Aparatos A Prueba de Explosion
Aparatos A Prueba de Explosion
Aparatos A Prueba de Explosion
PHOTO: BASF
SENSORS FOR
HAZARDOUS AREAS
Sensors are essential to meet the various
2
CONTENTS
STANDARD DESIGN
CAPACITIVE AND MAGNETIC 22
ACCESSORIES Cordsets 37
Reflectors for photoelectric sensors 38
Mounting accessories for photoelectric sensors 38
Accessories for the F25 series 39
3
ATEX – EXPLOSION PROTECTION
What does the Directive 94/9/EC stipulate? What are the practical consequences of Directive 94/9/EC?
■ Definition of device groups I and II. ■ Existing installations may continue to be operated with
■ Definition of device categories (classification of devices having old certificates
devices according to hazardous areas) ■ New installations may only be put into operation and run with
■ Conformity evaluation procedure (which manufacturers are devices having new certificates.
allowed to produce devices in which category) ■ Only devices with certificates according to Directive 94/9/EC
■ From July 01, 2003 only Directive 94/9/EC applies! may be sold.
What consequences does Directive 94/9/EC have for the legal Intrinsic safety
situation? The characteristic voltage and current values are kept at such a
■ Zones 0, 1, 2 for areas at risk from gas explosions. low level that the NAMUR* proximity sensor can be used in
■ Zones 20, 21, 22 for areas at risk from dust explosions. potentially explosive environments (“intrinsic safety” type of
■ No zone classification for areas used for medical purposes protection). This product series is identified by an N at the end
■ No national requirements for zone 0 devices (1020). of the code, sometimes in combination with a number.
■ Standardized, European-wide installation guidelines. The power limitation is implemented in the corresponding
equipment. This means that the circuit containing a NAMUR
European standards: proximity sensor is only intrinsically safe if it is supplied via a
■ EN 1127-1 corresponding isolating amplifier. The conformity of the electrical
Explosive atmospheres - Explosion prevention and protection characteristics of proximity sensors and isolation amplifiers is
Part 1: Basic concepts and methodology ascertained by an “intrinsic safety test”. The cable inductivity
■ EN 60079-10 and the capacitance are included in the test as they constitute
Electrical apparatus for explosive gas atmospheres energy stores.
(Classification of hazardous areas of zones 0, 1, 2) For more information on explosion protection and intrinsic
■ EN 61241-10 safety, refer to our “Explosion Protection” manual.
Electrical apparatus for use in the presence of combustible
dust (Classification of hazardous areas of zones 20, 21, 22) SIL - Safety Integrity Level Functional Safety in accordance with
■ EN 60079-14 IEC 61508
Electrical apparatus for explosive gas atmospheres The combination of explosion protection and functional safety is
■ EN 61241-14 gaining increasing significance in process technology
Electrical apparatus for use in the presence of combustible dust applications. Already there is increasing reference to IEC 61508,
which as DIN EN 61508 has meanwhile become part and parcel
National regulations of the German and European controlling standards.
All relevant German regulations have been accordingly amended Pepperl+Fuchs is able to provide you with the corresponding
and adjusted in view of the introduction of Directive 94/9/EC on data, such as failure rates and safe-failure fractions for a range
March 01, 1996: of sensors; these sensors are identified in the following tables
■ 11th enactment of Equipment Safety Law - Explosion with the relevant SIL classification (single-channel version).
Protection Regulation
■ ExVO * NAMUR: Normenarbeitsgemeinschaft für Mess- und Regelungstechnik der
■ BetrSichV chemischen Industrie. Standards Working Group for Control and
■ EX-RL Instrumentation in the Chemical Industry.
4
ATEX – MARKING AND MEANING
II 1G E Ex
AREA OF APPLICATION EXPLOSION
Equipment certified according to ATEX95 Directive is provided with an PROTECTION
additional marking which describes the installation location (or, in the
case of associated electrical equipment, explains where the signal
cables may lead). First the device group is indicated, then the CERTIFICATION
category and finally the atmosphere (gas and/or dust). The following E = CENELEC STANDARDS
categorization applies to device group II: A = AMERICAN STANDARDS
5
Electrical equipment is divided
into temperature classes
according to its maximum
surface temperatures. The
gases are classified according
to the different ignition ZONE CLASSIFICATION
temperatures.
Areas in which a hazardous, explosive atmosphere may occur are divided into
Highest surface zones according to the probability of occurrence of these hazardous
temperature of the
atmospheres.
equipment
In the case of gas atmospheres, a classification is made into zone 0, 1 and 2.
CENELEC Typical Ignition T 1 450 °C In the case of dust atmospheres, a classification is made into zone 20, 21 and 22.
Marking gas power T 2 300 °C
µJ T 3 200 °C Zone Definition
T 4 135 °C Gas Dust
I Methane 280 T 5 100 °C 0 20 Present continuously or for long periods of time
II A Propane > 180 T 6 85 °C 1 21 Likely to exist under normal operations
II B Ethylene 60 … 180 2 22 Not likely under normal conditions; if so, only for short periods
II C Hydrogen <60 TEMPERATURE
CLASSES
DEVICE GROUPS
ia IIC T6
(circulating machines, fuses, lights,
measuring instruments and equipment with low power)
FOR AREAS AT RISK FROM GAS EXPLOSIONS TYPE OF PROTECTION “n”, SELECTION
Protection type Gen. requirements Flameproof Increased safety Intrinsic safety Encapsulation Protection type “n”
Symbol
6
7
PHOTO: BASF
STANDARD SENSORS FOR BOX INSTALLATION
Box solutions involve the integration of sensor systems in connector and distribution
boxes where there is a mechanical connection between sensors and actuators.
This eliminates direct exposure of sensors to ambient
ng on
influences and enables the use of conventional standard sensors.
nali
sig
back tioners
Different types of sensors can be used in these standard boxes:
■ Cylindrical sensors with a typical design length of 40 mm ed
Fe posi
■ Rectangular sensors with standard mechanical micro-switch
e
dimensions
■ Slot-shaped sensors with a slot width of 3.5 mm
valv
Most well-known actuator manufacturers provide standard boxes with or without an
optical display and equipped with sensors that are supplied by Pepperl+Fuchs.
■ Versatile –
Individual connection options
■ Reliable –
Protects the installation against manipulations, dirt and freezing
■ Safe –
Conforms with accident prevention legislation
■ Simple –
Installation with pre-adjusted sensors
■ Standardized –
Connection designation of measuring and control equipment conforms
with DIN 45140 T.1 and VDI/VDE 3845 mechanical stability
BOX SOLUTIONS WITH SLOT SENSORS (for more slot sensors see page 15 and 21)
Model number Switch element Slot Installation Connection Ex-designation EC prototype SIL
function width test certificate
Slot-shaped
SC3,5-N0 BLAU1) NAMUR NC 3.5 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 112 °C X
II 3G EEx nL IIC T6 X
SC3,5-N0 GELB1) NAMUR NC 3.5 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SC3,5-N0 GRUEN1) NAMUR NC 3.5 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SC3,5-N0 WEISS1) NAMUR NC 3.5 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SC3,5-G-N0 NAMUR NC 3.5 mm 135 mm, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 112 °C X
II 3G EEx nL IIC T6 X
SJ3,5-SN 2) NAMUR NC 3.5 mm 0.5 m, LIY leads II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 112 °C X
II 3G EEx nL IIC T6 X
SJ3,5-S1N NAMUR NO 3.5 mm 0.5 m, LIY leads II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 112 °C X
II 3G EEx nL IIC T6 X
1) See data sheet for hysteresis designation 2) Also available with integrated fixing nut M2 (as SC3,5-G-NO)
8
BOX SOLUTION WITH CYLINDRICAL AND RECTANGULAR SENSORS (for more sensors see pages 16 – 21)
Model number Switch element Switching Installation Connection Ex-designation EC prototype SIL
function distance test certificate
Cylindrical
NCB2-12GM35-N0 NAMUR NC 2 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 109 °C X
II 3G EEx nA IIC T6 X
NCB2-12GM35-N0-V1 NAMUR NC 2 mm Flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN4-12GM35-N0 NAMUR NC 4 mm Not flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 109 °C X
NCN4-12GM35-N0-V1 NAMUR NC 4 mm Not flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB2-12GK35-N0 NAMUR NC 2 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN4-12GK35-N0 NAMUR NC 4 mm Not flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ2-11-SN NAMUR NC 2 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ2-11-SN-G NAMUR NC 2 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ2-12GK-SN NAMUR NC 2 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ4-12GK-SN NAMUR NC 4 mm Not flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 111 °C X
II 3G EEx nA IIC T6 X
NCB5-22GK35-Z4 DC NO 5 mm Flush 2 m, PUR cable II 2G EEx m II T4 BVS 03 ATEX E 346
NJ2-12GM40-E2-3G-3D PNP NO 2 mm Flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 104 °C X
NJ4-12GM40-E2-3G-3D PNP NO 4 mm Not flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
NJ4-12GM40-E2-V1-3G-3D PNP NO 4 mm Not flush V1, quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
NBB4-12GM50-E2-3D PNP NO 4 mm Flush 2 m, PVC cable II 3D IP67 T 94 °C X
Rectangular
NJ2-V3-N NAMUR NC 2 mm Flush 100 mm, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ2-V3-N-V5 NAMUR NC 2 mm Flush Quick disconnect 4.8 mm II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB2-V3-N0 NAMUR NC 2 mm Flush 100 mm, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB2-V3-N0-V5 NAMUR NC 2 mm Flush Quick disconnect 4.8 mm II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN4-V3-N0 NAMUR NC 4 mm Not flush 110 mm, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN4-V3-N0-V5 NAMUR NC 4 mm Not flush Quick disconnect 4.8 mm II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NBB3-V3-Z4-3D DC NO 3 mm Flush 100 mm, PVC cable II 3D IP67 T 102 °C X
NBB2-V3-E2-3G-3D PNP NO 2 mm Flush 100 mm, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 99 °C X
NBN4-V3-E2-3G-3D PNP NO 4 mm Not flush 100 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 99 °C X
* See data sheet for hysteresis designation · Other types with II 3G nL resp. nA designation available on request.
9
DUAL SENSORS FOR BOX INSTALLATION
The F25 sensor series from Pepperl+Fuchs offers an effective alternative for applications involving feedback
signaling on valve positioners.
These sensors are suitable for both the box solution and direct fitting to the actuator.
aling
k sign ners
ed bac ositio
Fe lve p
a
on v
■ Dual sensor –
The sensor has 2 active zones
■ Safe –
Fingers cannot fit between the actuating element and sensor, thus complying with accident prevention regulations
■ Variable –
Installs directly on the actuator or fitting, using a bracket or in the box
■ Simple –
No adjustment or additional setting is required during installation
■ Individual –
Several sensors can be stacked if more than 2 switching points are required
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NCN3-F25-N4-0,14 NAMUR Dual NC 3 mm Flush installation 180 mm, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
NCN3-F25-SN4-0,14 DC Dual NC 3 mm Flush installation 180 mm, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 3
NCN3-F25F-N4-V1 NAMUR Dual NC 3 mm Flush installation V1 quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
II 3G EEx nL IIC T6 X
II 3D IP67 T 111 °C X
NBN3-F25F-E8-V1-3D PNP Dual NO 3 mm Flush installation V1 quick disconnect II 3D IP67 T 124 °C X
NBN3-F25-E8-0,14-3D PNP Dual NO 3 mm Flush installation 180 mm, PVC cable II 3D IP67 T 122 °C X
10
PCB SOLUTION FOR BOX INSTALLATION
The box in this version serves as a terminal compartment for both sensor and valve connection. Coded cage clamp plug-in
terminals are provided for this purpose. LEDs on the dual sensors enable you to check the switching status. The LED on the
PCB enables checking of the valve status.
Versions with screen connections (NAMUR only) and 2 valve actuators are also available.
a ling
ck sign oners
ed ba ositi
Fe lve p
a
on v
■ Plug & Play –
Coded plug-in terminal strip for easy, error-proof installation
■ Inexpensive –
The connection option for the actuator control valve eliminates the need for an additional terminal box or plug
■ Simple –
Error detection is facilitated by the LED status display
■ Safe connection –
The coded terminal strips help to eliminate incorrect connection
■ Operationally safe –
Completely ex-works tested with no additional adjustment requirements
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range (system/valve) test certificate
PL2-F25-N4-K NAMUR Dual NC 3 mm Flush installation Cage clamp terminals II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
II 3G EEx nL IIC T6 X
PL3-F25-N4-K NAMUR Dual NC 3 mm Flush installation Cage clamp terminals II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
II 3G EEx nL IIC T6 X
PL4-F25-N4-K NAMUR Dual NC 3 mm Flush installation Cage clamp terminals II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
II 3G EEx nL IIC T6 X
PL2-F25-SN4-K DC Dual NC 3 mm Flush installation Connector strip II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 3
II 3G EEx nL IIC T6 X
PL3-F25-SN4-K DC Dual NC 3 mm Flush installation Cage clamp terminals II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 3
II 3G EEx nL IIC T6 X
11
DUAL SENSORS FOR OPEN CONSTRUCTION
Are you looking for an open feedback signaling solution with ■ Safe –
sensors and actuating elements that are robust, sturdy, and The sensors have been tested by the TÜV (Technical Inspection
easy to install? Association) in accordance with the EC Machine Directive
The F31 and F31K series from Pepperl+Fuchs are ideally suited RL 89/392/EEC and pose no risk to the user
to install directly on positioners. Position feedback, regardless ■ Variable –
of size or make, can be implemented with just two actuating The sensors are suitable for all standard actuators,
elements. regardless of size and make
■ Secure fitting –
The F31K series for system and valve connection offers a Round mounting holes in the sensor housing enable reliable
terminal compartment with cage clamp terminal technology. mounting position
Versions are available, without a valve connection, with one ■ Universal –
valve connection, or with two connections. Feedback is independent of clockwise and counterclockwise-
rotating actuators
■ Precise positioning –
Precise hole mounting pattern enables a fixed, reliable mounting
position
■ Versatile –
You can choose between a cable or quick disconnect
(V1, V16 or V18)
■ Transparent –
LEDs clearly display the switching status, electrical power supply
and valve actuation
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NCN3-F25-N4-0,14 NAMUR Dual NC 3 mm Flush installation 180 mm PVC II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
NCN3-F25-N4-V1 NAMUR Dual NC 3 mm Flush installation V1 quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
NCN3-F25-N4-5M NAMUR Dual NC 3 mm Flush installation 5 m, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
II 3G EEx nL IIC T6 X
NCN3-F25-SN4 5M DC Dual NC 3 mm Flush installation 5 m, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 3
II 3G EEx nL IIC T6 X
NCN3-F25-SN4-V1 DC Dual NC 3 mm Flush installation V1 quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 3
II 3G EEx nL IIC T6 X
NBN3-F25-E8-3D-5M PNP Dual NO 3 mm Flush installation 5 m, PVC cable II 3D IP67 T 122 °C X
NBN3-F25-E8-V1-3D PNP Dual NO 3 mm Flush installation V1 quick disconnect II 3D IP67 T 122 °C X
naling
ck sig oners
ed ba ositi
Fe vep
al
on v
F31 AND F31K OPEN SOLUTION WITH VALVE ACTUATION
Model number Switch element Sensing Installation Connection Connection Ex-designation EC prototype SIL
function range (system) (valve) test certificate
NCN3-F31-N4-K NAMUR Dual NC 3 mm Flush install. 5 m, PVC cable II 1G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
II 3D IP67 T 109 °C X
II 3G EEx nL IIC T6 X
NCN3-F31-N4-K-K NAMUR Dual NC 3 mm Flush install. 5 m, PVC cable 0.5 m, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
II 3D IP67 T 109 °C X
II 3G EEx nL IIC T6 X
NCN3-F31-N4-V16-K NAMUR Dual NC 3 mm Flush install. V16 quick disconnect 0.5 m, PVC cable II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
II 3G EEx nL IIC T6 X
NCN3-F31-N4-V16-V16 NAMUR Dual NC 3 mm Flush install. V16 quick disconnect V16 Device II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
quick disconnect II 3G EEx nL IIC T6 X
NCN3-F31-N4-V18 NAMUR Dual NC 3 mm Flush install. V18 quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
II 3G EEx nL IIC T6 X
NCN3-F31K-N4 NAMUR Dual NC 3 mm Flush install. Cage clamp II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
terminals II 3D IP68 T 109 °C X
II 3G EEx nL IIC T6 X
NCN3-F31K-N4-K NAMUR Dual NC 3 mm Flush install. Cage clamp Cage clamp II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
terminals terminals II 3D IP68 T 109 °C X
II 3G EEx nL IIC T6 X
NCN3-F31K-N4-V1-V1 NAMUR Dual NC 3 mm Flush install. Cage clamp V1 Device II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
terminals quick disconnect II 3D IP67 T 109 °C X
II 3G EEx nL IIC T6 X
NCN3-F31-N5-V18-V1 NAMUR Dual NC 3 mm Flush install. V18 quick disconnect V1 Dev. quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X
NCN3-F31-N4-V1 NAMUR Dual NC 3 mm Flush install. V1 quick disconnect II 2G EEx ia IIC T6 TÜV 99 ATEX 1479 X 2
II 3D IP67 T109 °C X
II 3G EEx nL IIC T6 X
NBN3-F31-E8-K-3G-3D PNP Dual NO 3 mm Flush install. 5 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 97 °C X
NBN3-F31K-E8-3G-3D PNP Dual NO 3 mm Flush install. Cage clamp II 3G EEx nA IIC T6 X
terminals II 3D IP65 T 98 °C X
NBN3-F31-E8-K-K-3G-3D PNP Dual NO 3 mm Flush install. 5 m, PVC cable 0.5 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
NBN3-F31-E8-V1-3G-3D PNP Dual NO 3 mm Flush install. V1 Dev. quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 97 °C X
NBN3-F31-E8-V18-3G PNP Dual NO 3 mm Flush install. V18 Dev. quick disconnect II 3G EEx nA IIC T6 X
NBN3-F31K-E8-K-3D PNP Dual NO 3 mm Flush install. Cage clamp Cage clamp II 3D IP67 T 97 °C X
terminals terminals
NBN3-F31K-E8-V1-V1-3D PNP Dual NO 3 mm Flush install. Cage clamp terminals V1 Dev. quick disconnect II 3D IP67 T 97 °C X
NBN3-F31K-Z8-3G-3D DC Dual NO 3 mm Flush install. Device clamp II 3G EEx nA IIC T6 X
terminals II 3D IP65 T 93 °C X
NBN3-F31K-Z8-K-3D DC Dual NO 3 mm Flush install. Cage clamp terminals Cage clamp terminals II 3D IP68 T 93 °C X
NBN3-F31-Z8-K-3G-3D PNP Dual NO 3 mm Flush install. 5 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 94 °C X
NBN3-F31K-Z8-V1-V1-3D DC Dual NO 3 mm Flush install. Cage clamp terminals V1 Dev. quick disconnect II 3D IP68 T 92 °C X
NBN3-F31-Z8-V1-3G-3D Dual NO 3 mm Flush install. V1 Dev. quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 93 °C X
■ Versatile –
10 and 15 mm diameters
■ Reliable –
Reliable NAMUR electronics
■ Simple –
Bi-stable versions can also be operated with standard NAMUR
amplifiers and do not require a separate control unit
le area g
ariab surin
V mea
flow
RING-TYPE SENSOR (For more sensors in the ring-type design see page 21)
14
SLOT-TYPE SENSORS
SC2-N0-GELB* NAMUR NC 2 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 113 °C X
II 3G EEx nA IIC T6 X
SC2-N0-GRUEN* NAMUR NC 2 mm 0.5 m, PVC leads II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 113 °C X
II 3G EEx nA IIC T6 X
SJ2-SN NAMUR NC 2 mm 0.5 m, leads LIFYW II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128
II 3D IP67 T 112 °C X
II 3G EEx nA IIC T6 X
SJ2-S1N NAMUR NO 2 mm 0.5 m, leads LIFYW II 1G EEx ia IIC T6 PTB 00 ATEX 2049 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128
II 3G EEx nA IIC T6 X
II 3G EEx nL IIC T6 X
II 3D IP67 T 112 °C X
SB2-Z0-3D GELB DC NO 2 mm 0.5 m, leads LIFYW II 3D IP67 T 108 °C X
SB2-Z0-3D GRUEN DC NO 2 mm 0.5 m, leads LIFYW II 3D IP67 T 108 °C X
SB3,5-E2-3D PNP NO 3.5 mm 0.5 m, leads LIY II 3D IP67 T 100 °C X
SB3,5-G-E2-3D PNP NO 3.5 mm 135 mm, PVC leads II 3D IP67 T 100 °C X
r s for The SJ... and SC... series are slot-type, limit value
t value ators
u
Limi ion act
t
posi
■ Versatile –
A variety of sizes are possible, thanks to the
compact dimensions
■ Safe –
Functional safety criteria based on IEC61508 or
VDE 660/209 are met
■ Easy installation –
The SC series LED enables visual indication to
verify functionality
15
STANDARD DESIGNS INDUCTIVE
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NJ0.8-4,5-N NAMUR NC 0.8 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ0,8-5GM-N NAMUR NC 0.8 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ1,5-6,5-N NAMUR NC 1.5 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB1,5-6,5M25-N0 NAMUR NC 1.5 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
NCB1,5-6,5M25-N0-V1 NAMUR NC 1.5 mm Flush V1 quick disconnect II 2 G EEx ia IIC T6 PTB 00 ATEX 2048 X
NCB1,5-8GM25-N0 NAMUR NC 1.5 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 111 °C X
NCB1,5-8GM25-N0-V1 NAMUR NC 1.5 mm Flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ2-11-N NAMUR NC 2 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6
II 3G EEx nA IIC T6 X
II 1D Ex iaD 20 T 108 °C
II 3D IP68 T 112 °C PTB 00 ATEX 2048 X 2
II 3G EEx nL IIC T6 X ZELM 03 ATEX 0128 X
NJ2-11-N-G NAMUR NC 2 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6
II 1D Ex iaD 20 T 108 °C PTB 00 ATEX 2048 X 2
II 3G EEx nL IIC T6 X ZELM 03 ATEX 0128 X
NJ5-11-N NAMUR NC 5 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ5-11-N-G NAMUR NC 5 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ2-12GK-N NAMUR NC 2 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ4-12GK-N NAMUR NC 4 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
Ex II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB4-12GM40-N0 NAMUR NC 4 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCB4-12GM40-N0-V1 NAMUR NC 4 mm Flush V1 quick disconnect II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCB5-18GM40-N0 NAMUR NC 5 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 109 °C X
II 3G EEx nA IIC T6 X
NCB5-18GM40-N0-V1 NAMUR NC 8 mm Not flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB8-18GM40-N0 NAMUR NC 8 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCB8-18GM40-N0-V1 NAMUR NC 8 mm Flush V1 quick disconnect II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCN8-18GM40-N0 NAMUR NC 8 mm Not flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3G EEx nA IIC T6 X
NCN8-18GM40-N0-V1 NAMUR NC 8 mm Not flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
16
■ Versatile – ■ Inexpensive –
Diameters from 4.5 mm ... 30 mm PNP, N.O. outputs are
■ Variable – available in nickel-plated
Available in both cable brass housings
and quick disconnect
CYLINDRICAL DESIGN
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NCB5-18GK40-N0 NAMUR NC 5 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN8-18GK40-N0 NAMUR NC 8 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ5-18GK-N NAMUR NC 5 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ5-18GK-N-150 NAMUR NC 5 mm Flush 2 m, SIHF cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
NJ8-18GK-N NAMUR NC 5 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ8-18GK-N-150 NAMUR NC 8 mm Not flush 2 m, SIHF cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
NJ6-22-N NAMUR NC 6 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6
II 3G EEx nA IIC T6 X
II 3D IP68 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NJ6-22-N-G NAMUR NC 6 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 2
NJ10-22-N NAMUR NC 10 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
NJ10-22-N-G NAMUR NC 10 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ4-30GM-N-200 NAMUR NC 4 mm Flush 5 m, SIHF cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
NCB10-30GM40-N0 NAMUR NC 10 mm Flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP67 T 109 °C X
II 3G EEx nA IIC T6 X
NCB10-30GM40-N0-V1 NAMUR NC 10 mm Flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB15-30GM40-N0 NAMUR NC 15 mm Quasi flush 2 m, PVC cable II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCB15-30GM40-N0-V1 NAMUR NC 15 mm Quasi flush V1 quick disconnect II 1G EEx ia IIC T6
II 3D IP67 T 111 °C X
II 3G EEx nL IIC T6 X PTB 00 ATEX 2048 X 2
NCN15-30GM40-N0 NAMUR NC 15 mm Not flush 2 m, PVC cable II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN15-30GM40-N0-V1 NAMUR NC 15 mm Not flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB10-30GK40-N0 NAMUR NC 10 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN15-30GK40-N0 NAMUR NC 15 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ10-30GK-N NAMUR NC 10 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ15-30GK-N NAMUR NC 15 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ10-30GKK-N NAMUR NC 10 mm Flush Terminal compartment II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ15-30GKK-N NAMUR NC 15 mm Not flush Terminal compartment II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X 2
NJ20-40-N NAMUR NC 20 mm Not flush Terminal compartment II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
NJ25-50-N NAMUR NC 25 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2048 X
NJ3-18GK-S1N NAMUR NO 3 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
in St37 II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3G EEx nL IIC T6 X
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NJ5-18GK-SN NAMUR NC 5 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3G EEx nL IIC T6 X
II 3D IP68 T 111 °C X
NJ8-18GK-SN NAMUR NC 8 mm Not flush 2 m, Silicon cable II 2G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 3G EEx nL IIC T6 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 111 °C X
II 3G EEx nA IIC T6 X
NJ6-22-SN NAMUR NC 6 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ6-22-SN-G NAMUR NC 6 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ5-30GK-S1N NAMUR NO 5 mm Flush in St37 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ10-30GK-SN NAMUR NC 10 mm Flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ15-30GK-SN NAMUR NC 15 mm Not flush 2 m, Silicon cable II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 3G EEx nL IIC T6X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 111 °C X
II 3G EEx nA IIC T6 X
NBB2-12GM40-Z0-3D DC NO 2 mm Flush 2 m, PVC cable II 3D IP67 T 95 °C X
NCB2-12GM40-Z0-3D DC NO 2 mm Flush 2 m, PUR cable II 3D IP67 T 96 °C X
NCB2-12GM40-Z0-V1-3G-3D PNP NO 2 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 92 °C X
NCN4-12GM40-Z0-3G-3D DC NO 4 mm Not flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
NBB5-18GM40-Z0-3G-3D DC NO 5 mm Flush 2 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 90 °C X
NCB5-18GM40-Z0-3G-3D DC NO 5 mm Flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 90 °C X
NCB5-18GM40-Z0-3G-3D 10M DC NO 5 mm Flush 10 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 90 °C X
NCB5-18GM40-Z0-V1-3G-3D DC NO 5 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 89 °C X
NCN8-18GM40-Z0-3G-3D DC NO 8 mm Not flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 89 °C X
NBB10-30GM40-Z0-3G-3D DC NO 10 mm Flush 2 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 86 °C X
NCB10-30GM40-Z0-3G-3D DC NO 10 mm Flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 89 °C X
NCB10-30GM40-Z0-V1-3G-3D DC NO 10 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 85 °C X
NCN15-30GM40-Z0-3G-3D DC NO 15 mm Not flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 87 °C X
NBB0,8-4M25-E2-3G-3D PNP NO 0.8 mm Flush 2 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 112 °C X
NBB0,8-5GM25-E2-3G-3D PNP NO 1.5 mm Flush 2 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 109 °C X
NBB2-8GM50-E2-3G-3D PNP NO 2 mm Flush 2 m, PVC cable II 3G EEx nA IIC T6 X
II 3D IP67 T 97 °C X
NBB2-8GM40-E2-V1-3G-3D PNP NO 2 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 90 °C X
NJ2-8GM40-E2-3G-3D PNP NO 2 mm Not flush 2 m, PUR cable II 3G EEx nA IIC T6 X
II 3D IP67 T 104 °C X
18
STANDARD DESIGNS INDUCTIVE
CYLINDRICAL DESIGN
Model number Switch element Switching Installation Connection Ex-designation EC prototype SIL
function distance test certificate
NJ1,5-8GM40-E2-V1-3G-3D PNP NO 1.5 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 99 °C X
NJ2-12GM40-E2-V1-3G-3D PNP NO 2 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 105 °C X
NJ4-12GM40-E2-V1-3G-3D PNP NO 4 mm Not flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
19
STANDARD DESIGNS INDUCTIVE
■ Versatile –
Terminal compartment versions enable a variety of cable connections
■ Variable –
5-way, quick-pivot head allows sensing head rotation
As with the cylindrical sensors, a range of rectangular housing styles are available, with cable or terminal
compartment connections and detection ranges extending to 50 mm.
NJ0.8-F-N NAMUR NC 0.8 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
NJ4-F-N NAMUR NC 4 mm Not flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
NJ6-F-N NAMUR NC 6 mm Flush 2 m, PUR cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
NJ10-F-N NAMUR NC 10 mm Not flush 2 m, PUR cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
NJ2-F1-N NAMUR NC 2 mm Flush 2 m, PVC cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
FJ6-110-N NAMUR NC 6 mm Flush 2 m, PUR cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
FJ7-N NAMUR NC 7 mm Flush 2 m, PUR cable II 2G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 3D IP67 T 109 °C X
NCN15-M1K-N0 NAMUR NC 15 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB15+U1+N0 NAMUR NC 15 mm Flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 112 °C X
NCN20+U1+N0 NAMUR NC 20 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 112 °C X
NCN30+U1+N0 NAMUR NC 30 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 112 °C X
NCN40+U1+N0 NAMUR NC 40 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
II 3D IP68 T 112 °C X
NJ6S1+U1+N1 NAMUR NO 6 mm Flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ15S+U1+N NAMUR NC 15 mm Flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ20S+U1+N NAMUR NC 20 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ 15+U1+E2-3G-3D PNP NO 15 mm Flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 108 °C X
NJ 20+U1+E2-3G-3D PNP NO 20 mm Flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 102 °C X
NJ 30+U1+E2-3G-3D PNP NO 30 mm Not flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 102 °C X
NJ 40+U1+E2-3G-3D PNP NO 40 mm Not flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 105 °C X
NBB20-L2-A2-V1-3G-3D PNP antivalent 20 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP69K T 107 °C X
NBN40-L2-A2-V1-3G-3D PNP antivalent 40 mm Not flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP69K T 107 °C X
NCB20-L2-N0-V1 NAMUR NC 20 mm Flush V1 quick disconnect II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 3D IP69K T 112 °C X
II 3G EEx nL IIC T6 X
NCN40-L2-N0-V1 NAMUR NC 40 mm Not flush V1 quick disconnect I 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 3D IP69K T 112 °C X
II 3G EEx nL IIC T6 X
20
RECTANGULAR DESIGN (For more rectangular sensors see page 9)
Model number Switch element Sensing Installation Connection Ex-designation EC prototype SIL
function range test certificate
NCB40-FP-N0-P1 NAMUR NC 40 mm Flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCN50-FP-N0-P1 NAMUR NC 50 mm Not flush Terminal compartment II 1G EEx ia IIC T6 PTB 00 ATEX 2032 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NJ40-FP-SN-P1 NAMUR NC 40 mm Not flush Terminal compartment II 2G EEx ia IIC T6 PTB 00 ATEX 2049 X 3
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
NCB40-FP-A2-P1-3G-3D PNP antivalent 40 mm Flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
NCB50-FP-A2-P1-3G-3D PNP antivalent 50 mm Flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 95 °C X
NCB50-FP-E2-P1-V1-3G-3D PNP NO 50 mm Flush V1 quick disconnect II 3G EEx nA IIC T6 X
II 3D IP67 T 95 °C X
NCN50-FP-A2-P1-3G-3D PNP antivalent 50 mm Not flush Terminal compartment II 3G EEx nA IIC T6 X
II 3D IP67 T 96 °C X
RING-TYPE DESIGN (For more sensors in ring-type design see page 14)
Model number Switch element Inside diameter Connection Ex-designation EC prototype
function test certificate
SLOT-TYPE SENSORS (For more slot-type sensors see page 8 and page 15)
Model number Switch element Slot width Connection Ex-designation EC prototype SIL
function test certificate
SJ5-N NAMUR NC 5 mm 0.5 m, leads LIY II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SJ5-G-N NAMUR NC 5 mm 0.5 m, leads LIY II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SJ5-K-N NAMUR NC 5 mm 2 m, PVC cable II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SJ10-N NAMUR NC 10 mm 2 m, PVC cable II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X 2
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SJ15-N NAMUR NC 15 mm 2 m, PVC cable II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
SJ30-N NAMUR NC 30 mm 2 m, PVC cable II 1G EEx ia IIC T6 PTB 99 ATEX 2219 X
II 1D Ex iaD 20 T 108 °C ZELM 03 ATEX 0128 X
Capacitive sensors can be used to detect non-metallic objects. They are useful
for level measurement of liquid or granular substances, and the detection of
the position of plastic or wooden containers.
Various cylindrical and rectangular sensors are
also available, with cable or quick disconnects.
22
MAGNETIC SENSORS, CYLINDRICAL
MC60-12GM50-1N NAMUR NO 60 mm Flush, 2 m, PVC cable II 2G EEx ia IIC T6 TÜV 01 ATEX 1718
in non-magnetic metal
MC60-12GM50-1N-V1 NAMUR NO 60 mm Flush, V1 quick disconnect II 2G EEx ia IIC T6 TÜV 01 ATEX 1718
in non-magnetic metal
MJ35-F12-1N NAMUR NO 35 mm Flush 2 m, PVC cable II 2G EEx ib IIC T6 TÜV 01 ATEX 1718
23
PHOTOELECTRIC SENSORS FOR HAZARDOUS AREAS (ZONE 1)
at ion
design 6
h E x- a IIC T
t
Wi EEx i
G
II 2
M11/MV11-Ex/40b/112 Thru-beam 0 m ... 10 m Red, modulated light M12 quick disconnect, II 2G EEx ia IIC T6 PTB 99 ATEX 2036 X
4-pole, 90° rotation
MLV11-54-Ex/40b/112 Polarized 0 m ... 3 m Red, modulated light M12 quick disconnect, II 2G EEx ia IIC T6 PTB 99 ATEX 2036 X
retro-reflective 4-pole, 90° rotation
MLV11-8-500-Ex/40b/112 Diffused 0 mm ... 500 mm Infrared, M12 quick disconnect, II 2G EEx ia IIC T6 PTB 99 ATEX 2036 X
modulated light 4-pole, 90° rotation
24
Model number Function Detection/ Light type Connection Ex-designation EC prototype
sensing range test certificate
L36/LV36-Ex/40b/116 Thru-beam 0 m ... 30 m Red, modulated light Terminal compartment II 2G EEx ia IIC T6 PTB 01 ATEX 2184 X
RL36-55-Ex/40b/116 Polarized 0 m ... 8 m Infrared, Terminal compartment II 2G EEx ia IIC T6 PTB 01 ATEX 2184 X
retro-reflective modulated light
RL36-8-2000-Ex/40b/116 Diffused 0 m ... 2 m Infrared, modulated light Terminal compartment II 2G EEx ia IIC T6 PTB 01 ATEX 2184 X
roval 0
X app zone 2
ATE 1 and
zone
OCS2000-M1K-N2 Polarized 0 m ... 2 m Red, modulated light Terminal II 2G EEx ia IIC T6 PTB 01 ATEX 2203 X
retro-reflective compartment II 1D Ex iaD 20T 85 °C ZELM 03 ATEX 0196 X
OCT300-M1K-N2* Diffused 0 mm ... 300 mm Infrared, modulated light Terminal II 2G EEx ia IIC T6 PTB 01 ATEX 2203 X
compartment II 1D Ex iaD 20T 85 °C ZELM 03 ATEX 0196 X
* Glass fiber optics can be connected
25
PHOTOELECTRIC SENSORS FOR HAZARDOUS AREAS (ZONE 2 AND 22)
Model number Description Scanning Signal output Light type Ex-designation EC prototype
distance test certificate
VCS110/133 Color sensor Max. 100 mm 5 PNP, short-circuit-proof White light II 2/3G EEx nA II T4 TÜV 01 ATEX 1969 X
with color memory
26
Series 32 has already established itself as an all-purpose sensor in material handling. The
harmony of a compact, slender design and the excellent visibility of the LEDs and 4-pole
M12 connector quick disconnect make installation a snap. The scratch-resistant and solvent-
resistant lens cover means that these devices are now also certified for use in hazardous
areas with a dusty environment.
■ EC prototype certificate:
TÜV 01 ATEX 1765 X
■ Signal output: 2 PNP, complementary, reverse polarity
protection and short-circuit-proof
ation
■ Light on/dark on modes
d esign
■ Operating voltage: 10 V DC ... 30 V DC
h E x-
■ Operating temperature: -20 °C ... +50 °C
wit nd
■ Connection:
ies 4 a
er IT
32 s Ex nA I
Plastic quick disconnect M12,
4-pin
I 3 G E T 75 °C
I
D IP65
II 3
Model number Function Detection/ Light type Light spot diameter Special characteristics
sensing range
L32/LV32-Ex2/47/73c Thru-beam 0 m ... 20 m Red, modulated light Approx. 500 mm at 10 m Test input
L32/LV32-Ex2/35/47/73c Thru-beam 0 m ... 45 m Red, modulated light Test input
RL32-54-Ex2/47/73c Retro-reflective 0 m ... 7 m Red, modulated light Approx. 100 mm at 4 m Polarization filter
for reflection protection
RL32-55-Ex2/47/73c Retro-reflective 0 m ... 15 m Red, modulated light Approx. 250 mm at 10 m Polarization filter
for reflection protection
RL32-8-H-800-Ex2/47/73c Diffused mode with 30 mm ... 800 mm, Infrared, modulated light Approx. 25 mm at 800 mm Sensing range adjustment
background suppression adjustable
RL32-8-H-2482-400-Ex2/47/73c Diffused mode with 30 mm ... 400 mm, Infrared, modulated light Approx. 12 mm at 400 mm Sensing range adjustment
background suppression adjustable
27
SAFETY LIGHT CURTAINS FOR ZONE 2 AND 22 HAZARDOUS AREAS
Safety light curtains in the SLC series secure intervention points or access points in danger
zones. These devices can now be used in zone 2 and 22 hazardous areas. All SLC series light
curtains comply with Directive 94/9/EC (ATEX).
28
■ Conformity: PRDE-2684
■ Self-monitoring
(type 4 conforming with IEC/EN 61496-1)
■ Start/Restart inhibitor
■ Integrated function display
■ Operating voltage: 24 V DC
■ Electrically isolated semiconductor OSSD
(Output Signal Switching Devices) safety
outputs
■ Connection: M20 cable gland, terminal
compartment with screw terminals
■ Comprehensive accessories
a tion
d e sign nd
E x- T 4 a
With x nA II
G EE 0 °C
II 3 T 9
P 6 6
I 3 DI
I
* Other protective field heights available: 150 mm, 300 mm, 450 mm, 600 mm, 750 mm, 1050 mm, 1200 mm, 1350 mm, 1500 mm, 1650 mm, 1800 mm 29
ROTARY ENCODERS FOR HAZARDOUS AREAS – PRESSURE-RESISTANT OR INTRINSICALLY SAFE
Pepperl+Fuchs provides rotary encoders with two different types of protection. A difference is made between flame-proof
(EEx d), intrinsic safety (EEx i) and use in zone 2/zone 22.
so lute
Ab ders
enco PVS14/
PSS58X
PSM58X
AVS14 AVM14 BVE14 BVM14 PVM14 PVS/PVM58X
Ex-designation II 2G EEx d II C T6 II 2G EEx d II C T6 II 2G EEx d II C T6 II 2G EEx d II C T6 II 2G EEx d II C T6 II 3G EEx nA II T4
II 2D IP66 T 80 °C II 3D IP64 T 120 °C
EC prototype test certificate ZELM 02 ATEX 0078 ZELM 02 ATEX 0078 ZELM 02 ATEX 0078 ZELM 02 ATEX 0078 ZELM 02 ATEX 0078 X ZELM 06 ATEX 3290 X
Singleturn resolution 4,096 4,096 8,192 8,192 8,192 65,536
Multiturn resolution 1 4,096 1 4,096 4,096 16,384
Design [mm] ø116 ø116 ø116 ø116 ø116 ø58
Flange type Clamping flange Clamping flange Clamping flange Clamping flange Clamping flange Clamping or servo flange
Pilot [mm] ø40 ø40 ø40 ø40 ø40 ø36
Solid shaft [mm] ø12 x 25 ø12 x 25 ø12 x 25 ø12 x 25 ø12 x 25 ø10, ø6
Hollow shaft [mm] – – – – – ø10, 12, 15
Recessed hollow shaft [mm] – – – – – –
Max. rotational speed [min– ] 6,000
1
6,000 6,000 6,000 6,000 6,000
Max. shaft load, axial [N] 60 60 40 40 60 40
Max. shaft load, radial [N] 80 80 60 60 80 110
Operating voltage [V] 10 … 30 10 … 30 29.5 … 31.6 29.5 … 31.6 10 … 30 10 … 30
Interfaces SSI SSI AS-Interface AS-Interface PROFIBUS PROFIBUS
Output type RS 422 RS 422 – – – –
30
en tal rs
nc rem code
I y en
ta r
ro Series 14
Ex-designation II 2G EEx d IIC T6
II 2D IP66 T 80 °C
EC prototype test certificate ZELM 02 ATEX 0078 X
Number of pulses ≤ 5,000
Design [mm] ø116
Flange type Clamping flange
Pilot [mm] ø40
Solid shaft [mm] ø12 x 25
Hollow shaft [mm] –
Recessed hollow shaft [mm] –
Max. rotational speed [min– ]
1
6,000
Max. shaft load, axial [N] 60
Max. shaft load, radial [N] 80
Operating voltage [V] 5 or 10 … 30
Output type Push-pull, RS 422
Max. output frequency [kHz] 100
Signal outputs A, Ā , B, B̄, 0, 0̄
Protection class IP66
ental rs
em e
Incr y encod
r
rota RVI58X RVS58X RVI84
Ex-designation II 3G EEx nA II T4 II 3G EEx nA II T4 II 2G EEx ia II C T6
II 3D IP65 T 105 °C II 3D IP65 T 105 °C
EC prototype test certificate ZELM 96 ATEX 3297 X ZELM 96 ATEX 3297 X 94/9/EG
Number of pulses ≤ 5,000 ≤ 5,000 ≤ 25
Design [mm] ø58 ø58 ø78
Flange type Clamping or servo flange Hollow shaft flange Servo flange
Pilot [mm] ø36 – ø56
Solid shaft [mm] ø10 or ø6 – ø10 x 23
Hollow shaft [mm] – – –
Recessed hollow shaft [mm] – ø12 or ø10 –
Max. rotational speed [min ]
–1
6,000 6,000 3,000
Max. shaft load, axial [N] 40 – 50
Max. shaft load, radial [N] 60 – 100
Operating voltage [V] 5 or 10 … 30 5 or 10 … 30 8
Output type Push-pull, RS 422 Push-pull, RS 422 NAMUR
Max. output frequency [kHz] 200 200 5
Signal outputs A, Ā , B, B̄, 0, 0̄ A, Ā , B, B̄, 0, 0̄ A, B
Protection class IP65 IP54 IP65
31
AS-INTERFACE MODULES FOR HAZARDOUS AREAS
AS-Interface modules are ATEX certified and can be used in zone 1 hazardous areas. A module with 4 inputs for NAMUR sensors
and 2 outputs, and a module with 4 outputs are available. The modules conform with EX II (1)2G EEX me [ia] IIB/IIC T4
explosion protection and are equipped with lead breakage and short-circuit monitoring. Diagnostic LEDs provide information
about bus communication and I/O status.
VAA-4E2A-G5-N/V2-Ex G5 187 x 150 x 46 4 sensors complying with 4 outputs for II (1)2 G EEx me [ia] IIB/IIC T4 DMT 02 ATEX E 125
IEC 60947-5-6 actuation of
(NAMUR) or intrinsically safe
mechanical contacts valves
VAA-4A-G5-V2-Ex G5 187 x 150 x 46 – 4 outputs for II (1)2 G EEx me [ia] IIB/IIC T4 DMT 99 ATEX E 072
actuation of
intrinsically safe
valves
zone 2
es for
l
m odu areas
I/O rdous
haza
The G2 flat module is ATEX certified and can be used in zone 2 hazardous areas.
It can be easily mounted with only one screw and has an IP67 protection rating.
32
RFID: CODE AND DATA CARRIERS FOR HAZARDOUS AREAS
The code and data carriers are ATEX certified and can be used in zone 1 hazardous areas.
They provide IP67 protection and a 28 bit fix code or 1 kBit memory. The …-30GK-… design
can be screwed into a M30x15 thread, while the …-30F-… can be fitted with 2 mounting
screws. The read/write heads must be installed outside the hazardous area, or a suitable
protective housing must be used.
Solutions for applications up to zone 1 can be achieved with an ATEX-approved pressure-
resistant housing where read/write points are also required in hazardous areas.
fa ce s area
r
nte ule dou
S-I zar
A
mod the ha
I/O in
33
THE K-SYSTEM – DIN RAIL MOUNTED INTERFACE MODULES
xible –
m is fle it
- Syste u need
K
The e way yo
th
just
■ C-Series: 12.5 mm wide for maximum single
channel signal integrity
■ F-Series: 20 mm wide for maximum installation density
■ F-Series: 40 mm wide for special applications
■ High-quality galvanic isolation
■ Power Rail power supply
■ Redundant power supply
■ Error detection
■ Collective error messaging
■ Plug-in surge protection
■ Also available for non-intrinsically safe circuits
34
d
fiel
he
to t
C
D
V
24
er
Pow
24 V DC
pp ly redundant
u
itter s fiers lt
Fau ing
r an sm ampli n
war nal
sig ized n
T tral
o la faul
Is m on odu
ed m s
Spe control former trol
sys
tem
e s rs
Valv ing tran nsduce
con
he
to t
at a
Isol uring tr
s rs
Mea mplifie ■ Group power supply and centralized fault alarm:
a Power Rail – Supply power and collective error messaging without additional
Trip wiring via Power Rail
Model number Function Channels Input Output Supply Explosion protection Safety
voltage
KFD2-SR2-Ex2.W Isolating amplifier 2 EN 60947-5-6 Relay contact 24 V DC II (1) G D [EEx ia] II C SIL 2 (IEC 61508)
(DIN 19234, NAMUR) PTB 00 ATEX 2080
KFA6-SR2-Ex2.W Isolating amplifier 2 EN 60947-5-6 Relay contact 230 V AC II (1) G D [EEx ia] II C SIL 2 (IEC 61508)
(DIN 19234, NAMUR) PTB 00 ATEX 2081
KFD2-SRA-Ex4 Isolating amplifier 4 EN 60947-5-6 Relay contact 24 V DC II (1) G [EEx ia] II C
(DIN 19234, NAMUR) ZELM 99 ATEX 0009
KFD2-ST2-Ex2 Isolating amplifier 2 EN 60947-5-6 Electronic 24 V DC II (1) G D [EEx ia] II C SIL 2 (IEC 61508)
(DIN 19234, NAMUR) output II 3 G EEx n A II T4
For use in zone 2
PTB 00 ATEX 2035
KFD2-SOT2-Ex2 Isolating amplifier 2 EN 60947-5-6 Opto coupler 24 V DC II (1) G D [EEx ia] II C SIL 2 (IEC 61508)
(DIN 19234, NAMUR) II 3 G EEx n A II T4
For use in zone 2
PTB 00 ATEX 2035
KFA6-SOT2-Ex2 Isolating amplifier 2 EN 60947-5-6 Opto coupler 230 V AC II (1) G D [EEx ia] II C SIL 2 (IEC 61508)
(DIN 19234, NAMUR) PTB 98 ATEX 2164
KFD2-SH-Ex1 Fail-safe 1 For fail-safe Relay contact 24 V DC II (1) G D [EEx ia] II C DIN V 19250,
isolating amplifier proximity switches SN,S1N PTB 00 ATEX 2042 VDE 0660 Part 209
SIL 3
KHA6-SH-Ex1 Fail-safe 1 For fail-safe Relay contact 230 V AC II (1) G D [EEx ia] II C DIN V 19250,
isolating amplifier proximity switches SN,S1N PTB 00 ATEX 2042 SIL 3
KFD2-DWB-Ex1.D Pulse evaluation unit, 1 EN 60947-5-6 Relay contact 24 V DC II (1) G D [EEx ia] II C SIL 2
speed monitor, (DIN 19234, NAMUR) TÜV 99 ATEX 1408
with display
KFA6-DWB-Ex1.D Pulse evaluation unit, 1 EN 60947-5-6 Relay contact 230 V AC II (1) G D [EEx ia] II C SIL 2
speed monitor, (DIN 19234, NAMUR) TÜV 99 ATEX 1408
with display
KFU8-UFT-Ex2.D Slip and rotation 2 EN 60947-5-6 4 ... 20 mA, 20 ... 90 V DC, II (1) G D [EEx ia] II C
direction monitor (DIN 19234, NAMUR) relay contact 48 ... 253 V AC TÜV 99 ATEX 1471
with display electronic
output
KFU8-UFC-Ex1.D Frequency current converter 1 EN 60947-5-6 4 ... 20 mA, 20 ... 90 V DC II (1) G D [EEx ia] II C SIL 2
with limit value and display (DIN 19234, NAMUR) relay contact, 48 ... 253 V AC TÜV 99 ATEX 1471
electronic
output
35
SCANEX – EX i BARCODE READING SYSTEMS
36
ACCESSORIES
Co accessories that will withstand your dirty, oily, and wet applications and
ensure a longer life in harsh environments.
What more do you need?
M12 CORDSETS
FOR NAMUR PROXIMITY SENSORS
These blue cordsets are suitable for NAMUR sensors
and series MLV11, 32 and VCS110 photoelectric sensors.
Model number Design Cable sheath Length No. of cores ø mm2 Pin configuration
4 3
V1-W-N-2M-PUR Angled PUR, blue 2m 2 0.34
V1-W-N-5M-PUR Angled PUR, blue 5m 2 0.34
V1-W-N-10M-PUR Angled PUR, blue 10 m 2 0.34 1 2
V1-G Socket, straight Screw terminal, PG7 screw fitting 4-pole Max. 0.75
V1-W Socket, angled Screw terminal, PG7 screw fitting 4-pole Max. 0.75
37
ACCESSORIES
RD 24 X 1/8 CORDSETS
rdsets
(BINDER SERIES 692) Co
Suitable for F31 dual proximity sensor
Model number Design Cable sheath Length No. of ø mm2 Pin configuration
cores
V16-G Socket Rd24 x 1/8, straight Screw terminal, PG7 screw fitting 6-pole + PE Max. 0.75
V16-W Socket, Angled Screw terminal, PG7 screw fitting 4-pole Max. 0.75
V16S-G Male socket Rd24 x 1/8, straight Screw terminal, PG7 screw fitting 6-pole + PE Max. 0.75
e
Refl Model number Description
C110-2 Diameter 84 mm
H50 50.9 mm x 50. 9 mm
VR10 60 mm x 19.2 mm
H60 60 mm x 40.5 mm
H85 84.5 mm x 84.5 mm
H160 60 mm x 18 mm
Reflective foil F2000 100 mm x 100 mm
38
F25 SERIES ACCESSORIES
Installation kit Shaft height Shaft diameter* Fixing hole spacing Consisting of: Fig.
Model number Actuator Bracket
* The snap ring height, and not the shaft diameter, is decisive if the ring is higher than 3 mm.
Actuator
BT32 ≤ 34 mm – Height of active surface: 28 mm 8
BT33 ≤ 34 mm – Height of active surface: 38 mm 9
BT34 ≥ 34 mm – Height of active surface: 28 mm, sits on shaft 10
BT37 ≥ 34 mm – BT37 actuator with 4 mm groove for controller fitting –
Bracket
K2 – 30 mm x 80 mm – 2
K3 – 30 mm x 130mm – 4
K4 – 30 mm x 130mm – 5
ø 28 mm
ø 32 mm
ø 34 mm
ø 40 mm
ø 34 mm
ø 40 mm
ø 34 mm
ø 40 mm
39
ACTUATORS FOR SERIES 31
BT65
■ Standard attachment size 80 mm x 30 mm
■ For shaft heights of 20 mm or 30 mm
(spacer included in the scope of delivery)
■ For shaft diameters of max. 58 mm
■ For right or left rotating actuators
■ With three trigger elements (fixed offset of 90°)
BT115A
■ Standard attachment size 130 mm x 30 mm
■ For shaft heights of 30 mm or 50 mm
(spacer included in the scope of delivery)
■ For shaft diameters of max. 90 mm BT65B
■ For right or left rotating actuators with 180° rotation
■ With four trigger elements (fixed offset of 90°)
SPECIAL CHARACTERISTICS:
■ Any positions can be monitored thanks to two levels that can
be adjusted smoothly and independently of each other
■ Two possible directions of action:
Query “end position dampened” or “end position
undampened” (metal is detected during rotation while the
sensors in the end positions to be monitored are not
actuated).
Contact
Pepperl+Fuchs GmbH
Königsberger Allee 87
68307 Mannheim · Germany
Tel. +49 621 776-4411 · Fax +49 621 776-27-4411
E-mail: [email protected]
Worldwide Headquarters
Pepperl+Fuchs GmbH · Mannheim · Germany
E-mail: [email protected]
USA Headquarters
Pepperl+Fuchs Inc. · Twinsburg · USA
E-mail: [email protected]
www.pepperl-fuchs.com
Subject to reasonable modifications due to technical advances · Copyright PEPPERL+FUCHS · Printed in Germany · Part. No. 126713 08/06 02