The document provides answers to questions about instrumentation wiring systems, impulse tubing tests, grounding systems, enclosure types for hazardous environments, transducers, meters, control systems, and other instrumentation topics. The standard for wiring is NFPA 70. Impulse tubing tests are at 1.1 times design pressure for 30 minutes. Grounding systems include AC safety ground and instrument DC shield ground. Enclosures for severe corrosion are NEMA type 4X. Transducers include piezoelectric, strain gauges, and thermocouples. Control systems topics addressed include feedback, controllers, and process variables.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
126 views

Notes

The document provides answers to questions about instrumentation wiring systems, impulse tubing tests, grounding systems, enclosure types for hazardous environments, transducers, meters, control systems, and other instrumentation topics. The standard for wiring is NFPA 70. Impulse tubing tests are at 1.1 times design pressure for 30 minutes. Grounding systems include AC safety ground and instrument DC shield ground. Enclosures for severe corrosion are NEMA type 4X. Transducers include piezoelectric, strain gauges, and thermocouples. Control systems topics addressed include feedback, controllers, and process variables.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

1.

 What is the standard used for instrumentation wiring system. 

A. NFPA (70) 

2. What is the test pressure for instrument impulse tubing leak test? 

A.1.1 X designed pressure 

3. What is the holding time for instrument impulse tubing leak test. 

A. 30 Minutes 

4. Minimum impulse line size? 

A.1/2” x O.D 0.049” 

5. Maximum allowable length of spur in fieldbus system? 

A.120 m 

6. What are the two grounding system used in instrumentation system? 

A. AC safety Ground & instrument DC shield ground 

7. What is the AC system grounding system? 

A. All exposed non‐current carrying metallic parts that could become 
energized with hazardous potentials must be reliably connected to the 
equipment grounding circuits. 

8. Which topology is not preferred in foundation fieldbus system? 

A. Daisy Chain topology 

9. What is instrumentation? 

A. It is a branch of engineering that studies measurement and control of 
process variables. 

10. What is the type of enclosure used in severe corrosive environment? 

A. NEMA type 4X 

11. Which is considered as severe corrosive environment? 

A. outdoor offshore area 

12. Piezo‐electric transducers are 

A. Inverse transducers 

13. Which of the following are peizo‐electric transducers? 

A. lead zirconate (Please check not sure) 

14. Self‐generating type transducers are? 

A. Active 
15. The full scale deflection current of an ammeter is 1MA and its internal 
resistance is 100ohm if this meter is to have full deflection at 5A, what is the 
real value of the shunt resistance to be used? 

A. 1/49.99 kohms (Please check not sure) 

16. An oscilloscope indicates? 

A. peak to peak value of voltage 

17. In a ballistic galvanometer, the deflecting torque is proportional to? 

A. the current through the coil 

18. What are the elements of measuring pressure? 

A. Bellows, Burdon tube, diaphragm, capsule, pressure springs. 

19. The resistance of LDR ‐‐‐‐‐‐‐‐when exposed to radiant energy? 

A. decreases 

20. Strain gauge, LVDT, thermocouple are example of? 

A. Analog Transducers 

21. In which hazardous area is intrinsically safe circuit to be used? 

A. zone 0 

22. What is the standard height of instrument transmitter? 

A. 1.5 

23. What is the type of cable used for field instrument to junction box 
through a conduit? 

A. Thermocouple cable 

24. What is the purpose of flexible conduit used at the field instrument? 

A. protection against thermal expansion 

25. Maximum length of process impulse tubing? 

A. 6mtr 

26. Two voltmeters have the same range 0‐400v. The internal impedance are 
30000 ohms and 20000 ohms. If they are connected in series and 600v be 
applied across them the readings are? 

A. 360V and 240V 

27. What is the standard cable size used for instrumentation cables from 
field junction box to marshalling cabinets? 

A. 18 AWG 

28. Maximum support distance of impulse tubing/process tubing? 
A. 4feet 

29. Fasteners used for cable tray assembly in severe corrosive areas shall be? 

A. 316 SS 

30. Temperature ratings required for LFMC? 

A. >80 degrees 

31. Minimum size of grounding conductor? 

A. 25mm2 

32. What is the minimum length of LFMC? 

A. 460mm 

33. What is the maximum length of LFMC? 

A. 1000mm 

34. Instrument cable tagging? 

A. both ends & each end 

35. Cable protection for grease or oil? 

A. clear heat shrinks 

36. Used type of termination in secondary cable? 

A. screw type 

37. Dial size of Pressure gauge? 

A. 100mm 

38. Standard Pneumatic signal? 

A. 3to 15 psi 

39. Instrument calibration to measure signal? 

A. 0 to 600 PSI 

40. In general the primary cable up to termination from JB to? 

A. marshalling cabinet 

41. Pick up the appropriate word for a reading obtained from the motion of 
pointer on a scale? 

A.  Analog 

42. Resolution of transducers depends on? 

A. Diameter of wire 

43. The sensitivity factor of strain gauge is normally in the order? 

A. 1.5 to 2.0 
44. for the system? 

A. The system is uncontrollable and unstable 

45. All control system that fit into the usual pattern area? 

A. closed loop 

46. In an automatic control system which of the following elements is not 
used? 

A. oscillator 

47. Regenerative feedback is also called as? 

A. positive feedback 

48. Which of the following are integrating instruments? 

A. Ampere hour meter, watt hour meter. 

49. In low power meter wattmeter, the pressure coil is connected? 

A. The load side of the current coil 

50. In a 3 phase power measurement by two wattmeter method by 
wattmeter’s had identical reading. The power of the load was? 

A. Unity 

51. A direct current can be measured by? 

A.DC potentiometer in conjunction with standard resistance 

52. In instrumentation what is the required number of grounding? 

A. 2 

53. The charges endues due to mechanical stress on the conductor is called? 

A. electro static current or static electricity 

54. Which international standard is used to manufacture instrument junction 
boxes? 

A. NEMA 250 and ICS 6 

55. All cable ties used in field shall be? 

A. nylon jacketed SS 316 

56. What is the type of junction boxes used in severe corrosive environment? 

A.  NEMA 4X 

57. The slope of all main branch headers for instrument air shall be? 

A. 1:12 

58. What kind of waveform is used for oscilloscope operation? 
A. sinusoidal 

59. The flow meter is used for no loss is called? 

A. ultrasonic flow transmitter/MAGNATIC FLOW MWTER 

60. The flexible conduits is used at the termination point of the filled 
instruments to prevent from 

A. protection against thermal expansion 

61. All fasteners (nuts, bolts, washers etc) used to connect and assemble the 
cable tray system shall be? 

A. 304 ss 

62. Multiple signals as input can be used in which system? 

A. field bus 

63. Using a voltmeter measure value is 24.3v while its true value is 24V. What 
is the relative error of measurement? 

A. 1.25 

64. What is the name equipment used to test the resistance? 

A. ohmmeter 

65. The maximum allowed length of a field bus segment is? 

A. 1900 m 

66. The maximum length of cable from the wiring block to FF device is? 

A.120m 

67. What is the thickness of IC cable insulation? 

A. 0.38mm 

68. What is the output of NAND gates if the inputs are 00? 

A. 1 

69. Gain & proportional bands are? 

A. reciprocally related 

70. 200‐300 psi range & single is 4‐20 MA at 235 psi, how many milliamp? 

A. 9.6 

71. In feedback control system the controller gets from the? 

A. controller variables 

72. What we say URV & LRV? 

A. span 
73. Which of the following adjustment is usually adjustment first is 
instrument requiring calibration? 

A. zero 

74. In a feedback control system the input variables are called? 

A. manipulated variables 

75. Derivative controller is beneficial for which process? 

A. temperature 

76. Adaptive gain is used for controlling process? 

A. Non‐linear 

77. The primary controller is a cascade control system must be tuned? 

A. After the secondary controller is tuned 

78. If a close loop controller is adjusted to produce a 0.25 drop when 
subjected to step change the system gain is? 

A. 0.5 

79. Two position controller (on/off) valve always? 

A. control around a point 

80. A proportional controller is being used to control a process & offset b/w 
set point control point must be held to a minimum this would dictate the 
proportional band ? 

A. be as narrow as possible 

81. When we adjust internal time in a controller? 

A. we determine as RC time content 

82. Automatic controller operates on the difference b/w set point & 
measurement is called? 

A. ERROR 

83. We have a close loop system which is cycling we should? 

A. Close and adjust/ Check and adjust both 

84. Any closed loop system with in phase feedback and a gain one or more 
with? 

A. Cycle or oscillate 

85. A straight proportional controller is controller is employed to control a 
process of narrowing the proportional band will? 

A. Decrease the offset 

86. In the modem controller, derivative action is applied? 
A. measurement 

87. A smart transmitter is one that. 

A. has a micro processer built inside 

88. How many NAND gates are needed to realize an OR gate? 

A. Three 

89. Minimum size of a main instrument air header? 

A. 2 inches 

90. Drain wire is? 

A. Bare conductor and in contact with shield. 

91. Purpose of shield in instrument cable? 

A. To reduce electrical noise and electromagnetic radiation. 

92. The main purpose of a control valve positioner is? 

A. improve precision of a valve. 

93. Which instrument is used for liquid expansion? 

A. Thermometer 

94. Maintenance access for fixed ladder? 

A. 1.5 feet 

95. Instrument to measure AC current only? 

A. Induction ammeter 

96.  Rocheal and quartz belongs to 

A. natural group of peizo electrical material. 

97. What type of gland shall be used in severe corrosive area? 

A. Flameproof and explosion proof 

98. The purpose of documenting as found calibration in addition to 
document as left calibration for an instrument? 

A. Measure calibration drift 

99. Potentiometer is? 

A. Variable resistor 

100. If the instrument is to have a wide range, the instrument should have 

A. logarithmic scale 

101. Which secondary cable tray cannot be used to pull single pair cable? 

A. Wire mesh or ladder 
102.  Zero initial system for systems means? 

A. system is at rest with no energy is stored in any components. 

103. A galvanometer has? 

A. EDDY current damping. 

104. In a single phase power factor meter the phase difference b/w the 
current in the two pressure coils? 

A. Exactly 90 degrees. 

105. The transducers which require an external power? 

A. Passive transducers. 

106. Level measurement with wet leg and installed tapping point? 

A. 1.4m 

107. Controlling torque in indicating instrument? 

A. Flat spiral spring 

108. Which gauge can be used to measure pressure? 

A. Ionization gauge 

109. The error of an instrument is normally given as a percentage? 

A. Full scale value. 

110. The repeat accuracy of an instrument can be judged from its? 

A. Standard deviation of error. 

Apart from this above question refer J‐902 thoroughly. 