0% found this document useful (0 votes)
366 views12 pages

Instruction Bulletin Hand-Held Test Kit

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
366 views12 pages

Instruction Bulletin Hand-Held Test Kit

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

48049-184-03

08/2004
Instruction Bulletin Cedar Rapids, IA, USA
ECN 656B

Hand-Held Test Kit

ENGLISH
for Micrologic® Series 2.0 and Above Trip Units and Compact® NS Circuit
Breakers Equipped with STR Trip Units
Retain for future use.

IDENTIFICATION

Figure 1: Hand-held Test Kit

A— Battery Compartment (five 9.0 V)


B— Short-circuit Trip LED (red)
06133786
C— Ground-fault Trip LED (red)
D— Ground-fault Inhibit LED (green)
E— Thermal-imaging Inhibit LED (green)
F— Trip Unit Power Supply LED (green) A
G—Low Battery LED (amber)
H— Good Battery LED (green)
I— Trip Unit Test Cable 10-pin Port
J— 9 V Battery Test Button O
B
K— Trip Unit Power Supply Button
L— Thermal-imaging Inhibit Button N
M—Ground-fault Inhibit Button
C
N— Ground-fault Trip Button M
O—Short-circuit Trip Button D

E L

F K

J
G

H
I

Figure 2: Hand-held Test Kit Accessories


06133770
06133771

06135367

2-pin Test Cable for STR Trip Units 7-pin Test Cable for Micrologic® Trip Units Primary Injection Adapter

© 2000–2004 Schneider Electric All Rights Reserved 1


Hand-Held Test Kit 48049-184-03
08/2004

BATTERY INSTALLATION NOTE: The Hand-held Test Kit uses five 9.0 V alkaline batteries (not
supplied). Recommended battery is Panasonic Industrial Alkaline 9 V, part
ENGLISH

number 6AM-6PIX/1S, or equivalent. Do not use nickel metal hydride, NiCd,


manganese or lithium batteries as damage can result to the internal circuitry
of the Hand-held Test Kit.
NOTE: There are no repairable internal parts for the Hand-held Test Kit.
Housing should only be opened to install or replace batteries.

1. Remove six screws (A).


CAUTION 2. Separate front housing (B) of Hand-held Test Kit from back housing (C).
HAZARD OF EQUIPMENT DAMAGE 3. Carefully remove battery circuit board (D).
This equipment uses five 9.0 V alkaline 4. If replacing batteries, remove old batteries.
batteries only. Do not use nickel metal hydride, 5. Insert new batteries (E) making sure polarity is correct.
NiCd, manganese or lithium batteries. 6. Carefully install battery circuit board (D).
Failure to follow this instruction can result in 7. Attach back housing (C) of Hand-held Test Kit to front housing (B) using
damage to the internal circuitry of this six previously removed tapping screws (A).
equipment.
Figure 3: Battery Installation

C
06133794

A
3.13 lb-in
E (0.35 N•m)

DETERMINE TRIP UNIT COMPATIBILITY Refer to Table 1 to determine which tests and functions are applicable then
follow appropriate connection procedures. Read this instruction bulletin
in its entirety before initiating any test or function.

Table 1: Trip Unit Compatibility*

Test Functions Inhibit Functions


Trip Unit
Test Short- Ground- Thermal- Battery
Trip Unit Type Ground- Power
Cable circuit fault imaging Test
fault Trip Supply
Trip Inhibit Inhibit
STR22, STR23, STR43 2-pin Test t t
STR53 Cable t t t
Non-
communicating ET1.0I, ET 1.0M t t
Micrologic 2.0, 3.0, 5.0 7-pin Test t t
Micrologic 2.0A, 3.0A, 5.0A, 5.0P, 5.0H Cable t t t t
Communicating
Micrologic 6.0A, 6.0P, 6.0H, 7.0A, 7.0P, 7.0H t t t t t
2- or 7-pin
No Trip Unit Connected t
Test Cable
*If a non-supported test or inhibit function is initiated on a trip unit, an error message will appear and circuit breaker may trip.

2 © 2000–2004 Schneider Electric All Rights Reserved


48049-184-03 Hand-Held Test Kit
08/2004

CONNECTIONS NOTE: Trip unit must be installed in circuit breaker in order to properly
execute Hand-held Test Kit tests and inhibit functions.

ENGLISH
Compact® NS Circuit Breakers Equipped 1. Connect test cable 10-pin connector (A) to 10-pin port on Hand-held
with STR Trip Units Test Kit.
2. Connect test cable 2-pin connector (B) to test port on STR trip units.
Make sure to observe correct polarity.
NOTE: Refer to Ground-fault Trip Test for proper ground-fault connection.

Figure 4: Connection to STR Trip Units

06133797
Test Kit
33594

I0 Ir Im
Test Test
Test
+ - Déclench
ement court-circ
Short-circuit uit
trip
Disparo cortocirc
uito

test Déclench
ement protectio
Ground-f n terre
ault trip
Disparo proteccio
n de tierra

Inhibiton
Inhibit Supre
Protectio cion
n terre
Ground fault
Proteccion
de tierra

Mémoire
thermiq
Therma ue
l imaging
Proteccion
de tierra

Alimen
tation déclen
Trip unit cheur
power supply
Alimen
tacion del

+ -
dispara
dor

B 9 V - Battery
test

-
+
test +-

Micrologic® Trip Units

Short-circuit Trip Test 1. Connect test cable 10-pin connector (A) to 10-pin port on Hand-held
Test Kit.
2. Connect test cable 7-pin connector (B) to test port on Micrologic trip
units. Refer to instruction label on test cable for connection instructions.

Figure 5: Connection to Micrologic Trip Units for Short-circuit Trip


Test
06133796

Test Kit
33594

gic 2.0
Microlo

Test Test
Test
Déclench
ement court-circ
Short-circuit uit
trip
Disparo cortocirc
uito

Déclench
ement protectio
Ground-f n terre
ault trip
Disparo proteccio
n de tierra

Inhibiton
Inhibit Supre
Protectio cion
n terre
Ground fault
Proteccio
n de tierra

Mémoire
thermiq
Therma ue
l imaging
Protecc
ion de tierra

Alimen
tation déclenc
Trip unit
power supplyheur
Alimen
tacion del
dispara
dor

B 9 V - Battery
test
-
+

© 2000–2004 Schneider Electric All Rights Reserved 3


Hand-Held Test Kit 48049-184-03
08/2004

Inhibit Functions and Trip Unit Power Supply 1. Connect primary injection test adapter 10-pin connector (A) to 10-pin
port on Hand-held Test Kit.
ENGLISH

2. Connect test cable 10-pin connector (B) to 10-pin port on primary


injection test adapter.
3. Connect test cable 7-pin connector (C) to test port on Micrologic trip
units. Refer to instruction label on test cable for connection instructions.

Figure 6: Connection to Micrologic Trip Units for Inhibit Functions


and Trip Unit Power

06135346
Test Kit
33594

Test Test
Test
Déclenchement
Short-circuit court-circuit
trip
Disparo cortocirc
uito

Déclenchement
protection
Ground-fault terre
trip
Disparo protecci
on de tierra

Inhibiton
Inhibit Supre
Protectio cion
n terre
Ground fault
Proteccion
de tierra

Mémoire
thermique
Therma
l imagin
Proteccion g
de tierra

Alimen
tation déclen
Trip unit cheur
power supply
Alimen
tacion del
dispara
dor

9 V - Battery
test

-
+
gic 2.0
Microlo

Error Message Indication An error message is indicated by all LEDs lighting at once. If an error
message is displayed during Hand-held Test Kit operation, check all
connections then refer to Table 1 and Troubleshooting section.

4 © 2000–2004 Schneider Electric All Rights Reserved


48049-184-03 Hand-Held Test Kit
08/2004

TESTS

ENGLISH
Short-circuit Trip Test This test verifies operation of trip unit short-circuit protection function. The
Hand-held Test Kit supplies power to trip unit while injecting a secondary
fault signal large enough to cause tripping of circuit breaker. For Micrologic
DANGER A trip units only, performing this test will reset to zero the maximum
HAZARD OF ELECTRIC SHOCK, recorded value on each phase. If necessary, record maximum values before
EXPLOSION OR ARC FLASH testing.

• Apply appropriate personal protective NOTE: Short-circuit tests will not be recorded in trip log of Micrologic P and
equipment (PPE) and follow safe electrical H trip units. Advanced protection and alarms will also be disabled during
work practices. See NFPA 70E test. Refer to trip unit instruction bulletin for advanced protection features.
• This equipment must be installed and 1. Close circuit breaker being tested. Use a properly rated voltage sensing
serviced only by qualified electrical device to verify circuit breaker is not carrying current.
personnel. 2. Press short-circuit trip button (A).
• Turn off all power supplying this equipment
a. For non-communicating trip units (see Table 1), the red short-circuit
before working on or inside equipment.
trip LED will light solid indicating short-circuit trip test is in progress.
• Always use a properly rated voltage sensing
b. For communicating trip units (see Table 1), the red short-circuit trip
device to confirm power is off.
LED will flicker indicating communication activity with the trip unit
• Replace all devices, doors and covers before while short-circuit trip test is in progress.
turning on power to this equipment.
NOTE: All LEDs lighting at once indicates Hand-held Test Kit cannot
Failure to follow this instruction will result in establish communication with trip unit. The trip unit gives communication
death or serious injury. priority to the circuit breaker communications module (BCM). When
BCM is powered and operating, its communication activities take
Figure 7: Short-circuit Trip Button precedence over Hand-held Test Kit commands. After all LEDs go out,
repeat step 2. If all LEDs light up again, disconnect power from E1 and
A E2 terminals of BCM and repeat step 2.
3. Confirm test was successful by verifying circuit breaker tripped. Refer to
06133788

circuit breaker and trip unit instruction bulletins for proper circuit breaker
operation.
4. For communicating trip units wait for test exit communication, indicated
by flickering red short-circuit trip LED, before disconnecting Hand-held
Test Kit.
5. Test exit communication is complete when red short-circuit trip LED
turns off automatically with no error display.

© 2000–2004 Schneider Electric All Rights Reserved 5


Hand-Held Test Kit 48049-184-03
08/2004

Ground-fault Trip Test The Hand-held Test Kit can be used to verify ground-fault protection for
STR53 trip units only.
ENGLISH

CAUTION NOTE: To test ground-fault trip on Micrologic 6.0P, 6.0H, 7.0P and 7.0H trip
units, press test button located directly above trip unit test port. To prevent
HAZARD OF INVALID READING logging of ground-fault trip test in trip unit’s trip history, use Hand-held Test
Kit to inhibit thermal-imaging, as described in this instruction bulletin.
Make sure to reverse the polarity of 2-pin test
cable before performing ground-fault trip test. 1. Close circuit breaker being tested. Use a properly rated voltage sensing
device to verify circuit breaker is not carrying current.
Failure to follow this instruction can result in
2. Make sure to reverse the polarity of 2-pin test cable connection as
inaccurate test results.
shown in Figure 8.
Figure 8: Reverse Polarity
06133798

I0 Ir Im

+ - +

test
-

test -+

Figure 9: Ground-fault Trip Button 3. Press ground-fault trip button (A). The red ground-fault trip LED will light
solid indicating ground-fault trip test is in progress.
A
4. Confirm test was successful by verifying circuit breaker tripped. Refer to
circuit breaker and trip unit instruction bulletins for proper circuit breaker
06133789

operation.
5. Once ground-fault trip test is successfully completed, red ground-fault
trip LED turns off automatically with no error display.

6 © 2000–2004 Schneider Electric All Rights Reserved


48049-184-03 Hand-Held Test Kit
08/2004

INHIBIT FUNCTIONS Inhibit functions are only available during long-time, short-time,
instantaneous and ground-fault (LSIG) primary-injection testing of certain

ENGLISH
communicating Micrologic trip units (see Table 1). For Micrologic P and H
trip units, inhibit functions disable advanced protection, alarms and logging
of events during testing. Refer to trip unit instruction bulletin for advanced
protection features.

Ground-fault Inhibit NOTE: Activating ground-fault inhibit will automatically activate thermal-
imaging inhibit and enable zone-selective interlocking (ZSI) self-restraint.
Figure 10: Ground-fault Inhibit Button
1. Make sure primary injection adapter is connected as shown in Figure 6.
A 2. Press ground-fault inhibit button (A). This action, indicated by flickering
green ground-fault inhibit LED, powers the trip unit and sends a
message to inhibit ground fault, inhibit thermal imaging and ZSI self-
06133790

restrain the circuit breaker. Once green LED lights solid, ground fault
and thermal imaging are being inhibited and the circuit breaker is ZSI
self-restrained and ready for primary injection testing. Green LED will
remain continuously lit with exception of one flash every minute to
indicate communication activity with trip unit.
NOTE: All LEDs lighting at once indicates Hand-held Test Kit cannot
establish communication with trip unit. The trip unit gives communication
priority to the circuit breaker communications module (BCM). When
BCM is powered and operating, its communication activities take
precedence over Hand-held Test Kit commands. After all LEDs go out,
repeat step 2. If all LEDs light up again, disconnect power from E1 and
E2 terminals of BCM and repeat step 2.
3. Once primary injection testing is completed, press ground-fault inhibit
button (A) to terminate ground-fault inhibit, thermal-imaging inhibit and
ZSI self-restrain and turn off Hand-held Test Kit.
NOTE: When performing multiple primary-injection tests, stop the
ground-fault inhibit function between each test by pressing the ground-
fault inhibit button (A) and waiting until all Hand-held Test Kit LEDs turn
off. Restart the ground-fault inhibit function by following step 2 above.
4. Before disconnecting Hand-held Test Kit, wait for test exit
communication indicated by flickering green ground-fault inhibit LED.
Test exit communication is complete when green ground-fault inhibit
LED turns off.
NOTE: If no buttons are pressed for 15 minutes after ground-fault inhibit is
initiated, Hand-held Test Kit will automatically turn off terminating ground-
fault inhibit, thermal-imaging inhibit and ZSI self-restrain.

© 2000–2004 Schneider Electric All Rights Reserved 7


Hand-Held Test Kit 48049-184-03
08/2004

Thermal-imaging Inhibit Thermal imaging provides continuous temperature rise status of circuit
breaker cabling both before and after a device trips. Under normal
ENGLISH

Figure 11: Thermal-imaging Inhibit Button conditions a 15-minute delay is required following a device tripping to allow
system to cool before returning to normal functionality. The thermal-imaging
A inhibit function inhibits thermal imaging, thus overriding the 15-minute delay
and allowing for multiple consecutive primary injection tests.
06133791

NOTE: Activating thermal-imaging inhibit will automatically enable zone-


selective interlocking (ZSI) self-restraint. However, activating thermal-
imaging inhibit will not automatically activate ground-fault inhibit.
1. Make sure primary injection adapter is connected as shown in Figure 6.
2. Press thermal-imaging inhibit button (A). This action, indicated by
flickering green thermal-imaging inhibit LED, powers trip unit and sends
a message to inhibit thermal imaging and ZSI self-restrain the circuit
breaker. Once green LED lights solid, thermal imaging is being inhibited
and the circuit breaker is ZSI self-restrained and ready for primary
injection testing. Green LED will remain continuously lit with exception of
one flash every minute to indicate communication activity with trip unit.
NOTE: All LEDs lighting at once indicates Hand-held Test Kit cannot
establish communication with trip unit. The trip unit gives communication
priority to the circuit breaker communications module (BCM). When
BCM is powered and operating, its communication activities take
precedence over Hand-held Test Kit commands. After all LEDs go out,
repeat step 2. If all LEDs light up again, disconnect power from E1 and
E2 terminals of BCM and repeat step 2.
3. Once primary injection testing is completed, press thermal-imaging
inhibit button (A) to terminate thermal-imaging inhibit and ZSI self-
restrain and turn off Hand-held Test Kit.
NOTE: When performing multiple primary-injection tests, stop the
thermal-imaging inhibit function between each test by pressing the
thermal-imaging inhibit button (A) and waiting until all Hand-held Test Kit
LEDs turn off. Restart the thermal-imaging inhibit function by following
step 2 above.
4. Before disconnecting Hand-held Test Kit, wait for test exit
communication indicated by flickering green thermal-imaging inhibit
LED. Test exit communication is complete when green thermal-imaging
inhibit LED turns off.
NOTE: If no buttons are pressed for 15 minutes after thermal-imaging inhibit
is initiated, Hand-held Test Kit will automatically turn off terminating thermal-
imaging inhibit and ZSI self-restrain.

8 © 2000–2004 Schneider Electric All Rights Reserved


48049-184-03 Hand-Held Test Kit
08/2004

TRIP UNIT POWER SUPPLY The Hand-held Test Kit provides power to communicating Micrologic trip
units (see Table 1) to allow setup and testing. It can also be used in

ENGLISH
Figure 12: Trip Unit Power Supply Button conjunction with the Full-function Test Kit to verify functionality of zone-
selective interlocking (ZSI). In this application, the Hand-held Test Kit
A provides power to an upstream trip unit while the Full-function Test Kit
performs ZSI test.
06133792

1. Make sure primary injection adapter is connected as shown in Figure 6.


2. Press trip unit power supply button (A). The green trip unit power supply
LED will light solid indicating Hand-held Test Kit is providing power to
trip unit.
3. Once any setup or testing functions are complete, press trip unit power
supply button (A) to terminate power to trip unit and to turn off Hand-held
Test Kit.
4. Before disconnecting Hand-held Test Kit, make sure green trip unit
power supply LED turns off.
NOTE: If no buttons are pressed for 15 minutes after trip unit power supply
function is initiated, Hand-held Test Kit will automatically turn off and power
to trip unit will be terminated.

BATTERY TEST This function tests voltage of Hand-held Test Kit’s batteries.

Figure 13: Battery Test Button 1. Press 9 V-battery test button (A).
2. Both LEDs will light followed by one of the following:
A — Solid green LED indicates good batteries.
— Solid amber LED indicates low batteries.
06133793

NOTE: Both LEDs off indicates exhausted batteries or batteries not


installed.

© 2000–2004 Schneider Electric All Rights Reserved 9


Hand-Held Test Kit 48049-184-03
08/2004

TROUBLESHOOTING
ENGLISH

Table 2: Troubleshooting

Condition Probable Causes Solutions


Pressed any button and no LEDs turned 1. Exhausted batteries or batteries not installed. 1. Install fresh batteries and press battery test
on. button.
2. Defective Hand-held Test Kit. 2. Contact local field office.
Pressed either test button, red LED 1. Circuit breaker not properly reset. 1. Verify circuit breaker is reset and closed.
turned on and then off; circuit breaker did 2. Loose test cable connections between Hand- 2. Check test cable connections and restart
not trip. held Test Kit and trip unit. test.
3. Defective Hand-held Test Kit, trip unit or 3. Contact local field office.
circuit breaker.
Pressed any test or inhibit function 1. Loose or no test cable connections between 1. Check test cable connections and restart
button, all LEDs turned on and then off; Hand-held Test Kit and trip unit. test.
circuit breaker did not trip. 2. Test attempted not applicable to trip unit type. 2. Refer to Table 1 to determine if test is
General applicable to trip unit type.
3. Circuit breaker communication module 3. Wait a few seconds and restart test or
(BCM) is in active communicating mode. disconnect power from E1 and E2 terminals
on circuit breaker communications module.
4. Defective Hand-held Test Kit, trip unit or 4. Contact local field office.
circuit breaker.
Pressed any test or inhibit function Communication error occurred while test in Wait a few seconds and restart test or
button and after one minute of duration progress. disconnect power from E1 and E2 terminals on
all LEDs turned on and then off. circuit breaker communications module.
Pressed any test or inhibit function Circuit breaker communication module (BCM) in Wait a few seconds and restart test or
button and after LED flickered all LEDs active communicating mode. disconnect power from E1 and E2 terminals on
turned on and then off. circuit breaker communications module.
Pressed short-circuit trip test button, red 1. Circuit breaker not properly reset. 1. Verify circuit breaker is reset.
LED turned on and then off; circuit 2. Primary injection adapter connected. 2. Disconnect primary injection adapter.
breaker did not trip. 3. Loose test cable connections between Hand- 3. Check test cable connections and restart
held Test Kit and trip unit. short-circuit trip test.
4. Circuit breaker communication module 4. Wait a few seconds and restart test or
(BCM) in active communicating mode. disconnect power from E1 and E2 terminals
on circuit breaker communications module.
Short-circuit trip 5. Defective Hand-held Test Kit, trip unit or 5. Contact local field office.
test circuit breaker.
Pressed Short-circuit trip test button, red 1. No test cable connections between Hand- 1. Check test cable connections.
LED turned on followed by all LEDs held Test Kit and trip unit.
turning on and then off; circuit breaker 2. Communication error with communicating 2. Check test cable connections and restart
did not trip. MICROLOGIC trip unit. short-circuit trip test.
3. Circuit breaker communication module 3. Wait a few seconds and restart test or
(BCM) in active communicating mode. disconnect power from E1 and E2 terminals
on circuit breaker communications module.
Pressed ground-fault trip test button, red 1. Polarity on 2-pin test cable not reversed. 1. Reverse polarity on 2-pin test cable
LED turned on and then off; circuit connection.
breaker did not trip. 2. Circuit breaker not properly reset. 2. Verify circuit breaker is reset.
3. Primary injection adapter connected. 3. Disconnect primary injection adapter.
4. Loose test cable connections between Hand- 4. Check test cable connections and restart
Ground-fault trip held Test Kit and trip unit. short-circuit trip test.
test 5. Defective Hand-held Test Kit, trip unit or 5. Contact local field office.
circuit breaker.
Pressed ground-fault trip test button, red 1. No test cable connections between Hand- 1. Check test cable connections and restart
LED turned on followed by all LEDs held Test Kit and trip unit. ground-fault trip test.
turning on and then off; circuit breaker 2. Ground-fault trip test not applicable to trip unit 2. Refer to Table 1 to determine if ground-fault
did not trip. type. trip test is applicable to trip unit type.
Continued on next page

10 © 2000–2004 Schneider Electric All Rights Reserved


48049-184-03 Hand-Held Test Kit
08/2004

Table 2: Troubleshooting (continued)

Condition Probable Causes Solutions

ENGLISH
Pressed ground-fault inhibit button and 1. Loose or no test cable connections between 1. Check test cable connections and restart
green LED turned on followed by all Hand-held Test Kit and trip unit. ground-fault inhibit function.
LEDs turning on and then off. 2. Communication error with communicating 2. Check test cable connections and restart
MICROLOGIC trip unit. ground-fault inhibit function.
3. Ground-fault inhibit function not applicable to 3. Refer to Table 1 to determine if ground-fault
trip unit type. inhibit function is applicable to trip unit type.
4. Circuit breaker communication module 4. Wait a few seconds and restart test or
(BCM) in active communicating mode. disconnect power from E1 and E2 terminals
Ground-fault inhibit on circuit breaker communications module.
function 5. Defective Hand-held Test Kit, trip unit or 5. Contact local field office.
circuit breaker.
Circuit breaker trips on ground fault, but During multiple primary-injection tests, ground- When performing multiple primary-injection tests,
Hand-held Test Kit indicates it is fault inhibit was not stopped and then restarted stop ground-fault inhibit function between each
inhibiting ground fault (i.e., green ground- between each test. test by pressing ground-fault inhibit button and
fault inhibit LED is on). waiting until all Hand-held Test Kit LEDs turn off.
Restart ground-fault inhibit function for next
primary-injection test.
Pressed thermal-imaging inhibit button 1. Loose or no test cable connections between 1. Check test cable connections and restart
and green LED turned on followed by all Hand-held Test Kit and trip unit. thermal-imaging inhibit function.
LEDs turning on and then off. 2. Communication error with communicating 2. Check test cable connections and restart
MICROLOGIC trip unit. thermal-imaging inhibit function.
3. Thermal-imaging inhibit function not 3. Refer to Table 1 to determine if thermal-
applicable to trip unit type. imaging inhibit function is applicable to trip
unit type.
4. Circuit breaker communication module 4. Wait a few seconds and restart test or
Thermal-imaging (BCM) in active communicating mode. disconnect power from E1 and E2 terminals
inhibit function on circuit breaker communications module.
5. Defective Hand-held Test Kit, trip unit or 5. Contact local field office.
circuit breaker.
Circuit breaker trips earlier than During multiple primary-injection tests, thermal- When performing multiple primary-injection tests,
expected. imaging inhibit was not stopped and then stop thermal-imaging inhibit function between
restarted between each test. each test by pressing thermal-imaging inhibit
button and waiting until all Hand-held Test Kit
LEDs turn off. Restart thermal-imaging inhibit
function for next primary-injection test.
Pressed trip unit power supply button 1. No test cable connections between Hand- 1. Check test cable connections and restart trip
and green LED turned on followed by all held Test Kit and trip unit. unit power supply function.
Trip unit power
LEDs turning on and then off. 2. Trip unit power supply function not applicable 2. Refer to Table 1 to determine if trip unit
supply
to trip unit type. power supply function is applicable to trip unit
type.
Pressed any button and solid yellow LED 1. Low batteries. 1. Install fresh batteries and press battery test
Battery test
turned on and then off. button.

© 2000–2004 Schneider Electric All Rights Reserved 11


Hand-Held Test Kit 48049-184-03
Instruction Bulletin 08/2004
ENGLISH

Schneider Electric USA


3700 Sixth St SW, PO Box 3069 Electrical equipment should be installed, operated, serviced, and maintained only by
Cedar Rapids, IA 52406-3069 USA qualified personnel. No responsibility is assumed by Schneider Electric for any
1-888-SquareD (1-888-778-2733) consequences arising out of the use of this material.
www.us.SquareD.com

12 © 2000–2004 Schneider Electric All Rights Reserved

You might also like