Lightning Protection and Earthing System
Lightning Protection and Earthing System
Lightning Protection and Earthing System
Lightning
Protection and
Earthing System
[LIGHTNING PROTECTION AND EARTHING
Chapter 9 SYSTEM]
Ø Lightning protection:
3) Ground rods properly sized and installed to carry the charge to the
earth.
(Air termination)
The earth termination is that part which discharges the current into the
general mass of the earth. In other words, it is one or more earth electrodes.
Earth electrodes for lightning protection are no different from earth
electrodes for short-circuit protection systems. The total resistance of an
earthing system, with all electrodes in parallel, should not exceed 10ohms. It
is clearly safer to ensure that the resistance of each electrode is less than
10ohms. The electrodes should be rod or strip type, and should be either
beneath or as near as possible to, the building being protected
(Grounding rod)
In order to prevent side flash over; all metallic objects should be bonded to
each other to the protection system
P=Ac×Ng×10 exp(-6)
Where:
Ng=lightning flash density, i.e. the number of flashes to ground per km2 per
year.
Also
= + + +
Where:
And (Ng) factor can be taken from the standard map that gives number of
flashes to ground per year for each region in the world.
=
× × × × ×
The standard recommends that protection is needed if RF is greater than
(1/100,000) per year
Ø In our hotel:
Ac= 38732.44
A= 1.7
B=0.4
C=1.7
D=1
E=0.3
The air termination must be a network of conductors on the roof. One strip
will run round the perimeter, and an additional lengthwise strip down the
centre of the roof.
= (2×28) + (2×34) =124m and the number of down conductors required will
therefore be124/20=7. Each will terminate in a rod type earth electrode.
When installing an earth system; the resistivity of the nearby ground should
be measured. Inaccurate resistivity tests can lead to unnecessary cost in the
design of the system. In order to obtain a low enough value of earth
resistance, earth systems may consist of an earth mat covering a large area
or many interconnected rods.
Despite the low conductivity of soil and rock, large volumes surrounding the
earth electrode enable a low resistance to earth to be obtained.
economic barriers restrict the size and type of electrodes, leaving the soil
conductivity as the only flexible parameter, to improve grounding
effectiveness.
2) Temperature:
With the fall in soil temperature; the resistivity increases. For a change in soil
temperature from +20°C to -5°C the resis vity increase more than ten mes.
For a mixture of sand & clay, at 15% humidity the behaviour is as below:
3) Moisture Content:
Different minerals and salts affect soil resistivity. Although the addition of
salt can lower soil resistivity but it increases the corrosion.
Buildings are connected to the ground and therefore the floors on which we
stand are at the same potential. The electrical connections that come into
our homes and offices need to be safe. This is why the earth connection in a
domestic location is usually made to a metal pipe (such as water pipes)
somewhere close to where it enters the ground. It was found that when the
distribution transformer has an earth connection, it usually be in the form of
a copper rod anchored in the ground. Lightning conductors that are found on
tall buildings will also be rooted in the ground, so that in the event of a
lightning strike the current passes harmlessly to ground and not into the
structure of the building, thus saving the building from damage.
N = Neutral
S = Separate
C = Combined
The system will either be TN-S, TN-C-S (PME) or TT for a low voltage supply
given in accordance with the Electricity Safety, Quality and Continuity
Regula ons 2002. This is because TN-C requires an exemption from the
Electricity Safety, Quality and Continuity Regulations.
C) TT system earthing
D) IT system earthing
We connect a network of
electrodes under the hotel
building connected in parallel
with the water and gas pipe
lines to decrease the
grounding resistance as
shown.
With TT, the consumer must provide their own connection to earth, i.e. by
installing a suitable earth electrode local to the installation. In some
circumstances; the distributor can’t provide a means of earthing for the
consumer such as:
1- When the distributor cannot guarantee the earth connection back to the
source, e.g. a low voltage overhead supply, where there is the likelihood of
the earth wire either becoming somehow disconnected or even stolen.
Rods can only be as effective as the contact they make with the surrounding
material. Thus, they should be driven into virgin ground, not disturbed
ground.
When it is necessary to drive two or more rods and connect them together
to achieve a satisfactory result, the separation between rods should be at
least equal to their combined driven depth to obtain maximum advantage
from each rod. In some locations low soil resistivity is found to be
concentrated in the topsoil layer, beneath which there may be rock or other
impervious layers which prevents the deep driving of rods, or a deep layer of
high resistivity. Only a test or known information about the ground can
reveal this kind of information. In such circumstances, the installation of
copper earth tapes, or pipes or plates, would be most likely to provide a
satisfactory earth electrode resistance value. Whatever form an earth
electrode takes, the possibility of soil drying and freezing, and of corrosion,
must be taken into account. Preferably, testing of an earth electrode should
be carried out under the least favorable conditions, i.e. after prolonged dry
weather. Further information on earthing principles and practice can be
found in BS 7430: 1998 “Code of Prac ce for Earthing”.