replace a communication channel.
Direct transfer trip DTT
The logic can be controlled either by the autorecloser (zone Low active power and power factor protection LAPPGAPC
extension) or by the loss-of-load current (loss-of-load
acceleration). Low active power and power factor protection (LAPPGAPC)
function measures power flow. It can be used for protection and
Scheme communication logic for residual overcurrent monitoring of:
protection ECPSCH
To achieve fast fault clearance of earth faults on the part of the • phase wise low active power
line not covered by the instantaneous step of the residual • phase wise low power factor
overcurrent protection, the directional residual overcurrent • phase wise reactive power and apparent power as service
protection can be supported with a logic that uses values
communication channels.
36 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Following features are available: Zero sequence overcurrent protection LCZSPTOC


Zero sequence components are present in all abnormal
• Definite time stage for low active power protection conditions involving earth. They have a considerably high value
• Definite time stage for low power factor protection during earth faults.
• Individual enabling of Low active power and Low power
factor functions Three phase overcurrent LCP3PTOC
• Low active power trip with 2 selection modes '1 out of 3' Three phase overcurrent (LCP3PTOC) is designed for
and '2 out of 3' overcurrent conditions.
• Phase wise calculated values of apparent power, reactive
power, active power and power factor are available as Features:
service values
• Phase wise start and trip signals
• Insensitive to small variations in voltage and current
• Overcurrent protection
Compensated over and undervoltage protection COUVGAPC • Phase wise RMS current is available as service values
Compensated over and undervoltage protection (COUVGAPC) • Single definite time stage trip function.
function calculates the remote end voltage of the transmission
Three phase undercurrent LCPCPTUC
line utilizing local measured voltage, current and with the help of
Three phase undercurrent function (LCP3PTUC) is designed for
transmission line parameters, that is, line resistance, reactance,
detecting loss of load conditions.
capacitance and local shunt reactor. For protection of long
transmission line for in zone faults, COUVGAPCcan be Features:
incorporated with local criteria within direct transfer trip logic to
ensure tripping of the line only under abnormal conditions. • Phase wise start and trip signals
• Phase wise RMS current is available as service values
Sudden change in current variation SCCVPTOC • Single definite time stage trip function
Sudden change in current variation (SCCVPTOC) function is a
fast way of finding any abnormality in line currents. When there
is a fault in the system, the current changes faster than the
12. Logic
voltage. SCCVPTOC finds abnormal condition based on phase-
to-phase current variation. The main application is as a local Tripping logic SMPPTRC
criterion to increase security when transfer trips are used. A function block for protection tripping is always provided as
basic for each circuit breaker involved in the tripping of the fault.
Carrier receive logic LCCRPTRC
It provides a settable pulse prolongation to ensure a trip pulse
In Direct transfer trip (DTT) scheme, the received CR signal
of sufficient length, as well as all functionality necessary for
gives the trip to the circuit breaker after checking certain local
correct co-operation with autoreclosing functions.
criteria functions in order to increase the security of the overall
tripping functionality. Carrier receive logic (LCCRPTRC) The trip function block also includes a settable latch
function gives final trip output of the DTT scheme. functionality for evolving faults and breaker lock-out.

Features: Trip matrix logic TMAGAPC


The trip matrix logic TMAGAPC function is used to route trip
• Carrier redundancy to ensure security in DTT scheme
signals and other logical output signals to different output
• Blocking function output on CR Channel Error
contacts on the IED.
• Phase wise trip outputs
The trip matrix logic function has 3 output signals and these
Negative sequence overvoltage protection LCNSPTOV
outputs can be connected to physical tripping outputs
Negative sequence components are present in all types of fault
according to the specific application needs for settable pulse or
condition. Negative sequence voltage and current get high
steady output.
values during unsymmetrical faults.

Zero sequence overvoltage protection LCZSPTOV


Zero sequence components are present in all abnormal
conditions involving earth. They can reach considerably high
values during earth faults.

Negative sequence overcurrent protection LCNSPTOC


Negative sequence components are present in all types of fault
condition. They can reach considerably high values during
abnormal operation.

ABB 37
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

• TIMERSET function has pick-up and drop-out delayed


Group alarm logic function ALMCALH outputs related to the input signal. The timer has a settable
The group alarm logic function ALMCALH is used to route time delay.
several alarm signals to a common indication, LED and/or
contact, in the IED. • XOR function block. Each block has two outputs where one is
inverted.
Group warning logic function WRNCALH
The group warning logic function WRNCALH is used to route
several warning signals to a common indication, LED and/or Extension logic package
contact, in the IED. The logic extension block package includes additional trip
matrix logic and configurable logic blocks.
Group indication logic function INDCALH
The group indication logic function INDCALH is used to route Logic rotating switch for function selection and LHMI
several indication signals to a common indication, LED and/or presentation SLGAPC
contact, in the IED. The logic rotating switch for function selection and LHMI
presentation SLGAPC (or the selector switch function block) is
Basic configurable logic blocks used to get an enhanced selector switch functionality
The basic configurable logic blocks do not propagate the time compared to the one provided by a hardware selector switch.
stamp and quality of signals (have no suffix QT at the end of Hardware selector switches are used extensively by utilities, in
their function name). A number of logic blocks and timers are order to have different functions operating on pre-set values.
always available as basic for the user to adapt the configuration Hardware switches are however sources for maintenance
to the specific application needs. The list below shows a issues, lower system reliability and an extended purchase
summary of the function blocks and their features. portfolio. The selector switch function eliminates all these
problems.
These logic blocks are also available as part of an extension
logic package with the same number of instances. Selector mini switch VSGAPC
The Selector mini switch VSGAPC function block is a
• AND function block. Each block has four inputs and two multipurpose function used for a variety of applications, as a
outputs where one is inverted. general purpose switch.
• GATE function block is used for whether or not a signal VSGAPC can be controlled from the menu or from a symbol on
should be able to pass from the input to the output. the single line diagram (SLD) on the local HMI.
• INVERTER function block that inverts one input signal to the Fixed signal function block
output. The Fixed signals function FXDSIGN generates nine pre-set
(fixed) signals that can be used in the configuration of an IED,
• LLD function block. Loop delay used to delay the output
either for forcing the unused inputs in other function blocks to a
signal one execution cycle.
certain level/value, or for creating certain logic. Boolean,
• OR function block. Each block has up to six inputs and two integer, floating point, string types of signals are available.
outputs where one is inverted.
One FXDSIGN function block is included in all IEDs.
• PULSETIMER function block can be used, for example, for
Elapsed time integrator with limit transgression and overflow
pulse extensions or limiting of operation of outputs, settable
supervision (TEIGAPC)
pulse time.
The Elapsed time integrator function TEIGAPC is a function that
• RSMEMORY function block is a flip-flop that can reset or set accumulates the elapsed time when a given binary signal has
an output from two inputs respectively. Each block has two been high.
outputs where one is inverted. The memory setting controls
The main features of TEIGAPC
if, after a power interruption, the flip-flop resets or returns to
the state it had before the power interruption. RESET input • Applicable to long time integration (≤999 999.9 seconds).
has priority. • Supervision of limit transgression conditions and overflow.
• Possibility to define a warning or alarm with the resolution
• SRMEMORY function block is a flip-flop that can set or reset
of 10 milliseconds.
an output from two inputs respectively. Each block has two
• Retaining of the integration value.
outputs where one is inverted. The memory setting controls
• Possibilities for blocking and reset.
if, after a power interruption, the flip-flop resets or returns to
• Reporting of the integrated time.
the state it had before the power interruption. The SET input
has priority.

38 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

• positive, negative and zero sequence currents and


Boolean 16 to Integer conversion with logic node voltages
representation BTIGAPC • mA, input currents
Boolean 16 to integer conversion with logic node • pulse counters
representation function BTIGAPC is used to transform a set of
16 binary (logical) signals into an integer. The block input will
freeze the output at the last value. Supervision of mA input signals
The main purpose of the function is to measure and process
BTIGAPC can receive remote values via IEC 61850 depending signals from different measuring transducers. Many devices
on the operator position input (PSTO). used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current
Integer to Boolean 16 conversion IB16 values, usually in the range 4-20 mA or 0-20 mA.
Integer to boolean 16 conversion function IB16 is used to
transform an integer into a set of 16 binary (logical) signals. Alarm limits can be set and used as triggers, e.g. to generate
trip or alarm signals.
Integer to Boolean 16 conversion with logic node
representation ITBGAPC The function requires that the IED is equipped with the mA input
Integer to boolean conversion with logic node representation module.
function ITBGAPC is used to transform an integer which is
transmitted over IEC 61850 and received by the function to 16 Disturbance report DRPRDRE
binary coded (logic) output signals. Complete and reliable information about disturbances in the
primary and/or in the secondary system together with
ITBGAPC function can only receive remote values over IEC continuous event-logging is accomplished by the disturbance
61850 when the R/L (Remote/Local) push button on the front report functionality.
HMI, indicates that the control mode for the operator is in
position R (Remote i.e. the LED adjacent to R is lit ), and the Disturbance report DRPRDRE, always included in the IED,
corresponding signal is connected to the input PSTO ITBGAPC acquires sampled data of all selected analog input and binary
function block. The input BLOCK will freeze the output at the signals connected to the function block with a, maximum of 40
last received value and blocks new integer values to be received analog and 96 binary signals.
and converted to binary coded outputs.
The Disturbance report functionality is a common name for
Comparator for integer inputs INTCOMP several functions:
The function gives the possibility to monitor the level of integer
• Event list
values in the system relative to each other or to a fixed value. It
• Indications
is a basic arithmetic function that can be used for monitoring,
• Event recorder
supervision, interlocking and other logics.
• Trip value recorder
Comparator for real inputs REALCOMP • Disturbance recorder
The function gives the possibility to monitor the level of real • Fault locator
value signals in the system relative to each other or to a fixed
The Disturbance report function is characterized by great
value. It is a basic arithmetic function that can be used for
flexibility regarding configuration, starting conditions, recording
monitoring, supervision, interlocking and other logics.
times, and large storage capacity.

13. Monitoring A disturbance is defined as an activation of an input to the


AnRADR or BnRBDR function blocks, which are set to trigger
Measurements CVMMXN, CMMXU, VNMMXU, VMMXU, the disturbance recorder. All connected signals from start of
CMSQI, VMSQI pre-fault time to the end of post-fault time will be included in the
The measurement functions are used to get on-line information recording.
from the IED. These service values make it possible to display
on-line information on the local HMI and on the Substation Every disturbance report recording is saved in the IED in the
automation system about: standard Comtrade format as a reader file HDR, a configuration
file CFG, and a data file DAT. The same applies to all events,
• measured voltages, currents, frequency, active, reactive which are continuously saved in a ring-buffer. The local HMI is
and apparent power and power factor used to get information about the recordings. The disturbance
• measured analog values from merging units report files may be uploaded to PCM600 for further analysis
• primary phasors using the disturbance handling tool.

ABB 39
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Event list DRPRDRE Disturbance recorder DRPRDRE


Continuous event-logging is useful for monitoring the system The Disturbance recorder function supplies fast, complete and
from an overview perspective and is a complement to specific reliable information about disturbances in the power system. It
disturbance recorder functions. facilitates understanding system behavior and related primary
and secondary equipment during and after a disturbance.
The event list logs all binary input signals connected to the Recorded information is used for different purposes in the short
Disturbance recorder function. The list may contain up to 1000 perspective (for example corrective actions) and long
time-tagged events stored in a ring-buffer. perspective (for example functional analysis).

Indications DRPRDRE The Disturbance recorder acquires sampled data from selected
To get fast, condensed and reliable information about analog- and binary signals connected to the Disturbance
disturbances in the primary and/or in the secondary system it is recorder function (maximum 40 analog and 128 binary signals).
important to know, for example binary signals that have The binary signals available are the same as for the event
changed status during a disturbance. This information is used recorder function.
in the short perspective to get information via the local HMI in a
straightforward way. The function is characterized by great flexibility and is not
dependent on the operation of protection functions. It can
There are three LEDs on the local HMI (green, yellow and red), record disturbances not detected by protection functions. Up
which will display status information about the IED and the to ten seconds of data before the trigger instant can be saved in
Disturbance recorder function (triggered). the disturbance file.

The Indication list function shows all selected binary input The disturbance recorder information for up to 100
signals connected to the Disturbance recorder function that disturbances are saved in the IED and the local HMI is used to
have changed status during a disturbance. view the list of recordings.

Event recorder DRPRDRE Event function


Quick, complete and reliable information about disturbances in When using a Substation Automation system with LON or SPA
the primary and/or in the secondary system is vital, for example, communication, time-tagged events can be sent at change or
time-tagged events logged during disturbances. This cyclically from the IED to the station level. These events are
information is used for different purposes in the short term (for created from any available signal in the IED that is connected to
example corrective actions) and in the long term (for example the Event function (EVENT). The event function block is used for
functional analysis). LON and SPA communication.

The event recorder logs all selected binary input signals Analog and double indication values are also transferred
connected to the Disturbance recorder function. Each through EVENT function.
recording can contain up to 150 time-tagged events.
Generic communication function for Single Point indication
The event recorder information is available for the disturbances SPGAPC
locally in the IED. Generic communication function for Single Point indication
SPGAPC is used to send one single logical signal to other
The event recording information is an integrated part of the
systems or equipment in the substation.
disturbance record (Comtrade file).
Generic communication function for Measured Value MVGAPC
Trip value recorder DRPRDRE
Generic communication function for Measured Value MVGAPC
Information about the pre-fault and fault values for currents and
function is used to send the instantaneous value of an analog
voltages are vital for the disturbance evaluation.
signal to other systems or equipment in the substation. It can
The Trip value recorder calculates the values of all selected also be used inside the same IED, to attach a RANGE aspect to
analog input signals connected to the Disturbance recorder an analog value and to permit measurement supervision on that
function. The result is magnitude and phase angle before and value.
during the fault for each analog input signal.
Measured value expander block RANGE_XP
The trip value recorder information is available for the The current and voltage measurements functions (CVMMXN,
disturbances locally in the IED. CMMXU, VMMXU and VNMMXU), current and voltage
sequence measurement functions (CMSQI and VMSQI) and IEC
The trip value recorder information is an integrated part of the 61850 generic communication I/O functions (MVGAPC) are
disturbance record (Comtrade file). provided with measurement supervision functionality. All
measured values can be supervised with four settable limits:
low-low limit, low limit, high limit and high-high limit. The
40 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

measure value expander block (RANGE_XP) has been setting values for limits. The output for each limit is activated
introduced to enable translating the integer output signal from when the counted value reaches that limit.
the measuring functions to 5 binary signals: below low-low limit,
below low limit, normal, above high limit or above high-high Overflow indication is included for each up-counter.
limit. The output signals can be used as conditions in the
Running hour-meter (TEILGAPC)
configurable logic or for alarming purpose.
The Running hour-meter (TEILGAPC) function is a function that
Gas medium supervision SSIMG accumulates the elapsed time when a given binary signal has
Gas medium supervision SSIMG is used for monitoring the been high.
circuit breaker condition. Binary information based on the gas
The main features of TEILGAPC are:
pressure in the circuit breaker is used as input signals to the
function. In addition, the function generates alarms based on • Applicable to very long time accumulation (≤ 99999.9
received information. hours)
• Supervision of limit transgression conditions and rollover/
Liquid medium supervision SSIML
overflow
Liquid medium supervision SSIML is used for monitoring the
• Possibility to define a warning and alarm with the
circuit breaker condition. Binary information based on the oil
resolution of 0.1 hours
level in the circuit breaker is used as input signals to the
• Retain any saved accumulation value at a restart
function. In addition, the function generates alarms based on
• Possibilities for blocking and reset
received information.
• Possibility for manual addition of accumulated time
Breaker monitoring SSCBR • Reporting of the accumulated time
The breaker monitoring function SSCBR is used to monitor
different parameters of the breaker condition. The breaker
requires maintenance when the number of operations reaches 14. Metering
a predefined value. For a proper functioning of the circuit
breaker, it is essential to monitor the circuit breaker operation, Pulse-counter logic PCFCNT
spring charge indication or breaker wear, travel time, number of Pulse-counter logic (PCFCNT) function counts externally
operation cycles and estimate the accumulated energy during generated binary pulses, for instance pulses coming from an
arcing periods. external energy meter, for calculation of energy consumption
values. The pulses are captured by the binary input module and
then read by the PCFCNT function. A scaled service value is
Fault locator LMBRFLO available over the station bus. The special Binary input module
The accurate fault locator is an essential component to with enhanced pulse counting capabilities must be ordered to
minimize the outages after a persistent fault and/or to pin-point achieve this functionality.
a weak spot on the line.
Function for energy calculation and demand handling
The fault locator is an impedance measuring function giving the (ETPMMTR)
distance to the fault in km, miles or % of line length. The main Measurements function block (CVMMXN) can be used to
advantage is the high accuracy achieved by compensating for measure active as well as reactive power values. Function for
load current and for the mutual zero-sequence effect on double energy calculation and demand handling (ETPMMTR) uses
circuit lines. measured active and reactive power as input and calculates the
accumulated active and reactive energy pulses, in forward and
The compensation includes setting of the remote and local
reverse direction. Energy values can be read or generated as
sources and calculation of the distribution of fault currents from
pulses. Maximum demand power values are also calculated by
each side. This distribution of fault current, together with
the function. This function includes zero point clamping to
recorded load (pre-fault) currents, is used to exactly calculate
remove noise from the input signal. As output of this function:
the fault position. The fault can be recalculated with new source
periodic energy calculations, integration of energy values,
data at the actual fault to further increase the accuracy.
calculation of energy pulses, alarm signals for limit violation of
Especially on heavily loaded long lines, where the source energy values and maximum power demand, can be found.
voltage angles can be up to 35-40 degrees apart, the accuracy
The values of active and reactive energies are calculated from
can be still maintained with the advanced compensation
the input power values by integrating them over a selected time
included in fault locator.
tEnergy. The integration of active and reactive energy values will
Event counter with limit supervison L4UFCNT happen in both forward and reverse directions. These energy
The 30 limit counter L4UFCNT provides a settable counter with values are available as output signals and also as pulse outputs.
four independent limits where the number of positive and/or Integration of energy values can be controlled by inputs
negative flanks on the input signal are counted against the
ABB 41
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

(STARTACC and STOPACC) and EnaAcc setting and it can be 16. Basic IED functions
reset to initial values with RSTACC input.
Time synchronization
The maximum demand for active and reactive powers are The time synchronization function is used to select a common
calculated for the set time interval tEnergy and these values are source of absolute time for the synchronization of the IED when
updated every minute through output channels. The active and it is a part of a protection system. This makes it possible to
reactive maximum power demand values are calculated for compare events and disturbance data between all IEDs within a
both forward and reverse direction and these values can be station automation system and in between sub-stations. A
reset with RSTDMD input. common source shall be used for IED and merging unit when
IEC 61850-9-2LE process bus communication is used.

15. Human machine interface 17. Station communication

Local HMI Communication protocols


Each IED is provided with a communication interface, enabling
it to connect to one or many substation level systems or
equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus.

Available communication protocols are:

• IEC 61850-8-1 communication protocol


• IEC 61850-9-2LE communication protocol
• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol

Several protocols can be combined in the same IED.

IEC 61850-8-1 communication protocol


IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in PCM600.
The IED is equipped with single or double optical Ethernet rear
ports (order dependent) for IEC 61850-8-1 station bus
communication. The IEC 61850-8-1 communication is also
possible from the electrical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different
vendors to exchange information and simplifies system
engineering. IED-to-IED communication using GOOSE and
client-server communication over MMS are supported.
Disturbance recording file (COMTRADE) uploading can be done
IEC13000239-2-en.vsd
over MMS or FTP.
IEC13000239 V2 EN

Figure 16. Local human-machine interface IEC 61850-9-2LE communication protocol


Single optical Ethernet port communication standard IEC
61850-9-2LE for process bus is provided. IEC 61850-9-2LE
The LHMI of the IED contains the following elements: allows Non Conventional Instrument Transformers (NCIT) with
• Graphical display capable of showing a user defined single Merging Units (MU) or stand alone Meging Units to exchange
line diagram and provide an interface for controlling information with the IED and simplifies SA engineering.
switchgear.
• Navigation buttons and five user defined command buttons LON communication protocol
to shortcuts in the HMI tree or simple commands. Existing stations with ABB station bus LON can be extended
• 15 user defined three-color LEDs. with use of the optical LON interface. This allows full SA
• Communication port for PCM600. functionality including peer-to-peer messaging and
cooperation between the IEDs.

The LHMI is used for setting, monitoring and controlling. SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation

42 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

automation systems but the main use is for Substation


Monitoring Systems SMS. Galvanic X.21 line data communication module X.21-LDCM
A module with built-in galvanic X.21 converter which e.g. can
IEC 60870-5-103 communication protocol be connected to modems for pilot wires is also available.
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple substation Galvanic interface G.703 resp G.703E1
automation systems including equipment from different The external galvanic data communication converter G.703/G.
vendors. Disturbance files uploading is provided. 703E1 makes an optical-to-galvanic conversion for connection
to a multiplexer. These units are designed for 64 kbit/s resp
DNP3.0 communication protocol 2Mbit/s operation. The converter is delivered with 19” rack
An electrical RS485 and an optical Ethernet port is available for mounting accessories.
the DNP3.0 communication. DNP3.0 Level 2 communication
with unsolicited events, time synchronizing and disturbance
19. Hardware description
reporting is provided for communication to RTUs, Gateways or
HMI systems. Hardware modules
Power supply module PSM
Multiple command and transmit
The power supply module is used to provide the correct internal
When IEDs are used in Substation Automation systems with
voltages and full isolation between the IED and the battery
LON, SPA or IEC 60870-5-103 communication protocols, the
system. An internal fail alarm output is available.
Event and Multiple Command function blocks are used as the
communication interface for vertical communication to station Binary input module BIM
HMI and gateway, and as interface for horizontal peer-to-peer The binary input module has 16 optically isolated inputs and is
communication (over LON only). available in two versions, one standard and one with enhanced
pulse counting capabilities on the inputs to be used with the
IEC 62439-3 Parallel Redundancy Protocol
pulse counter function. The binary inputs are freely
Redundant station bus communication according to IEC
programmable and can be used for the input of logical signals
62439-3 Edition 1 and IEC 62439-3 Edition 2 parallel
to any of the functions. They can also be included in the
redundancy protocol (PRP) are available as options when
disturbance recording and event-recording functions. This
ordering IEDs. Redundant station bus communication
enables extensive monitoring and evaluation of operation of the
according to IEC 62439-3 uses both port AB and port CD on
IED and for all associated electrical circuits.
the OEM module.
Binary output module BOM
18. Remote communication The binary output module has 24 independent output relays
and is used for trip output or any signaling purpose.
Analog and binary signal transfer to remote end
Three analog and eight binary signals can be exchanged Static binary output module SOM
between two IEDs. This functionality is mainly used for the line The static binary output module has six fast static outputs and
differential protection. However it can be used in other products six change over output relays for use in applications with high
as well. An IED can communicate with up to 4 remote IEDs. speed requirements.

Binary signal transfer to remote end, 192 signals Binary input/output module IOM
If the communication channel is used for transfer of binary The binary input/output module is used when only a few input
signals only, up to 192 binary signals can be exchanged and output channels are needed. The ten standard output
between two IEDs. For example, this functionality can be used channels are used for trip output or any signaling purpose. The
to send information such as status of primary switchgear two high speed signal output channels are used for applications
apparatus or intertripping signals to the remote IED. An IED can where short operating time is essential. Eight optically isolated
communicate with up to 4 remote IEDs. binary inputs cater for required binary input information.

Line data communication module, short, medium and long mA input module MIM
range LDCM The milli-ampere input module is used to interface transducer
The line data communication module (LDCM) is used for signals in the –20 to +20 mA range from for example OLTC
communication between the IEDs situated at distances <110 position, temperature or pressure transducers. The module has
km/68 miles or from the IED to optical to electrical converter six independent, galvanically separated channels.
with G.703 or G.703E1 interface located on a distances < 3
Optical ethernet module OEM
km/1.9 miles away. The LDCM module sends and receives
The optical fast-ethernet module is used for fast and
data, to and from another LDCM module. The IEEE/ANSI
interference-free communication of synchrophasor data over
C37.94 standard format is used.
IEEE C37.118 and/or IEEE 1344 protocols. It is also used to
connect an IED to the communication buses (like the station
ABB 43
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

bus) that use the IEC 61850-8-1 protocol (OEM rear port A, B). Electrical (BNC) and optical connection (ST) for 0XX and 12X
The process bus use the IEC 61850-9-2LE protocol (OEM rear IRIG-B support.
port C, D). The module has one or two optical ports with ST
connectors. Transformer input module TRM
The transformer input module is used to galvanically separate
Serial and LON communication module SLM, supports and adapt the secondary currents and voltages generated by
SPA/IEC 60870-5-103, LON and DNP 3.0 the measuring transformers. The module has twelve inputs in
The serial and LON communication module (SLM) is used for different combinations of currents and voltage inputs.
SPA, IEC 60870-5-103, DNP3 and LON communication. The
module has two optical communication ports for plastic/plastic, Alternative connectors of Ring lug or Compression type can be
plastic/glass or glass/glass. One port is used for serial ordered.
communication (SPA, IEC 60870-5-103 and DNP3 port) and
High impedance resistor unit
one port is dedicated for LON communication.
The high impedance resistor unit, with resistors for pick-up
Line data communication module LDCM value setting and a voltage dependent resistor, is available in a
Each module has one optical port, one for each remote end to single phase unit and a three phase unit. Both are mounted on a
which the IED communicates. 1/1 19 inch apparatus plate with compression type terminals.

Alternative cards for Long range (1550 nm single mode), Layout and dimensions
Medium range (1310 nm single mode) and Short range (850 nm Dimensions
multi mode) are available.

Galvanic X.21 line data communication module X.21-LDCM


The galvanic X.21 line data communication module is used for
connection to telecommunication equipment, for example
E
leased telephone lines. The module supports 64 kbit/s data
communication between IEDs.

Examples of applications:

• Line differential protection A


• Binary signal transfer
D

Galvanic RS485 serial communication module


The Galvanic RS485 communication module (RS485) is used
for DNP3.0 and IEC 60870-5-103 communication. The module
has one RS485 communication port. The RS485 is a balanced
serial communication that can be used either in 2-wire or 4-wire
connections. A 2-wire connection uses the same signal for RX B
and TX and is a multidrop communication with no dedicated
C
Master or slave. This variant requires however a control of the
output. The 4-wire connection has separated signals for RX and
TX multidrop communication with a dedicated Master and the IEC08000163-2-en.vsd

rest are slaves. No special control signal is needed in this case. IEC08000163 V2 EN

Figure 17. Case with rear cover


GPS time synchronization module GTM
This module includes a GPS receiver used for time
synchronization. The GPS has one SMA contact for connection
to an antenna. It also includes an optical PPS ST-connector
output.

IRIG-B Time synchronizing module


The IRIG-B time synchronizing module is used for accurate time
synchronizing of the IED from a station clock.

The Pulse Per Second (PPS) input shall be used for


synchronizing when IEC 61850-9-2LE is used.

44 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

K
F

IEC06000182-2-en.vsd
IEC06000182 V2 EN

G Figure 19. A 1/2 x 19” size IED side-by-side with RHGS6.


J
H
xx08000165.vsd

IEC08000165 V1 EN

Figure 18. Case with rear cover and 19” rack mounting kit

Case size A B C D E F G H J K
(mm)/(inches)

6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00

6U, 3/4 x 19” 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00

6U, 1/1 x 19” 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00

The H and K dimensions are defined by the 19” rack mounting kit.

Mounting alternatives See ordering for details about available mounting alternatives.
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/8.27”
– 3/4 case size (h) 254.3 mm/10.01” (w) 322.4 mm/12.69”
– 1/1 case size (h) 254.3 mm/10.01” (w) 434.7 mm/17.11”
• Wall mounting kit

ABB 45
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

20. Connection diagrams Connection diagrams for Configured products

Connection diagrams Connection diagram, RED670 2.1, A31 1MRK002803-HA


The connection diagrams are delivered on the IED Connectivity
package DVD as part of the product delivery. Connection diagram, RED670 2.1, B31 1MRK002803-HB

The latest versions of the connection diagrams can be Connection diagram, RED670 2.1, A32 1MRK002803-HC
downloaded from http://www.abb.com/substationautomation.
Connection diagram, RED670 2.1, B32 1MRK002803-HD
Connection diagrams for Customized products
Connection diagrams for Customized products
Connection diagram, 670 series 2.11MRK002801-AF
Connection diagram, 670 series 2.1 1MRK002802-AF

46 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

21. Technical data

General

Definitions

Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment

Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified
requirements

Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements

Energizing quantities, rated values and limits


Analog inputs

Table 7. TRM - Energizing quantities, rated values and limits for protection transformer modules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0.2-40) × Ir

Operative range (0-100) x Ir

Permissive overload 4 × Ir cont.


100 × Ir for 1 s *)

Burden < 150 mVA at Ir = 5 A


< 20 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V

Permissive overload 420 V cont.


450 V 10 s

Burden < 20 mVA at 110 V

Frequency fr = 50/60 Hz ±5%

*) max. 350 A for 1 s when COMBITEST test switch is included.

Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0-1.8) × Irat Ir = 1 A


(0-1.6) × Irat Ir = 5 A

Permissive overload 1.1 × Ir cont.


1.8 × Ir for 30 min at Ir = 1 A
1.6 × Ir for 30 min at Ir = 5 A

Burden < 350 mVA at Ir = 5 A


< 200 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V

Permissive overload 420 V cont.


450 V 10 s

Burden < 20 mVA at 110 V

Frequency fr = 50/60 Hz ±5%

ABB 47
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 9. MIM - mA input module

Quantity: Rated value: Nominal range:

Input resistance Rin = 194 Ohm -

Input range ±5, ±10, ±20mA -


0-5, 0-10, 0-20, 4-20mA

Power consumption -
each mA-board £2W
each mA input £ 0.1 W

Table 10. OEM - Optical ethernet module

Quantity Rated value

Number of channels 1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118 and port C, D for IEC 61850-9-2LE / IEEE
C37.118)

Standard IEEE 802.3u 100BASE-FX

Type of fiber 62.5/125 mm multimode fibre

Wave length 1300 nm

Optical connector Type ST

Communication speed Fast Ethernet 100 Mbit/s

Auxiliary DC voltage

Table 11. PSM - Power supply module

Quantity Rated value Nominal range

Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ±20%


EL = (90 - 250) V EL ±20%

Power consumption 50 W typically -

Auxiliary DC power in-rush < 10 A during 0.1 s -

48 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Binary inputs and outputs

Table 12. BIM - Binary input module

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
110/125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input

Counter input frequency 10 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Debounce filter Settable 1–20ms

Maximum 176 binary input channels may be


activated simultaneously with influencing
factors within nominal range.

Table 13. BIM - Binary input module with enhanced pulse counting capabilities

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input

Counter input frequency 10 pulses/s max -

Balanced counter input frequency 40 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Debounce filter Settable 1-20 ms

Maximum 176 binary input channels may be


activated simultaneously with influencing
factors within nominal range.

ABB 49
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 14. IOM - Binary input/output module

Quantity Rated value Nominal range

Binary inputs 8 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input

Counter input frequency 10 pulses/s max

Oscillating signal discriminator Blocking settable 1-40 Hz


Release settable 1-30 Hz

Debounce filter Settable 1-20 ms

Maximum 176 binary input channels may be


activated simultaneously with influencing
factors within nominal range.

Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)

Binary outputs 10 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open contact, 1 min 1000 V rms 800 V DC

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A

Making capacity at inductive load with L/R>10 ms

0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A


110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

50 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)

Binary outputs IOM: 10 IOM: 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open contact, 250 V rms 250 V rms


1 min

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, 12 A 12 A
continuous

Making capacity at inductive


loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A


j>0.4

Breaking capacity for DC with L/R 48 V/1 A 48 V/1 A


< 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs

Function of quantity Static binary output trip

Rated voltage 48 - 60 VDC 110 - 250 VDC

Number of outputs 6 6

Impedance open state ~300 kΩ ~810 kΩ

Test voltage across open contact, 1 min No galvanic separation No galvanic separation

Current carrying capacity:

Continuous 5A 5A

1.0s 10A 10A

Making capacity at capacitive load with the


maximum capacitance of 0.2 μF :

0.2s 30A 30A

1.0s 10A 10A

Breaking capacity for DC with L/R ≤ 40ms 48V / 1A 110V / 0.4A

60V / 0.75A 125V / 0.35A

220V / 0.2A

250V / 0.15A

Operating time <1ms <1ms

ABB 51
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs

Function of quantity Trip and signal relays

Max system voltage 250V AC/DC

Number of outputs 6

Test voltage across open contact, 1 min 1000V rms

Current carrying capacity:

Continuous 8A

1.0s 10A

Making capacity at capacitive load with the maximum capacitance of 0.2


μF:

0.2s 30A

1.0s 10A

Breaking capacity for DC with L/R ≤ 40ms 48V / 1A

110V / 0.4A

125V / 0.35A

220V / 0.2A

250V / 0.15A

Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays

Binary outputs 24

Max system voltage 250 V AC, DC

Test voltage across open contact, 1 min 1000 V rms

Current carrying capacity


Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A

Making capacity at inductive load with L/R>10 ms


0.2 s 30 A
1.0 s 10 A

Breaking capacity for AC, cos j>0.4 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A


110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Influencing factors

Table 20. Temperature and humidity influence

Parameter Reference value Nominal range Influence

Ambient temperature, operate +20°C -10 °C to +55°C 0.02% / °C


value

Relative humidity 10%-90% 10%-90% -


Operative range 0%-95%

Storage temperature - -40 °C to +70 °C -

52 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 21. Auxiliary DC supply voltage influence on functionality during operation

Dependence on Reference value Within nominal Influence


range

Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% / %


Operative range Full wave rectified

Auxiliary voltage dependence, operate ±20% of EL 0.01% / %


value

Interrupted auxiliary DC voltage 24-60 V DC ± 20%

90-250 V DC ±20%
Interruption interval
0–50 ms
No restart

0–∞ s Correct behaviour at power down

Restart time <300 s

Table 22. Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence

Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0% / Hz


fr ±3.0 Hz for 60 Hz

Frequency dependence for distance protection operate value fr ±2.5 Hz for 50 Hz ±2.0% / Hz
fr ±3.0 Hz for 60 Hz

Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%

Harmonic frequency dependence for distance protection (10% content) 2nd, 3rd and 5th harmonic of fr ±10.0%

Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)

Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0% / Hz

ABB 53
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Type tests according to standards

Table 23. Electromagnetic compatibility

Test Type test values Reference standards

1 MHz burst disturbance 2.5 kV IEC 60255-26

100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III

Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV

Surge withstand capability test 2.5 kV, oscillatory IEEE/ANSI C37.90.1


4.0 kV, fast transient

Electrostatic discharge 15 kV air discharge IEC 60255-26


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV

Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.1


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge

Fast transient disturbance 4 kV IEC 60255-26, Zone A

Surge immunity test 2-4 kV, 1.2/50 ms IEC 60255-26, Zone A


high energy

Power frequency immunity test 150-300 V, 50 Hz IEC 60255-26, Zone A

Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV

Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.

Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V

Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V

Radiated electromagnetic field disturbance 20 V/m, 80-1000 MHz IEC 60255-26

1.4-2.7 GHz

Radiated electromagnetic field disturbance 20 V/m IEEE/ANSI C37.90.2


80-1000 MHz

Conducted electromagnetic field disturbance 10 V, 0.15-80 MHz IEC 60255-26

Radiated emission 30-5000 MHz IEC 60255-26

Radiated emission 30-5000 MHz IEEE/ANSI C63.4, FCC

Conducted emission 0.15-30 MHz IEC 60255-26

Table 24. Insulation

Test Type test values Reference standard

Dielectric test 2.0 kV AC, 1 min. IEC 60255-27


ANSI C37.90
Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J

Insulation resistance >100 MW at 500 VDC

54 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 25. Environmental tests

Test Type test value Reference standard

Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1

Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1

Dry heat operation test Test Bd for 16 h at +70°C IEC 60068-2-2

Dry heat storage test Test Bb for 16 h at +85°C IEC 60068-2-2

Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14

Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78

Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle = 24 IEC 60068-2-30
hours)

Table 26. CE compliance

Test According to

Immunity EN 60255–26

Emissivity EN 60255–26

Low voltage directive EN 60255–27

Table 27. Mechanical tests

Test Type test values Reference standards

Vibration response test Class II IEC 60255-21-1

Vibration endurance test Class I IEC 60255-21-1

Shock response test Class I IEC 60255-21-2

Shock withstand test Class I IEC 60255-21-2

Bump test Class I IEC 60255-21-2

Seismic test Class II IEC 60255-21-3

ABB 55
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Differential protection

Table 28. Restricted earth-fault protection, low impedance REFPDIF

Function Range or value Accuracy

Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio >95% -

Minimum pickup, IdMin (4.0-100.0)% of IBase ±1.0% of Ir

Directional characteristic Fixed 180 degrees or ±60 to ±90 ±2.0 degrees


degrees

Operate time, trip at 0 to 10 x Min. = 15 ms -


IdMin Max. = 30 ms

Reset time, trip at 10 to 0 x IdMin Min. = 15 ms -


Max. = 30 ms

Second harmonic blocking 60.0% of fundamental (hidden ±1.0% of Ir


setting)

Table 29. 1Ph High impedance differential protection HZPDIF

Function Range or value Accuracy

Operate voltage (10-900) V ±1.0% of Ir at I ≤ Ir


I=U/R ±1.0% of I at I > Ir

Reset ratio >95% at (30-900) V -

Maximum continuous power U>Trip2/SeriesResistor ≤200 W -

Operate time at 0 to 10 x Ud Min. = 5 ms


Max. = 15 ms

Reset time at 10 to 0 x Ud Min. = 75 ms


Max. = 95 ms

Critical impulse time 2 ms typically at 0 to 10 x Ud -

Operate time at 0 to 2 x Ud Min. = 25 ms


Max. = 35 ms

Reset time at 2 to 0 x Ud Min. = 50 ms


Max. = 70 ms

Critical impulse time 15 ms typically at 0 to 2 x Ud -

56 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 30. Line differential protection L3CPDIF,L6CPDIF,LT3CPDIF,LT6CPDIF

Function Range or value Accuracy

*Minimum operate current (20-200)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

SlopeSection2 (10.0-50.0)% -

SlopeSection3 (30.0-100.0)% -

EndSection 1 (20–150)% of IBase -

EndSection 2 (100–1000)% of IBase -

*Unrestrained limit function (100–5000)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

*Second harmonic blocking (5.0–100.0)% of fundamental ±1.0% of Ir


Note: fundamental magnitude = 100% of Ir

*Fifth harmonic blocking (5.0–100.0)% of fundamental ±2.0% of Ir


Note: fundamental magnitude = 100% of Ir

*Inverse characteristics, see table 16 curve types See table 171, 172 and table 173
171, 172 and table 172

Critical impulse time 2ms typically at 0 to 10 x Id -

Charging current compensation On/Off -

LT3CPDIF and LT6CPDIF:

*Operate time, restrained function at Min. = 25 ms -


0 to 10 x Id Max. = 35 ms

*Reset time, restrained function at 10 Min. = 5 ms -


to 0 x Id Max. = 15 ms

*Operate time, unrestrained function Min. = 5 ms -


at 0 to 10 x Id Max. = 15 ms

*Reset time, unrestrained function at Min. = 15 ms -


10 to 0 x Id Max. = 25 ms

L3CPDIF and L6CPDIF:

*Operate time, restrained function at Min. = 10 ms -


0 to 10 x Id Max. = 25 ms

*Reset time, restrained function at 10 Min. = 15 ms -


to 0 x Id Max. = 25 ms

*Operate time, unrestrained function Min. = 5 ms -


at 0 to 10 x Id Max. = 15 ms

*Reset time, unrestrained function at Min. = 15 ms -


10 to 0 x Id Max. = 25 ms

*Note: Data valid for a single IED with two local current input groups

ABB 57
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 31. Additional security logic for differential protection LDRGFC

Function Range or value Accuracy

Operate current, zero sequence current (1-100)% of lBase ±1.0% of Ir

Operate current, low current operation (1-100)% of lBase ±1.0% of Ir

Operate voltage, phase to neutral (1-100)% of UBase ±0.5% of Ur

Operate voltage, phase to phase (1-100)% of UBase ±0.5% of Ur

Independent time delay, zero sequence current at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater

Independent time delay, low current operation at 2 x Iset to 0 (0.000-60.000) s ±0.2% or ± 40 ms


whichever is greater

Independent time delay, low voltage operation at 2 x Uset to 0 (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater

Reset time delay for startup signal at 0 to 2 x Uset (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater

58 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Impedance protection

Table 32. Distance measuring zone, Quad ZMQPDIS

Function Range or value Accuracy

Number of zones Max 5 with selectable -


direction

Minimum operate residual (5-1000)% of IBase -


current, zone 1

Minimum operate current, phase- (10-1000)% of IBase -


to-phase and phase-to-earth

Positive sequence reactance (0.10-3000.00) Ω/ ±2.0% static accuracy


phase ±2.0 degrees static angular accuracy
Conditions:
Positive sequence resistance (0.01-1000.00) Ω/
Voltage range: (0.1-1.1) x Ur
phase
Current range: (0.5-30) x Ir
Zero sequence reactance (0.10-9000.00) Ω/ Angle: at 0 degrees and 85 degrees
phase

Zero sequence resistance (0.01-3000.00) Ω/


phase

Fault resistance, phase-to-earth (0.10-9000.00) Ω/loop

Fault resistance, phase-to-phase (0.10-3000.00) Ω/loop

Dynamic overreach <5% at 85 degrees -


measured with CVT’s
and 0.5<SIR<30

Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
E operation

Operate time 25 ms typically IEC 60255-121

Reset ratio 105% typically -

Reset time at 0.1 to 2 x Zreach Min. = 20 ms -


Max. = 35 ms

ABB 59
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 33. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS

Function Range or value Accuracy

Number of zones Max 5 with selectable direction -

Minimum operate residual (5-1000)% of IBase -


current, zone 1

Minimum operate current, Ph-Ph (10-1000)% of IBase -


and Ph-E

Positive sequence reactance (0.10-3000.00) Ω/phase ±2.0% static accuracy


±2.0 degrees static angular accuracy
Positive sequence resistance (0.10-1000.00) Ω/phase
Conditions:
Zero sequence reactance (0.01-9000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Zero sequence resistance (0.01-3000.00) Ω/phase
Angle: at 0 degrees and 85 degrees
Fault resistance, Ph-E (0.10-9000.00) Ω/loop

Fault resistance, Ph-Ph (0.10-3000.00) Ω/loop

Dynamic overreach <5% at 85 degrees measured with -


CCVT’s and 0.5<SIR<30

Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ± 35 ms whichever is greater
E operation

Operate time 25 ms typically IEC 60255-121

Reset ratio 105% typically -

Reset time at 0.1 to 2 x Zreach Min. = 20 ms -


Max. = 35 ms

Table 34. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS

Function Range or value Accuracy

Minimum operate current (5-500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reactive reach, positive (0.50–3000.00) Ω/phase ±2.5% static accuracy


sequence ±2.0 degrees static angular accuracy
Conditions:
Resistive reach, positive (0.10–1000.00) Ω/phase
Voltage range: (0.1-1.1) x Ur
sequence
Current range: (0.5-30) x Ir
Reactive reach, zero sequence (0.50–9000.00) Ω/phase Angle: at 0 degrees and 85 degrees

Resistive reach, zero sequence (0.50–3000.00) Ω/phase

Fault resistance, phase-to-earth (1.00–9000.00) Ω/loop


faults, forward and reverse

Fault resistance, phase-to-phase (0.50–3000.00) Ω/loop


faults, forward and reverse

Load encroachment criteria:


Load resistance, forward and (1.00–3000.00) Ω/phase
reverse (5-70) degrees
Safety load impedance angle

Reset ratio 105% typically -

60 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 35. Full-scheme distance protection, Mho characteristic ZMHPDIS

Function Range or value Accuracy

Number of zones, Ph-E Max 5 with selectable direction -

Minimum operate current (10–30)% of IBase -

Positive sequence impedance, (0.005–3000.000) W/phase ±2.0% static accuracy


Ph-E loop Conditions:
Voltage range: (0.1-1.1) x Ur
Positive sequence impedance (10–90) degrees
Current range: (0.5-30) x Ir
angle, Ph-E loop
Angle: 85 degrees
Reverse reach, Ph-E loop (0.005–3000.000) Ω/phase
(Magnitude)

Magnitude of earth return (0.00–3.00)


compensation factor KN

Angle for earth compensation (-180–180) degrees


factor KN

Dynamic overreach <5% at 85 degrees measured -


with CVT’s and 0.5<SIR<30

Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±60 ms whichever is greater
E operation

Operate time 22 ms typically IEC 60255-121

Reset ratio 105% typically -

Reset time at 0.5 to 1.5 x Zreach Min. = 30 ms -


Max. = 45 ms

Table 36. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS

Function Range or value Accuracy

Number of zones Max 5 with selectable direction -

Minimum operate current (10-30)% of IBase -

Positive sequence reactance (0.50-3000.00) W/phase ±2.0% static accuracy


±2.0 degrees static angular accuracy
Positive sequence resistance (0.10-1000.00) Ω/phase
Conditions:
Zero sequence reactance (0.50-9000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Zero sequence resistance (0.50-3000.00) Ω/phase
Angle: at 0 degrees and 85 degrees
Fault resistance, Ph-E (1.00-9000.00) W/loop

Dynamic overreach <5% at 85 degrees measured with -


CCVT’s and 0.5<SIR<30

Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
E operation

Operate time 25 ms typically IEC 60255-121

Reset ratio 105% typically -

Reset time at 0.1 to 2 x Zreach Min. = 20 ms -


Max. = 35 ms

ABB 61
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 37. Faulty phase identification with load encroachment FMPSPDIS

Function Range or value Accuracy

Load encroachment criteria: Load (1.00–3000.00) W/phase ±2.0% static accuracy


resistance, forward and reverse (5–70) degrees Conditions:
Voltage range: (0.1–1.1) x Ur
Current range: (0.5–30) x Ir
Angle: at 0 degrees and 85 degrees

Table 38. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS

Function Range or value Accuracy

Number of zones Max 5 with selectable -


direction

Minimum operate residual (5-1000)% of IBase -


current, zone 1

Minimum operate current, phase- (10-1000)% of IBase -


to-phase and phase-to-earth

Positive sequence reactance (0.10-3000.00) Ω/ ±2.0% static accuracy


phase ±2.0 degrees static angular accuracy
Conditions:
Positive sequence resistance (0.01-1000.00) Ω/
Voltage range: (0.1-1.1) x Ur
phase
Current range: (0.5-30) x Ir
Zero sequence reactance (0.10-9000.00) Ω/ Angle: at 0 degrees and 85 degrees
phase

Zero sequence resistance (0.01-3000.00) Ω/


phase

Fault resistance, phase-to-earth (0.10-9000.00) Ω/loop

Fault resistance, phase-to-phase (0.10-3000.00) Ω/loop

Dynamic overreach <5% at 85 degrees -


measured with CVT’s
and 0.5<SIR<30

Definite time delay phase-phase (0.000-60.000) s ±0.2% or ±40 ms whichever is greater


and phase-earth operation

Operate time 25 ms typically IEC 60255-121

Reset ratio 105% typically -

Reset time at 0.1 to 2 x Zreach Min. = 20 ms -


Max. = 35 ms

62 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 39. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS

Function Range or value Accuracy

Minimum operate current (5-500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reactive reach, positive (0.50–3000.00) Ω/phase ±2.0% static accuracy


sequence ±2.0 degrees static angular accuracy
Conditions:
Resistive reach, positive (0.10–1000.00) Ω/phase
Voltage range: (0.1-1.1) x Ur
sequence
Current range: (0.5-30) x Ir
Reactive reach, zero sequence (0.50–9000.00) Ω/phase Angle: at 0 degrees and 85 degrees

Resistive reach, zero sequence (0.50–3000.00) Ω/phase

Fault resistance, Ph-E faults, (1.00–9000.00) Ω/loop


forward and reverse

Fault resistance, Ph-Ph faults, (0.50–3000.00) Ω/loop


forward and reverse

Load encroachment criteria:


Load resistance, forward and (1.00–3000.00) Ω/phase
reverse (5-70) degrees
Safety load impedance angle

Reset ratio 105% typically -

Table 40. High speed distance protection ZMFPDIS, ZMFCPDIS

Function Range or value Accuracy

Number of zones 3 selectable directions, -


3 fixed directions

Minimum operate current, Ph-Ph (5-6000)% of IBase ±1.0% of Ir


and Ph-E

Positive sequence reactance (0.01 - 3000.00) ohm/


reach, Ph-E and Ph-Ph loop phase

Positive sequence resistance (0.00 - 1000.00) ohm/


reach, Ph-E and Ph-Ph loop phase

Zero sequence reactance reach (0.01 - 9000.00) ohm/p ±2.0% of static accuracy
±2.0 degrees static angular accuracy
Zero sequence resistive reach (0.00 - 3000.00) ohm/p Conditions:
Fault resistance reach, Ph-E and (0.01 -9000.00) ohm/l Voltage range: (0.1-1.1) x Ur
Ph-Ph Current range: (0.5-30) x Ir
Angle: At 0 degrees and 85 degrees
Dynamic overreach < 5% at 85 degrees
measured with CVTs
and 0.5 < SIR < 30

Definite time delay to trip, Ph-E (0.000-60.000) s ±2.0% or ±35 ms whichever is greater
and Ph-Ph operation

Operate time 16 ms typically IEC 60255-121

Reset time at 0.1 to 2 x Zreach Min. = 20 ms -


Max. = 35 ms

Reset ratio 105% typically -

ABB 63
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 41. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS

Function Range or value Accuracy

Number of zones 3 selectable directions, -


3 fixed directions

Minimum operate current, Ph-Ph (5 - 6000)% of IBase ±1.0% of In


and Ph-E

Positive sequence reactance (30 - 3000) Ω/phase


reach, Ph-E and Ph-Ph loop

Positive sequence resistance (30 - 3000) Ω/phase


reach, Ph-E and Ph-Ph loop

Zero sequence reactance reach (100.00 - 9000.00) Ω/p


" +- 2.0% static accuracy +- 2.0 deg static angular accuracy Conditions: Voltage range:
Zero sequence resistive reach (15.00 - 3000.00) Ω/p (0.1 - 1.1) x Ur Current range: (0.5 - 30) x Ir Angle: At 0 deg and 85 deg"
Fault resistance reach, Ph-E and (1.00 - 9000.00) Ω/l
Ph-Ph

Dynamic overreach < 5% at 85 deg


measured with CVT's
and 0.5 < SIR <30

Definite time delay to trip, Ph-E (0.000 - 60.000) s


±0.2% or ±35 ms whichever is greater
and Ph-Ph operation

Operate time 16 ms typically IEC 60255-121

Reset time at 0.1 to 2 x Zreach Min = 20 ms


-
Max = 35 ms

Reset ratio 105% typically -

Table 42. Power swing detection ZMRPSB

Function Range or value Accuracy

Reactive reach (0.10-3000.00) W/phase ±2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
Resistive reach (0.10–1000.00) W/loop

Power swing detection operate (0.000-60.000) s ±0.2% or ±10 ms whichever is greater


time

Second swing reclaim operate (0.000-60.000) s ±0.2% or ±20 ms whichever is greater


time

Minimum operate current (5-30)% of IBase ±1.0% of Ir

64 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 43. Power swing logic PSLPSCH

Function Range or value Accuracy

Permitted maximum operating (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater


time difference between
higher and lower zone

Delay for operation of (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater


underreach zone with
detected difference in
operating time

Conditional timer for sending (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
the CS at power swings

Conditional timer for tripping at (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
power swings

Timer for blocking the (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
overreaching zones trip

Table 44. Pole slip protection PSPPPAM

Function Range or value Accuracy

Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of Ur/Ir

Zone 1 and Zone 2 trip counters (1 - 20) -

Table 45. Out-of-step protection OOSPPAM

Function Range or value Accuracy

Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of Ur/(√3 ⋅ Ir)

Rotor start angle (90.0 - 130.0) degrees ±5.0 degrees

Rotor trip angle (15.0 - 90.0) degrees ±5.0 degrees

Zone 1 and Zone 2 trip counters (1 - 20) -

ABB 65
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 46. Phase preference logic PPLPHIZ

Function Range or value Accuracy

Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of Ur


and phase-to-neutral
undervoltage

Reset ratio, undervoltage < 105% -

Operate value, residual voltage (5 - 300)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Reset ratio, residual voltage > 95% -

Operate value, residual current (10 - 200)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
residual current at 0 to 2 x Iset

Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
residual voltage at 0.8 to 1.2 x Uset

Independent dropoff-delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater


residual voltage at 1.2 to 0.8 x Uset

Operating mode No Filter, NoPref


Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a, 312a, 321a

Table 47. Automatic switch onto fault logic ZCVPSOF

Parameter Range or value Accuracy

Operate voltage, detection of dead line (1–100)% of ±0.5% of Ur


UBase

Operate current, detection of dead line (1–100)% of IBase ±1.0% of Ir

Time delay to operate for the switch onto fault function (0.03-120.00) s ±0.2% or ±20 ms whichever is greater

Time delay for UI detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater

Delay time for activation of dead line detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater

Drop-off delay time of switch onto fault function (0.000-60.000) s ±0.2% or ±30 ms whichever is greater

66 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Current protection

Table 48. Instantaneous phase overcurrent protection PHPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of IBase -

Operate time at 0 to 2 x Iset Min. = 15 ms -


Max. = 25 ms

Reset time at 2 to 0 x Iset Min. = 15 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Iset Min. = 5ms -


Max. = 15ms

Reset time at 10 to 0 x Iset Min. = 25ms -


Max. = 40 ms

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

ABB 67
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 49. Four-step phase overcurrent protection OC4PTOC

Function Setting range Accuracy

Operate current, step 1 - 4 (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -

Minimum operate current, step 1 - 4 (1-10000)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Relay characteristic angle (RCA) (40.0–65.0) degrees ±2.0 degrees

Relay operating angle (ROA) (40.0–89.0) degrees ±2.0 degrees

Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Independent time delay at 0 to 2 x (0.000-60.000) s ±0.2 % or ±35 ms whichever is greater


Iset, step 1 - 4

Minimum operate time for inverse (0.000-60.000) s ±0.2 % or ±35 ms whichever is greater
curves , step 1 - 4

Inverse time characteristics, see 16 curve types See table 171, table 172 and table 173
table 171, table 172 and table 173

Operate time, start non-directional Min. = 15 ms -


at 0 to 2 x Iset
Max. = 30 ms

Reset time, start non-directional at Min. = 15 ms -


2 to 0 x Iset
Max. = 30 ms

Operate time, start non-directional Min. = 5 ms -


at 0 to 10 x Iset Max. = 20 ms

Reset time, start non-directional at Min. = 20 ms -


10 to 0 x Iset Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Table 50. Instantaneous residual overcurrent protection EFPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -

Operate time at 0 to 2 x Iset Min. = 15 ms -


Max. = 25 ms

Reset time at 2 to 0 x Iset Min. = 15 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Iset Min. = 5 ms -


Max. = 15 ms

Reset time at 10 to 0 x Iset Min. = 25 ms -


Max. = 35 ms

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

68 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 51. Four step residual overcurrent protection EF4PTOC technical data

Function Range or value Accuracy

Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of lBase -

Relay characteristic angle (-180 to 180) degrees ±2.0 degrees


(RCA)

Operate current for directional (1–100)% of lBase For RCA ±60 degrees:
release ±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Independent time delay at 0 to 2 x (0.000-60.000) s ±0.2% or ±35 ms whichever is


Iset, step 1 - 4 greater

Minimum operate time for inverse (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
curves, step 1 - 4 greater

Inverse time characteristics, see 16 curve types See Table 171, Table 172 and
Table 171, Table 172 and Table Table 173
173

Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Minimum polarizing current (2-100)% of IBase ±1.0% of Ir

Real part of source Z used for (0.50-1000.00) W/phase -


current polarization

Imaginary part of source Z used (0.50–3000.00) W/phase -


for current polarization

Operate time, start non- Min. = 15 ms -


directional at 0 to 2 x Iset Max. = 30 ms

Reset time, start non-directional Min. = 15 ms -


at 2 to 0 x Iset Max. = 30 ms

Operate time, start non- Min. = 5 ms -


directional at 0 to 10 x Iset Max. = 20 ms

Reset time, start non-directional Min. = 20 ms -


at 10 to 0 x Iset Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

ABB 69
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 52. Four step negative sequence overcurrent protection NS4PTOC

Function Range or value Accuracy

Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of IBase -

Independent time delay at 0 to 2 (0.000-60.000) s ±0.2% or ±35 ms whichever is


x Iset, step 1 - 4 greater

Minimum operate time for (0.000 - 60.000) s ±0.2% or ±35 ms whichever is


inverse curves, step 1 - 4 greater

Inverse time characteristics, see 16 curve types See table 171, table 172 and table
table 171, table 172 and table 173
173

Minimum operate current, step 1 (1.00 - 10000.00)% of IBase ±1.0% of Ir at I ≤ Ir


-4 ±1.0% of I at I > Ir

Relay characteristic angle (-180 to 180) degrees ±2.0 degrees


(RCA)

Operate current for directional (1–100)% of IBase For RCA ±60 degrees:
release ±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Minimum polarizing current (2-100)% of IBase ±1.0% of Ir

Real part of negative sequence (0.50-1000.00) W/phase -


source impedance used for
current polarization

Imaginary part of negative (0.50–3000.00) W/phase -


sequence source impedance
used for current polarization

Operate time, start non- Min. = 15 ms -


directional at 0 to 2 x Iset Max. = 30 ms

Reset time, start non-directional Min. = 15 ms -


at 2 to 0 x Iset Max. = 30 ms

Operate time, start non- Min. = 5 ms -


directional at 0 to 10 x Iset Max. = 20 ms

Reset time, start non-directional Min. = 20 ms -


at 10 to 0 x Iset Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Transient overreach <10% at τ = 100 ms -

70 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 53. Sensitive directional residual overcurrent and power protection SDEPSDE

Function Range or value Accuracy

Operate level for 3I0·cosj (0.25-200.00)% of lBase ±1.0% of Ir at I £ Ir


directional residual ±1.0% of I at I > Ir
overcurrent

Operate level for ·3I0·3U0 cosj (0.25-200.00)% of SBase ±1.0% of Sr at S £ Sr


directional residual power ±1.0% of S at S > Sr

Operate level for 3I0 and j (0.25-200.00)% of lBase ±1.0% of Ir at £ Ir


residual overcurrent ±1.0% of I at I > Ir

Operate level for non- (1.00-400.00)% of lBase ±1.0% of Ir at I £ Ir


directional overcurrent ±1.0% of I at I > Ir

Operate level for non- (1.00-200.00)% of UBase ±0.5% of Ur at U £ Ur


directional residual ±0.5% of U at U > Ur
overvoltage

Residual release current for all (0.25-200.00)% of lBase ±1.0% of Ir at I £ Ir


directional modes ±1.0% of I at I > Ir

Residual release voltage for all (1.00-300.00)% of UBase ±0.5% of Ur at U £ Ur


directional modes ±0.5% of U at U > Ur

Operate time for non- Min. = 40 ms


directional residual
Max. = 65 ms
overcurrent at 0 to 2 x Iset

Reset time for non-directional Min. = 40 ms


residual overcurrent at 2 to 0 x
Max. = 65 ms
Iset

Operate time for directional Min. = 110 ms


residual overcurrent at 0 to 2 x
Max. = 160 ms
Iset

Reset time for directional Min. = 20 ms


residual overcurrent at 2 to 0 x
Max. = 60 ms
Iset

Independent time delay for (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater


non-directional residual
overvoltage at 0.8 to 1.2 x Uset

Independent time delay for (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater


non-directional residual
overcurrent at 0 to 2 x Iset

Independent time delay for (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is


directional residual greater
overcurrent at 0 to 2 x Iset

Inverse characteristics, see 16 curve types See table "", table "" and table ""
table "", table "" and table ""

Relay characteristic angle (-179 to 180) degrees ±2.0 degrees


(RCADir)

Relay operate angle (ROADir) (0 to 90) degrees ±2.0 degrees

ABB 71
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 54. Thermal overload protection, one time constant LCPTTR/LFPTTR

Function Range or value Accuracy

Reference current (2-400)% of IBase ±1.0% of Ir

Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F

Operate time: Time constant t = (1–1000) IEC 60255-8, ±5.0% or ±200 ms whichever is greater
minutes
é ù
ê I - Ip
2 2 ú
t = t ln ê ú
ê 2 2 TTrip - TAmb 2 ú
ê I - Ip - T × I ref
ú
ë ref û
EQUATION13000039 V2 EN (Equation 1)

TTrip= set operate temperature


TAmb = ambient temperature
Tref = temperature rise above ambient at Iref
Iref = reference load current
I = actual measured current
Ip = load current before overload occurs

Alarm temperature (0-200)°C, (0-400)°F ±2.0°C, ±4.0°F

Operate temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F

Reset level temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F

Table 55. Breaker failure protection CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio > 95% -

Operate time for current detection 20 ms typically -

Reset time for current detection 25 ms maximum -

Time delay for re-trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is


greater

Time delay for back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater

Time delay for back-up trip at multi-phase start at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater

Additional time delay for a second back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater

Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater

72 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 56. Stub protection STBPTOC

Function Range or value Accuracy

Operating current (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50-2500)% of IBase -

Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is


greater

Operate time, start at 0 to 2 x Iset Min. = 10 ms -


Max. = 20 ms

Reset time, start at 2 to 0 x Iset Min. = 10 ms -


Max. = 20 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Table 57. Pole discordance protection CCPDSC

Function Range or value Accuracy

Operate current (0–100)% of IBase ±1.0% of Ir

Independent time delay between (0.000-60.000) s ±0.2% or ± 25 ms whichever is greater


trip condition and trip signal

Table 58. Directional underpower protection GUPPDUP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr


for Step 1 and Step 2 ±1.0% of S at S > Sr
where

S r = 1.732 × U r × I r

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2

Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 to 0.5 x Sr and k=0.000

Table 59. Directional overpower protection GOPPDOP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr


for Step 1 and Step 2 ±1.0% of S at S > Sr

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2

Operate time, start at 0.5 to 2 x Sr and k=0.000 Min. =10 ms

Max. = 25 ms

Reset time, start at 2 to 0.5 x Sr and k=0.000 Min. = 35 ms

Max. = 55 ms

Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 to 2 x Sr and k=0.000

ABB 73
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 60. Broken conductor check BRCPTOC

Function Range or value Accuracy

Minimum phase current for operation (5–100)% of IBase ±1.0% of Ir

Unbalance current operation (50–90)% of maximum current ±1.0% of Ir

Independent operate time delay (0.000-60.000) s ±0.2% or ±45 ms whichever is greater

Independent reset time delay (0.010-60.000) s ±0.2% or ±30 ms whichever is greater

Start time at current change from Ir to 0 Min. = 25 ms -


Max. = 35 ms

Reset time at current change from 0 to Ir Min. = 5 ms -


Max. = 20 ms

74 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Voltage protection

Table 61. Two step undervoltage protection UV2PTUV

Function Range or value Accuracy

Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur

Internal blocking level, step 1 and step 2 (1–50)% of UBase ±0.5% of Ur

Inverse time characteristics for step 1 and step 2, see table 175 - See table 175

Definite time delay, step 1 at 1.2 to 0 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is
greater

Definite time delay, step 2 at 1.2 to 0 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is
greater

Minimum operate time, inverse characteristics (0.000–60.000) s ±0.5% or ±40ms whichever is


greater

Operate time, start at 2 to 0 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Operate time, start at 1.2 to 0 x Uset Min. = 5 ms -


Max. = 25 ms

Reset time, start at 0 to 1.2 x Uset Min. = 15 ms -


Max. = 35 ms

Critical impulse time 5 ms typically at 1.2 to 0 x Uset -

Impulse margin time 15 ms typically -

ABB 75
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 62. Two step overvoltage protection OV2PTOV

Function Range or value Accuracy

Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Inverse time characteristics for steps 1 and 2, see table 174 - See table 174

Definite time delay, low step (step 1) at 0 to 1.2 x Uset (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater

Definite time delay, high step (step 2) at 0 to 1.2 x Uset (0.000-60.000) s ±0.2% or ±45 ms whichever is greater

Minimum operate time, Inverse characteristics (0.000-60.000) s ±0.2% or ±45 ms whichever is greater

Operate time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 to 0 x Uset Min. = 15 ms -


Max. = 30 ms

Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -


Max. = 35 ms

Reset time, start at 1.2 to 0 x Uset Min. = 5 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Table 63. Overexcitation protection OEXPVPH

Function Range or value Accuracy

Operate value, start (100–180)% of (UBase/frated) ±0.5% of U

Operate value, alarm (50–120)% of start level ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Operate value, high level (100–200)% of (UBase/frated) ±0.5% of U

Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is greater

(0.18 × k )
IEEE : t =
( M - 1) 2

EQUATION1319 V1 EN (Equation 2)

where M = (E/f)/(Ur/fr)

Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is greater
function

Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is greater
function

Alarm time delay (0.00–9000.00) ±1.0% or ±45 ms, whichever is greater

76 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 64. Voltage differential protection VDCPTOV

Function Range or value Accuracy

Voltage difference for alarm and (2.0–100.0) % of UBase ±0.5% of Ur


trip

Under voltage level (1.0–100.0) % of UBase ±0.5% of Ur

Independent time delay for (0.000–60.000)s ±0.2% or ±40 ms whichever is greater


voltage differential alarm at 0.8 to
1.2 x UDAlarm

Independent time delay for (0.000–60.000)s ±0.2% or ±40 ms whichever is greater


voltage differential trip at 0.8 to 1.2
x UDTrip

Independent time delay for (0.000–60.000)s ±0.2% or ±40 ms whichever is greater


voltage differential reset at 1.2 to
0.8 x UDTrip

Table 65. Loss of voltage check LOVPTUV

Function Range or value Accuracy

Operate voltage (1–100)% of UBase ±0.5% of Ur

Pulse timer when disconnecting (0.050–60.000) s ±0.2% or ±15 ms whichever is greater


all three phases

Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration

Operate time delay when (0.000–60.000) s ±0.2% or ±35 ms whichever is greater


disconnecting all three phases

Time delay to block when all three (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
phase voltages are not low

Table 66. Radial feeder protection PAPGAPC

Function Range or value Accuracy

Residual current detection (10 - 150)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio >95% at (50 - 150)% of IBase -

Operate time, residual current detection at 0 to 2 Min. = 15 ms -


x Iset
Max. = 30 ms

Independent time delay to operate, residual (0.000 - 60.000) s ±0.2% or ±40 ms whichever is greater
current detection at 0 to 2 x Iset

Voltage based phase selection (30 - 100)% of UBase ±1.0% of Ur

Reset ratio <115% -

Operate time, voltage based phase selection at Min. = 15 ms -


1.2 to 0.8 x Uset
Max. = 30 ms

Independent time delay to operate, voltage (0.000 – 60.000) s ±0.2% or ±40 ms whichever is greater
based phase selection at 1.2 to 0.8 x Uset

ABB 77
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Frequency protection

Table 67. Underfrequency protection SAPTUF

Function Range or value Accuracy

Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz


phase voltage

Operate time, start at fset + 0.02 Hz to fset - 0.02 Hz Min. = 80 ms


fn = 50 Hz
Max. = 95 ms
-
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms

Reset time, start at fset - 0.02 Hz to fset + 0.02 Hz Min. = 15 ms


-
Max. = 30 ms

Operate time, definite time function at fset + 0.02 Hz to (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
fset - 0.02 Hz

Reset time, definite time function at fset - 0.02 Hz to fset (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
+ 0.02 Hz

Voltage dependent time delay Settings: ±1.0% or ±120 ms whichever is greater


UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent=0.0-5.0
tMax=(0.010–60.000)s
tMin=(0.010–60.000)s

Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN (Equation 3)

U=Umeasured

Table 68. Overfrequency protection SAPTOF

Function Range or value Accuracy

Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz

Operate time, start at fset -0.02 Hz to fset +0.02 Hz Min. = 80 ms -


fn = 50Hz
Max. = 95 ms

Min. = 65 ms
fn = 60 Hz
Max. = 80 ms

Reset time, start at fset +0.02 Hz to fset -0.02 Hz Min. = 15 ms -


Max. = 30 ms

Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater

Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater

78 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 69. Rate-of-change frequency protection SAPFRC

Function Range or value Accuracy

Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s

Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz

Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is


greater

Definite time delay for frequency gradient trip (0.200-60.000) s ±0.2% or ±120 ms whichever is
greater

Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is


greater

ABB 79
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Multipurpose protection

Table 70. General current and voltage protection CVGAPC

Function Range or value Accuracy

Measuring current input phase1, phase2, phase3, PosSeq, - -


NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2-
phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Measuring voltage input phase1, phase2, phase3, PosSeq, - -


NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2-
phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Start overcurrent, step 1 - 2 (2 - 5000)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Start undercurrent, step 1 - 2 (2 - 150)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Independent time delay, overcurrent at 0 to 2 x Iset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

Independent time delay, undercurrent at 2 to 0 x Iset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

Overcurrent (non-directional):

Start time at 0 to 2 x Iset Min. = 15 ms -


Max. = 30 ms

Reset time at 2 to 0 x Iset Min. = 15 ms -


Max. = 30 ms

Start time at 0 to 10 x Iset Min. = 5 ms -


Max. = 20 ms

Reset time at 10 to 0 x Iset Min. = 20 ms -


Max. = 35 ms

Undercurrent:

Start time at 2 to 0 x Iset Min. = 15 ms -


Max. = 30 ms

Reset time at 0 to 2 x Iset Min. = 15 ms -


Max. = 30 ms

Overcurrent:

Inverse time characteristics, see table 171, 172 and table 173 16 curve types See table 171, 172 and table 173

Overcurrent:

Minimum operate time for inverse curves, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

Voltage level where voltage memory takes over (0.0 - 5.0)% of UBase ±0.5% of Ur

Start overvoltage, step 1 - 2 (2.0 - 200.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Independent time delay, overvoltage at 0.8 to 1.2 x Uset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

80 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 70. General current and voltage protection CVGAPC , continued


Function Range or value Accuracy

Independent time delay, undervoltage at 1.2 to 0.8 x Uset, step 1 - (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
2 greater

Overvoltage:

Start time at 0.8 to 1.2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time at 1.2 to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Undervoltage:

Start time at 1.2 to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time at 1.2 to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Overvoltage:

Inverse time characteristics, see table 174 4 curve types See table 174

Undervoltage:

Inverse time characteristics, see table 175 3 curve types See table 175

High and low voltage limit, voltage dependent operation, step 1 - 2 (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
±1.0% of U at U > Ur

Directional function Settable: NonDir, forward and reverse -

Relay characteristic angle (-180 to +180) degrees ±2.0 degrees

Relay operate angle (1 to 90) degrees ±2.0 degrees

Reset ratio, overcurrent > 95% -

Reset ratio, undercurrent < 105% -

Reset ratio, overvoltage > 95% -

Reset ratio, undervoltage < 105% -

Overcurrent:

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Undercurrent:

Critical impulse time 10 ms typically at 2 to 0 x Iset -

Impulse margin time 15 ms typically -

Overvoltage:

Critical impulse time 10 ms typically at 0.8 to 1.2 x Uset -

Impulse margin time 15 ms typically -

Undervoltage:

Critical impulse time 10 ms typically at 1.2 to 0.8 x Uset -

Impulse margin time 15 ms typically -

ABB 81
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 71. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4

Function Range or value

For machines with:

• rated field voltage up to 350 V DC

• static exciter with rated supply 700 V 50/60 Hz


voltage up to

Supply voltage 120 or 230 V 50/60 Hz

Operate earth fault resistance Approx. 1–20 kΩ


value

Influence of harmonics in the DC Negligible influence of 50 V, 150


field voltage Hz or 50 V, 300 Hz

Permitted leakage capacitance (1–5) μF

Permitted shaft earthing Maximum 200 Ω


resistance

Protective resistor 220 Ω, 100 W, plate


(the height is 160 mm (6,2 inches)
and width 135 mm (5,31 inches))

82 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 72. Voltage-restrained time overcurrent protection VRPVOC

Function Range or value Accuracy

Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio, overcurrent > 95% -

Operate time, start overcurrent at 0 to 2 x Iset Min. = 15 ms -

Max. = 30 ms

Reset time, start overcurrent at 2 to 0 x Iset Min. = 15 ms -

Max. = 30 ms

Operate time, start overcurrent at 0 to 10 x Iset Min. = 5 ms -


Max. = 20 ms

Reset time, start overcurrent at 10 to 0 x Iset Min. = 20 ms -


Max. = 35 ms

Independent time delay to operate at 0 to 2 x Iset (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

Inverse time characteristics, 13 curve types See tables 171 and 172
see tables 171 and 172

Minimum operate time for inverse time characteristics (0.00 - 60.00) s ±0.2% or ±35 ms whichever is
greater

High voltage limit, voltage dependent operation (30.0 - 100.0)% of UBase ±1.0% of Ur

Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of Ur

Reset ratio, undervoltage < 105% -

Operate time start undervoltage at 2 to 0 x Uset Min. = 15 ms -

Max. = 30 ms

Reset time start undervoltage at 0 to 2 x Uset Min. = 15 ms -

Max. = 30 ms

Independent time delay to operate, undervoltage at 2 to 0 x Uset (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater

Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of Ur

Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically

Undervoltage: -
Critical impulse time 10ms typically at 2 to 0 x Uset
Impulse margin time 15 ms typically

ABB 83
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Secondary system supervision

Table 73. Current circuit supervision CCSSPVC

Function Range or value Accuracy

Operate current (10-200)% of IBase ±10.0% of Ir at I ≤ Ir


±10.0% of I at I > Ir

Reset ratio, Operate current >90%

Block current (20-500)% of IBase ±5.0% of Ir at I ≤ Ir


±5.0% of I at I > Ir

Reset ratio, Block current >90% at (50-500)% of IBase

Table 74. Fuse failure supervision FUFSPVC

Function Range or value Accuracy

Operate voltage, zero sequence (1-100)% of UBase ±0.5% of Ur

Operate current, zero sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage, negative sequence (1-100)% of UBase ±0.5% of Ur

Operate current, negative sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage change level (1-100)% of UBase ±10.0% of Ur

Operate current change level (1–100)% of IBase ±10.0% of Ir

Operate phase voltage (1-100)% of UBase ±0.5% of Ur

Operate phase current (1–100)% of IBase ±0.5% of Ir

Operate phase dead line voltage (1-100)% of UBase ±0.5% of Ur

Operate phase dead line current (1–100)% of IBase ±0.5% of Ir

Operate time, start, 1 ph, at 1 to 0 x Ur Min. = 10 ms -


Max. = 25 ms

Reset time, start, 1 ph, at 0 to 1 x Ur Min. = 15 ms -


Max. = 30 ms

84 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 75. Fuse failure supervision VDSPVC

Function Range or value Accuracy

Operate value, block of main fuse (10.0-80.0)% of UBase ±0.5% of Ur


failure

Reset ratio <110%

Operate time, block of main fuse Min. = 5 ms –


failure at 1 to 0 x Ur
Max. = 15 ms

Reset time, block of main fuse Min. = 15 ms –


failure at 0 to 1 x Ur
Max. = 30 ms

Operate value, alarm for pilot fuse (10.0-80.0)% of UBase ±0.5% of Ur


failure

Reset ratio <110% –

Operate time, alarm for pilot fuse Min. = 5 ms –


failure at 1 to 0 x Ur
Max. = 15 ms

Reset time, alarm for pilot fuse Min. = 15 ms –


failure at 0 to 1 x Ur
Max. = 30 ms

ABB 85
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Control

Table 76. Synchronizing, synchrocheck and energizing check SESRSYN

Function Range or value Accuracy

Phase shift, jline - jbus (-180 to 180) degrees -

Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Reset ratio, synchrocheck > 95% -

Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz

Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees

Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck

Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s ±0.2% or ±35 ms whichever is
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees greater

Frequency difference minimum limit for synchronizing (0.003-0.250) Hz ±2.5 mHz

Frequency difference maximum limit for synchronizing (0.050-0.500) Hz ±2.5 mHz

Breaker closing pulse duration (0.050-60.000) s ±0.2% or ±15 ms whichever is


greater

tMaxSynch, which resets synchronizing function if no close has been made (0.000-6000.00) s ±0.2% or ±35 ms whichever is
before set time greater

Minimum time to accept synchronizing conditions (0.000-60.000) s ±0.2% or ±35 ms whichever is


greater

Voltage high limit for energizing check (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Reset ratio, voltage high limit > 95% -

Voltage low limit for energizing check (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio, voltage low limit < 105% -

Maximum voltage for energizing (50.0-180.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s ±0.2% or ±100 ms whichever is
Urated greater

Operate time for synchrocheck function when angle difference between bus Min. = 15 ms –
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees Max. = 30 ms

Operate time for energizing function when voltage jumps from 0 to 90% of Min. = 70 ms –
Urated Max. = 90 ms

86 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 77. Autorecloser SMBRREC

Function Range or value Accuracy

Number of autoreclosing shots 1-5 -

Autoreclosing open time:


shot 1 - t1 1Ph (0.000-120.000) s ±0.2% or ±35 ms
shot 1 - t1 2Ph whichever is greater
shot 1 - t1 3PhHS
shot 1 - t1 3Ph

shot 2 - t2 3Ph (0.00-6000.00) s ±0.2% or ±35 ms


shot 3 - t3 3Ph whichever is greater
shot 4 - t4 3Ph
shot 5 - t5 3Ph

Extended autorecloser open time (0.000-60.000) s ±0.2% or ±35 ms


whichever is greater

Minimum time CB must be closed before AR becomes ready for autoreclosing cycle (0.00-6000.00) s ±0.2% or ±35 ms
whichever is greater

Maximum operate pulse duration (0.000-60.000) s ±0.2% or ±15 ms


whichever is greater

Reclaim time (0.00-6000.00) s ±0.2% or ±15 ms


whichever is greater

Circuit breaker closing pulse length (0.000-60.000) s ±0.2% or ±15 ms


whichever is greater

Wait for master release (0.00-6000.00) s ±0.2% or ±15 ms


whichever is greater

Inhibit reset time (0.000-60.000) s ±0.2% or ±45 ms


whichever is greater

Autorecloser maximum wait time for sync (0.00-6000.00) s ±0.2% or ±45 ms


whichever is greater

CB check time before unsuccessful (0.00-6000.00) s ±0.2% or ±45 ms


whichever is greater

Wait time after close command before proceeding to next shot (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater

ABB 87
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Scheme communication

Table 78. Scheme communication logic for distance or overcurrent protection ZCPSCH

Function Range or value Accuracy

Scheme type Off -


Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking

Operate voltage, Delta U (0–100)% of UBase ±5.0% of ΔU

Operate current, Delta I (0–200)% of IBase ±5.0% of ΔI

Operate zero sequence voltage, (0–100)% of UBase ±10.0% of Δ3U0


Delta 3U0

Operate zero sequence current, (0–200)% of IBase ±10.0% of Δ3I0


Delta 3I0

Co-ordination time for blocking (0.000-60.000) s ±0.5% ±10 ms


communication scheme

Minimum duration of a carrier send (0.000-60.000) s ±0.5% ±10 ms


signal

Security timer for loss of guard signal (0.000-60.000) s ±0.5% ±10 ms


detection

Operation mode of unblocking logic Off -


NoRestart
Restart

Table 79. Phase segregated scheme communication logic for distance protection ZC1PPSCH

Function Range or value Accuracy

Scheme type Intertrip -


Permissive UR
Permissive OR
Blocking

Co-ordination time for blocking (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


communication scheme

Minimum duration of a carrier send (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


signal

Table 80. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH

Function Range or value Accuracy

Detection level phase to neutral (10-90)% of UBase ±0.5% of Ur


voltage

Detection level phase to phase (10-90)% of UBase ±0.5% of Ur


voltage

Reset ratio <105% at (20-90)% of UBase -

Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Coordination time for weak-end (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


infeed logic

88 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 81. Scheme communication logic for residual overcurrent protection ECPSCH

Function Range or value Accuracy

Scheme type Permissive Underreaching -


Permissive Overreaching
Blocking

Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater


coordination time

Table 82. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH

Function Range or value Accuracy

Operate mode of WEI logic Off -


Echo
Echo & Trip

Operate voltage 3U0 for WEI trip (5-70)% of UBase ±0.5% of Ur

Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic

Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater

Coordination time for weak-end (0.000–60.000) s ±0.2% or ±30 ms whichever is greater


infeed logic

ABB 89
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Direct transfer trip

Table 83. Low active power and power factor protection LAPPGAPC

Function Range or value Accuracy

Operate value, low active power (2.0-100.0)% of SBase ±1.0% of Sr

Reset ratio, low active power <105% -

Operate value, low power factor 0.00-1.00 ±0.02

Independent time delay to operate for low active power at 1.2 to 0.8 (0.000-60.000) s ±0.2% or ±40 ms whichever is
x Pset greater

Independent time delay to operate for low power factor at 1.2 to 0.8 (0.000-60.000) s ±0.2% or ±40 ms whichever is
x PFset greater

Critical impulse time, low active power 10 ms typically at 1.2 to 0.8 x Pset -

Impulse margin time, low active power 10 ms typically -

Table 84. Compensated over- and undervoltage protection COUVGAPC

Function Range or value Accuracy

Operate value, undervoltage (1-100)% of UBase ±0,5% of Ur

Absolute hysteresis (0.00–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Critical impulse time, undervoltage 10 ms typically at 1.2 to 0.8x Uset -

Impulse margin time, undervoltage 15 ms typically -

Operate value, overvoltage (1-200)% of UBase ±0.5% of Ur at U≤Ur


± 0.5% of U at U>Ur

Critical impulse time, overvoltage 10 ms typically at 0.8 to 1.2 x Uset -

Impulse margin time, overvoltage 15 ms typically -

Independent time delay for undervoltage functionality at 1.2 to (0.000-60.000) s ±0.2% or ±40 ms whichever is
0.8 x Uset greater

Independent time delay for overvoltage functionality at 0.8 to 1.2 (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
x Uset

Table 85. Sudden change in current variation SCCVPTOC

Function Range or value Accuracy

Operate value, overcurrent (5-100)% of IBase ±2.0% of Ir

Hold time for operate signal at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater

Table 86. Carrier receive logic LCCRPTRC

Function Range or value Accuracy

Operation mode 1 Out Of 2 -


2 Out Of 2

Independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is


greater

90 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 87. Negative sequence overvoltage protection LCNSPTOV

Function Range or value Accuracy

Operate value, negative sequence overvoltage (1-200)% of UBase ±0.5% of Ur at U≤Ur


±0.5% of U at U>Ur

Reset ratio, negative sequence overvoltage >95% at (10–200)% of UBase -

Operate time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 to 0 x Uset Min. = 15 ms -


Max. = 30 ms

Critical impulse time, negative sequence overvoltage 10 ms typically at 0 to 2 x Uset -

Impulse margin time, negative sequence overvoltage 15 ms typically -

Independent time delay to operate at 0 to 1.2 x Uset (0.000-120.000) s ±0.2% or ±40 ms whichever is
greater

Table 88. Zero sequence overvoltage protection LCZSPTOV

Function Range or value Accuracy

Operate value, zero sequence overvoltage (1-200)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Reset ratio, zero sequence overvoltage >95% at (10–200)% of UBase -

Operate time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 to 0 x Uset Min. = 15 ms -


Max. = 30 ms

Critical impulse time, zero sequence overvoltage 10 ms typically at 0 to 2 x Uset -

Impulse margin time, zero sequence overvoltage 15 ms typically -

Independent time delay to operate at 0 to 1.2 x Uset (0.000-120.000) s ±0.2% or ±40 ms whichever is
greater

ABB 91
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 89. Negative sequence overcurrent protection LCNSPTOC

Function Range or value Accuracy

Operate value, negative sequence overcurrent (3 - 2500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio, negative sequence overcurrent >95% at (50–2500)% of IBase -

Operate time, start at 0 to 2 x Iset Min. = 15 ms -


Max. = 25 ms

Reset time, start at 2 to 0 x Iset Min. = 15 ms -


Max. = 25 ms

Operate time, start at 0 to 10 x Iset Min. = 10 ms -


Max. = 20 ms

Reset time, start at 10 to 0 x Iset Min. = 20 ms -


Max. = 35 ms

Critical impulse time, negative sequence overcurrent 10 ms typically at 0 to 2 x Iset -


2 ms typically at 0 to 10 x Iset

Impulse margin time, negative sequence overcurrent 15 ms typically -

Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms, whichever is


greater

Transient overreach, start function <5% at τ = 100 ms -

Table 90. Zero sequence overcurrent protection LCZSPTOC

Function Range or value Accuracy

Operate value, zero sequence overcurrent (3-2500)% of IBase ±1.0% of Ir at I≤Ir


±1.0% of I at I>Ir

Reset ratio, zero sequence overcurrent >95% at (50–2500)% of IBase -

Operate time, start at 0 to 2 x Iset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 to 0 x Iset Min. = 15 ms -


Max. = 30 ms

Operate time, start at 0 to 10 x Iset Min. = 10 ms -


Max. = 20 ms

Reset time, start at 10 to 0 x Iset Min. = 20 ms -


Max. = 35 ms

Critical impulse time, zero sequence overcurrent 10 ms typically at 0 to 2 x Iset -


2 ms typically at 0 to 10 x Iset

Impulse margin time, zero sequence overcurrent 15 ms typically -

Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is


greater

92 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 91. Three phase overcurrent LCP3PTOC

Function Range or value Accuracy

Operate value, overcurrent (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio, overcurrent > 95% at (50-2500)% of IBase -

Start time at 0 to 2 x Iset Min. = 10 ms -


Max. = 25 ms

Reset time at 2 to 0 x Iset Min. = 20 ms -


Max. = 35 ms

Critical impulse time, overcurrent 5 ms typically at 0 to 2 x Iset -


2 ms typically at 0 to 10 x Iset

Impulse margin time, overcurrent 10 ms typically -

Independent time delay to operate at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is


greater

Table 92. Three phase undercurrent LCP3PTUC

Function Range or value Accuracy

Operate value, undercurrent (1.00-100.00)% of IBase ±1.0% of Ir

Reset ratio, undercurrent < 105% at (50.00-100.00)% of IBase -

Start time at 2 to 0 x Iset Min. = 15 ms -


Max. = 30 ms

Reset time at 0 to 2 x Iset Min. = 10 ms -


Max. = 25 ms

Critical impulse time, undercurrent 10 ms typically at 2 to 0 x Iset -

Impulse margin time, undercurrent 10 ms typically -

Independent time delay to operate at 2 to 0 x Iset (0.000-60.000) s ±0.2% or ±45 ms whichever is


greater

ABB 93
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Logic

Table 93. Tripping logic common 3-phase output SMPPTRC

Function Range or value Accuracy

Trip action 3-ph, 1/3-ph, 1/2/3-ph -

Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater

Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Table 94. Number of SMPPTRC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

SMPPTRC 6 - -

Table 95. Number of TMAGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

TMAGAPC 6 6 -

Table 96. Number of ALMCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

ALMCALH - - 5

Table 97. Number of WRNCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

WRNCALH - - 5

Table 98. Number of INDCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

INDCALH - 5 -

Table 99. Number of AND instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

AND 60 60 160

Table 100. Number of GATE instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

GATE 10 10 20

94 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 101. Number of INV instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INV 90 90 240

Table 102. Number of LLD instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

LLD 10 10 20

Table 103. Number of OR instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

OR 69 60 160

Table 104. Number of PULSETIMER instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms

Table 105. Number of RSMEMORY instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

RSMEMORY 10 10 20

Table 106. Number of SRMEMORY instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

SRMEMORY 10 10 20

Table 107. Number of TIMERSET instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms

Table 108. Number of XOR instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

XOR 10 10 20

ABB 95
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 109. Number of ANDQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

ANDQT - 20 100

Table 110. Number of INDCOMBSPQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INDCOMBSPQT - 10 10

Table 111. Number of INDEXTSPQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INDEXTSPQT - 10 10

Table 112. Number of INVALIDQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INVALIDQT - 6 6

Table 113. Number of INVERTERQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INVERTERQT - 20 100

Table 114. Number of ORQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

ORQT - 20 100

Table 115. Number of PULSETIMERQT instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

PULSETIMERQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms

Table 116. Number of RSMEMORYQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

RSMEMORYQT - 10 30

96 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 117. Number of SRMEMORYQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

SRMEMORYQT - 10 30

Table 118. Number of TIMERSETQT instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

TIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms

Table 119. Number of XORQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

XORQT - 10 30

Table 120. Number of instances in the extension logic package

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

AND 40 40 100

GATE - - 49

INV 40 40 100

LLD - - 49

OR 40 40 100

PULSETIMER 5 5 49

SLGAPC 10 10 54

SRMEMORY - - 110

TIMERSET - - 49

VSGAPC 10 10 110

XOR - - 49

Table 121. Number of B16I instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

B16I 6 4 8

Table 122. Number of BTIGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

BTIGAPC 4 4 8

ABB 97
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 123. Number of IB16 instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

IB16 6 4 8

Table 124. Number of ITBGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

ITBGAPC 4 4 8

Table 125. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC

Function Cycle time (ms) Range or value Accuracy

Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is greater

8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever is


greater

100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever is


greater

Table 126. Number of TEIGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

TEIGAPC 4 4 4

Table 127. Running hour-meter TEILGAPC

Function Range or value Accuracy

Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value

Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value

Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%

98 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Monitoring

Table 128. Measurements CVMMXN

Function Range or value Accuracy

Frequency (0.95-1.05) x fr ±2.0 mHz

Voltage (10 to 300) V ±0.3% of U at U≤ 50 V


±0.2% of U at U> 50 V

Current (0.1-4.0) x Ir ±0.8% of I at 0.1 x Ir< I < 0.2 x Ir


± 0.5% of I at 0.2 x Ir< I < 0.5 x Ir
±0.2% of I at 0.5 x Ir< I < 4.0 x Ir

Active power, P (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of P


(0.5-2.0) x Ir
cos φ< 0.7

Reactive power, Q (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of Q


(0.5-2.0) x Ir
cos φ> 0.7

Apparent power, S (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S >0.5 x Sr

(100 to 220) V ±0.2% of S


(0.5-2.0) x Ir

Power factor, cos (φ) (10 to 300) V <0.02


(0.1-4.0) x Ir

(100 to 220) V <0.01


(0.5-2.0) x Ir

Table 129. Phase current measurement CMMXU

Function Range or value Accuracy

Current at symmetrical load (0.1-4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


±0.3% of I at I > 0.5 × Ir

Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

Table 130. Phase-phase voltage measurement VMMXU

Function Range or value Accuracy

Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V

ABB 99
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 131. Phase-neutral voltage measurement VNMMXU

Function Range or value Accuracy

Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V

Table 132. Current sequence component measurement CMSQI

Function Range or value Accuracy

Current positive sequence, I1 (0.1–4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Current zero sequence, 3I0 Three (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


phase settings ±0.3% of I at I > 0.5 × Ir

Current negative sequence, I2 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

Table 133. Voltage sequence measurement VMSQI

Function Range or value Accuracy

Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Voltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Voltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V

Table 134. Supervision of mA input signals

Function Range or value Accuracy

mA measuring function ±5, ±10, ±20 mA ±0.1 % of set value ±0.005 mA


0-5, 0-10, 0-20, 4-20 mA

Max current of transducer to (-20.00 to +20.00) mA


input

Min current of transducer to (-20.00 to +20.00) mA


input

Alarm level for input (-20.00 to +20.00) mA

Warning level for input (-20.00 to +20.00) mA

Alarm hysteresis for input (0.0-20.0) mA

Table 135. Limit counter L4UFCNT

Function Range or value Accuracy

Counter value 0-65535 -

Max. count up speed 30 pulses/s (50% duty cycle) -

100 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 136. Disturbance report DRPRDRE

Function Range or value Accuracy

Pre-fault time (0.05–9.90) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–10.0) s -

Maximum number of recordings 100, first in - first out -

Time tagging resolution 1 ms See table 167

Maximum number of analog inputs 30 + 10 (external + internally -


derived)

Maximum number of binary inputs 96 -

Maximum number of phasors in the Trip Value recorder per recording 30 -

Maximum number of indications in a disturbance report 96 -

Maximum number of events in the Event recording per recording 150 -

Maximum number of events in the Event list 1000, first in - first out -

Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz

Sampling rate 1 kHz at 50 Hz -


1.2 kHz at 60 Hz

Recording bandwidth (5-300) Hz -

Table 137. Insulation gas monitoring function SSIMG

Function Range or value Accuracy

Pressure alarm level 1.00-100.00 ±10.0% of set value

Pressure lockout level 1.00-100.00 ±10.0% of set value

Temperature alarm level -40.00-200.00 ±2.5% of set value

Temperature lockout level -40.00-200.00 ±2.5% of set value

Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

ABB 101
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 138. Insulation liquid monitoring function SSIML

Function Range or value Accuracy

Oil alarm level 1.00-100.00 ±10.0% of set value

Oil lockout level 1.00-100.00 ±10.0% of set value

Temperature alarm level -40.00-200.00 ±2.5% of set value

Temperature lockout level -40.00-200.00 ±2.5% of set value

Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Table 139. Breaker monitoring SSCBR

Function Range or value Accuracy

Alarm level for open and close travel time (0 – 200) ms ±3 ms

Alarm level for number of operations (0 – 9999) -

Independent time delay for spring charging time (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm

Independent time delay for gas pressure alarm (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater

Independent time delay for gas pressure lockout (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater

CB Contact Travel Time, opening and closing ±3 ms

Remaining Life of CB ±2 operations

Accumulated Energy ±1.0% or ±0.5 whichever is greater

Table 140. Fault locator LMBRFLO

Function Value or range Accuracy

Reactive and resistive reach (0.001-1500.000) Ω/phase ±2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir

Phase selection According to input signals -

Maximum number of fault 100 -


locations

Table 141. Event list

Function Value

Buffer capacity Maximum number of events in the list 1000

Resolution 1 ms

Accuracy Depending on time synchronizing

102 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 142. Indications

Function Value

Buffer capacity Maximum number of indications presented for single disturbance 96

Maximum number of recorded disturbances 100

Table 143. Event recorder

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending on time


synchronizing

Table 144. Trip value recorder

Function Value

Buffer capacity Maximum number of analog inputs 30

Maximum number of disturbance reports 100

Table 145. Disturbance recorder

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 96

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at 50 Hz
channels, typical value) 280 seconds (80 recordings) at 60 Hz

Table 146. Limit counter L4UFCNT

Function Range or value Accuracy

Counter value 0-65535 -

Max. count up speed 30 pulses/s (50% duty cycle) -

ABB 103
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Metering

Table 147. Pulse-counter logic PCFCNT

Function Setting range Accuracy

Input frequency See Binary Input Module (BIM) -

Cycle time for report of counter (1–3600) s -


value

Table 148. Energy metering ETPMMTR

Function Range or value Accuracy

Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import

104 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Station communication

Table 149. Communication protocols

Function Value

Protocol IEC 61850-8-1

Communication speed for the IEDs 100BASE-FX

Protocol IEC 60870–5–103

Communication speed for the IEDs 9600 or 19200 Bd

Protocol DNP3.0

Communication speed for the IEDs 300–19200 Bd

Protocol TCP/IP, Ethernet

Communication speed for the IEDs 100 Mbit/s

Table 150. IEC 61850-9-2 communication protocol

Function Value

Protocol IEC 61850-9-2

Communication speed for the IEDs 100BASE-FX

Table 151. LON communication protocol

Function Value

Protocol LON

Communication speed 1.25 Mbit/s

Table 152. SPA communication protocol

Function Value

Protocol SPA

Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd

Slave number 1 to 899

Table 153. IEC 60870-5-103 communication protocol

Function Value

Protocol IEC 60870-5-103

Communication speed 9600, 19200 Bd

Table 154. SLM – LON port

Quantity Range or value

Optical connector Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)


Plastic fiber: 7 dB (10m/35ft typically *)

Fiber diameter Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation

ABB 105
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 155. SLM – SPA/IEC 60870-5-103/DNP3 port

Quantity Range or value

Optical connector Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)


Plastic fiber: 7 dB (25m/80ft m typically *)

Fiber diameter Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation

Table 156. Galvanic X.21 line data communication module (X.21-LDCM)

Quantity Range or value

Connector, X.21 Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch

Connector, ground selection 2 pole screw terminal

Standard CCITT X21

Communication speed 64 kbit/s

Insulation 1 kV

Maximum cable length 100 m

Table 157. Galvanic RS485 communication module

Quantity Range or value

Communication speed 2400–19200 bauds

External connectors RS-485 6-pole connector


Soft ground 2-pole connector

Table 158. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol

Function Value

Communication speed 100 Base-FX

106 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Remote communication

Table 159. Line data communication module

Characteristic Range or value

Type of LDCM Short range (SR) Medium range (MR) Long range (LR)

Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm


multimode
62.5/125 µm

Peak Emission Wave length


Nominal 820 nm 1310 nm 1550 nm
Maximum 865 nm 1330 nm 1580 nm
Minimum 792 nm 1290 nm 1520 nm

Optical budget 13 dB (typical 22 dB (typical 26 dB (typical distance 110 km/68


Graded-index multimode 62.5/125 mm, distance about 3 distance 80 km/50 mile *)
km/2 mile *) mile *)
9 dB (typical
Graded-index multimode 50/125 mm distance about 2
km/1 mile *)

Optical connector Type ST Type FC/PC Type FC/PC

Protocol C37.94 C37.94 C37.94 implementation **)


implementation **)

Data transmission Synchronous Synchronous Synchronous

Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s

Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal

*) depending on optical budget calculation


**) C37.94 originally defined just for multimode; using same header, configuration and data format as C37.94

ABB 107
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Hardware
IED

Table 160. Case

Material Steel sheet

Front plate Steel sheet profile with cut-out for HMI

Surface treatment Aluzink preplated steel

Finish Light grey (RAL 7035)

Table 161. Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)

Sides, top and bottom IP20

Rear side IP20 with screw compression type


IP10 with ring lug terminals

Table 162. Weight

Case size Weight

6U, 1/2 x 19” £ 10 kg/22 lb

6U, 3/4 x 19” £ 15 kg/33 lb

6U, 1/1 x 19” £ 18 kg/40 lb

Electrical safety

Table 163. Electrical safety according to IEC 60255-27

Equipment class I (protective earthed)

Overvoltage category III

Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)

Connection system

Table 164. CT and VT circuit connectors

Connector type Rated voltage and current Maximum conductor area

Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)


2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)

Table 165. Auxiliary power supply and binary I/O connectors

Connector type Rated voltage Maximum conductor area

Screw compression type 250 V AC 2.5 mm2 (AWG14)


2 × 1 mm2 (2 x AWG18)

Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)

Because of limitations of space, when ring between two adjacent IO cards. Please refer
lug terminal is ordered for Binary I/O to the ordering particulars for details.
connections, one blank slot is necessary

108 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Basic IED functions

Table 166. Self supervision with internal event list

Data Value

Recording manner Continuous, event controlled

List size 40 events, first in-first out

Table 167. Time synchronization, time tagging

Function Value

Time tagging resolution, events and sampled measurement values 1 ms

Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values

Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically

Table 168. GPS time synchronization module (GTM)

Function Range or value Accuracy

Receiver – ±1µs relative UTC

Time to reliable time reference with antenna in new <30 minutes –


position or after power loss longer than 1 month

Time to reliable time reference after a power loss longer <15 minutes –
than 48 hours

Time to reliable time reference after a power loss shorter <5 minutes –
than 48 hours

Table 169. GPS – Antenna and cable

Function Value

Max antenna cable attenuation 26 db @ 1.6 GHz

Antenna cable impedance 50 ohm

Lightning protection Must be provided externally

Antenna cable connector SMA in receiver end


TNC in antenna end

Accuracy +/-1μs

ABB 109
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 170. IRIG-B

Quantity Rated value

Number of channels IRIG-B 1

Number of optical channels 1

Electrical connector:

Electrical connector IRIG-B BNC

Pulse-width modulated 5 Vpp

Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp

Supported formats IRIG-B 00x, IRIG-B 12x

Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x

Input impedance 100 k ohm

Optical connector:

Optical connector IRIG-B Type ST

Type of fibre 62.5/125 μm multimode fibre

Supported formats IRIG-B 00x

Accuracy +/- 1μs

110 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Inverse characteristic

Table 171. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 ,


1.5 x Iset ≤ I ≤ 20 x Iset ±2.0% or ±40 ms
æ
A
ö whichever is greater
t=ç + B ÷ × k + tDef
è
P
(
çç I - 1 ÷÷
ø)
EQUATION1249-SMALL V2 EN

Reset characteristic:

tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

ABB 111
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 172. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Programmable characteristic k = (0.05-999) in steps of 0.01


Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷
è ø TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
EQUATION1370-SMALL V1 EN
PR=(0.005-3.000) in steps of 0.001
Reset characteristic:

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN

I = Imeasured/Iset

Table 173. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever is
1 greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN

I = Imeasured/Iset

RD type logarithmic inverse characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

112 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 174. Inverse time characteristics for overvoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms


whichever is greater
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k ⋅ 480
t = + 0.035
2.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1437-SMALL V2 EN

Type C curve: k = (0.05-1.10) in steps of 0.01

k ⋅ 480
t = + 0.035
3.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1438-SMALL V2 EN

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
k×A B = (0.50-100.00) in steps of 0.01
t = +D C = (0.0-1.0) in steps of 0.1
P
æB × U -U > ö D = (0.000-60.000) in steps of 0.001
ç -C÷
è U > ø P = (0.000-3.000) in steps of 0.001
EQUATION1439-SMALL V1 EN

ABB 113
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 175. Inverse time characteristics for undervoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms


whichever is greater
k
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN

U< = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN

U< = Uset
U = Umeasured

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
é ù B = (0.50-100.00) in steps of 0.01
ê k×A
ú C = (0.0-1.0) in steps of 0.1
t =ê ú+D D = (0.000-60.000) in steps of 0.001
ê æ U < -U ö
P
ú P = (0.000-3.000) in steps of 0.001
êçB × -C÷ ú
ëè U < ø û
EQUATION1433-SMALL V1 EN

U< = Uset
U = Umeasured

114 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 176. Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater


0.01
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of


0.01
k ⋅ 480
t = + 0.035
2.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1437-SMALL V2 EN

Type C curve: k = (0.05-1.10) in steps of


0.01
k ⋅ 480
t = + 0.035
3.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1438-SMALL V2 EN

Programmable curve: k = (0.05-1.10) in steps of


0.01
k×A A = (0.005-200.000) in
t = +D steps of 0.001
P
æB × U - U > ö B = (0.50-100.00) in steps
ç -C÷
è U > ø of 0.01
EQUATION1439-SMALL V1 EN C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001

ABB 115
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

22. Ordering for customized IED

Table 177. General guidelines

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

Table 178. Example ordering code

To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0
Example of a complete code: RED670*2.1 - F00X00 - A00000030211111 - B5225255221255221111101000 - C3300032122020022221000300 - D22212 011 - E2220 -
F4 - S6 - G232 - H20401100000 - K11111111 - L11 - M21 - P01 - B1X0 - AC -MB - B - A3X0 - D1D1ARGN1N1XXXXXXX - AAFXXX - AX

Product definition - Differential protection -


RED670* 2.1 - X00 - A 0 0 0 0 0 0 0 -

Impedance protection -
B 0 0 0 0 -

Current protection -
C 00 0 00 1 0 0 0 0 0 -

Voltage protection - Frequency protection - Multipurpose - General -


protection calculation
D 0 1 - E 0 - F - S -

Secondary system supervision - Control -


G - H 0 0 0 0 0 0 0 -

Scheme communication - Logic - Monitoring - Station communication -


K - L - M 1 - P 0 0 0 0 0 0 0 0 0 0 0 -

Langu - Casing - Connection - HMI - Analog input - Binary input/output -


age and and power
Mounting
B - - - - - -
1

Remote end serial communication - Serial communication unit for station communication
-

Table 179. Product definition

RED670* 2.1 X00

Table 180. Product definition ordering codes

Product RED670*
Software version 2.1
Configuration alternatives
Line differential protection RED670 F00
Line differential protection RED670 61850-9-2LE N00
Selection:
ACT configuration
No ACT configuration downloaded X00

Table 181. Differential protection

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14
A 0 0 0 0 0 0 0

116 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 182. Differential functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
1Ph High impedance differential protection HZPDIF 1MRK005904-HA 7 0-3
Restricted earth fault protection, low impedance REFPDIF 1MRK005904-LC 9 0-2
Line differential protection, 3 CT sets, 2-3 line ends L3CPDIF 1MRK005904-MB 10 0-1 Note: One,
and only
Line differential protection, 6 CT sets, 3-5 line ends L6CPDIF 1MRK005904-NB 11 0-1
one PDIF
Line differential protection 3 CT sets, with inzone transformers, 2-3 line LT3CPDIF 1MRK005904-PB 12 0-1 must be
ends ordered.
Line differential protection 6 CT sets, with inzone transformers, 3-5 line LT6CPDIF 1MRK005904-RB 13 0-1
ends
Additional security logic for differential protection LDRGFC 1MRK005904-TA 14 0-1

Table 183. Impedance protection

Po 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
siti
on
B 0 0 0 0

ABB 117
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 184. Impedance functions, alternatives

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Note: One, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative.
Alternative 1 Distance protection, quadrilateral
Distance protection zone, quadrilateral characteristic ZMQPDIS, 1MRK005907-AA 1 0-5
ZMQAPDIS
Directional impedance quadrilateral ZDRDIR 1MRK005907-BA 2 0-2
Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS 1MRK005907-CA 3 0-2
Alternative 2 Distance protection for series compensated lines, quadrilateral
Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS 1MRK005907-CA 3 0-2
Distance measuring zone, quadrilateral characteristic for series ZMCPDIS, 1MRK005907-DA 4 0-5
compensated lines ZMCAPDIS
Directional impedance quadrilateral, including series compensation ZDSRDIR 1MRK005907-EA 5 0-2
Alternative 3 Distance protection, mho (mho for phase - phase fault and mho in parallel with quad for earth fault)
Fullscheme distance protection, mho characteristic ZMHPDIS 1MRK005907-FA 6 0-5
Fullscheme distance protection, quadrilateral for earth faults ZMMPDIS, 1MRK005907-GA 7 0-5
ZMMAPDIS
Directional impedance element for mho characteristic ZDMRDIR 1MRK005907-HA 8 0-2
Additional distance protection directional function for earth faults ZDARDIR 1MRK005907-KA 9 0-2
Mho Impedance supervision logic ZSMGAPC 1MRK005907-LA 10 0-1
Faulty phase identification with load encroachment FMPSPDIS 1MRK005907-MA 11 0-2
Alternative 4 Distance protection, quadrilateral with separate settings for PP and PE
Directional impedance quadrilateral ZDRDIR 1MRK005907-BA 2 0-2
Distance protection zone, quadrilateral characteristic, separate settings ZMRPDIS, 1MRK005907-NA 12 0-5
ZMRAPDIS
Phase selection, quadrilateral characteristic with settable angle FRPSPDIS 1MRK005907-PA 13 0-2
Alternative 5 High speed distance protection, quadrilateral and mho
High speed distance protection, quad and mho characteristic ZMFPDIS 1MRK005907-SB 14 0-1
Alternative 6 High speed distance protection for series compensated lines, quadrilateral and mho
High speed distance protection for series compensated lines, quad and ZMFCPDIS 1MRK005907-RB 15 0-1
mho characteristic
Optional for alternative 1
Directional impedance element for mho characteristic ZDMRDIR 1MRK005907-HA 8 0-2
Optional for alternative 3
Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS 1MRK005907-CA 3 0-2
Optional for alternatives 1, 2 and 4
Additional distance protection directional function for earth faults ZDARDIR 1MRK005907-KA 9 0-2
Faulty phase identification with load encroachment FMPSPDIS 1MRK005907-MA 11 0-2
Optional with any alternative

Power swing detection ZMRPSB 1MRK005907-UA 16 0-1


Automatic switch onto fault logic, voltage and current based ZCVPSOF 1MRK005908-AA 17 0-1
Power swing logic PSLPSCH 1MRK005907-VA 18 0-1
PoleSlip/Out-of-step protection PSPPPAM 1MRK005908-CB 19 0-1
Out-of-step protection OOSPPAM 1MRK005908-GA 20 0-1
Phase preference logic PPLPHIZ 1MRK005908-DA 22 0-1

Table 185. Current protection

Pos 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
itio
n
C 00 0 00 1 0 0 0 0 0

118 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 186. Current functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AC 1 0-3
Four step phase overcurrent protection OC4PTOC 1MRK005910-BB 2 0-3
Instantaneous residual overcurrent protection EFPIOC 1MRK005910-DC 4 0-1
Four step residual overcurrent protection EF4PTOC 1MRK005910-EC 5 0-3
Four step directional negative phase sequence overcurrent protection NS4PTOC 1MRK005910-FB 6 0-2
Sensitive Directional residual over current and power protetcion SDEPSDE 1MRK005910-GA 7 0-1
Thermal overload protection, one time constant, Celcius LCPTTR 1MRK005911-BA 8 0-2
Thermal overload protection, one time constant, Fahrenheit LFPTTR 1MRK005911-AA 9 0-2
Breaker failure protection CCRBRF 1MRK005910-LA 11 0-2
Stub protection STBPTOC 1MRK005910-NA 13 0-2
Pole discordance protection CCPDSC 1MRK005910-PA 14 0-2
Directional Underpower protection GUPPDUP 1MRK005910-RA 15 0-2
Directional Overpower protection GOPPDOP 1MRK005910-TA 16 0-2
Broken conductor check BRCPTOC 1MRK005910-SA 17 1
Voltage restrained overcurrent protection VRPVOC 1MRK005910-XA 21 0-3

Table 187. Voltage protection

Position 1 2 3 4 5 6 7 8
D 0 1

Table 188. Voltage functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Two step undervoltage protection UV2PTUV 1MRK005912-AA 1 0-2
Two step overvoltage protection OV2PTOV 1MRK005912-BA 2 0-2
Two step residual overvoltage protection ROV2PTOV 1MRK005912-CA 3 0-2
Overexcitation protection OEXPVPH 1MRK005912-DA 4 0-1
Voltage differential protection VDCPTOV 1MRK005912-EA 5 0-2
Loss of voltage check LOVPTUV 1MRK005912-GA 7 1
Radial feeder protection PAPGAPC 1MRK005912-HA 8 0-1

Table 189. Frequency protection

Position 1 2 3 4
E 00

Table 190. Frequency functions

Function Function Ordering no positi Available Selected Notes and


identification on qty qty rules
Underfrequency protection SAPTUF 1MRK005914-AA 1 0-6
Overfrequency protection SAPTOF 1MRK005914-BA 2 0-6
Rate-of-change frequency protection SAPFRC 1MRK005914-CA 3 0-6

Table 191. Multipurpose protection

Position 1
F

Table 192. Multipurpose functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty Qty rules
General current and voltage protection CVGAPC 1MRK005915-AA 1 0-4

ABB 119
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 193. General calculation

Position 1
S

Table 194. General calculation functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Frequency tracking filter SMAIHPAC 1MRK005915-KA 1 0-6

Table 195. Secondary system supervision

Position 1 2 3
G

Table 196. Secondary system supervision functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Current circuit supervison CCSSPVC 1MRK005916-AA 1 0-2
Fuse failure supervision FUFSPVC 1MRK005916-BA 2 0-3
Fuse failure supervision based on voltage difference VDSPVC 1MRK005916-CA 3 0-2

Table 197. Control

Position 1 2 3 4 5 6 7 8 9 10 11
H 0 0 0 0 0 0 0

Table 198. Control functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty Qty rules
Synchrocheck, energizing check and synchronizing SESRSYN 1MRK005917-AA 1 0-2
Autorecloser SMBRREC 1MRK005917-BA 3 0-4
Apparatus control for single bay, max 10 app. (1CB) incl. Interlocking APC10 1MRK005917-AY 5 0-1 Note: Only
one
Apparatus control for single bay, max 15 app. (2CBs) incl. Interlocking APC15 1MRK005917-BY 6 0-1
Apparatus
control
can be
ordered.

Table 199. Scheme communication

Position 1 2 3 4 5 6 7 8
K

Table 200. Scheme communication functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Scheme communication logic for distance or Overcurrent protection ZCPSCH 1MRK005920-AA 1 0-2 Note: Only
one of
Phase segregated Scheme communication logic for distance protection ZC1PPSCH 1MRK005920-BA 2 0-2
ZCPSCH/
Current reversal and weak-end infeed logic for distance protection ZCRWPSCH 1MRK005920-CA 3 0-2 ZC1PPSC
Current reversal and weak-end infeed logic for phase segregated ZC1WPSCH 1MRK005920-DA 4 0-2 H can be
communication selected
Note: Only
one of
ZCRWPS
CH/
ZC1WPS
CH to be
selected
Local acceleration logic ZCLCPSCH 1MRK005920-EA 5 0-1
Scheme communication logic for residual overcurrent protection ECPSCH 1MRK005920-FA 6 0-1
Current reversal and weakend infeed logic for residual overcurrent ECRWPSCH 1MRK005920-GA 7 0-1
protection
Direct transfer trip DTT 1MRK005921-AX 8 0-1

120 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 201. Logic

Position 1 2
L

Table 202. Logic functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Configurable logic blocks Q/T 1MRK005922-MX 1 0-1
Extension logic package 1MRK005922-AY 2 0-1

Table 203. Monitoring

Position 1 2
M 1

Table 204. Monitoring functions

Function Function Ordering no Positi Available Selected Notes and


identification on qty qty rules
Circuit breaker condition monitoring SSCBR 1MRK005924-HA 1 00-06
Fault locator LMBRFLO 1MRK005925-XB 2 1

Table 205. Station communication

Position 1 2 3 4 5 6 7 8 9 10 11 12 13
P 0 0 0 0 0 0 0 0 0 0 0

Table 206. Station communication functions

Function Function Ordering no Position Available qty Selected qty Notes and rules
identification
Process Bus communication IEC 61850-9-2 1MRK005930-TA 1 0 if F00 is Note: RED670
selected, 6 if customized qty =
N00 is selected 0, RED670
61850-9-2 qty = 6
IEC 62439-3 parallel redundancy protocol PRP 1MRK002924-YB 2 1 Note: Not valid in
RED670
61850-9-2LE
product
Note: Requires
2–channel OEM

Table 207. Language selection

First local HMI user dialogue language Selection Notes and Rules
HMI language, English IEC B1
Additional HMI language
No additional HMI language X0
HMI language, English US A12
Selected

Table 208. Casing selection

Casing Selection Notes and Rules


1/2 x 19" case A
3/4 19” case 1 TRM slot B
3/4 x 19" case 2 TRM slots C
1/1 x 19” case 1 TRM slot D
1/1 x 19" case 2 TRM slots E
Selected

ABB 121
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 209. Mounting selection

Mounting details with IP40 of protection from the front Selection Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selected

Table 210. Connection type for Power supply module

Selection Notes and Rules


Compression terminals M
Ringlug terminals N
Auxiliary power supply
Power supply module 24-60 VDC A
Power supply module 90-250 VDC B
Selected

Table 211. Connection type for Input/Output modules

Selection Notes and Rules


Compression terminals P
Ringlug terminals R
Selected

Table 212. Human machine interface selection

Human machine hardware interface Selection Notes and Rules


Medium size - graphic display, IEC keypad symbols B
Medium size - graphic display, ANSI keypad symbols C
Selected

122 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 213. Analog system selection

Analog system Selection Notes and Rules


No first TRM included X0 Note: Only valid in RED670–N00
Compression terminals A Note: Only the same type of TRM
(compression or ringlug) in the
Ringlug terminals B
same terminal.
First TRM 12I 1A, 50/60Hz 1
First TRM 12I 5A, 50/60Hz 2
First TRM 9I+3U 1A, 100/220V, 50/60Hz 3
First TRM 9I+3U 5A, 100/220V, 50/60Hz 4
First TRM 5I, 1A+4I, 5A+3U, 100/220V, 50/60Hz 5
First TRM 6I+6U 1A, 100/220V, 50/60Hz 6
First TRM 6I+6U 5A, 100/220V, 50/60Hz 7
First TRM 6I 1A, 50/60Hz 8 Maximum qty = 1
First TRM 6I 5A, 50/60Hz 9 Maximum qty = 1
First TRM 7I+5U 1A, 100/220V, 50/60Hz 12
First TRM 7I+5U 5A, 100/220V, 50/60Hz 13
First TRM 6I, 5A + 1I, 1A + 5U, 110/220V, 50/60Hz 14
First TRM 3I, 5A + 4I, 1A + 5U, 110/220V, 50/60Hz 15
First TRM 3I, 5A + 3I, 1A + 6U, 110/220V, 50/60Hz 16
First TRM 3IM, 1A + 4IP, 1A + 5U, 110/220V, 50/60Hz 17
First TRM 3IM, 5A + 4IP, 5A + 5U, 110/220V, 50/60Hz 18
No second TRM included X0
Compression terminals A
Ringlug terminals B
Second TRM 12I 1A, 50/60Hz 1
Second TRM 12I 5A, 50/60Hz 2
Second TRM 9I+3U 1A, 100/220V, 50/60Hz 3
Second TRM 9I+3U 5A, 100/220V, 50/60Hz 4
Second TRM 5I, 1A+4I, 5A+3U, 100/220V, 50/60Hz 5
Second TRM 6I+6U 1A, 100/220V, 50/60Hz 6
Second TRM 6I+6U 5A, 100/220V, 50/60Hz 7
Second TRM 6I 1A, 50/60Hz 8 Maximum qty = 1
Second TRM 6I 5A, 50/60Hz 9 Maximum qty = 1
Second TRM 7I+5U 1A, 100/220V, 50/60Hz 12
Second TRM 7I+5U 5A, 100/220V, 50/60Hz 13
Second TRM 6I, 5A + 1I, 1A + 5U, 110/220V, 50/60Hz 14
Second TRM 3I, 5A + 4I, 1A + 5U, 110/220V, 50/60Hz 15
Second TRM 3I, 5A + 3I, 1A + 6U, 110/220V, 50/60Hz 16
Second TRM 3IM, 1A + 4IP, 1A + 5U, 110/220V, 50/60Hz 17
Second TRM 3IM, 5A + 4IP, 5A + 5U, 110/220V, 50/60Hz 18
Selected

Table 214. Maximum quantity of I/O modules

Note: When ordering I/O modules, observe the maximum quantities according to the table below
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19”, one (1) TRM 14 6 4 4 14 cards, including a combination of four cards of type BOM, SOM and MIM
1/1 x 19”, two (2) TRM 11 6 4 4 11 cards, including a combination of four cards of type BOM, SOM and MIM
3/4 x 19”, one (1) TRM 8 6 4 4 8 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
3/4 x 19”, two (2) TRM 5 5 4 4 5 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
1/2 x 19”, one (1) TRM 3 3 3 1 3 cards

ABB 123
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 215. Binary input/output module selection

Binary input/output Selection Notes and Rules


modules
Slot position (rear view) Note! Max 3 positions in 1/2 rack, 8
X31

X41

X51

X61

X71

X81

X91

X101

X111

X121

X131

X141

X151

X161
in 3/4 rack with 1TRM, 5 in 3/4 rack
1/2 Case with 1 TRM █ █ █ with 2 TRM, 11 in 1/1 rack with 2
TRM and 14 in 1/1 rack with 1 TRM
3/4 Case with 1 TRM █ █ █ █ █ █ █ █
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X X X
Binary output module 24 A A A A A A A A A A A A A A
output relays (BOM)
BIM 16 inputs, RL24-30 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
VDC, 50 mA
BIM 16 inputs, RL48-60 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
VDC, 50 mA
BIM 16 inputs, D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110-125 VDC, 50 mA
BIM 16 inputs, E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220-250 VDC, 50 mA
BIM 16 inputs, 220-250 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
VDC, 120mA
BIMp 16 inputs, RL24-30 F F F F F F F F F F F F F F
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, RL48-60 G G G G G G G G G G G G G G
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, H H H H H H H H H H H H H H
RL110-125 VDC, 30 mA,
for pulse counting
BIM 16 inputs, K K K K K K K K K K K K K K
RL220-250 VDC, 30 mA,
for pulse counting
IOM 8 inputs, 10+2 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
output, RL24-30 VDC, 50
mA
IOM 8 inputs, 10+2 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
output, RL48-60 VDC, 50
mA
IOM 8 inputs, 10+2 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
output, RL110-125 VDC,
50 mA
IOM 8 inputs, 10+2 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
output, RL220-250 VDC,
50 mA
IOM 8 inputs 10+2 output P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
relays, 220-250 VDC,
110mA
IOM with MOV 8 inputs, U U U U U U U U U U U U U U
10-2 output, 24-30 VDC,
30 mA
IOM with MOV 8 inputs, V V V V V V V V V V V V V V
10-2 output, 48-60 VDC,
30 mA
IOM with MOV 8 inputs, W W W W W W W W W W W W W W
10-2 output, 110-125
VDC, 30 mA
IOM with MOV 8 inputs, Y Y Y Y Y Y Y Y Y Y Y Y Y Y
10-2 output, 220-250
VDC, 30 mA
mA input module MIM 6 R R R R R R R R R R R R R R
channels

124 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Table 215. Binary input/output module selection, continued


Binary input/output Selection Notes and Rules
modules
SOM Static output T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 Note: SOM must not be placed in
module, 12 outputs, the following positions; 1/2 case
48-60 VDC slot X51, 3/4 case 1 TRM slot
X101, 3/4 case 2 TRM slot X71,
SOM static outputs T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2
1/1 case 1 TRM slot X161, 1/1
module, 12 outputs,
case 2 TRM slot X131
110-250 VDC
Selected.

Table 216. Remote end serial communication selection

Remote end communication, DNP serial comm. and time synchronization modules Selection Notes and Rules
Slot position (rear view) Note: The maximum number and

X312

X313

X302

X303

X322

X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2, 3/4 or 1/1 case with 1TRM █ █ █ █ Note: Max 2 LDCM in 1/2 case
Available slots in 3/4 and 1/1 case with 2 TRM █ █ █ █ █ █
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Max 4 LDCM (same or different
type) can be selected.
Optical medium range, LDCM 1310 nm B B B B B B
Always place LDCM modules on
Optical long range, LDCM 1550 nm C C C C C C the same board to support
Galvanic X21 line data communication module E E E E E E redundant communication; in
P30:2 and P30:3, P31:2 and P31:3
or P32:2 and P32:3
IRIG-B Time synchronization module F F F F F F
Galvanic RS485 communication module G G G G G G
GPS time synchronization module S S S S
Selected

Table 217. Serial communication unit for station communication selection

Serial communication unit for station communication Selection Notes and Rules
Slot position (rear view)
X301

X311

No communication board included X X


Serial SPA/LON/DNP/IEC 60870-5-103 plastic interface A
Serial SPA/LON/DNP/IEC 60870-5-103 plastic/glass interface B
Serial SPA/LON/DNP/IEC 60870-5-103 glass interface C
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selected.

ABB 125
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

23. Ordering for pre-configured IED

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RED670 *2.1-A30X00- A02H02-B1A3-AC-MB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-13 specified as
RED670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 8-9-10 10 10 10-110 11 11 11 11 11 11 11 11 11 11-12 12 12 12 12 12-13 13
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
RED670* - - - - - . - -

10 - 11 - 12 - 13
- . -

Position
SOFTWARE #1 Notes and Rules
Version number
Version no 2.1
Selection for position #1.

Configuration alternatives #2 Notes and Rules


Single breaker, 3 phase tripping A31
Multi breaker, 3 phase tripping B31
Single breaker, 1 phase tripping A32
Multi breaker, 1 phase tripping B32
ACT configuration
ABB standard configuration X00
Selection for position #2.

126 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Software options #3 Notes and Rules


No option X All fields in the ordering
00 form do not need to be
filled in
High impedance differential protection A
02
Line differential protection 6 CT sets, 3-5 line A Note: Only one Line
ends 04 differential protection
have to be selected
Line differential protection 3 CT sets, with in- A
Note: A04/A05 only in
zone transformers, 2-3 line ends 05
A31/A32
Line differential protection 6 CT sets, with in- A
zone transformers, 3-5 line ends 06
Power swing logic B
03
Phase preference logic B Note: Only for A31
04
Phase segregated scheme communication B Note: Only for A32 and
05 B32
Distance zones quadrilateral, 4th zone B Note: Only one of
10 B10/B11/B16/B17/B28/B
29 to be selected.
Distance zones quadrilateral, 3 zones B
B11 is required with B10.
11
1 block of STBPTOC
Distance zones quadrilateral series B alrady included on
compensation, 3 zones 16 B31/B32
Line Distance protection - mho - 4 zones B
17
Directional distance protection with phase B
selection 28
Directional distance protection with phase B
selection, series compensation 29
Out-of-step protection B
22
Sensitive directional residual overcurrent C
and power protection 16
Directional power protection C
17
Residual overcurrent protection C
24
Overexcitation protection D
03
Frequency protections - line E
02
General current and voltage protection F0
1
Fuse failure supervision based on voltage G
difference 03
Autorecloser, 1 circuit breaker H Note: H04 only for A31/
04 A32, 1 block already
included
Autorecloser, 2 circuit breaker H Note: H05 only for B31/
05 B32, 2 blocks already
included
Apparatus control 10 objects H Note: Only one
27 Apparatus control can be
ordered
Apparatus control 15 objects H
Note: H27 only for A31/
08
A32, H08 only for
B31/B32
Circuit breaker condition monitoring - 3 CB M Note: M13 only for
13 A31/32, M15 only for
B31/B32
Circuit breaker condition monitoring - 6 CB M
15
IEC 62439-3 parallel redundancy protocol P Note: P03 requires a 2-
03 channel OEM.
Selection for position #3

ABB 127
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

First local HMI user dialogue language #4 Notes and Rules


HMI language, English IEC B1
Additional local HMI user dialogue language
No additional HMI language X0
HMI language, English US A12
Selection for position #4.

Casing #5 Notes and Rules


1/2 x 19" case A
3/4 x 19" case 1 TRM slot B
3/4 x 19" case 2 TRM slots C
1/1 x 19" case 1TRM slots D
1/1 x 19" case 2 TRM slots E
Selection for position #5.

Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.

Connection type for Power supply module #7 Notes and Rules


Compression terminals M
Ringlug terminals N
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.

Connection type for Input/output and Communication modules #8 Notes and Rules
Compression terminals P
Selection for position #8.

Human machine hardware interface #9 Notes and Rules


Medium size - graphic display, IEC keypad symbols B
Medium size - graphic display, ANSI keypad symbols C
Selection for position #9.

128 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Analog input system #10 Notes and Rules


Compression terminals A
Ringlug terminals B
First TRM, 6I+6U 1A, 100/220V 6
First TRM, 6I+6U 5A, 100/220V 7
First TRM, 3I, 5A + 3I, 1A + 6U, 110/220V 16 Note: Only for A31 and A32
No second TRM included X0
Compression terminals A
Ringlug terminals B
Second TRM, 9I+3U 1A, 110/220V 3
Second TRM, 9I+3U 5A, 110/220V 4
Second TRM, 5I, 1A+4I, 5A+3U, 110/220V 5
Second TRM, 6I+6U, 1A, 110/220V 6
Second TRM, 6I+6U, 5A, 110/220V 7
Second TRM, 6I, 1A, 110/220V 8
Second TRM, 6I, 5A, 5A, 110/220V 9
Second TRM, 7I+5U 1A, 110/220V 12
Second TRM, 7I+5U 5A, 110/220V 13
Second TRM, 3I, 5A + 3I, 1A + 6U, 110/220V 16 Note: Only for A31 and A32
Selection for position #10.

ABB 129
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Binary input/output module, mA and time synchronizating #11 Notes and Rules
boards.
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability
is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
Slot position (rear view) Note: Max 3 positions in 1/2 rack, 8

X31

X41

X51

X61

X71

X81

X91

X101

X111

X121

X131

X141

X151

X161
in 3/4 rack with 1 TRM, 5 in 3/4
rack with 2 TRM, 14 in 1/1 rack
with 1 TRM and 11 in 1/1 rack with
2 TRM
1/2 Case with 1 TRM █ █ █
3/4 Case with 1 TRM █ █ █ █ █ █ █ █
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X X X
Binary output module 24 output relays (BOM) A A A A A A A A A A A A A Note: Maximum 4 (BOM+SOM
+MIM) boards.
BIM 16 inputs, RL24-30 VDC, 50 mA B B B B B B B B B B B B B
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C C C C C C C C C C C C
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 mA D D D D D D D D D D D D D
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 mA E E E E E E E E E E E E E
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, 220-250 VDC, 120mA E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting F F F F F F F F F F F F
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting G G G G G G G G G G G G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting H H H H H H H H H H H H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting K K K K K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L L L L L L L L L L L L
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M M M M M M M M M M M M
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N N N N N N N N N N N N
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P P P P P P P P P P P P
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA P P P P P P P P P P P P
2 2 2 2 2 2 2 2 2 2 2 2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA U U U U U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA V V V V V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA W W W W W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA Y Y Y Y Y Y Y Y Y Y Y Y
mA input module MIM 6 channels R R R R R R R R R R R R Note: maximum 1 MIM board in
1/2 case
SOM Static output module, 12 outputs, 48-60 VDC T T T T T T T T T T T T Note: SOM must not to be placed
1 1 1 1 1 1 1 1 1 1 1 1 in position nearest to NUM; 1/2
case slot P5, 3/4 case 1 TRM slot
SOM static outputs module, 12 outputs, 110-250 VDC T T T T T T T T T T T T
P10, 3/4 case 2 TRM slot P7, 1/1
2 2 2 2 2 2 2 2 2 2 2 2
case 1 TRM slot P16, 1/1 case 2
TRM slot P13
Selection for position #11.

130 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Remote end communication, DNP serial comm. and time synchronization modules #12 Notes and Rules
Slot position (rear view) Note: The maximum number and

X312

X313

X302

X303

X322

X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2 and 3/4 case with 1TRM █ █ █ █ Note: Only for A31/A32. One
LDCM must be ordered. Max 2
LDCM in 1/2 case.
Available slots in 3/4 and 1/1 case with 2 TRM █ █ █ █ █ █ Note: 2 LDCM in B31 and B32
must be ordered. Max 4 LDCM
No remote communication board included X X X X X A31 and A32 - 1 LDCM always in
position P30:2(X302)
No remote communication board included X X X X B31 and B32 - 1 LDCM always in
position P30:2(X302) and
P30:3(X303)
Optical short range LDCM A A A A A A Max 4 LDCM (same or different
type) can be selected.
Optical medium range, LDCM 1310 nm B B B B B B
Always place LDCM modules on
Optical long range, LDCM 1550 nm C C C C C C the same board to support
Galvanic X21 line data communication module E E E E E E redundant communication; in
P30:2 and P30:3, P31:2 and P31:3
IRIG-B Time synchronization module, with PPS F F F F F F or P32:2 and P32:3
Galvanic RS485 communication module G G G G G Note: No RS485 in position X303
in B31/B32
GPS time module GTM S S S S
Selection for position #12.

Serial communication unit for station communication #13 Notes and Rules
Slot position (rear view)

X301

X311
No first communication board included X
No second communication board included X
Serial and LON communication module (plastic) A
Serial (plastic) and LON (glass) communication module B
Serial and LON communication module (glass) C
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selection for position #13.

ABB 131
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

24. Ordering for Accessories

Accessories
GPS antenna and mounting details

GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA

Cable for antenna, 20 m (Appx. 65 ft) Quantity: 1MRK 001 665-AA

Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA

Interface converter (for remote end data communication)

External interface converter from C37.94 to G703 Quantity: 1 2 3 4


1MRK 002 245-AA

External interface converter from C37.94 to G703.E1 Quantity: 1 2 3 4


1MRK 002 245-BA

Test switch Multi-breaker/Single or Three Phase trip with internal neutral on


The test system COMBITEST intended for use with the IEDs is current circuits (ordering number RK926 315-BE).
described in 1MRK 512 001-BEN and 1MRK 001024-CA.
Please refer to the website: Multi-breaker/Single or Three Phase trip with external neutral
www.abb.com/substationautomation for detailed information. on current circuit (ordering number RK926 315-BV).

Due to the high flexibility of our product and the wide variety of The normally open "In test mode" contact 29-30 on the RTXP
applications possible the test switches needs to be selected for test switches should be connected to the input of the test
each specific application. function block to allow activation of functions individually during
testing.
Select your suitable test switch base on the available contacts
arrangements shown in the reference documentation. Test switches type RTXP 24 is ordered separately. Please refer
to Section Related documents for references to corresponding
However our proposals for suitable variants are; documents.

Single breaker/Single or Three Phase trip with internal neutral RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and the
on current circuits (ordering number RK926 315-AK). on/off switch for dc-supply are ordered separately. Please refer
to Section Related documents for references to corresponding
Single breaker/Single or Three Phase trip with external neutral documents.
on current circuits (ordering number RK926 315-AC).
Protection cover

Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE

Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC

Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB

Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA

132 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

External resistor unit

High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V 1 2 3
operating voltage Quantity: RK 795 101-MA

High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V Quantity: RK 795 101-MB
operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 100-400V 1 2 3
operating voltage Quantity: RK 795 101-CB

High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 100-400V Quantity: RK 795 101-DC
operating voltage

Combiflex

Key switch for settings

Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A

Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.

Mounting kit Ordering number


Side-by-side mounting kit Quantity: 1MRK 002 420-Z

Configuration and monitoring tools

Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Manuals

Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual and Getting started guide), Connectivity
packages and LED label template is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AD

ABB 133
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 505 343-UEN

ANSI Quantity: 1MRK 505 307-UUS

Technical manual IEC Quantity: 1MRK 505 308-UEN

ANSI Quantity: 1MRK 505 308-UUS

Commissioning manual IEC Quantity: 1MRK 505 345-UEN

ANSI Quantity: 1MRK 505 309-UUS

Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 349-UEN

Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 350-UEN

Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 351-UEN

Communication protocol manual, LON IEC Quantity: 1MRK 511 352-UEN

Communication protocol manual, SPA IEC Quantity: 1MRK 511 353-UEN

Communication protocol manual, DNP ANSI Quantity: 1MRK 511 348-UUS

Point list manual, DNP ANSI Quantity 1MRK 511 354-UUS

Operation manual IEC Quantity: 1MRK 500 123-UEN

ANSI Quantity: 1MRK 500 123-UUS

Installation manual IEC Quantity: 1MRK 514 024-UEN

ANSI Quantity: 1MRK 514 024-UUS

134 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1

Engineering manual, 670 series IEC Quantity: 1MRK 511 355-UEN

ANSI Quantity: 1MRK 511 355-UUS

Cyber security guideline IEC Quantity: 1MRK 511 356-UEN

Reference information

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Related documents
670 series manuals Document numbers

Documents related to RED670 Document numbers Operation manual IEC:1MRK 500 123-UEN
ANSI:1MRK 500 123-UUS
Application manual IEC:1MRK 505 343-UEN
ANSI:1MRK 505 343-UUS Engineering manual IEC:1MRK 511 355-UEN
ANSI:1MRK 511 355-UUS
Commissioning manual IEC:1MRK 505 345-UEN
ANSI:1MRK 505 345-UUS Installation manual IEC:1MRK 514 024-UEN
ANSI:1MRK 514 024-UUS
Product guide 1MRK 505 346-BEN
Communication protocol manual, 1MRK 511 348-UUS
Technical manual IEC:1MRK 505 308-UEN DNP3
ANSI:1MRK 505 308-UUS
Communication protocol manual, 1MRK 511 351-UEN
Type test certificate IEC:1MRK 505 346-TEN IEC 60870-5-103
ANSI:1MRK 505 346-TUS
Communication protocol manual, 1MRK 511 349-UEN
IEC 61850 Edition 1

Communication protocol manual, 1MRK 511 350-UEN


IEC 61850 Edition 2

Communication protocol manual, 1MRK 511 352-UEN


LON

Communication protocol manual, 1MRK 511 353-UEN


SPA

Point list manual, DNP3 1MRK 511 354-UUS

Accessories guide IEC:1MRK 514 012-BEN


ANSI:1MRK 514 012-BUS

Cyber security deployment 1MRK 511 356-UEN


guideline

Connection and Installation 1MRK 513 003-BEN


components

Test system, COMBITEST 1MRK 512 001-BEN

ABB 135
136
Contact us

1MRK 505 346-BEN - © Copyright 2015 ABB. All rights reserved.