Line differential protection RED670 2.1 IEC
Product version: 2.1 Issued: December 2015
Revision: -
certificates and the distribution of such, a procedure completely • Single-breaker (double or single bus) with three phase
transparent to the user. tripping (A31)
• Single-breaker (double or single bus) with single phase
The Flexible Product Naming allows the customer to use an tripping (A32)
IED-vendor independent 61850 model of the IED. This • Multi-breaker (one-and a half or ring) with three phase
customer model will be exposed in all IEC 61850 tripping (B31)
communication, but all other aspects of the IED will remain • Multi-breaker (one-and a half or ring) with single phase
unchanged (e.g., names on the local HMI and names in the tripping (B32)
tools). This offers significant flexibility to adapt the IED to the
customers system and standard solution Optional functions are not configured but a maximum
configuration with all optional functions are available as
Communication via optical connections ensures immunity template in the graphical configuration tool. Analog inputs and
against disturbances. binary input/output signals are pre-defined for basic use. Other
signals may be required by each particular application.
Four packages have been defined for following applications:
Add binary I/O boards as required for the application when
ordering.
4 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
WA1
RED670 A31 – Single Breaker with Three phase tripping
WA2 12AI (6I+6U)
WA2_VT
QB1 QB2
MET UN
VN MMXU
WA1_VT
MET UN
VN MMXU
LINE_CT
50BF 3I>BF 50 3I>> 46 Iub> 26 θ>
CC RBRF PH PIOC BRC PTOC LC PTTR
REM CT
Optional Functions
87 Id> 87LT 3Id/I> 87L 3Id/I> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
HZ PDIF LT3C PDIF L6C PDIF LT6C PDIS NS4 PTOC EF PIOC EF4 PTOC SDEPSDE
S SCBR
IEC05000842 V4 EN
ABB 5
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
WA1
RED670 A32 – Single Breaker with Single phase tripping
WA2 12AI (6I+6U)
WA2_VT
QB1 QB2
MET UN
VN MMXU
WA1_VT
MET UN
VN MMXU
LINE_CT
52PD PD 50BF 3I>BF 50 3I>> 46 Iub> 26 θ>
CC PDSC CC RBRF PH PIOC BRC PTOC LC PTTR
REM CT
Optional Functions
87 Id> 87LT 3Id/I> 87L 3Id/I> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
HZ PDIF LT3C PDIF L6C PDIF LT6C PDIS NS4 PTOC EF PIOC EF4 PTOC SDEPSDE
85 85
S SCBR ZC1P PSCH ZC1W PSCH
IEC05000840 V4 EN
6 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
WA1
RED670 B31: interruptor múltiple con disparo trifásico
12AI (6I+6U)
QB1 WA1_VT
WA1_CT
50BF 3I>BF MET UN
CC RBRF VN MMXU
50BF 3I>BF
WA1_QA1
CC RBRF
REM CT1
REM CT2
WA1_QB6
LINE1_QB9 87L 87L 3Id/I>
TIE_CT
MET U MET UN 27 3U< 27 3U< 59 3U>
V MMXU VN MMXU UV2 PTUV LOV PTUV OV2 PTOV
LINE2_VT
MET UN
QB62
WA2_VT VN MMXU
MET UN 94
94 1→0
1→0 79
79 0→1
5(0→1) 25 SC
25 SC/VC
LINE2_QB9 SMP
VN MMXU SMPPTRC
PTRC SMB
SMBRREC
RREC SES
SESRSYN
RSYN
WA2_QB6 71 52PD PD
S SIML CC PDSC
Funciones opcionales
87 Id> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
WA2_QA1 HZ PDIF LT6C PDIF NS4 PTOC EF PIOC EF4 PTOC SDE PSDE
3 Control
Q CRSV S SCBR
IEC05000843 V4 EN
ABB 7
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
WA1
RED670 B32 – Multi Breaker with Single phase tripping
12AI (6I+6U)
QB1 WA1_VT
WA1_CT
50BF 3I>BF 52PD PD MET UN
CC RBRF CC PDSC VN MMXU
REM CT2
WA1_QB6
LINE1_QB9 87L 87L 3Id/I>
TIE_CT
MET U MET UN 27 3U< 27 3U< 59 3U>
V MMXU VN MMXU UV2 PTUV LOV PTUV OV2 PTOV
LINE2_VT
MET UN
QB62 WA2_VT VN MMXU
MET UN 94
94 1→0
1→0 79
79 0→1
5(0→1) 25 SC
25 SC/VC
LINE2_QB9 SMP
VN MMXU SMPPTRC
PTRC SMB
SMBRREC
RREC SES
SESRSYN
RSYN
WA2_QB6 71
S SIML
Optional Functions
87 Id> 87LT 3Id/I> 46I2 4(I2>) 50N IN>> 51N_67N 4(IN>) 67N IN>
WA2_QA1 HZ PDIF LT6C PDIF NS4 PTOC EF PIOC EF4 PTOC SDE PSDE
3 Control 85 85
Q CRSV S SCBR ZC1P PSCH ZC1W PSCH
IEC05000841 V4 EN
8 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
2. Available functions
ABB 9
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
Differential protection
HZPDIF 87 1Ph high impedance differential protection 0-3 3-A02 3-A02 3-A02 3-A02
L6CPDIF 87L Line differential protection, 6 CT sets, 3–5 line ends 1 1-A04 1 1-A04 1
LT3CPDIF 87LT Line differential protection, 3 CT sets, with inzone 1 1-A05 1-A05
transformers, 2–3 line ends
LT6CPDIF 87LT Line differential protection, 6 CT sets, with inzone 1 1-A06 1-A06 1-A06 1-A06
transformers, 3–5 line ends
Impedance protection
ZMQPDIS, 21 Distance protection zone, quadrilateral characteristic 0-5 1-B10 1-B10 1-B10 1-B10
ZMQAPDIS 3-B11 3-B11 3-B11 3-B11
ZDRDIR 21D Directional impedance quadrilateral 0-2 1-B11 1-B11 1-B11 1-B11
ZMCPDIS, 21 Distance measuring zone, quadrilateral characteristic 0-5 3-B16 3-B16 3-B16 3-B16
ZMCAPDIS for series compensated lines
ZDSRDIR 21D Directional impedance quadrilateral, including series 0-2 1-B16 1-B16 1-B16 1-B16
compensation
FDPSPDIS 21 Phase selection, quadrilateral characteristic with fixed 0-2 1-B11 1-B11 1-B11 1-B11
angle 1-B16 1-B16 1-B16 1-B16
ZMHPDIS 21 Fullscheme distance protection, mho characteristic 0-5 4-B17 4-B17 4-B17 4-B17
ZMMPDIS, 21 Fullscheme distance protection, quadrilateral for 0-5 4-B17 4-B17 4-B17 4-B17
ZMMAPDIS earth faults
ZDMRDIR 21D Directional impedance element for mho characteristic 0-2 1-B17 1-B17 1-B17 1-B17
ZDARDIR Additional distance protection directional function for 0-2 1-B17 1-B17 1-B17 1-B17
earth faults
ZSMGAPC Mho impedance supervision logic 0-1 1-B17 1-B17 1-B17 1-B17
FMPSPDIS 21 Faulty phase identification with load enchroachment 0-2 2-B17 2-B17 2-B17 2-B17
ZMFCPDIS 21 High speed distance protection for series 0–1 1-B19 1-B19 1-B19 1-B19
compensated lines
10 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
ZCVPSOF Automatic switch onto fault logic, voltage and current 0-1 1-B11 1-B11 1-B11 1-B11
based 1-B16 1-B16 1-B16 1-B16
1-B17 1-B17 1-B17 1-B17
ABB 11
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
Current protection
EFPIOC 50N Instantaneous residual overcurrent 0-1 1-C24 1-C24 1-C24 1-C24
protection
EF4PTOC 51N Four step residual overcurrent protection 0-3 1-C24 1-C24 1-C24 1-C24
67N2)
NS4PTOC 46I2 Four step directional negative phase 0-2 1-C24 1-C24 1-C24 1-C24
sequence overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent 0-1 1-C16 1-C16 1-C16 1-C16
and power protection
Voltage protection
Frequency protection
12 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
Multipurpose protection
CVGAPC General current and voltage protection 0-4 4-F01 4-F01 4-F01 4-F01
General calculation
1) 67 requires voltage
2) 67N requires voltage
ABB 13
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
Control
APC10 3 Apparatus control for single bay, max 10 apparatuses 0-1 1-H27 1-H27
(1CB) incl. interlocking
APC15 3 Apparatus control for single bay, max 15 apparatuses 0-1 1-H08 1-H08
(2CBs) incl. interlocking
Secondary system
supervision
VDSPVC 60 Fuse failure supervision based on voltage difference 0-3 1-G03 1-G03 1-G03 1-G03
Logic
14 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-280 40-28 40-280 40-28 40-28
LLD, OR, 0 0 0
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Monitoring
CVMMXN, Measurements 6 6 6 6 6
VMMXU, CMSQI,
VMSQI, VNMMXU
CMMXU Measurements 10 10 10 10 10
ABB 15
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
Metering
16 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
AND 280
GATE 40
INV 420
LLD 40
OR 289
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
AND 180
GATE 49
INV 180
LLD 49
OR 180
PULSETIMER 59
SLGAPC 74
SRMEMORY 110
TIMERSET 49
VSGAPC 130
XOR 49
ABB 17
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Communication
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
Station communication
RS485GEN RS485 1 1 1 1 1
MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND
18 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
RED670 (B31)
RED670 (B32)
RED670 (A31)
RED670 (A32)
RED670
(Customized)
PRP IEC 62439-3 parallel redundancy protocol 0-1 1-P03 1-P03 1-P03 1-P03
Remote communication
Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
Scheme communication
ZCPSCH 85 Scheme communication logic for distance or 0-1 1-B11 1-B11 1-B11 1-B11
overcurrent protection 1-B16 1-B16 1-B16 1-B16
ZCRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-B11 1-B11 1-B11 1-B11
distance protection 1-B16 1-B16 1-B16 1-B16
ZC1WPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-B05 1-B05
phase segregated communication
ECPSCH 85 Scheme communication logic for residual 0-1 1-C24 1-C24 1-C24 1-C24
overcurrent protection
ECRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-C24 1-C24 1-C24 1-C24
residual overcurrent protection
ABB 19
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
INTERRSIG
SELFSUPEVLST Self supervision with internal event list
20 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
3. Differential protection
Restricted earth-fault protection, low impedance REFPDIF
1Ph High impedance differential protection HZPDIF Restricted earth-fault protection, low-impedance function
The 1Ph High impedance differential protection HZPDIF REFPDIF can be used on all directly or low-impedance earthed
functions can be used when the involved CT cores have the windings. The REFPDIF function provides high sensitivity and
same turns ratio and similar magnetizing characteristics. It high speed tripping as it protects each winding separately and
utilizes an external CT secondary current summation by wiring. thus does not need inrush stabilization.
Actually all CT secondary circuits which are involved in the
differential scheme are connected in parallel. External series The REFPDIF function is a percentage biased function with an
resistor, and a voltage dependent resistor which are both additional zero sequence current directional comparison
mounted externally to the IED, are also required. criterion. This gives excellent sensitivity and stability during
through faults.
The external resistor unit shall be ordered under IED
accessories in the Product Guide. REFPDIF can also protect autotransformers. Five currents are
measured at the most complicated configuration as shown in
HZPDIF can be used to protect tee-feeders or busbars, Figure 5.
reactors, motors, auto-transformers, capacitor banks and so
on. One such function block is used for a high-impedance
restricted earth fault protection. Three such function blocks are
used to form three-phase, phase-segregated differential
protection. Several function block instances (for example, six)
can be available in a single IED.
ABB 21
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Protected zone
IEC05000039-3-en.vsd
IEC05000039 V3 EN
Protected zone
IEC05000040_2_en.vsd
IEC05000040 V2 EN
The current differential algorithm provides high sensitivity for A special feature with this function is that applications with
internal faults and it has excellent stability for external faults. small power transformers (rated current less than 50% of the
Current samples from all CTs are exchanged between the IEDs differential current setting IdMin) connected as line taps (that is,
in the line ends (master-master mode) or sent to one IED as shunt power transformers), without measurements of
(master-slave mode) for evaluation. currents in the tap, can be handled. The normal load current is
considered to be negligible, and special measures must be
A restrained dual biased slope evaluation is made where the taken in the event of a short circuit on the LV side of the
bias current is the highest phase current in any line end, giving a transformer. In this application, the tripping of the differential
secure through-fault stability even with heavily saturated CTs. protection can be time-delayed for low differential currents to
In addition to the restrained evaluation, an unrestrained achieve coordination with downstream overcurrent IEDs. The
(instantaneous) high differential current setting can be used for local protection of the small tap power transformer is given the
fast tripping of internal faults with very high currents. time needed to disconnect the faulty transformer.
22 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Protected zone
IED
IEC05000042_2_en.vsd
IEC05000042 V2 EN
Figure 8. Example of application on a three-terminal line with an in-line power transformer in the protection zone
Protected zone
IED IED
Comm.
Channels
IEC0500043_2_en.vsd
IEC05000043 V2 EN
ABB 23
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Protected zone
RED RED
670 670
Comm.
Channels
en05000044.vsd
IEC05000044 V1 EN
Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an
each other, must be time coordinated so that the current automatic switchover to a standby link is possible after a preset
differential algorithm can be executed correctly, this is done time.
with the echo method.For applications where transmit and
receive times can differ, the optional built in GPS receivers can
be used
4. Impedance protection gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and
Distance measuring zone, quadrilateral characteristic lengths.
ZMQPDIS, ZMQAPDIS
The line distance protection is an up to five (depending on ZMQPDIS together with Phase selection with load
product variant) zone full scheme protection function with three encroachment FDPSPDIS has functionality for load
fault loops for phase-to-phase faults and three fault loops for encroachment, which increases the possibility to detect high
phase-to-earth faults for each of the independent zones. resistive faults on heavily loaded lines, as shown in figure11.
Individual settings for each zone in resistive and reactive reach
24 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
X X
Forward Forward
operation operation
R R
Reverse Reverse
operation operation
en05000034.vsd en05000034.vsd
IEC05000034 V1 EN IEC05000034 V1 EN
Figure 11. Typical quadrilateral distance protection zone with Phase Figure 12. Typical quadrilateral distance protection zone with load
selection with load encroachment function FDPSPDIS encroachment function activated
activated
The distance protection zones can operate independently of The distance protection zones can operate, independent of
each other in directional (forward or reverse) or non-directional each other, in directional (forward or reverse) or non-directional
mode. This makes them suitable, together with different mode. This makes them suitable, together with different
communication schemes, for the protection of power lines and communication schemes, for the protection of power lines and
cables in complex network configurations, such as parallel cables in complex network configurations, such as parallel
lines, multi-terminal lines. lines, multi-terminal lines.
Distance measuring zone, quadrilateral characteristic for Phase selection, quadrilateral characteristic with fixed angle
series compensated lines ZMCPDIS, ZMCAPDIS FDPSPDIS
The line distance protection is a five three zone full scheme The operation of transmission networks today is in many cases
protection with three fault loops for phase-to-phase faults and close to the stability limit. Due to environmental considerations,
three fault loops for phase-to-earth fault for each of the the rate of expansion and reinforcement of the power system is
independent zones. Individual settings for each zone resistive reduced, for example, difficulties to get permission to build new
and reactive reach give flexibility for use on overhead lines and power lines. The ability to accurately and reliably classify the
cables of different types and lengths. different types of fault, so that single pole tripping and
autoreclosing can be used plays an important role in this
Quadrilateral characteristic is available.
matter. Phase selection, quadrilateral characteristic with fixed
ZMCPDIS function has functionality for load encroachment angle FDPSPDIS is designed to accurately select the proper
which increases the possibility to detect high resistive faults on fault loop in the distance function dependent on the fault type.
heavily loaded lines.
The heavy load transfer that is common in many transmission
networks may make fault resistance coverage difficult to
achieve. Therefore, FDPSPDIS has a built-in algorithm for load
encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring
zones without interfering with the load.
ABB 25
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
The extensive output signals from the phase selection gives mode (offset). This makes them suitable, together with different
also important information about faulty phase(s), which can be communication schemes, for the protection of power lines and
used for fault analysis. cables in complex network configurations, such as parallel
lines, multi-terminal lines and so on.
A current-based phase selection is also included. The
measuring elements continuously measure three phase The possibility to use the phase-to-earth quadrilateral
currents and the residual current and, compare them with the impedance characteristic together with the mho characteristic
set values. increases the possibility to overcome eventual lack of sensitivity
of the mho element due to the shaping of the curve at remote
Full-scheme distance measuring, Mho characteristic end faults.
ZMHPDIS
The numerical mho line distance protection is a four zone full The integrated control and monitoring functions offer effective
scheme protection for back-up detection of short circuit and solutions for operating and monitoring all types of transmission
earth faults. The numerical mho line distance protection is a and sub-transmission lines.
three zone full scheme protection for back-up detection of short
circuit and earth faults. Full-scheme distance protection, quadrilateral for earth faults
ZMMPDIS, ZMMAPDIS
The line distance protection is an up to five (depending on
The four zones have fully independent measuring and settings, product variant) zone full scheme protection function with three
which gives high flexibility for all types of lines. fault loops for phase-to-earth fault for each of the independent
zones. Individual settings for each zone resistive and reactive
The IED can be used up to the highest voltage levels. It is
reach give flexibility for use on overhead lines and cables of
suitable for the protection of heavily loaded lines and multi-
different types and lengths.
terminal lines where the requirement for tripping is one-, two-
and/or three-pole. The Full-scheme distance protection, quadrilateral for earth
fault functions have functionality for load encroachment, which
The independent measurement of impedance for each fault
increases the possibility to detect high resistive faults on heavily
loop together with a sensitive and reliable phase selection
loaded lines , see Figure 11.
makes the function suitable in applications with single phase
autoreclosing.
X
Built-in selectable zone timer logic is also provided in the
function.
Forward
Adaptive load compensation algorithm prevents overreaching operation
at phase-to-earth faults on heavily loaded power lines, see
Figure 13.
jX
R
Reverse
Operation area Operation area
operation
R
en05000034.vsd
Operation area IEC05000034 V1 EN
IEC07000117-2-en.vsd
IEC07000117 V2 EN
The independent measurement of impedance for each fault
Figure 13. Load encroachment influence on the offset mho
loop together with a sensitive and reliable built in phase
characteristic
selection makes the function suitable in applications with single
phase auto-reclosing.
The distance protection zones can operate, independent of
each other, in directional (forward or reverse) or non-directional
26 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
The distance protection zones can operate, independent of for load encroachment, which increases the possibility to
each other, in directional (forward or reverse) or non-directional detect high resistive faults on heavily loaded lines, as shown in
mode. This makes them suitable, together with different figure 11.
communication schemes, for the protection of power lines and
cables in complex network configurations, such as parallel
lines, multi-terminal lines. X
ZMRPDIS together with Phase selection, quadrilateral The heavy load transfer that is common in many transmission
characteristic with settable angle FRPSPDIS has functionality networks may make fault resistance coverage difficult to
ABB 27
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
achieve. Therefore, the function has a built in algorithm for load can even be decided separate for the phase-to-ground or
encroachment, which gives the possibility to enlarge the phase-to-phase loops. The six zones can operate either
resistive setting of both the phase selection and the measuring independent of each other, or their start can be linked (per
zones without interfering with the load. zone) through the phase selector or the first starting zone. This
can provide fast operate times for evolving faults.
The extensive output signals from the phase selection gives
also important information about faulty phase(s) which can be The operation of the phase-selection is primarily based on a
used for fault analysis. current change criteria (i.e. delta quantities), however there is
also a phase selection criterion operating in parallel which
A current-based phase selection is also included. The bases its operation on voltage and current phasors exclusively.
measuring elements continuously measure three phase Additionally the directional element provides a fast and correct
currents and the residual current and, compare them with the directional decision under difficult operating conditions,
set values. including close-in three-phase faults, simultaneous faults and
faults with only zero-sequence in-feed.
High speed distance protection, quadrilateral and mho
ZMFPDIS During phase-to-earth faults on heavily loaded power lines
The high speed distance protection (ZMFPDIS) provides a sub- there is an adaptive load compensation algorithm that prevents
cycle, down towards a half-cycle operate time. Its six zone, full overreaching of the distance zones in the load exporting end,
scheme protection concept is entirely suitable in applications improving the selectivity of the function. This also reduces
with single-phase autoreclosing. underreach in the importing end.
Each measurement zone is designed with the flexibility to Power swing detection ZMRPSB
operate in either quadrilateral or mho characteristic mode. This Power swings may occur after disconnection of heavy loads or
can even be decided separate for the phase-to-ground or trip of big generation plants.
phase-to-phase loops. The six zones can operate either
independent of each other, or their start can be linked (per Power swing detection function ZMRPSB is used to detect
zone) through the phase selector or the first starting zone. This power swings and initiate block of all distance protection zones.
can provide fast operate times for evolving faults. Occurrence of earth-fault currents during a power swing
inhibits the ZMRPSB function, to allow fault clearance.
The operation of the phase-selection is primarily based on a
current change criteria (i.e. delta quantities), however there is Power swing logic PSLPSCH
also a phase selection criterion operating in parallel which Power Swing Logic (PSLPSCH) is a complementary function to
bases its operation on voltage and current phasors exclusively. Power Swing Detection (ZMRPSB) function. It provides
Additionally the directional element provides a fast and correct possibility for selective tripping of faults on power lines during
directional decision under difficult operating conditions, system oscillations (power swings or pole slips), when the
including close-in three-phase faults, simultaneous faults and distance protection function should normally be blocked. The
faults with only zero-sequence in-feed.During phase-to-earth complete logic consists of two different parts:
faults on heavily loaded power lines there is an adaptive load
compensation algorithm that prevents overreaching of the • Communication and tripping part: provides selective
distance zones in the load exporting end, improving the tripping on the basis of special distance protection zones
selectivity of the function. This also reduces underreach in the and a scheme communication logic, which are not
importing end. blocked during the system oscillations.
• Blocking part: blocks unwanted operation of
Distance zones quad with high speed distance for series instantaneous distance protection zone 1 for oscillations,
compensated networks ZMFCPDIS which are initiated by faults and their clearing on the
The high speed distance protection (ZMCPDIS) provides a sub- adjacent power lines and other primary elements.
cycle, down towards a half-cycle operate time. Its six zone, full
scheme protection concept is entirely suitable in applications
Pole slip protection PSPPPAM
with single-phase autoreclosing.
The situation with pole slip of a generator can be caused by
High speed distance protection ZMFCPDIS is fundamentally different reasons.
the same function as ZMFPDIS but provides more flexibility in
A short circuit may occur in the external power grid, close to the
zone settings to suit more complex applications, such as series
generator. If the fault clearing time is too long, the generator will
compensated lines. In operation for series compensated
accelerate so much, that the synchronism cannot be
networks, the parameters of the directional function are altered
maintained.
to handle voltage reversal.
Undamped oscillations occur in the power system, where
Each measurement zone is designed with the flexibility to
generator groups at different locations, oscillate against each
operate in either quadrilateral or mho characteristic mode. This
28 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
other. If the connection between the generators is too weak the phase, when each group is equipped with current transformers.
magnitude of the oscillations will increase until the angular The protection function performs a simple summation of the
stability is lost. currents of the two channels I3P1 and I3P2.
The operation of a generator having pole slip will give risk of Phase preference logic PPLPHIZ
damages to the generator, shaft and turbine. The optional phase preference logic main purpose is to provide
a selective tripping for cross-country faults in isolated or high
• At each pole slip there will be significant torque impact on impedance-earthed networks.
the generator-turbine shaft.
• In asynchronous operation there will be induction of Automatic switch onto fault logic, voltage and current based
currents in parts of the generator normally not carrying ZCVPSOF
current, thus resulting in increased heating. The Automatic switch onto fault logic (ZCVPSOF) is a function that
consequence can be damages on insulation and stator/ gives an instantaneous trip at closing of breaker onto a fault. A
rotor iron. dead line detection check is provided to activate the function
when the line is dead.
The Pole slip protection (PSPPPAM) function shall detect pole
slip conditions and trip the generator as fast as possible if the
locus of the measured impedance is inside the generator- 5. Current protection
transformer block. If the centre of pole slip is outside in the
Instantaneous phase overcurrent protection PHPIOC
power grid, the first action should be to split the network into
The instantaneous three phase overcurrent function has a low
two parts, after line protection action. If this fails there should be
transient overreach and short tripping time to allow use as a
operation of the generator PSPPPAM in zone 2, to prevent
high set short-circuit protection function.
further damages to the generator, shaft and turbine.
Four-step phase overcurrent protection OC4PTOC
Pole slip protection PSPPPAM
The four step three-phase overcurrent protection function
Sudden events in an electric power system such as large
OC4PTOC has an inverse or definite time delay independent for
changes in load, fault occurrence or fault clearance, can cause
step 1 to 4 separately.
power oscillations referred to as power swings. In a non-
recoverable situation, the power swings become so severe that All IEC and ANSI inverse time characteristics are available
the synchronism is lost, a condition referred to as pole slipping. together with an optional user defined time characteristic.
The main purpose of the pole slip protection (PSPPPAM) is to
detect, evaluate, and take the required action for pole slipping The directional function needs voltage as it is voltage polarized
occurrences in the power system. with memory. The function can be set to be directional or non-
directional independently for each of the steps.
Out-of-step protection OOSPPAM
The out-of-step protection OOSPPAM function in the IED can A second harmonic blocking level can be set for the function
be used for both generator protection and as well for line and can be used to block each step individually.
protection applications.
Instantaneous residual overcurrent protection EFPIOC
The main purpose of the OOSPPAM function is to detect, The Instantaneous residual overcurrent protection EFPIOC has
evaluate, and take the required action during pole slipping a low transient overreach and short tripping times to allow the
occurrences in the power system. use for instantaneous earth-fault protection, with the reach
limited to less than the typical eighty percent of the line at
The OOSPPAM function detects pole slip conditions and trips minimum source impedance. EFPIOC is configured to measure
the generator as fast as possible, after the first pole-slip if the the residual current from the three-phase current inputs and
center of oscillation is found to be in zone 1, which normally can be configured to measure the current from a separate
includes the generator and its step-up power transformer. If the current input.
center of oscillation is found to be further out in the power
system, in zone 2, more than one pole-slip is usually allowed Four step residual overcurrent protection, zero sequence and
before the generator-transformer unit is disconnected. A negative sequence direction EF4PTOC
parameter setting is available to take into account the circuit The four step residual overcurrent protection EF4PTOC has an
breaker opening time. If there are several out-of-step relays in inverse or definite time delay independent for each step.
the power system, then the one which finds the center of
oscillation in its zone 1 should operate first. All IEC and ANSI time-delayed characteristics are available
together with an optional user defined characteristic.
Two current channels I3P1 and I3P2 are available in OOSPPAM
function to allow the direct connection of two groups of three- EF4PTOC can be set directional or non-directional
phase currents; that may be needed for very powerful independently for each of the steps.
generators, with stator windings split into two groups per
ABB 29
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
IDir, UPol and IPol can be independently selected to be either There is also available one nondirectional 3I0 step and one 3U0
zero sequence or negative sequence. overvoltage tripping step.
Second harmonic blocking can be set individually for each step. No specific sensitive current input is needed. SDEPSDE can be
set as low 0.25% of IBase.
EF4PTOC can be used as main protection for phase-to-earth
faults. Thermal overload protection, one time constant LCPTTR/
LFPTTR
EF4PTOC can also be used to provide a system back-up for The increasing utilization of the power system closer to the
example, in the case of the primary protection being out of thermal limits has generated a need of a thermal overload
service due to communication or voltage transformer circuit protection for power lines.
failure.
A thermal overload will often not be detected by other
Directional operation can be combined together with protection functions and the introduction of the thermal
corresponding communication logic in permissive or blocking overload protection can allow the protected circuit to operate
teleprotection scheme. Current reversal and weak-end infeed closer to the thermal limits.
functionality are available as well.
The three-phase current measuring protection has an I2 t
Residual current can be calculated by summing the three phase
characteristic with settable time constant and a thermal
currents or taking the input from neutral CT
memory. The temperature is displayed in either Celsius or
Four step negative sequence overcurrent protection Fahrenheit, depending on whether the function used is LCPTTR
NS4PTOC (Celsius) or LFPTTR (Fahrenheit).
Four step negative sequence overcurrent protection
An alarm level gives early warning to allow operators to take
(NS4PTOC) has an inverse or definite time delay independent
action well before the line is tripped.
for each step separately.
Estimated time to trip before operation, and estimated time to
All IEC and ANSI time delayed characteristics are available
reclose after operation are presented.
together with an optional user defined characteristic.
Breaker failure protection CCRBRF
The directional function is voltage polarized.
Breaker failure protection (CCRBRF) ensures a fast backup
tripping of the surrounding breakers in case the own breaker
NS4PTOC can be set directional or non-directional
fails to open. CCRBRF can be current-based, contact-based or
independently for each of the steps.
an adaptive combination of these two conditions.
NS4PTOC can be used as main protection for unsymmetrical
A current check with extremely short reset time is used as
fault; phase-phase short circuits, phase-phase-earth short
check criterion to achieve high security against inadvertent
circuits and single phase earth faults.
operation.
NS4PTOC can also be used to provide a system backup for
Contact check criteria can be used where the fault current
example, in the case of the primary protection being out of
through the breaker is small.
service due to communication or voltage transformer circuit
failure.
CCRBRF can be single- or three-phase initiated to allow use
with single phase tripping applications. For the three-phase
Directional operation can be combined together with
version of CCRBRF the current criteria can be set to operate
corresponding communication logic in permissive or blocking
only if two out of four for example, two phases or one phase
teleprotection scheme. The same logic as for directional zero
plus the residual current start. This gives a higher security to the
sequence current can be used. Current reversal and weak-end
back-up trip command.
infeed functionality are available.
Sensitive directional residual overcurrent and power CCRBRF function can be programmed to give a single- or
protection SDEPSDE three-phase re-trip of its own breaker to avoid unnecessary
tripping of surrounding breakers at an incorrect initiation due to
In isolated networks or in networks with high impedance
mistakes during testing.
earthing, the earth fault current is significantly smaller than the
short circuit currents. In addition to this, the magnitude of the Stub protection STBPTOC
fault current is almost independent on the fault location in the
When a power line is taken out of service for maintenance and
network. The protection can be selected to use either the
the line disconnector is opened in multi-breaker arrangements
residual current or residual power component 3U0·3I0·cos j,
the voltage transformers will mostly be outside on the
for operating quantity with maintained short circuit capacity.
disconnected part. The primary line distance protection will
thus not be able to operate and must be blocked.
30 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
The stub protection STBPTOC covers the zone between the 6. Voltage protection
current transformers and the open disconnector. The three-
phase instantaneous overcurrent function is released from a Two step undervoltage protection UV2PTUV
normally open, NO (b) auxiliary contact on the line Undervoltages can occur in the power system during faults or
disconnector. abnormal conditions. Two step undervoltage protection
(UV2PTUV) function can be used to open circuit breakers to
Pole discordance protection CCPDSC prepare for system restoration at power outages or as long-
An open phase can cause negative and zero sequence currents time delayed back-up to primary protection.
which cause thermal stress on rotating machines and can
cause unwanted operation of zero sequence or negative UV2PTUV has two voltage steps, each with inverse or definite
sequence current functions. time delay.
Normally the own breaker is tripped to correct such a situation. UV2PTUV has a high reset ratio to allow settings close to
If the situation persists the surrounding breakers should be system service voltage.
tripped to clear the unsymmetrical load situation.
Two step overvoltage protection OV2PTOV
The Pole discordance protection function CCPDSC operates Overvoltages may occur in the power system during abnormal
based on information from auxiliary contacts of the circuit conditions such as sudden power loss, tap changer regulating
breaker for the three phases with additional criteria from failures, and open line ends on long lines.
unsymmetrical phase currents when required.
Two step overvoltage protection (OV2PTOV) function can be
Directional over/underpower protection GOPPDOP/ used to detect open line ends, normally then combined with a
GUPPDUP directional reactive over-power function to supervise the
The directional over-/under-power protection GOPPDOP/ system voltage. When triggered, the function will cause an
GUPPDUP can be used wherever a high/low active, reactive or alarm, switch in reactors, or switch out capacitor banks.
apparent power protection or alarming is required. The
OV2PTOV has two voltage steps, each of them with inverse or
functions can alternatively be used to check the direction of
definite time delayed.
active or reactive power flow in the power system. There are a
number of applications where such functionality is needed. OV2PTOV has a high reset ratio to allow settings close to
Some of them are: system service voltage.
ABB 31
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
The PAPGAPC function performs phase selection using SAPTOF measures frequency with high accuracy, and is used
measured voltages. Each phase voltage is compared to the mainly for generation shedding and remedial action schemes. It
opposite phase-phase voltage. A phase is deemed to have a is also used as a frequency stage initiating load restoring. A
fault if its phase voltage drops below a settable percentage of definite time delay is provided for operate.
the opposite phase-phase voltage. The phase - phase voltages
SAPTOF is provided with an undervoltage blocking.
include memory. This memory function has a settable time
constant. The operation is based on positive sequence voltage
measurement and requires two phase-phase or three phase-
The voltage-based phase selection is used for both fast and
neutral voltages to be connected. For information about how to
delayed tripping. To achieve fast tripping, scheme
connect analog inputs, refer to Application manual/IED
communication is required. Delayed tripping does not require
application/Analog inputs/Setting guidelines
scheme communication. It is possible to permit delayed
tripping only upon failure of the communications channel by Rate-of-change frequency protection SAPFRC
blocking the delayed tripping logic with a communications The rate-of-change frequency protection function SAPFRC
channel healthy input signal. gives an early indication of a main disturbance in the system.
SAPFRC measures frequency with high accuracy, and can be
On receipt of the communications signal, phase selective
used for generation shedding, load shedding and remedial
outputs for fast tripping are set based on the phase(s) in which
action schemes. SAPFRC can discriminate between a positive
the phase selection function has operated.
or negative change of frequency. A definite time delay is
For delayed tripping, single pole and three pole delays are provided for operate.
separately and independently settable. Furthermore, it is
SAPFRC is provided with an undervoltage blocking. The
possible to enable or disable single pole and three pole delayed
operation is based on positive sequence voltage measurement
tripping. For single phase faults, it is possible to include a
and requires two phase-phase or three phase-neutral voltages
residual current check in the tripping logic. Three pole tripping
to be connected. For information about how to connect analog
is always selected for phase selection on more than one phase.
inputs, refer to Application manual/IED application/Analog
Three pole tripping will also occur if the residual current
inputs/Setting guidelines.
exceeds the set level during fuse failure for a time longer than
the three pole trip delay time.
8. Multipurpose protection
32 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Control operation can be performed from the local HMI with Bay control QCBAY
authority control if so defined. The Bay control QCBAY function is used together with Local
remote and local remote control functions to handle the
34 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
selection of the operator place per bay. QCBAY also provides same role as functions GOOSEBINRCV (for IEC 61850) and
blocking functions that can be distributed to different MULTICMDRCV (for LON).
apparatuses within the bay.
Single command, 16 signals
Local remote LOCREM/Local remote control LOCREMCTRL The IEDs can receive commands either from a substation
The signals from the local HMI or from an external local/remote automation system or from the local HMI. The command
switch are connected via the function blocks LOCREM and function block has outputs that can be used, for example, to
LOCREMCTRL to the Bay control QCBAY function block. The control high voltage apparatuses or for other user defined
parameter ControlMode in function block LOCREM is set to functionality.
choose if the switch signals are coming from the local HMI or
from an external hardware switch connected via binary inputs.
11. Scheme communication
Logic rotating switch for function selection and LHMI
Scheme communication logic for distance or overcurrent
presentation SLGAPC
protection ZCPSCH
The logic rotating switch for function selection and LHMI
To achieve instantaneous fault clearance for all line faults,
presentation SLGAPC (or the selector switch function block) is
scheme communication logic is provided. All types of
used to get an enhanced selector switch functionality
communication schemes for permissive underreaching,
compared to the one provided by a hardware selector switch.
permissive overreaching, blocking, delta based blocking,
Hardware selector switches are used extensively by utilities, in
unblocking and intertrip are available.
order to have different functions operating on pre-set values.
Hardware switches are however sources for maintenance The built-in communication module (LDCM) can be used for
issues, lower system reliability and an extended purchase scheme communication signaling when included.
portfolio. The selector switch function eliminates all these
problems. Phase segregated scheme communication logic for distance
protection ZC1PPSCH
Selector mini switch VSGAPC Communication between line ends is used to achieve fault
The Selector mini switch VSGAPC function block is a clearance for all faults on a power line. All possible types of
multipurpose function used for a variety of applications, as a communication schemes for example, permissive underreach,
general purpose switch. permissive overreach and blocking schemes are available. To
manage problems with simultaneous faults on parallel power
VSGAPC can be controlled from the menu or from a symbol on
lines phase segregated communication is needed. This will then
the single line diagram (SLD) on the local HMI.
replace the standard Scheme communication logic for distance
Generic communication function for Double Point indication or Overcurrent protection (ZCPSCH) on important lines where
DPGAPC three communication channels (in each subsystem) are
Generic communication function for Double Point indication available for the distance protection communication.
DPGAPC function block is used to send double indications to
The main purpose of the Phase segregated scheme
other systems, equipment or functions in the substation
communication logic for distance protection (ZC1PPSCH)
through IEC 61850-8-1 or other communication protocols. It is
function is to supplement the distance protection function such
especially used in the interlocking station-wide logics.
that:
Single point generic control 8 signals SPC8GAPC
• fast clearance of faults is also achieved at the line end for
The Single point generic control 8 signals SPC8GAPC function
which the faults are on the part of the line not covered by
block is a collection of 8 single point commands, designed to
its underreaching zone.
bring in commands from REMOTE (SCADA) to those parts of
• correct phase selection can be maintained to support
the logic configuration that do not need extensive command
single-pole tripping for faults occurring anywhere on the
receiving functionality (for example, SCSWI). In this way, simple
entire length of a double circuit line.
commands can be sent directly to the IED outputs, without
confirmation. Confirmation (status) of the result of the To accomplish this, three separate communication channels,
commands is supposed to be achieved by other means, such that is, one per phase, each capable of transmitting a signal in
as binary inputs and SPGAPC function blocks. The commands each direction is required.
can be pulsed or steady with a settable pulse time.
ZC1PPSCH can be completed with the current reversal and
AutomationBits, command function for DNP3.0 AUTOBITS WEI logic for phase segregated communication, when found
AutomationBits function for DNP3 (AUTOBITS) is used within necessary in Blocking and Permissive overreaching schemes.
PCM600 to get into the configuration of the commands coming
through the DNP3 protocol. The AUTOBITS function plays the
ABB 35
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Current reversal and weak-end infeed logic for phase This is why the IEDs have available additions to the scheme
segregated communication ZC1WPSCH communication logic.
Current reversal and weak-end infeed logic for phase
segregated communication (ZC1WPSCH) function is used to If parallel lines are connected to common busbars at both
prevent unwanted operations due to current reversal when terminals, overreaching permissive communication schemes
using permissive overreach protection schemes in application can trip unselectively due to fault current reversal. This
with parallel lines where the overreach from the two ends unwanted tripping affects the healthy line when a fault is cleared
overlaps on the parallel line. on the other line. This lack of security can result in a total loss of
interconnection between the two buses. To avoid this type of
The weak-end infeed logic is used in cases where the apparent disturbance, a fault current reversal logic (transient blocking
power behind the protection can be too low to activate the logic) can be used.
distance protection function. When activated, received carrier
signal together with local undervoltage criteria and no reverse Permissive communication schemes for residual overcurrent
zone operation gives an instantaneous trip. The received signal protection can basically operate only when the protection in the
is also echoed back to accelerate the sending end. remote IED can detect the fault. The detection requires a
sufficient minimum residual fault current, out from this IED. The
Local acceleration logic ZCLCPSCH fault current can be too low due to an opened breaker or high-
To achieve fast clearing of faults on the whole line, when no positive and/or zero-sequence source impedance behind this
communication channel is available, local acceleration logic IED. To overcome these conditions, weak-end infeed (WEI)
ZCLCPSCH can be used. This logic enables fast fault clearing echo logic is used. The weak-end infeed echo is limited to 200
and re-closing during certain conditions, but naturally, it can not ms to avoid channel lockup.
fully replace a communication channel.
Direct transfer trip DTT
The logic can be controlled either by the autorecloser (zone Low active power and power factor protection LAPPGAPC
extension) or by the loss-of-load current (loss-of-load
acceleration). Low active power and power factor protection (LAPPGAPC)
function measures power flow. It can be used for protection and
Scheme communication logic for residual overcurrent monitoring of:
protection ECPSCH
To achieve fast fault clearance of earth faults on the part of the • phase wise low active power
line not covered by the instantaneous step of the residual • phase wise low power factor
overcurrent protection, the directional residual overcurrent • phase wise reactive power and apparent power as service
protection can be supported with a logic that uses values
communication channels.
36 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 37
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
38 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 39
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Indications DRPRDRE The Disturbance recorder acquires sampled data from selected
To get fast, condensed and reliable information about analog- and binary signals connected to the Disturbance
disturbances in the primary and/or in the secondary system it is recorder function (maximum 40 analog and 128 binary signals).
important to know, for example binary signals that have The binary signals available are the same as for the event
changed status during a disturbance. This information is used recorder function.
in the short perspective to get information via the local HMI in a
straightforward way. The function is characterized by great flexibility and is not
dependent on the operation of protection functions. It can
There are three LEDs on the local HMI (green, yellow and red), record disturbances not detected by protection functions. Up
which will display status information about the IED and the to ten seconds of data before the trigger instant can be saved in
Disturbance recorder function (triggered). the disturbance file.
The Indication list function shows all selected binary input The disturbance recorder information for up to 100
signals connected to the Disturbance recorder function that disturbances are saved in the IED and the local HMI is used to
have changed status during a disturbance. view the list of recordings.
The event recorder logs all selected binary input signals Analog and double indication values are also transferred
connected to the Disturbance recorder function. Each through EVENT function.
recording can contain up to 150 time-tagged events.
Generic communication function for Single Point indication
The event recorder information is available for the disturbances SPGAPC
locally in the IED. Generic communication function for Single Point indication
SPGAPC is used to send one single logical signal to other
The event recording information is an integrated part of the
systems or equipment in the substation.
disturbance record (Comtrade file).
Generic communication function for Measured Value MVGAPC
Trip value recorder DRPRDRE
Generic communication function for Measured Value MVGAPC
Information about the pre-fault and fault values for currents and
function is used to send the instantaneous value of an analog
voltages are vital for the disturbance evaluation.
signal to other systems or equipment in the substation. It can
The Trip value recorder calculates the values of all selected also be used inside the same IED, to attach a RANGE aspect to
analog input signals connected to the Disturbance recorder an analog value and to permit measurement supervision on that
function. The result is magnitude and phase angle before and value.
during the fault for each analog input signal.
Measured value expander block RANGE_XP
The trip value recorder information is available for the The current and voltage measurements functions (CVMMXN,
disturbances locally in the IED. CMMXU, VMMXU and VNMMXU), current and voltage
sequence measurement functions (CMSQI and VMSQI) and IEC
The trip value recorder information is an integrated part of the 61850 generic communication I/O functions (MVGAPC) are
disturbance record (Comtrade file). provided with measurement supervision functionality. All
measured values can be supervised with four settable limits:
low-low limit, low limit, high limit and high-high limit. The
40 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
measure value expander block (RANGE_XP) has been setting values for limits. The output for each limit is activated
introduced to enable translating the integer output signal from when the counted value reaches that limit.
the measuring functions to 5 binary signals: below low-low limit,
below low limit, normal, above high limit or above high-high Overflow indication is included for each up-counter.
limit. The output signals can be used as conditions in the
Running hour-meter (TEILGAPC)
configurable logic or for alarming purpose.
The Running hour-meter (TEILGAPC) function is a function that
Gas medium supervision SSIMG accumulates the elapsed time when a given binary signal has
Gas medium supervision SSIMG is used for monitoring the been high.
circuit breaker condition. Binary information based on the gas
The main features of TEILGAPC are:
pressure in the circuit breaker is used as input signals to the
function. In addition, the function generates alarms based on • Applicable to very long time accumulation (≤ 99999.9
received information. hours)
• Supervision of limit transgression conditions and rollover/
Liquid medium supervision SSIML
overflow
Liquid medium supervision SSIML is used for monitoring the
• Possibility to define a warning and alarm with the
circuit breaker condition. Binary information based on the oil
resolution of 0.1 hours
level in the circuit breaker is used as input signals to the
• Retain any saved accumulation value at a restart
function. In addition, the function generates alarms based on
• Possibilities for blocking and reset
received information.
• Possibility for manual addition of accumulated time
Breaker monitoring SSCBR • Reporting of the accumulated time
The breaker monitoring function SSCBR is used to monitor
different parameters of the breaker condition. The breaker
requires maintenance when the number of operations reaches 14. Metering
a predefined value. For a proper functioning of the circuit
breaker, it is essential to monitor the circuit breaker operation, Pulse-counter logic PCFCNT
spring charge indication or breaker wear, travel time, number of Pulse-counter logic (PCFCNT) function counts externally
operation cycles and estimate the accumulated energy during generated binary pulses, for instance pulses coming from an
arcing periods. external energy meter, for calculation of energy consumption
values. The pulses are captured by the binary input module and
then read by the PCFCNT function. A scaled service value is
Fault locator LMBRFLO available over the station bus. The special Binary input module
The accurate fault locator is an essential component to with enhanced pulse counting capabilities must be ordered to
minimize the outages after a persistent fault and/or to pin-point achieve this functionality.
a weak spot on the line.
Function for energy calculation and demand handling
The fault locator is an impedance measuring function giving the (ETPMMTR)
distance to the fault in km, miles or % of line length. The main Measurements function block (CVMMXN) can be used to
advantage is the high accuracy achieved by compensating for measure active as well as reactive power values. Function for
load current and for the mutual zero-sequence effect on double energy calculation and demand handling (ETPMMTR) uses
circuit lines. measured active and reactive power as input and calculates the
accumulated active and reactive energy pulses, in forward and
The compensation includes setting of the remote and local
reverse direction. Energy values can be read or generated as
sources and calculation of the distribution of fault currents from
pulses. Maximum demand power values are also calculated by
each side. This distribution of fault current, together with
the function. This function includes zero point clamping to
recorded load (pre-fault) currents, is used to exactly calculate
remove noise from the input signal. As output of this function:
the fault position. The fault can be recalculated with new source
periodic energy calculations, integration of energy values,
data at the actual fault to further increase the accuracy.
calculation of energy pulses, alarm signals for limit violation of
Especially on heavily loaded long lines, where the source energy values and maximum power demand, can be found.
voltage angles can be up to 35-40 degrees apart, the accuracy
The values of active and reactive energies are calculated from
can be still maintained with the advanced compensation
the input power values by integrating them over a selected time
included in fault locator.
tEnergy. The integration of active and reactive energy values will
Event counter with limit supervison L4UFCNT happen in both forward and reverse directions. These energy
The 30 limit counter L4UFCNT provides a settable counter with values are available as output signals and also as pulse outputs.
four independent limits where the number of positive and/or Integration of energy values can be controlled by inputs
negative flanks on the input signal are counted against the
ABB 41
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
(STARTACC and STOPACC) and EnaAcc setting and it can be 16. Basic IED functions
reset to initial values with RSTACC input.
Time synchronization
The maximum demand for active and reactive powers are The time synchronization function is used to select a common
calculated for the set time interval tEnergy and these values are source of absolute time for the synchronization of the IED when
updated every minute through output channels. The active and it is a part of a protection system. This makes it possible to
reactive maximum power demand values are calculated for compare events and disturbance data between all IEDs within a
both forward and reverse direction and these values can be station automation system and in between sub-stations. A
reset with RSTDMD input. common source shall be used for IED and merging unit when
IEC 61850-9-2LE process bus communication is used.
The LHMI is used for setting, monitoring and controlling. SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
42 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Binary signal transfer to remote end, 192 signals Binary input/output module IOM
If the communication channel is used for transfer of binary The binary input/output module is used when only a few input
signals only, up to 192 binary signals can be exchanged and output channels are needed. The ten standard output
between two IEDs. For example, this functionality can be used channels are used for trip output or any signaling purpose. The
to send information such as status of primary switchgear two high speed signal output channels are used for applications
apparatus or intertripping signals to the remote IED. An IED can where short operating time is essential. Eight optically isolated
communicate with up to 4 remote IEDs. binary inputs cater for required binary input information.
Line data communication module, short, medium and long mA input module MIM
range LDCM The milli-ampere input module is used to interface transducer
The line data communication module (LDCM) is used for signals in the –20 to +20 mA range from for example OLTC
communication between the IEDs situated at distances <110 position, temperature or pressure transducers. The module has
km/68 miles or from the IED to optical to electrical converter six independent, galvanically separated channels.
with G.703 or G.703E1 interface located on a distances < 3
Optical ethernet module OEM
km/1.9 miles away. The LDCM module sends and receives
The optical fast-ethernet module is used for fast and
data, to and from another LDCM module. The IEEE/ANSI
interference-free communication of synchrophasor data over
C37.94 standard format is used.
IEEE C37.118 and/or IEEE 1344 protocols. It is also used to
connect an IED to the communication buses (like the station
ABB 43
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
bus) that use the IEC 61850-8-1 protocol (OEM rear port A, B). Electrical (BNC) and optical connection (ST) for 0XX and 12X
The process bus use the IEC 61850-9-2LE protocol (OEM rear IRIG-B support.
port C, D). The module has one or two optical ports with ST
connectors. Transformer input module TRM
The transformer input module is used to galvanically separate
Serial and LON communication module SLM, supports and adapt the secondary currents and voltages generated by
SPA/IEC 60870-5-103, LON and DNP 3.0 the measuring transformers. The module has twelve inputs in
The serial and LON communication module (SLM) is used for different combinations of currents and voltage inputs.
SPA, IEC 60870-5-103, DNP3 and LON communication. The
module has two optical communication ports for plastic/plastic, Alternative connectors of Ring lug or Compression type can be
plastic/glass or glass/glass. One port is used for serial ordered.
communication (SPA, IEC 60870-5-103 and DNP3 port) and
High impedance resistor unit
one port is dedicated for LON communication.
The high impedance resistor unit, with resistors for pick-up
Line data communication module LDCM value setting and a voltage dependent resistor, is available in a
Each module has one optical port, one for each remote end to single phase unit and a three phase unit. Both are mounted on a
which the IED communicates. 1/1 19 inch apparatus plate with compression type terminals.
Alternative cards for Long range (1550 nm single mode), Layout and dimensions
Medium range (1310 nm single mode) and Short range (850 nm Dimensions
multi mode) are available.
Examples of applications:
rest are slaves. No special control signal is needed in this case. IEC08000163 V2 EN
44 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
K
F
IEC06000182-2-en.vsd
IEC06000182 V2 EN
IEC08000165 V1 EN
Figure 18. Case with rear cover and 19” rack mounting kit
Case size A B C D E F G H J K
(mm)/(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00
6U, 3/4 x 19” 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00
6U, 1/1 x 19” 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00
The H and K dimensions are defined by the 19” rack mounting kit.
Mounting alternatives See ordering for details about available mounting alternatives.
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/8.27”
– 3/4 case size (h) 254.3 mm/10.01” (w) 322.4 mm/12.69”
– 1/1 case size (h) 254.3 mm/10.01” (w) 434.7 mm/17.11”
• Wall mounting kit
ABB 45
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
The latest versions of the connection diagrams can be Connection diagram, RED670 2.1, A32 1MRK002803-HC
downloaded from http://www.abb.com/substationautomation.
Connection diagram, RED670 2.1, B32 1MRK002803-HD
Connection diagrams for Customized products
Connection diagrams for Customized products
Connection diagram, 670 series 2.11MRK002801-AF
Connection diagram, 670 series 2.1 1MRK002802-AF
46 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified
requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Table 7. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) × Ir
Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules
ABB 47
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
Number of channels 1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118 and port C, D for IEC 61850-9-2LE / IEEE
C37.118)
Auxiliary DC voltage
48 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Binary inputs 16 -
Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
110/125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
ABB 49
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
50 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
ABB 51
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
52 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
90-250 V DC ±20%
Interruption interval
0–50 ms
No restart
Frequency dependence for distance protection operate value fr ±2.5 Hz for 50 Hz ±2.0% / Hz
fr ±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%
Harmonic frequency dependence for distance protection (10% content) 2nd, 3rd and 5th harmonic of fr ±10.0%
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)
Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0% / Hz
ABB 53
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
54 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle = 24 IEC 60068-2-30
hours)
Test According to
Immunity EN 60255–26
Emissivity EN 60255–26
ABB 55
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Differential protection
56 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
*Inverse characteristics, see table 16 curve types See table 171, 172 and table 173
171, 172 and table 172
*Note: Data valid for a single IED with two local current input groups
ABB 57
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Independent time delay, zero sequence current at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater
Independent time delay, low voltage operation at 2 x Uset to 0 (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater
Reset time delay for startup signal at 0 to 2 x Uset (0.000-60.000) s ±0.2% or ±40 ms
whichever is greater
58 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Impedance protection
Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
E operation
ABB 59
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 33. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS
Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ± 35 ms whichever is greater
E operation
Table 34. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
60 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±60 ms whichever is greater
E operation
Table 36. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
Definite time delay Ph-Ph and Ph- (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
E operation
ABB 61
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 38. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS
62 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 39. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS
Zero sequence reactance reach (0.01 - 9000.00) ohm/p ±2.0% of static accuracy
±2.0 degrees static angular accuracy
Zero sequence resistive reach (0.00 - 3000.00) ohm/p Conditions:
Fault resistance reach, Ph-E and (0.01 -9000.00) ohm/l Voltage range: (0.1-1.1) x Ur
Ph-Ph Current range: (0.5-30) x Ir
Angle: At 0 degrees and 85 degrees
Dynamic overreach < 5% at 85 degrees
measured with CVTs
and 0.5 < SIR < 30
Definite time delay to trip, Ph-E (0.000-60.000) s ±2.0% or ±35 ms whichever is greater
and Ph-Ph operation
ABB 63
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 41. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS
64 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Conditional timer for sending (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
the CS at power swings
Conditional timer for tripping at (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
power swings
Timer for blocking the (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
overreaching zones trip
ABB 65
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
residual current at 0 to 2 x Iset
Independent time delay for (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
residual voltage at 0.8 to 1.2 x Uset
Time delay to operate for the switch onto fault function (0.03-120.00) s ±0.2% or ±20 ms whichever is greater
Delay time for activation of dead line detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Drop-off delay time of switch onto fault function (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
66 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Current protection
ABB 67
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Minimum operate time for inverse (0.000-60.000) s ±0.2 % or ±35 ms whichever is greater
curves , step 1 - 4
Inverse time characteristics, see 16 curve types See table 171, table 172 and table 173
table 171, table 172 and table 173
68 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 51. Four step residual overcurrent protection EF4PTOC technical data
Operate current for directional (1–100)% of lBase For RCA ±60 degrees:
release ±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Minimum operate time for inverse (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
curves, step 1 - 4 greater
Inverse time characteristics, see 16 curve types See Table 171, Table 172 and
Table 171, Table 172 and Table Table 173
173
ABB 69
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Inverse time characteristics, see 16 curve types See table 171, table 172 and table
table 171, table 172 and table 173
173
Operate current for directional (1–100)% of IBase For RCA ±60 degrees:
release ±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
70 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 53. Sensitive directional residual overcurrent and power protection SDEPSDE
Inverse characteristics, see 16 curve types See table "", table "" and table ""
table "", table "" and table ""
ABB 71
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Operate time: Time constant t = (1–1000) IEC 60255-8, ±5.0% or ±200 ms whichever is greater
minutes
é ù
ê I - Ip
2 2 ú
t = t ln ê ú
ê 2 2 TTrip - TAmb 2 ú
ê I - Ip - T × I ref
ú
ë ref û
EQUATION13000039 V2 EN (Equation 1)
Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Time delay for back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater
Time delay for back-up trip at multi-phase start at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
Additional time delay for a second back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater
72 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
S r = 1.732 × U r × I r
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 to 0.5 x Sr and k=0.000
Max. = 25 ms
Max. = 55 ms
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 to 2 x Sr and k=0.000
ABB 73
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
74 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Voltage protection
Inverse time characteristics for step 1 and step 2, see table 175 - See table 175
Definite time delay, step 1 at 1.2 to 0 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is
greater
Definite time delay, step 2 at 1.2 to 0 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is
greater
ABB 75
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Inverse time characteristics for steps 1 and 2, see table 174 - See table 174
Definite time delay, low step (step 1) at 0 to 1.2 x Uset (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
Definite time delay, high step (step 2) at 0 to 1.2 x Uset (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
Minimum operate time, Inverse characteristics (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is greater
(0.18 × k )
IEEE : t =
( M - 1) 2
EQUATION1319 V1 EN (Equation 2)
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is greater
function
Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is greater
function
76 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration
Time delay to block when all three (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
phase voltages are not low
Independent time delay to operate, residual (0.000 - 60.000) s ±0.2% or ±40 ms whichever is greater
current detection at 0 to 2 x Iset
Independent time delay to operate, voltage (0.000 – 60.000) s ±0.2% or ±40 ms whichever is greater
based phase selection at 1.2 to 0.8 x Uset
ABB 77
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Frequency protection
Operate time, definite time function at fset + 0.02 Hz to (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 Hz to fset (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
+ 0.02 Hz
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN (Equation 3)
U=Umeasured
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater
Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater
78 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Definite time delay for frequency gradient trip (0.200-60.000) s ±0.2% or ±120 ms whichever is
greater
ABB 79
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Multipurpose protection
Independent time delay, overcurrent at 0 to 2 x Iset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Independent time delay, undercurrent at 2 to 0 x Iset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 171, 172 and table 173 16 curve types See table 171, 172 and table 173
Overcurrent:
Minimum operate time for inverse curves, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Voltage level where voltage memory takes over (0.0 - 5.0)% of UBase ±0.5% of Ur
Independent time delay, overvoltage at 0.8 to 1.2 x Uset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
80 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Independent time delay, undervoltage at 1.2 to 0.8 x Uset, step 1 - (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
2 greater
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 174 4 curve types See table 174
Undervoltage:
Inverse time characteristics, see table 175 3 curve types See table 175
High and low voltage limit, voltage dependent operation, step 1 - 2 (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
±1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
ABB 81
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 71. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4
82 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate at 0 to 2 x Iset (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Inverse time characteristics, 13 curve types See tables 171 and 172
see tables 171 and 172
Minimum operate time for inverse time characteristics (0.00 - 60.00) s ±0.2% or ±35 ms whichever is
greater
High voltage limit, voltage dependent operation (30.0 - 100.0)% of UBase ±1.0% of Ur
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate, undervoltage at 2 to 0 x Uset (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 to 0 x Uset
Impulse margin time 15 ms typically
ABB 83
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
84 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 85
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Control
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s ±0.2% or ±35 ms whichever is
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees greater
tMaxSynch, which resets synchronizing function if no close has been made (0.000-6000.00) s ±0.2% or ±35 ms whichever is
before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s ±0.2% or ±100 ms whichever is
Urated greater
Operate time for synchrocheck function when angle difference between bus Min. = 15 ms –
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees Max. = 30 ms
Operate time for energizing function when voltage jumps from 0 to 90% of Min. = 70 ms –
Urated Max. = 90 ms
86 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle (0.00-6000.00) s ±0.2% or ±35 ms
whichever is greater
Wait time after close command before proceeding to next shot (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
ABB 87
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Scheme communication
Table 78. Scheme communication logic for distance or overcurrent protection ZCPSCH
Table 79. Phase segregated scheme communication logic for distance protection ZC1PPSCH
Table 80. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
88 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 81. Scheme communication logic for residual overcurrent protection ECPSCH
Table 82. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
ABB 89
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 83. Low active power and power factor protection LAPPGAPC
Independent time delay to operate for low active power at 1.2 to 0.8 (0.000-60.000) s ±0.2% or ±40 ms whichever is
x Pset greater
Independent time delay to operate for low power factor at 1.2 to 0.8 (0.000-60.000) s ±0.2% or ±40 ms whichever is
x PFset greater
Critical impulse time, low active power 10 ms typically at 1.2 to 0.8 x Pset -
Independent time delay for undervoltage functionality at 1.2 to (0.000-60.000) s ±0.2% or ±40 ms whichever is
0.8 x Uset greater
Independent time delay for overvoltage functionality at 0.8 to 1.2 (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
x Uset
Hold time for operate signal at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
90 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Independent time delay to operate at 0 to 1.2 x Uset (0.000-120.000) s ±0.2% or ±40 ms whichever is
greater
Independent time delay to operate at 0 to 1.2 x Uset (0.000-120.000) s ±0.2% or ±40 ms whichever is
greater
ABB 91
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
92 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 93
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Logic
3 ms 8 ms 100 ms
SMPPTRC 6 - -
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
3 ms 8 ms 100 ms
ALMCALH - - 5
3 ms 8 ms 100 ms
WRNCALH - - 5
3 ms 8 ms 100 ms
INDCALH - 5 -
3 ms 8 ms 100 ms
AND 60 60 160
3 ms 8 ms 100 ms
GATE 10 10 20
94 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
INV 90 90 240
3 ms 8 ms 100 ms
LLD 10 10 20
3 ms 8 ms 100 ms
OR 69 60 160
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XOR 10 10 20
ABB 95
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
ANDQT - 20 100
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
3 ms 8 ms 100 ms
INVALIDQT - 6 6
3 ms 8 ms 100 ms
INVERTERQT - 20 100
3 ms 8 ms 100 ms
ORQT - 20 100
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
96 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XORQT - 10 30
3 ms 8 ms 100 ms
AND 40 40 100
GATE - - 49
INV 40 40 100
LLD - - 49
OR 40 40 100
PULSETIMER 5 5 49
SLGAPC 10 10 54
SRMEMORY - - 110
TIMERSET - - 49
VSGAPC 10 10 110
XOR - - 49
3 ms 8 ms 100 ms
B16I 6 4 8
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
ABB 97
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
IB16 6 4 8
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
Table 125. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value
98 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Monitoring
Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir
ABB 99
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
100 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
ABB 101
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Independent time delay for spring charging time (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure alarm (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure lockout (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
Function Value
Resolution 1 ms
102 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Function Value
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at 50 Hz
channels, typical value) 280 seconds (80 recordings) at 60 Hz
ABB 103
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
104 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Station communication
Function Value
Protocol DNP3.0
Function Value
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
ABB 105
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Insulation 1 kV
Table 158. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
106 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
ABB 107
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Hardware
IED
Table 161. Water and dust protection level according to IEC 60529
Electrical safety
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
Because of limitations of space, when ring between two adjacent IO cards. Please refer
lug terminal is ordered for Binary I/O to the ordering particulars for details.
connections, one blank slot is necessary
108 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
Time to reliable time reference after a power loss longer <15 minutes –
than 48 hours
Time to reliable time reference after a power loss shorter <5 minutes –
than 48 hours
Function Value
Accuracy +/-1μs
ABB 109
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
110 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Inverse characteristic
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ABB 111
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
112 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
U> = Uset
U = Umeasured
k ⋅ 480
t = + 0.035
2.0
32 ⋅ U − U > − 0.5
U >
EQUATION1437-SMALL V2 EN
k ⋅ 480
t = + 0.035
3.0
32 ⋅ U − U > − 0.5
U >
EQUATION1438-SMALL V2 EN
ABB 113
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
U< = Uset
U = Umeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
114 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
U> = Uset
U = Umeasured
ABB 115
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0
Example of a complete code: RED670*2.1 - F00X00 - A00000030211111 - B5225255221255221111101000 - C3300032122020022221000300 - D22212 011 - E2220 -
F4 - S6 - G232 - H20401100000 - K11111111 - L11 - M21 - P01 - B1X0 - AC -MB - B - A3X0 - D1D1ARGN1N1XXXXXXX - AAFXXX - AX
Impedance protection -
B 0 0 0 0 -
Current protection -
C 00 0 00 1 0 0 0 0 0 -
Remote end serial communication - Serial communication unit for station communication
-
Product RED670*
Software version 2.1
Configuration alternatives
Line differential protection RED670 F00
Line differential protection RED670 61850-9-2LE N00
Selection:
ACT configuration
No ACT configuration downloaded X00
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14
A 0 0 0 0 0 0 0
116 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Po 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
siti
on
B 0 0 0 0
ABB 117
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Pos 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
itio
n
C 00 0 00 1 0 0 0 0 0
118 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Position 1 2 3 4 5 6 7 8
D 0 1
Position 1 2 3 4
E 00
Position 1
F
ABB 119
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Position 1
S
Position 1 2 3
G
Position 1 2 3 4 5 6 7 8 9 10 11
H 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8
K
120 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Position 1 2
L
Position 1 2
M 1
Position 1 2 3 4 5 6 7 8 9 10 11 12 13
P 0 0 0 0 0 0 0 0 0 0 0
Function Function Ordering no Position Available qty Selected qty Notes and rules
identification
Process Bus communication IEC 61850-9-2 1MRK005930-TA 1 0 if F00 is Note: RED670
selected, 6 if customized qty =
N00 is selected 0, RED670
61850-9-2 qty = 6
IEC 62439-3 parallel redundancy protocol PRP 1MRK002924-YB 2 1 Note: Not valid in
RED670
61850-9-2LE
product
Note: Requires
2–channel OEM
First local HMI user dialogue language Selection Notes and Rules
HMI language, English IEC B1
Additional HMI language
No additional HMI language X0
HMI language, English US A12
Selected
ABB 121
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Mounting details with IP40 of protection from the front Selection Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selected
122 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Note: When ordering I/O modules, observe the maximum quantities according to the table below
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19”, one (1) TRM 14 6 4 4 14 cards, including a combination of four cards of type BOM, SOM and MIM
1/1 x 19”, two (2) TRM 11 6 4 4 11 cards, including a combination of four cards of type BOM, SOM and MIM
3/4 x 19”, one (1) TRM 8 6 4 4 8 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
3/4 x 19”, two (2) TRM 5 5 4 4 5 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
1/2 x 19”, one (1) TRM 3 3 3 1 3 cards
ABB 123
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
in 3/4 rack with 1TRM, 5 in 3/4 rack
1/2 Case with 1 TRM █ █ █ with 2 TRM, 11 in 1/1 rack with 2
TRM and 14 in 1/1 rack with 1 TRM
3/4 Case with 1 TRM █ █ █ █ █ █ █ █
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X X X
Binary output module 24 A A A A A A A A A A A A A A
output relays (BOM)
BIM 16 inputs, RL24-30 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
VDC, 50 mA
BIM 16 inputs, RL48-60 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
VDC, 50 mA
BIM 16 inputs, D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110-125 VDC, 50 mA
BIM 16 inputs, E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220-250 VDC, 50 mA
BIM 16 inputs, 220-250 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
VDC, 120mA
BIMp 16 inputs, RL24-30 F F F F F F F F F F F F F F
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, RL48-60 G G G G G G G G G G G G G G
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, H H H H H H H H H H H H H H
RL110-125 VDC, 30 mA,
for pulse counting
BIM 16 inputs, K K K K K K K K K K K K K K
RL220-250 VDC, 30 mA,
for pulse counting
IOM 8 inputs, 10+2 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
output, RL24-30 VDC, 50
mA
IOM 8 inputs, 10+2 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
output, RL48-60 VDC, 50
mA
IOM 8 inputs, 10+2 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
output, RL110-125 VDC,
50 mA
IOM 8 inputs, 10+2 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
output, RL220-250 VDC,
50 mA
IOM 8 inputs 10+2 output P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
relays, 220-250 VDC,
110mA
IOM with MOV 8 inputs, U U U U U U U U U U U U U U
10-2 output, 24-30 VDC,
30 mA
IOM with MOV 8 inputs, V V V V V V V V V V V V V V
10-2 output, 48-60 VDC,
30 mA
IOM with MOV 8 inputs, W W W W W W W W W W W W W W
10-2 output, 110-125
VDC, 30 mA
IOM with MOV 8 inputs, Y Y Y Y Y Y Y Y Y Y Y Y Y Y
10-2 output, 220-250
VDC, 30 mA
mA input module MIM 6 R R R R R R R R R R R R R R
channels
124 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Remote end communication, DNP serial comm. and time synchronization modules Selection Notes and Rules
Slot position (rear view) Note: The maximum number and
X312
X313
X302
X303
X322
X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2, 3/4 or 1/1 case with 1TRM █ █ █ █ Note: Max 2 LDCM in 1/2 case
Available slots in 3/4 and 1/1 case with 2 TRM █ █ █ █ █ █
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Max 4 LDCM (same or different
type) can be selected.
Optical medium range, LDCM 1310 nm B B B B B B
Always place LDCM modules on
Optical long range, LDCM 1550 nm C C C C C C the same board to support
Galvanic X21 line data communication module E E E E E E redundant communication; in
P30:2 and P30:3, P31:2 and P31:3
or P32:2 and P32:3
IRIG-B Time synchronization module F F F F F F
Galvanic RS485 communication module G G G G G G
GPS time synchronization module S S S S
Selected
Serial communication unit for station communication Selection Notes and Rules
Slot position (rear view)
X301
X311
ABB 125
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RED670 *2.1-A30X00- A02H02-B1A3-AC-MB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-13 specified as
RED670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 8-9-10 10 10 10-110 11 11 11 11 11 11 11 11 11 11-12 12 12 12 12 12-13 13
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
RED670* - - - - - . - -
10 - 11 - 12 - 13
- . -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 2.1
Selection for position #1.
126 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 127
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Input/output and Communication modules #8 Notes and Rules
Compression terminals P
Selection for position #8.
128 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 129
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Binary input/output module, mA and time synchronizating #11 Notes and Rules
boards.
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability
is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
Slot position (rear view) Note: Max 3 positions in 1/2 rack, 8
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
in 3/4 rack with 1 TRM, 5 in 3/4
rack with 2 TRM, 14 in 1/1 rack
with 1 TRM and 11 in 1/1 rack with
2 TRM
1/2 Case with 1 TRM █ █ █
3/4 Case with 1 TRM █ █ █ █ █ █ █ █
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X X X
Binary output module 24 output relays (BOM) A A A A A A A A A A A A A Note: Maximum 4 (BOM+SOM
+MIM) boards.
BIM 16 inputs, RL24-30 VDC, 50 mA B B B B B B B B B B B B B
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C C C C C C C C C C C C
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 mA D D D D D D D D D D D D D
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 mA E E E E E E E E E E E E E
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, 220-250 VDC, 120mA E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting F F F F F F F F F F F F
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting G G G G G G G G G G G G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting H H H H H H H H H H H H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting K K K K K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L L L L L L L L L L L L
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M M M M M M M M M M M M
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N N N N N N N N N N N N
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P P P P P P P P P P P P
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA P P P P P P P P P P P P
2 2 2 2 2 2 2 2 2 2 2 2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA U U U U U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA V V V V V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA W W W W W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA Y Y Y Y Y Y Y Y Y Y Y Y
mA input module MIM 6 channels R R R R R R R R R R R R Note: maximum 1 MIM board in
1/2 case
SOM Static output module, 12 outputs, 48-60 VDC T T T T T T T T T T T T Note: SOM must not to be placed
1 1 1 1 1 1 1 1 1 1 1 1 in position nearest to NUM; 1/2
case slot P5, 3/4 case 1 TRM slot
SOM static outputs module, 12 outputs, 110-250 VDC T T T T T T T T T T T T
P10, 3/4 case 2 TRM slot P7, 1/1
2 2 2 2 2 2 2 2 2 2 2 2
case 1 TRM slot P16, 1/1 case 2
TRM slot P13
Selection for position #11.
130 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Remote end communication, DNP serial comm. and time synchronization modules #12 Notes and Rules
Slot position (rear view) Note: The maximum number and
X312
X313
X302
X303
X322
X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2 and 3/4 case with 1TRM █ █ █ █ Note: Only for A31/A32. One
LDCM must be ordered. Max 2
LDCM in 1/2 case.
Available slots in 3/4 and 1/1 case with 2 TRM █ █ █ █ █ █ Note: 2 LDCM in B31 and B32
must be ordered. Max 4 LDCM
No remote communication board included X X X X X A31 and A32 - 1 LDCM always in
position P30:2(X302)
No remote communication board included X X X X B31 and B32 - 1 LDCM always in
position P30:2(X302) and
P30:3(X303)
Optical short range LDCM A A A A A A Max 4 LDCM (same or different
type) can be selected.
Optical medium range, LDCM 1310 nm B B B B B B
Always place LDCM modules on
Optical long range, LDCM 1550 nm C C C C C C the same board to support
Galvanic X21 line data communication module E E E E E E redundant communication; in
P30:2 and P30:3, P31:2 and P31:3
IRIG-B Time synchronization module, with PPS F F F F F F or P32:2 and P32:3
Galvanic RS485 communication module G G G G G Note: No RS485 in position X303
in B31/B32
GPS time module GTM S S S S
Selection for position #12.
Serial communication unit for station communication #13 Notes and Rules
Slot position (rear view)
X301
X311
No first communication board included X
No second communication board included X
Serial and LON communication module (plastic) A
Serial (plastic) and LON (glass) communication module B
Serial and LON communication module (glass) C
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selection for position #13.
ABB 131
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Accessories
GPS antenna and mounting details
Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA
Due to the high flexibility of our product and the wide variety of The normally open "In test mode" contact 29-30 on the RTXP
applications possible the test switches needs to be selected for test switches should be connected to the input of the test
each specific application. function block to allow activation of functions individually during
testing.
Select your suitable test switch base on the available contacts
arrangements shown in the reference documentation. Test switches type RTXP 24 is ordered separately. Please refer
to Section Related documents for references to corresponding
However our proposals for suitable variants are; documents.
Single breaker/Single or Three Phase trip with internal neutral RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and the
on current circuits (ordering number RK926 315-AK). on/off switch for dc-supply are ordered separately. Please refer
to Section Related documents for references to corresponding
Single breaker/Single or Three Phase trip with external neutral documents.
on current circuits (ordering number RK926 315-AC).
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
132 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V 1 2 3
operating voltage Quantity: RK 795 101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V Quantity: RK 795 101-MB
operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 100-400V 1 2 3
operating voltage Quantity: RK 795 101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 100-400V Quantity: RK 795 101-DC
operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual and Getting started guide), Connectivity
packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AD
ABB 133
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 505 343-UEN
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 349-UEN
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 350-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 351-UEN
134 ABB
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
670 series manuals Document numbers
Documents related to RED670 Document numbers Operation manual IEC:1MRK 500 123-UEN
ANSI:1MRK 500 123-UUS
Application manual IEC:1MRK 505 343-UEN
ANSI:1MRK 505 343-UUS Engineering manual IEC:1MRK 511 355-UEN
ANSI:1MRK 511 355-UUS
Commissioning manual IEC:1MRK 505 345-UEN
ANSI:1MRK 505 345-UUS Installation manual IEC:1MRK 514 024-UEN
ANSI:1MRK 514 024-UUS
Product guide 1MRK 505 346-BEN
Communication protocol manual, 1MRK 511 348-UUS
Technical manual IEC:1MRK 505 308-UEN DNP3
ANSI:1MRK 505 308-UUS
Communication protocol manual, 1MRK 511 351-UEN
Type test certificate IEC:1MRK 505 346-TEN IEC 60870-5-103
ANSI:1MRK 505 346-TUS
Communication protocol manual, 1MRK 511 349-UEN
IEC 61850 Edition 1
ABB 135
136