Protection of Substation
Protection of Substation
Protection of Substation
Protection of
Substation
Chapter 10 [PROTECTION OF SUBSTATION]
10.1. Introduction
In a power system consists of generators, transformers, transmission and
distribution circuits some failure may occur somewhere in the system. When
a fault occurs at any part of electric power system, it must be cleared quickly
in order to avoid damage or to maintain the rest of the system of continuous
operation. So; we should use protection systems.
We usually think of an electric power system in terms of its more effective
parts like the big generating stations, transformers, high-voltage lines, etc.
While these are some of the basic elements, there are many other necessary
and fascinating components. Protective relaying is one of these components.
In protection schemes; there is main and backup protection (or instantaneous
and inverse definite time protection) which can be applied on upstream part
up to transmission system. But main protection for our project is only in the
distribu on part (11Kvà.38Kv).
Table (10.2) illustrates some abnormal condi ons and associated protec on
systems for generator.
Table (10.4) summary of the methods used for protection of bus zones.
Method Particulars Remarks
Used in distribution
High set instantaneous
Bus protection by system (6-33)kV with
over current relays and earth
over current relays, transformers feeder
fault relays ,or definite time
of connected circuit supply to bus bars
relays
Time of order (100-400)ms
Used in the major
station
High impedance
High impedance circulating connected in series
current differential protection with relay coil to
Bus protection by
High impedance differential improve stability
differential
protection based on voltage Voltage drop across
protection
drop impedance is measured
Biased differential protection for discrimination
Biased coil gives
restrain for external
faults
Rapid reliable ,no problem of Referred in modern
Static protection
CT saturation installation
The zone of primary
Over current protection or protection of feeders is
Back up protection
distance protection extended to cover bus
zone
Table (10.4)
10.2.4. Motor protection
The protection of motors varies considerably and is less standardized in
general than the protection of the other apparatus or parts of the power
system. This results from the very wide variety of sizes, types, and
applications of motors. There are many variables involved in choosing motor
protection: Motor importance, motor rating (from one to several thousands
of horsepower), type of motor controller, etc. Therefore it is recommended
that protection for each specific motor installation be chosen to meet the
requirements of the specific motor and its use.
10.2.4.1. Motor hazards
The most effecting hazards which are normally considered:
1- Faults: Such as phase to phase and/or to ground.
2- Thermal damage from: - Over load (continuous or intermittent).
3- Locked rotor (failure to start or jamming).
4- Unbalanced operation.
5- Under voltage and over voltage.
6- Reversed phases.
The characteristics of O.C.Rs and E.F.Rs are adjusted (current setting and
time setting) according to the location of the protective devices in order to
maintain the required coordination. We will suggest the same protection
schemes for the cables in the system under study.