Controllogix 5570/5560 Redundancy: User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 244

ControlLogix 5570/5560 Redundancy

User Manual Original Instructions


ControlLogix 5570/5560 Redundancy User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).

2 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Table of Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 1
About ControlLogix Features of the ControlLogix Redundancy System . . . . . . . . . . . . . . . 12
Redundancy Systems Redundancy System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
I/O Modules in Redundancy Systems . . . . . . . . . . . . . . . . . . . . . . . 14
Redundancy System Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
System Qualification and Synchronization. . . . . . . . . . . . . . . . . . . 15
Switchovers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Restrictions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Chapter 2
Design a ControlLogix Redundant Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Redundancy System Redundant Chassis Configuration Requirements . . . . . . . . . . . . 22
Controllers in Redundant Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Redundancy Modules in Redundant Chassis. . . . . . . . . . . . . . . . . 24
Communication Modules in Redundant Chassis . . . . . . . . . . . . . 25
Power Supplies and Redundant Power Supplies in
Redundancy Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
EtherNet/IP Networks with Redundant Systems . . . . . . . . . . . . . . . . 28
Unicast Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Possible Communication Delays on EtherNet/IP and
ControlNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Bridge from an EtherNet/IP Network to a ControlNet
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ControlNet Networks with Redundant Systems . . . . . . . . . . . . . . . . . 30
ControlNet Network Requirements . . . . . . . . . . . . . . . . . . . . . . . . 30
Redundant ControlNet Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Other Communication Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
I/O Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1715 Redundant I/O Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Using HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
HMI Connected Via an EtherNet/IP Network . . . . . . . . . . . . . . 38
HMI Connected Via a ControlNet Network . . . . . . . . . . . . . . . . 39
Optional Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 3


Table of Contents

Chapter 3
Install the Redundancy System Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Redundancy System Quick Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Install the Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Install the First Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Install the Redundancy Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Environment and Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Removal and Insertion Under Power (RIUP) . . . . . . . . . . . . . . . . 47
European Hazardous Location Approval . . . . . . . . . . . . . . . . . . . . 48
Safety-related Programmable Electronic Systems . . . . . . . . . . . . . 48
Optical Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Small Form-factor Pluggable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
North American Hazardous Location Approval. . . . . . . . . . . . . . 49
Laser Radiation Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Install the Second Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Connect the Redundancy Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Connect the Fiber-optic Communication Cable to
Redundant Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connect the Fiber-optic Communication Cable to
Single Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Fiber-optic Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Use Dual Fiber Ports with the 1756-RM2 Redundancy
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Update Redundant Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Upgrade the Firmware in the First Chassis. . . . . . . . . . . . . . . . . . . 58
Upgrade the Firmware in the Second Chassis . . . . . . . . . . . . . . . . 61
Designate the Primary and Secondary Chassis . . . . . . . . . . . . . . . . . . . 61
After Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Conversion from a Non-redundant to a Redundant System . . . 62
Qualification Status Via the RMCT . . . . . . . . . . . . . . . . . . . . . . . . 63
Reset the Redundancy Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Remove or Replace the Redundancy Module. . . . . . . . . . . . . . . . . 64

Chapter 4
Configure the EtherNet/IP Requested Packet Interval. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Network CPU Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
IP Address Swapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Static Versus Dynamic IP Addresses. . . . . . . . . . . . . . . . . . . . . . . . . 68
Reset the IP Address for an EtherNet/IP Communication
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
CIP Sync . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Produce/Consume Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

4 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Table of Contents

Configure EtherNet/IP Communication Modules in a


Redundant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Options for Setting the IP Addresses of EtherNet/IP
Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Half/Full Duplex Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Use a Redundancy System with Device Level Ring . . . . . . . . . . . . . . . 76
Use a Redundancy System with Parallel Redundancy Protocol . . . . 77

Chapter 5
Configure the ControlNet Produce/Consume Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Network Network Update Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
NUTs with Multiple ControlNet Networks . . . . . . . . . . . . . . . . . 81
Scheduled or Unscheduled Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Use a Scheduled Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Use an Unscheduled Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Add Remote ControlNet Modules While Online . . . . . . . . . . . . 84
Schedule a New Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Update an Existing Scheduled Network . . . . . . . . . . . . . . . . . . . . . . . . . 87
Check the Network Keeper States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Save the Project for Each Primary Controller . . . . . . . . . . . . . . . . 90
Automatic Keeper Crossloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Chapter 6
Configure the Redundancy About the Redundancy Module Configuration Tool (RMCT). . . . 91
Modules Determine If Further Configuration Is Required. . . . . . . . . . . . . . . . . 92
Use the RMCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Identify the RMCT Version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Update the RMCT Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Module Info Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Auto-synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Chassis ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Enable User Program Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Redundancy Module Date and Time . . . . . . . . . . . . . . . . . . . . . . . 100
Synchronization Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Commands in the Synchronization Tab . . . . . . . . . . . . . . . . . . . . 102
Recent Synchronization Attempts Log . . . . . . . . . . . . . . . . . . . . . 103
Synchronization Status Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
System Update Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
System Update Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
System Update Lock Attempts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Locked Switchover Attempts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 5


Table of Contents

Chapter 7
Program the Redundant Configure the Redundant Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Controller Enable Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Crossloads, Synchronization, and Switchovers . . . . . . . . . . . . . . . . . . 116
Changing Crossload and Synchronization Settings . . . . . . . . . . 116
Default Crossload and Synchronization Settings . . . . . . . . . . . . 117
Recommended Task Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Continuous Task After Switchover . . . . . . . . . . . . . . . . . . . . . . . . 117
Multiple Periodic Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Crossloads and Scan Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Estimate the Crossload Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Redundancy Object Attributes for Crossload Times. . . . . . . . . 121
Equation for Estimating Crossload Times . . . . . . . . . . . . . . . . . . 122
Program to Minimize Scan Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Use a ControlLogix 5570 Controller with a 1756-RM2
Redundancy Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Use Multiple Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Minimize the Number of Programs . . . . . . . . . . . . . . . . . . . . . . . . 124
Manage Tags for Efficient Crossloads . . . . . . . . . . . . . . . . . . . . . . 124
Use Concise Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Program to Maintain Data Integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Array (File)/Shift Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Scan-dependent Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Optimize Task Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Periodic Task Configuration Optimization . . . . . . . . . . . . . . . . . 135
Continuous Task Configuration Optimization . . . . . . . . . . . . . 137
Change the System Overhead Time Slice . . . . . . . . . . . . . . . . . . . 138
Conduct a Test Switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Synchronization After a Switchover . . . . . . . . . . . . . . . . . . . . . . . . 140
Program Logic to Run After a Switchover . . . . . . . . . . . . . . . . . . . . . . 141
Use Messages for Redundancy Commands . . . . . . . . . . . . . . . . . . . . . 142
Verify User Program Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Use an Unconnected Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Configure the MSG Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Set the Task Watchdog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Minimum Value for the Watchdog Time . . . . . . . . . . . . . . . . . . . 148
Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Store a Redundancy Project to Nonvolatile Memory . . . . . . . . . . . . 149
Store a Project While the Controller is in Program or
Remote Program Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Store a Project While a System is Running . . . . . . . . . . . . . . . . . . 151
Load a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Online Edits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Support for Partial Import Online . . . . . . . . . . . . . . . . . . . . . . . . . 152
Plan for Test Edits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Assemble Edits with Caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Reserve Memory for Tags and Logic. . . . . . . . . . . . . . . . . . . . . . . . 158

6 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Table of Contents

Chapter 8
Monitor and Maintain a Controller Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Redundancy System Controller Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Controller Logging in Redundancy Systems . . . . . . . . . . . . . . . . 160
Component Change Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Monitor System Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Verify Date and Time Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Verify System Qualification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Check Qualification Status Via Module Status Displays . . . . . 164
Check Qualification Status Via the RMCT . . . . . . . . . . . . . . . . . 166
Check the EtherNet/IP Module Status . . . . . . . . . . . . . . . . . . . . . . . . 166
EtherNet/IP Module CPU Usage. . . . . . . . . . . . . . . . . . . . . . . . . . 167
EtherNet/IP Module Connections Used . . . . . . . . . . . . . . . . . . . 167
Monitor the EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . 167
Check the ControlNet Module Status . . . . . . . . . . . . . . . . . . . . . . . . . 168
ControlNet Module CPU Usage . . . . . . . . . . . . . . . . . . . . . . . . . . 169
ControlNet Module Connections Used . . . . . . . . . . . . . . . . . . . . 169
Monitor the ControlNet Network. . . . . . . . . . . . . . . . . . . . . . . . . 169

Chapter 9
Troubleshoot a Redundant General Troubleshooting Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
System Check the Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Use Programming Software to View Errors . . . . . . . . . . . . . . . . . . . . . 173
Redundant Controller Major Fault Codes . . . . . . . . . . . . . . . . . . 175
Use the RMCT for Synchronization Attempts and Status . . . . . . . 176
Recent Synchronization Attempts . . . . . . . . . . . . . . . . . . . . . . . . . 176
Module-level Synchronization Status. . . . . . . . . . . . . . . . . . . . . . . 177
Use the RMCT Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Interpret Event Log Information . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Export All Event Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Export Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Contact Rockwell Automation Technical Support . . . . . . . . . . 186
Controller Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Event Log Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Event Classifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Access Extended Information about an Event . . . . . . . . . . . . . . . 190
Interpret Extended Information for an Event . . . . . . . . . . . . . . . 191
Export Event Log Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Clear a Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
System Event History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
System Event History Column Descriptions . . . . . . . . . . . . . . . . 197
Edit a User Comment for a System Event. . . . . . . . . . . . . . . . . . . 198
Save System Event History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Event Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 7


Table of Contents

Keeper Status Causing Synchronize Failure. . . . . . . . . . . . . . . . . . . . . 201


Check the Module Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Check Keeper Status in RSNetWorx for ControlNet
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Valid Keeper Status and Signatures. . . . . . . . . . . . . . . . . . . . . . . . . 202
Partner Network Connection Lost . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Redundancy Module Connection Lost. . . . . . . . . . . . . . . . . . . . . . . . . 206
Redundancy Module Missing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Qualification Aborted Due to a Non-redundant Controller . . . . . 208
Redundancy Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . 209
1756-RM2 and 1756-RM2XT Status Indicators . . . . . . . . . . . . 209
1756-RM/A and 1756-RM/B Status Indicators. . . . . . . . . . . . . 213
Redundancy Module Fault Codes and Display Messages . . . . . 216
Recovery Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217

Appendix A
Convert from a Non-redundant Update the Configuration in Programming Software. . . . . . . . . . . . 220
System Replace Local I/O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Replace Aliases to Local I/O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Remove Other Modules from the Controller Chassis. . . . . . . . . . . . 224
Add an Identical Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Upgrade to Redundancy Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Update the Controller Revision and Download the Project . . . . . . 225

Appendix B
Redundancy Object Attributes Table of Redundancy Object Attributes. . . . . . . . . . . . . . . . . . . . . . . . 227

Appendix C
Redundancy System Checklists Chassis Configuration Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Remote I/O Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Redundancy Module Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
ControlLogix Controller Checklist . . . . . . . . . . . . . . . . . . . . . . . . 233
ControlNet Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
EtherNet/IP Module Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Project and Programming Checklist. . . . . . . . . . . . . . . . . . . . . . . . 236

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .237

8 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Preface

Summary of Changes This table contains the changes that are made to this revision.

Topic Page
Added firmware revision 33.051 219, 224

Overview In this publication, ‘ControlLogix Redundancy’ refers to


ControlLogix 5570/5560 Redundancy.

This publication provides this information specific to redundancy systems:


• Design and planning considerations
• Installation procedures
• Configuration procedures
• Maintenance and troubleshooting methods

This publication is designed for use by anyone responsible for planning and
implementing a ControlLogix® redundancy system:
• Application engineers
• Control engineers
• Instrumentation technicians

The contents of this publication are for anyone who already has an understanding
of Logix 5000™ control systems, programming techniques, and communication
networks.

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Table 1 - Additional Documentation

Resource Description
1715 Redundant I/O System Specifications Technical Data, publication 1715-TD001 Contains specifications on a Redundant I/O system.
1756 ControlLogix Controllers Technical Data, publication 1756-TD001 Contains specifications on ControlLogix controllers and redundancy modules.
ControlLogix 5580 Redundant Controller User Manual, publication 1756-UM015 Describes how to install, configure, program, operate, and troubleshoot
a ControlLogix® 5580 redundancy system..
High Availability Systems Reference Manual, publication HIGHAV-RM002 Provides information to help design and plan high availability systems.
ControlFLASH Firmware Upgrade Software User Manual, publication 1756-UM105 Describes how to use the ControlFLASH™ software to upgrade device firmware.
ControlFLASH Plus Quick Start Guide, publication CFP-QS001C-EN-E Describes how to use the ControlFLASH Plus™ software to upgrade device firmware.
ControlLogix Redundancy Update and Module Replacement Guidelines Reference Manual, Provides instructions for replacing modules or updating firmware in a powered-up
publication 1756-RM010 redundancy system.
ControlLogix System Selection Guide, publication 1756-SG001 Provides information on how to select components for a ControlLogix system.
ControlLogix System User Manual, publication 1756-UM001 Contains information on how to install, configure, program, and operate a
ControlLogix system.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 9


Preface

Table 1 - Additional Documentation

Resource Description
ControlNet Network Configuration User Manual, publication CNET-UM001 Describes ControlNet® modules and how to use ControlNet modules with a Logix
5000 controller.
EtherNet/IP Parallel Redundancy Protocol Application Technique, publication ENET-AT006 Describes how to configure a Parallel Redundancy Protocol (PRP) network with the
1756-EN2TP EtherNet/IP™ communication module and a Stratix® 5400 or 5410
switch.
EtherNet/IP Device Level Ring Application Technique, publication ENET-AT007 Describes how to install, configure, and maintain linear and Device Level Ring (DLR)
networks that use Rockwell Automation® EtherNet/IP devices with embedded switch
technology.
EtherNet/IP Socket Interface Application Technique, publication ENET-AT002 Logix 5000Describes the socket interface that you can use to program MSG
instructions to communicate between a Logix 5000 controller via an EtherNet/IP
module and Ethernet devices that do not support the EtherNet/IP application
protocol.
EtherNet/IP Network Devices User Manual, publication ENET-UM006 Describes how to use EtherNet/IP communication modules with your Logix 5000
controller and communicate with various devices on the Ethernet network.
Integrated Architecture and CIP Sync Configuration Application Technique, Provides an explanation of CIP Sync™ technology and how you can synchronize clocks
publication IA-AT003 within the Rockwell Automation Integrated Architecture®.
Logix 5000 Controllers Common Procedures Programming Manual, Provides links to a collection of programming manuals that describe how to use
publication 1756-PM001 procedures that are common to all Logix 5000 controllers projects.
Logix 5000 Controllers General Instructions Reference Manual, publication 1756-RM003 This manual provides details about each available instruction for a Logix-based
controller.
Logix 5000 Controllers Information and Status Programming Manual, Describes how Logix 5000 controllers use connections with other devices.
publication 1756-PM015
Logix 5000 Controllers I/O and Tag Data Programming Manual, publication 1756-PM004 Provides information on how to access I/O and tag data in Logix 5000 controllers.
Logix 5000 Controllers Major, Minor, and I/O Faults Programming Manual, Describes how to monitor and handle major and minor controller faults.
publication 1756-PM014
Logix 5000 Controllers Nonvolatile Memory Card Programming Manual, Provides information on how to access and use a memory card in Logix 5000
publication 1756-PM017 controllers.
Logix 5000 Produced and Consumed Tags Programming Manual, Provides information to produce and consume system-shared tags and produce a
publication 1756-PM011 large array with a Logix 5000 controller.
Logix 5000 Controllers Quick Start, publication 1756-QS001 Provides information to program and maintain Logix 5000 controllers.
Logix 5000 Controllers Tasks, Programs, and Routines Programming Manual, Provides information to configure controller tasks and the programs and routines for
publication 1756-PM005 the proper execution of these tasks.
PlantPAx DCS Configuration and Implementation User Manual, publication Elaborates on the application rules that are required to configure a PlantPAx® system.
PROCES-UM100
Using ControlLogix in SIL 2 Applications Safety Reference Manual, Provides safety-related information specific to the use of ControlLogix modules in SIL
publication 1756-RM001 2 systems.
Redundant I/O System User Manual, publication 1715-UM001 Contains information on how to install, configure, program, operate, and
troubleshoot a Redundant I/O system.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at


http://www.rockwellautomation.com/global/literature-library/overview.page.
To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.

10 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 1

About ControlLogix Redundancy Systems

Topic Page
Features of the ControlLogix Redundancy System 12
Redundancy System Components 13
Redundancy System Operations 15
Restrictions 19

IMPORTANT In this publication, ‘ControlLogix Redundancy’ refers to


ControlLogix 5570/5560 Redundancy.

The ControlLogix® Redundancy System is a system that provides greater


availability. The system has greater availability because it uses a redundant chassis
pair. The redundant chassis pair maintains process operation when events, such as
a fault on a controller, occur that stop process operation on
non-redundant systems.

The redundant chassis pair includes two synchronized ControlLogix chassis with
identically specific components in each. For example, one redundancy module
and at least one ControlNet® or EtherNet/IP™ communication module are
required.

Controllers are typically used in redundancy systems, but are not required if your
application only requires communication redundancy. Your application operates
from a primary chassis, but can switch over to the secondary chassis and
components if necessary.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 11


Chapter 1 About ControlLogix Redundancy Systems

Features of the The software and hardware components that are required to configure and use a
ControlLogix Redundancy ControlLogix redundancy system provide these features:
• Redundancy module speeds of up to 1000 Mbps when using a 1756-RM2
System module with another 1756-RM2 module. Redundancy module speeds up
to 100 Mbps when using a 1756-RM/A with another 1756-RM/A
module, and a 1756-RM/B module with another 1756-RM/B module.
• The 1756-RM2 and 1756-RM2XT modules are interference-free
regarding safety functions and can be used in ControlLogix SIL 2
applications. See the Using ControlLogix in SIL 2 Applications Safety
Reference Manual, publication 1756-RM001.
• Redundant fiber ports for crossloading; no single point of failure of a fiber
cable.
• Plug-and-play-style commissioning and configuration that does not
require extensive programming.
• ControlNet and EtherNet/IP network options for the redundant
chassis pair.
• Easy-to-use, fiber-optic communication cable that connects redundant
chassis pairs. Use the same cable for the 1756-RM2 or 1756-RM/B
modules.
• Simple redundant controller configuration by using a checkbox in the
Controller Properties dialog box in the Studio 5000 Automation &
Engineering Design Environment® programming software.
• A redundancy system ready to accept commands and monitor the
redundant system states after basic installation, connection, and powerup.
• Switchovers occur as fast as 20 ms.
• Support for FactoryTalk® applications for Ethernet communication
modules including, but not limited to:
– FactoryTalk Alarms and Events
– FactoryTalk Batch
– FactoryTalk PhaseManager™
• Instruction Based Alarms (IBA) considerations:
– 5560 supports up to 250 IBA's with 250 burst
– 5570 supports up to 500 IBA's with 250 burst
– For more information see the Knowledgebase Article, ALMA/ALMD
instructions limits
• Support for CIP Sync™ technology over an EtherNet/IP network to
establish time coordination across the redundant system.
• Access to remote I/O modules over an EtherNet/IP network.
• Access to 1715 Redundant I/O systems over an EtherNet/IP network.
• Ethernet socket support.
• Support for PhaseManager.
• Supports PRP topologies. See the EtherNet/IP Parallel Redundancy
Protocol Application Technique, publication ENET-AT006.
• Supports DLR and topologies. See the EtherNet/IP Device Level Ring
Application Technique, publication ENET-AT007.

12 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


About ControlLogix Redundancy Systems Chapter 1

Features Not Supported


• Any motion feature
• Any SIL 3 functional safety feature within the redundancy controllers
• Firmware Supervisor
• SequenceManager™
• Event Tasks

IMPORTANT For Ethernet modules, signed and unsigned firmware are available. Signed
modules provide the assurance that only validated firmware can be upgraded
into a module.

Signed and unsigned firmware:


• Both signed and unsigned firmware are available.
• Product is shipped with unsigned firmware. To obtain signed firmware,
you must upgrade the firmware for your product.
• To obtain signed and unsigned firmware, go to
http://www.rockwellautomation.com/global/support/firmware/
overview.page.
• Once signed firmware is installed, subsequent firmware updates must be
signed also.
There are no functional/feature differences between signed and unsigned
communication modules.

Redundancy System Communication between a redundant chassis pair that includes matching
Components components makes redundancy possible.

Each chassis in the redundant chassis pair contains these ControlLogix


components:
• One ControlLogix power supply - Required
• One ControlLogix redundancy module - Required
• Redundancy modules link the redundant chassis pair to monitor events in
each of chassis and initiate system responses as required.
• At least one ControlLogix ControlNet or EtherNet/IP communication
module - up to seven, optional (any combination)
• At least one controller - up to two controllers in the same family, optional

If the chassis is used as a redundant gateway, then a controller is not


required.

In addition, redundant chassis are connected to other components outside the


redundant chassis pair, for example, remote I/O chassis or human machine
interfaces (HMIs).

For more information about components you can use in a redundancy system, see
Chapter 2, Design a ControlLogix Redundancy System on page 21.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 13


Chapter 1 About ControlLogix Redundancy Systems

I/O Modules in Redundancy Systems

In a redundancy system, you can only use I/O modules in a remote chassis. You
cannot use I/O modules in the redundant chassis pair.

This table describes differences in network use for I/O in redundancy systems.

Remote I/O Module Placement Available with Redundancy System, Revision 19 and Later Available with Redundancy System, Revision 16 or Earlier
EtherNet/IP I/O network x -
ControlNet network x x
DeviceNet® network(1) x x
Data Highway Plus™(1) x x
Universal remote I/O(1)(2) x x
(1) In a redundancy system, you can access remote I/O modules on this network only via a ControlNet or EtherNet/IP network bridge.
(2) 1756-DHRIO module must be used with a channel configured for RIO.

For more information on how to use remote and 1715 redundant I/O over an
Ethernet network, see I/O Placement on page 36 and the Redundant I/O System
User Manual, publication 1715-UM001.

14 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


About ControlLogix Redundancy Systems Chapter 1

Redundancy System Once the redundancy modules in the redundant chassis pair are connected and
Operations powered, they determine which chassis is the primary chassis and which is the
secondary chassis.

The redundancy modules in both the primary and secondary chassis monitor
events that occur in each of the redundant chassis. If certain faults occur in the
primary chassis, the redundancy modules execute a switchover to the unfaulted,
secondary chassis.

System Qualification and Synchronization

When the redundant system is first started, the redundancy modules run checks
on the redundant chassis. These checks determine if the chassis contain the
appropriate modules and firmware to establish a redundant system. This stage of
checks is referred to as qualification.

After the redundancy modules complete qualification, synchronization can take


place. Synchronization is a state in which the redundancy modules execute these
tasks:

• Verify that the connection between redundancy modules is ready to


facilitate a switchover

• Verify that the redundant chassis continue to meet qualification


requirements

• Synchronize the data between the redundant controllers, also called


crossloading

This data is crossloaded:


– Updated tag values
– Forced values
– Online edits
– Other project information

Synchronization always takes place immediately following qualification. Also,


depending on your system configuration, synchronization takes place at the end
of each program that is run within the controller project, or at other intervals that
you specify.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 15


Chapter 1 About ControlLogix Redundancy Systems

Switchovers

During redundant system operation, if certain conditions occur on the primary


chassis, primary control is switched to the secondary chassis. These conditions
cause a switchover:

• Loss of power

• Major fault on the controller

• Removal or insertion of any module

• Failure of any module

• Damage to a ControlNet cable or tap - This event only causes a switchover


if it results in the ControlNet communication module transition to a
lonely state, that is, the module does not see any devices on the network.

• Loss of an EtherNet/IP connection - This event only causes a switchover if


it results in the EtherNet/IP communication module transition to a lonely
state, that is, the module does not see any devices on the network.

• A program-prompted command to switchover

• A command that is issued via the Redundancy Module Configuration


Tool (RMCT)

After a switchover occurs, the new primary controller continues to execute


programs, which begin with the highest-priority task that had been executing on
the previous primary controller.

For more information about how tasks execute after a switchover, see Crossloads,
Synchronization, and Switchovers on page 116.

Your application can require some programming considerations and potential


changes to accommodate a switchover. For more information on these
considerations, see Chapter 7, Program the Redundant Controller on page 111.

IMPORTANT During a switchover of the fiber channels of the 1756-RM2 module, scan
time encounters a delay of ~10 ms; however, the chassis always remains
synched.

16 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


About ControlLogix Redundancy Systems Chapter 1

Data Server Communication Recovery Time Reduction During a Switchover

Brief communication interruption occurs between FactoryTalk Linx software


and the redundant chassis pair when a switchover occurs. After the switchover is
complete, communication resumes automatically.

Data server communication recovery time is the time during a switchover from
primary to secondary, when tag data from the controller is unavailable for reading
or writing. Data server communication recovery time applies to any software that
uses tag data, such as HMI displays, data loggers, alarms systems, or historians.
Data server communication recovery time reduction is important to increase the
availability of the system.

IMPORTANT • Prior to firmware revision 30.051, the communication delays apply only
when communication is exclusively over EtherNet/IP networks.
• With firmware revision 30.051 or later, the communication delays apply to
both EtherNet/IP and ControlNet networks.

IMPORTANT FactoryTalk Linx software is part of FactoryTalk Services, which has been
releasing a series of Service Releases (SRs) that are backward compatible
with any CPR 9 products. Existing and new users who are using FactoryTalk
View version 5.0 (CPR9) or later can use the data server communication
recovery time feature.

As of revision 31.052, the communication delays over Ethernet during a


switchover event have been reduced significantly. When you configure the
connection between a FactoryTalk Linx data server, and a redundant
ControlLogix controller, you can configure redundant shortcut paths to the
primary and secondary controllers. These shortcut paths help reduce data server
communication recovery time that occurs during a redundancy switchover.

The following are required to take advantage of this:


• A dedicated pair of ControlLogix Communication Modules with
firmware revision 11.001 or later (1756-EN2TP, 1756-EN2TR,
1756-EN2T), that do not swap IP addresses. See Do Not Use IP Address
Swapping on page 66.
• ControlLogix 5570 redundancy controllers with redundancy firmware
revision 31.052 or later
• FactoryTalk Linx 6.00 with the FactoryTalk Linx patch available from
Rockwell Automation Knowledgebase Article Patch: FactoryTalk Linx
6.00 patch required to support ControlLogix V31.05 Redundancy, or later
versions of FactoryTalk Linx.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 17


Chapter 1 About ControlLogix Redundancy Systems

• Redundant ControlLogix Controller shortcut type in FactoryTalk Linx


that points to the Primary and Secondary controllers through the
communication modules, without swapping IP addresses. For information
on shortcuts in FactoryTalk Linx, see the FactoryTalk Linx Getting Results
Guide, publication LNXENT-GR001.

18 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


About ControlLogix Redundancy Systems Chapter 1

Some communication delays can occur during qualification. The existence and
duration of these delays depend on:
• Quantity and types of tags on scan in FactoryTalk Linx software
• Client screen and tag update rates (e.g. FactoryTalk Live Data/FactoryTalk
Historian)
• Number of data subscribers (i.e. FactoryTalk Alarms and Events,
FactoryTalk Batch)
• Size of the application in the redundant controller
• Controller loading, which includes the following:
• Number of tasks and scan rates (assumes no continuous task)
• Number of programs
• Memory usage
• Null task percentage available
• Network traffic

Restrictions There are restrictions that you must consider when using a redundancy system.
Most of these restrictions apply to all redundancy system revisions. Exceptions
are noted:
• See the release notes of the redundancy bundles for compatible products,
versions, and revisions
• The redundant controller program cannot contain these tasks:
– Event tasks
– Inhibited tasks
For recommendations and requirements that are related to programming
the redundant controller, see Program the Redundant Controller on
page 111.
• You cannot use the Match Project to Controller feature available in Studio
5000 Logix Designer® in a redundancy system.
• You cannot use motion in a redundant controller program.
• You cannot use SequenceManager.
• You cannot use consumed unicast connections in a redundancy system. If
you attempt to use consumed unicast connections, disqualification occurs
and qualification of an unsynchronized redundant chassis pair is not
allowed. You can use produced unicast connections that remote consumers
consume.
• Outputs controlled by specific instructions are not guaranteed to maintain
a bumpless transition during a switchover. Due to this, it is recommended
to avoid using the following instructions within a redundancy system:
– IOT
– HMIBC
• You can use a maximum of two controllers of the same family, and seven
ControlNet or EtherNet/IP communication modules in each chassis of a
redundant chassis pair.
• You can execute the tasks that were supported previously in a redundancy
system, revision 19.052 or greater.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 19


Chapter 1 About ControlLogix Redundancy Systems

This graphic shows an example ControlLogix redundancy system,


revision 19.053 or greater, which uses EtherNet/IP networks.

Figure 1 - Example ControlLogix Redundancy System using an EtherNet/IP Network

Catalyst 9300 24S Catalyst 9300 24S

NETWORK MODULE C9300-NM-2Q NETWORK MODULE C9300-NM-2Q

01 12 13 24 40G 1 40G 2 01 12 13 24 40G 1 40G 2

Catalyst 9300 24S

NETWORK MODULE C9300-NM-2Q

01 12 13 24 40G 1 40G 2

Catalyst 9300 24S

NETWORK MODULE C9300-NM-2Q

01 12 13 24 40G 1 40G 2

20 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 2

Design a ControlLogix Redundancy System

Topic Page
Redundant Chassis 21
Controllers in Redundant Chassis 22
EtherNet/IP Networks with Redundant Systems 28
ControlNet Networks with Redundant Systems 30
Other Communication Networks 34
I/O Placement 36
Using HMI 38
Optional Software 41

This chapter explains how to use the required and optional components to design
a redundancy system.

IMPORTANT There are module series level, firmware revision, and software version
requirements for redundancy systems.
For more information on these module series level, firmware revision, and
version requirements, see the current release notes at:
http://www.rockwellautomation.com/global/literature-library/
overview.page

Redundant Chassis You can use any ControlLogix® or ControlLogix-XT™ chassis in a redundant
chassis pair as long as the two chassis that are used are the same size. For example,
if the primary chassis in your redundant chassis pair uses a 1756-A4 chassis, the
secondary chassis must use a 1756-A4 chassis.

TIP When using 1756-L72, 1756-L73, 1756-L74, or 1756-L75 Redundant


controllers in your system, you must use firmware revision 19.053 or greater.
When using a 1756-L71 Redundant controller, you must use firmware
20.054 or greater.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 21


Chapter 2 Design a ControlLogix Redundancy System

Redundant Chassis Configuration Requirements

These configuration parameters must match for the components in a redundant


chassis pair during normal system operation:

• Module type

• Chassis size

• Slot placement

• Firmware revision

• Series level. See page 25

Figure 2 - Example of Redundant Chassis Pair

0 1 2 3 0 1 2 3

CH2 CH1 OK CH2 CH1 OK

1756-L64
1756-L64

Controllers in Redundant Remember these points when you place controllers in the redundant chassis pair:
Chassis • Controllers are typically included, but not required, in redundancy
systems. If you have a redundancy system without controllers, you have
only a redundant gateway rack.

• You can place up to two controllers in the same chassis. When you use two
controllers in the same chassis, they must be of the same product family.
The series of the controller in the primary and secondary chassis do not
need to match.

For example, you cannot place a ControlLogix 5560 controller and a


ControlLogix 5570 controller in the same chassis.

IMPORTANT When using a ControlLogix redundancy system, revision 16.081 or


earlier, you cannot use two 1756-L64 controllers in the same
chassis. You can, however, use a 1756-L64 controller in the same
chassis as a 1756-L61, 1756-L62, or 1756-L63 controller.

22 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

• You can use different catalog numbers from the same product family in the
same chassis. For example, you can use two ControlLogix 5560 controllers
in a chassis.

• Each ControlLogix 5560/5570 controller must have enough data memory


to store twice the amount of tag data that is associated with a redundant
controller project.

TIP ControlLogix 5580 controllers that are enabled for redundancy do not have
memory constraints.ControlLogix 5580 controllers that are enabled for
redundancy experience no reduction in memory from a standard use
ControlLogix 5580 controller.

• Each controller must have enough I/O memory to store twice the amount
of I/O memory used. To check the I/O memory that is used and available,
access the Memory tab of the Controller Properties dialog box in the
programming software.

For more information about data and I/O memory, see the
Knowledgebase Article Understanding ControlLogix Redundancy Memory
Usage.

• When you use the redundancy system update (RSU) feature to update a
redundancy system while the system continues operation, the updated
controllers must provide the same or greater memory than the existing
controllers.

This table describes the controllers to which you can upgrade, based on the
existing controller that is used, when using RSU.

Existing New Controller


1756-L61 1756-L61, 1756-L62, 1756-L63, 1756-L64, 1756-L65
1756-L62 1756-L62, 1756-L63, 1756-L64, 1756-L65
1756-L63 1756-L63, 1756-L64, 1756-L65
1756-L64 1756-L64, 1756-L65
1756-L65 1756-L65
1756-L71 1756-L71, 1756-L72, 1756-L73, 1756-L74, 1756-L75
1756-L72 1756-L72, 1756-L73, 1756-L74, 1756-L75
1756-L73 1756-L73, 1756-L74, 1756-L75
1756-L74 1756-L74, 1756-L75
1756-L75 1756-L75

Differences in controller types between chassis can exist only during the
system upgrade process. When you complete the system upgrade, the
controllers in the redundant chassis pair must match for the system to
synchronize.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 23


Chapter 2 Design a ControlLogix Redundancy System

Plan for Controller Connections

Consider these conditions when you plan controller connection use:


• ControlLogix 5560 controllers provide 250 total connections.
• ControlLogix 5570 controllers provide 500 total connections.

If you use the redundant controller at, or very near the connection limits, you can
experience difficulty synchronizing your chassis.

Redundancy Modules in Redundant Chassis


Two redundancy modules, one in each chassis of the redundant chassis pair,
jointly supervise the control system operating states and transitions, which
establishes the framework for system redundancy. This bridge between chassis
facilitates the exchange of control data and synchronization of operations.

The redundancy modules let you commission the redundant system in a plug-
and-play manner without any programming. You connect a redundancy module
pair with the default configuration in the redundant chassis pair and configure
the redundant system.

You can establish redundancy between chassis in either of these manners:

• Insert a redundancy module pair into two powered chassis that contain
redundancy-compliant components and redundancy-enabled application
programs, and then connect the redundancy modules.

• Insert and connect the redundancy modules in two chassis and then insert
redundancy-compliant components into each chassis.

IMPORTANT You are not required to develop any programming to migrate from a non-
redundant to a redundancy system if your application meets these
conditions:
• Your application meets the points that are listed in Restrictions on
page 19.
• The controller properties dialog box in your project has Redundancy
enabled.

Once the redundant chassis pair contains all desired components and is powered,
no further tasks are required in the redundancy modules to activate system
redundancy. The redundancy modules automatically determine the operational
state of each of the chassis pair and are ready to accept commands and provide
system monitoring.

24 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Communication Modules in Redundant Chassis

Remember these points when placing ControlLogix ControlNet® and


EtherNet/IP™ communication modules in the redundant chassis pair:

• You must use enhanced communication modules in redundancy systems.


Enhanced communication modules contain a ‘2’ in their catalog number.
For example, the 1756-EN2T module.

• Standard ControlNet and EtherNet/IP communication modules are not


supported. Standard communication modules contain a 'B' in their catalog
number. For example, the 1756-ENBT module.

• You can use the 1756-EN2TR module only with a redundancy system,
revision 19.052 or later.

• You can use the 1756-EN2F module only with a redundancy system,
revision 20.054 or later.

• You can use the 1756-EN2TP module only with a redundancy system,
revision 31.052 or later.

• You can use any combination of up to seven enhanced communication


modules in each redundant chassis.

• If you use a ControlNet network in your redundant chassis pair, you must
have two ControlNet communication modules outside the redundant
chassis pair. When you assign node address numbers, assign the lowest
node number address to a ControlNet communication module outside the
redundant chassis pair.

For more information, see Use at Least Four ControlNet Network Nodes
on page 30 through Assign Lowest Node Numbers to Remote ControlNet
Modules on page 31.

• You cannot use Series A ControlNet communication modules in a


redundancy system.

• The Series for EtherNet/IP communication modules is not required to


match in a partnered set. However, the firmware levels must be the same in
a partnered set. Also, if your application requires a feature specific to a
module series level, you must use the same series level for each module in a
partnered set.

For example, only the 1756-EN2T/C communication module only offers


the double-data rate (DDR) feature. You must use 1756-EN2T/C
modules in each chassis of the redundant chassis pair to use DDR.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 25


Chapter 2 Design a ControlLogix Redundancy System

• Do not use the USB ports of communication modules to access the


redundant system network while the system is running, that is, online. Use
of the USB ports while online can result in a loss of communication after a
switchover.

Plan for Communication Module Connections

A CIP™ connection is a point-to-point communication mechanism that is used


to transfer data between a producer and a consumer. These mechanisms are
examples of CIP connections:

• Logix 5000™ controller message transfer to Logix 5000 controller

• I/O or produced tag

• Program upload

• RSLinx® DDE/OPC client

• PanelView™ polling of a Logix 5000 controller

ControlLogix ControlNet communication modules provide 131 total CIP


connections. Consider these points when using CIP connections with
ControlLogix ControlNet communication modules:

• Three of the 131 CIP connections are reserved for redundancy. The three
redundant-system CIP connections always appear to be in use, even when
no connections are open.

• You can use the remaining 128 CIP connections in any manner that your
application requires, such as the examples listed previously.

ControlLogix EtherNet/IP communication modules provide 259 total CIP


connections. Consider these points when using CIP connections with
ControlLogix EtherNet/IP communication modules:

• Three of the 259 CIP connections are reserved for redundancy.

• You can use the remaining 256 connections in any manner that your
application requires, such as the examples listed previously.

26 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Power Supplies and Redundant Power Supplies in Redundancy


Systems
Redundancy systems can use standard power supplies. You can choose to use
redundant power supplies to maintain power to a ControlLogix chassis if one of
the supplies loses power. Use these hardware components to connect redundant
power supplies:

• Two redundant power supplies for each chassis

• One 1756-PSCA chassis adapter for each redundant chassis


• Two 1756-CPR cables for each redundant chassis to connect the power
supplies to the 1756-PSCA adapter

• Optional, user-supplied annunciator wiring to connect the power supplies


to remote input modules

Figure 3 - Redundant Power Supplies with Redundant Chassis

1756-PA75R or 1756-PB75R Power Supplies

Annunciator Wiring (optional)

For more information about redundant power supplies, see the ControlLogix
System Selection Guide, publication 1756-SG001.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 27


Chapter 2 Design a ControlLogix Redundancy System

EtherNet/IP Networks with The use of EtherNet/IP networks in a redundancy system is primarily dependent
Redundant Systems on your system revision.

IMPORTANT A remote chassis can be accessed over an EtherNet/IP network by using any
EtherNet/IP module that works in a non-redundant chassis with no
additional firmware requirement with the following exception. If the remote
chassis contains a controller that consumes a tag that is produced in the
redundant chassis pair, it can only consume the tag with the required
firmware revisions.

For more information on how to use an EtherNet/IP network in your


redundancy system, see Configure the EtherNet/IP Network on page 65.

Unicast Functionality

Redundancy systems support unicast produced tags. Unicast consumed tags are
not supported in redundancy systems. Unicast I/O is not supported in a
redundancy system.

Possible Communication Delays on EtherNet/IP and ControlNet


Networks
The connection between a component and the redundant chassis pair can
experience brief communication delays during a switchover. After the switchover
is complete, communication resumes automatically.

These connection types can experience the communication delay when the
switchover occurs:
• HMI to redundant chassis pair
• FactoryTalk® Batch server to redundant chassis pair
• FactoryTalk Alarms and Events Service to redundant chassis pair

IMPORTANT • Prior to firmware revision 30.051, the communication delays apply only
when communication is exclusively over EtherNet/IP networks.
• With firmware revision 30.051 or later, the communication delays apply to
both EtherNet/IP and ControlNet networks.

28 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Bridge from an EtherNet/IP Network to a ControlNet Network

Bridge from an EtherNet/IP network to a ControlNet network if you must


maintain the connection between the component and a redundant chassis pair
during a switchover.

IMPORTANT You can bridge from an EtherNet/IP network to a ControlNet network to


maintain the connection between the component and a redundant chassis
only in redundancy firmware revisions prior to revision 30.051.
I/O connections are not supported in any bridge configurations in any
version.

See Data Server Communication Recovery Time Reduction During a


Switchover on page 17.

This example graphic shows the recommended method to connect an HMI to a


redundant chassis pair if connection drops are a concern in your application. In
this graphic, the remote chassis contains I/O modules and the EtherNet/IP and
ControlNet communication modules. The I/O modules are not required and are
shown for example only. For all requirements, see ControlNet Networks with
Redundant Systems on page 30.

Figure 4 - Configuration Used to Eliminate Communication Delays on Switchover

HMI

EtherNet/IP

ControlNet

Redundant Chassis Pair

CH2 CH1 OK CH2 CH1 OK

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 29


Chapter 2 Design a ControlLogix Redundancy System

ControlNet Networks with ControlNet networks are used to connect redundant controller chassis to remote
Redundant Systems I/O and to other devices in the system.

IMPORTANT A remote chassis can be accessed over a ControlNet network that uses any
ControlNet module that works in a non-redundant chassis with no
additional firmware requirement.

ControlNet Network Requirements

If you use a ControlNet network in your redundancy system, you must


consider the following:
• Use at Least Four ControlNet Network Nodes
• Assign Lowest Node Numbers to Remote ControlNet Modules
• Set Partnered ControlNet Module Switches to the Same Address
• Reserve Consecutive Node Addresses for Partner Modules

Use at Least Four ControlNet Network Nodes

With redundant systems, at least four ControlNet network nodes are required
per ControlNet network. This configuration is required because two or more
ControlNet nodes must be used with the two ControlNet modules that are used
in the redundant chassis. One of the two nodes outside of the redundant chassis
must be at a lower node address than the ControlNet modules in the redundant
chassis.

If your ControlNet uses fewer than four nodes, and a switchover occurs,
connections can drop and outputs connected to that node can change state
during the switchover.

You can include these ControlNet modules and redundant ControlNet nodes:
• ControlNet bridges in remote chassis
• Any other ControlNet devices on the ControlNet network
• A workstation running RSLinx Classic communication software that is
connected via a ControlNet network

For more information, see Knowledgebase Article ControlNet Network Keeper


and ControlLogix Redundancy.

30 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Assign Lowest Node Numbers to Remote ControlNet Modules

Do not assign the lowest ControlNet node addresses to ControlNet modules in


the redundant chassis pair.

If you assign the lowest ControlNet node addresses to ControlNet modules in


the redundant chassis pair, you can experience these system behaviors:

• Upon a switchover, you can lose communication with I/O modules,


produced tags, and consumed tags.

• If you remove a ControlNet module from the redundant chassis, it can


result in lost communication with I/O modules, produced tags, and
consumed tags.

• If the entire system loses power, you can be required to cycle power to the
primary chassis to restore communication.

Set Partnered ControlNet Module Switches to the Same Address

Where ControlNet modules are used as partners in a redundant chassis pair, you
must set the node address switches to the same node address. The primary
ControlNet modules can be at even or odd node addresses.

For example, if partnered ControlNet modules are assigned to nodes 12 and 13


of the ControlNet network, set the node address switches of the modules to the
same address of 12.

Figure 5 - Example of Switch Address for Partnered ControlNet Modules


ControlNet Module Switches

CH2 CH1 OK CH2 CH1 OK


1756-L64
1756-L64

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 31


Chapter 2 Design a ControlLogix Redundancy System

Reserve Consecutive Node Addresses for Partner Modules

Where ControlNet modules are used as partners in redundant chassis, plan


consecutive node numbers for those partnered modules. Plan for consecutive
node addresses because the redundant system automatically assigns the
consecutive node address to the secondary ControlNet module.

For example, partnered ControlNet modules with address switches set at 12 are
assigned ControlNet node numbers 12 and 13 by the system.

TIP The primary chassis always assumes the lower of the two node
addresses.

Figure 6 - Example of Redundant ControlNet Modules at Consecutive Addresses

ControlNet Module Switches

Primary Chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK

Node 12 1756-L64 Node 13


1756-L64

32 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Redundant ControlNet Media

The use of redundant ControlNet media helps to prevent a loss of


communication if a trunkline or tap is severed or disconnected. A system that
uses redundant ControlNet media uses these components:

• 1756-CN2R, series B or later, communication modules in each redundant


chassis

• ControlNet modules that are designed for redundant media at each


ControlNet node on the network

• Redundant trunk cabling

• Redundant tap connections for each ControlNet module connected

Figure 7 - Redundant ControlNet Media with Redundant ControlLogix Chassis

Redundant ControlLogix Chassis with


1756-CN2R Modules Workstation with ControlNet
Interface Card

Redundant Trunk Lines

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 33


Chapter 2 Design a ControlLogix Redundancy System

Other Communication You can use only EtherNet/IP and ControlNet networks, and corresponding
Networks modules, in the local chassis for redundancy systems.

IMPORTANT Do not use the redundant chassis to bridge between networks. Bridging
through the redundant chassis to the same or different networks, or
routing messages through redundant chassis is not supported.

You can bridge to other communication networks outside of the redundant


chassis. You can bridge these networks via a remote chassis:
• DeviceNet
• Universal remote I/O
• Data Highway Plus™

Figure 8 - Example of Bridging to Remote I/O on Various Networks

Primary Chassis Secondary Chassis

Chassis Bridge from EtherNet/IP


to Remote I/O Networks

34 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

This table indicates what system components to use with each network that is
connected to a redundant system.

Table 1 - Communication Networks Available for Use with Redundancy Systems


Network Connection to Redundant System Component
I/O HMI
ControlNet Directly to redundant chassis Yes Yes
Via a bridge No Yes
DeviceNet Via a bridge Yes Yes
EtherNet/IP Directly to redundant chassis Yes - Redundancy System, Yes(1)
Revision 19.052 or later
Via a bridge No Yes
Universal remote I/O Via a bridge Yes Yes
Data Highway Plus Via a bridge Yes Yes
(1) Prior to redundancy firmware revision 30.051, you can connect the HMI to the redundant chassis pair via a bridge
from an EtherNet/IP network to a ControlNet network to help prevent a brief loss of communication with the
redundant chassis pair if a switchover occurs. For more information, see Possible Communication Delays on
EtherNet/IP and ControlNet Networks on page 28.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 35


Chapter 2 Design a ControlLogix Redundancy System

I/O Placement In a redundancy system, you can place I/O modules in these locations:

• Same ControlNet network as redundant controllers and communication


modules

• Same EtherNet/IP network as redundant controllers and communication


modules

• DeviceNet network that is connected via a bridge

• Universal remote I/O network that is connected via a bridge

IMPORTANT You cannot install I/O modules in the redundant chassis pair. You can only
install I/O modules in remote locations that are accessed over the networks
in this list.
You can connect to remote I/O modules over an EtherNet/IP network in a
redundancy system, revision 19.052 or later.

1715 Redundant I/O Systems

With a redundancy system revision 19.052 or greater, you can connect to 1715
Redundant I/O systems over an EtherNet/IP network.

The 1715 Redundant I/O system provides high availability and redundancy for
critical processes by using a redundant adapter pair and multiple I/O modules
that have diagnostics and are easily replaceable.

The 1715 Redundant I/O system consists of one, two-slot, adapter base unit that
houses a redundant adapter pair. The adapter base unit is connected to up to 8,
three-slot, I/O base units, which can hold up to 24 fully configurable digital and
analog I/O modules. You can configure a 1715 Redundant I/O system in a Ring
or Star topology.

Each 1715 Redundant I/O system uses one IP address as the primary IP address
for all communication. The redundant adapter pair consists of two active
modules, a primary adapter and its partner, a secondary module.

For more information about the 1715 Redundant I/O system, see the Redundant
I/O System User Manual, publication 1715-UM001.

36 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Figure 9 - Example of I/O Placement Options

Workstation

EtherNet/IP EtherNet/IP

1 2 3 4 5 6 7 8 9 10 11 12 25 26 1 4 5 10/100/1000 PoE+ 8 9 12
IN IN

13 14 15 16 17 18 19 20 21 22 23 24 27 28
Disp.
Mode OUT OUT
TOD
EIP Mod
EIP Net
Setup
GPS
TimeCD
1
2
Out
2
Speed
Duplex
PRP
DLR
PoE
GPS ANT. DIG.TimeCode ANA.TimeCode

1
3
4

Alarms PSU Express


Setup

13 16 17 100/1000 SFP 20 21 24 25 100/1000 SFP+ 28 Console Alarm

1 2 3 4 5 6 7 8 9 10 11 12 25 26 1 4 5 10/100/1000 PoE+ 8 9 12
IN IN

13 14 15 16 17 18 19 20 21 22 23 24 27 28
Disp.
Mode OUT OUT
TOD
EIP Mod
EIP Net
Setup
GPS
TimeCD
1
2
Out
2
Speed
Duplex
PRP
DLR
PoE

GPS ANT. DIG.TimeCode ANA.TimeCode


1
3
4

Alarms PSU Express


Setup

13 16 17 100/1000 SFP 20 21 24 25 100/1000 SFP+ 28 Console Alarm

EtherNet/IP Switches

Primary Chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK

EtherNet/IP

1734 POINT I/O™

Bridging Chassis
1715 Redundant I/O

1771 Chassis with ControlNet


DeviceNet Device
1771-ASB
Control Tower™

Universal remote I/O


DeviceNet

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 37


Chapter 2 Design a ControlLogix Redundancy System

Using HMI Depending on the network that is used to connect the redundant system to
HMIs, plan for certain placement and configuration requirements. You can
connect an HMI to a primary chassis over either of these networks:

• EtherNet/IP

• ControlNet

HMI Connected Via an EtherNet/IP Network


This table describes redundant system considerations specific to the HMI being
used on the EtherNet/IP network.

Type of HMI Used Considerations


PanelView Standard terminal Same as a non-redundant system.
• PanelView Plus terminal • Use FactoryTalk Linx software, version 5.0 or later.
• VersaView® industrial computer that runs • Set aside connections for each PanelView Plus or VersaView CE
the Windows CE operating system terminal as indicated in this table.

In this module Reserve


Controller 5 connections
1756-EN2T 5 connections

FactoryTalk View Site Edition software with • Use FactoryTalk Linx communication software, version 5.0 or
FactoryTalk Linx software later.
• Keep the HMI and both redundant chassis on the same subnet.
• Configure the network to use IP swapping.
• FactoryTalk View Site Edition software Limit the number of RSLinx servers that a controller uses to 1…3
with RSLinx Classic software, version 2.52 servers, where the use of one server is ideal.
or later
• RSView®32 software
• Any other HMI client software that uses
RSLinx Classic software, version 2.52 or
later

HMI connected to a redundant chassis pair exclusively over an EtherNet/IP


network can briefly drop the connection when a switchover occurs. The
connection is re-established, however, after the switchover is complete.

38 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

HMI Connected Via a ControlNet Network

This table describes redundant system considerations specific to the HMI being
used on the ControlNet network.

Type of HMI Used Considerations


• PanelView Standard terminal • If your HMI communicates via unscheduled communication, use
• PanelView 1000e or PanelView 1400e four terminals per controller.
terminal • If your HMI does not communicate via unscheduled
communication, use the number of terminals that are required
for your application.
• PanelView Plus terminal Set aside connections for each PanelView Plus or VersaView CE
• VersaView industrial computer that runs terminal.
the Windows CE operating system
In this module Reserve
Controller 5 connections
1756-CN2(1), 5 connections
1756-CN2R(1)
(1) You can use series B or later modules.

• FactoryTalk View Site Edition software Limit the number of RSLinx servers that a controller uses to 1 (ideal)
with RSLinx Classic software, version 2.52 to 3 (maximum).
or later
• RSView32 software
• Any other HMI client software that uses
RSLinx Classic software, version 2.52 or
later

For redundancy firmware revisions earlier than revision 30.051, an HMI


connected to a primary chassis exclusively over a ControlNet network or bridge
from an EtherNet/IP network to a ControlNet network maintains its
connections during a switchover.

For redundancy firmware revisions 30.051 or later, HMI connections are no


longer maintained on switchover with communications over ControlNet. After
the switchover is complete, the connection is re-established. This causes a
FactoryTalk Batch server to go to a held state.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 39


Chapter 2 Design a ControlLogix Redundancy System

Figure 10 shows an example of how to connect an HMI to a primary controller


over a ControlNet network.

Figure 10 - Connection from HMI Over a ControlNet Network

HMI

ControlNet

Redundant Chassis Pair

ControlNet CH2 CH1 OK CH2 CH1 OK

For an example of how to connect an HMI to a redundant chassis pair over a path
that bridges from an EtherNet/IP network to a ControlNet network, see
Bridge from an EtherNet/IP Network to a ControlNet Network on page 29.

40 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Design a ControlLogix Redundancy System Chapter 2

Optional Software Optional software can be needed depending on your redundancy system
program, configuration, and components. Optional software is listed in the
following table.

If using Then use this software


ControlNet network RSNetWorx™ for ControlNet
EtherNet/IP network RSNetWorx for EtherNet/IP
Alarms FactoryTalk Alarms and Events
Batches or recipes FactoryTalk Batch
HMI(1) • FactoryTalk View Site Edition
• FactoryTalk View Machine Edition
• FactoryTalk Linx software
• RSView32
Various FactoryTalk services FactoryTalk Services Platform
(1) See Using HMI on page 38 for additional information.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 41


Chapter 2 Design a ControlLogix Redundancy System

Notes:

42 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 3

Install the Redundancy System

Topic Page
Before You Begin 43
Redundancy System Quick Start 43
Install the Hardware 45
Connect the Redundancy Modules 52
Update Redundant Firmware 58
Designate the Primary and Secondary Chassis 61

Before You Begin Complete these tasks before you install the redundancy system:

• Verify that you have the components that are required to install your
system.

• Read and understand the safety and environmental considerations


explained in the installation instruction publication for each component.

• Order a 1756-RMCx fiber-optic communication cable if you do not have


one.

• If you choose to make your own fiber-optic cable for lengths that the
1756-RMCx catalog numbers do not support, refer to Fiber-optic Cable
on page 56.

Redundancy System Quick See these Quick Start steps when configuring your system for the first time.
Start 1. Review the release notes for the firmware bundle that you are installing.
Make sure that you have compatible hardware and the correct firmware
revisions.
2. Install/update the workstation software and firmware bundle.
Software applications that are needed include:
• Studio 5000 Logix Designer® application
• RSLinx® Classic communication software
• Redundancy Module Configuration Tool (RMCT). See Install the
Hardware on page 45

IMPORTANT If RSLinx Classic software is already on your system, make sure to shut it
down before installing/upgrading software.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 43


Chapter 3 Install the Redundancy System

3. To begin the hardware installation, determine the location of your


modules in the chassis of the system. Plug in the communication modules,
controller, and redundancy modules into the chassis, matching partners
slot for slot.
Install the following:
• The first chassis and power supply, see page 45.
• The first chassis communication modules.
a. Determine the IP address for your Ethernet communication modules.
Both Ethernet communication modules of the same pair have the same
IP address.
b. Set both Ethernet communication modules to the same IP address.
(This rule also applies to ControlNet® networks for node addresses.)
See Configure the EtherNet/IP Network on page 65.
• The first chassis controller.
• The first chassis redundancy module, see page 46.
• The second chassis, power supply, communication modules, controller,
and redundancy module. See page 52.
4. Plug in the fiber-optic communication cable to connect the redundancy
modules in both chassis. See Connect the Redundancy Modules on
page 52.
5. Upgrade the firmware of the redundant chassis modules. See Update
Redundant Firmware on page 58.
a. Apply power to the first chassis.
b. Launch ControlFLASH™ or ControlFLASH Plus™ software and
upgrade the firmware.
c. Upgrade the firmware of the redundancy module and verify that the
status is PRIM.
d. Update all remaining modules in the chassis using ControlFLASH or
ControlFLASH Plus software.
e. Power off the first chassis.
f. Power on the second chassis.
g. Follow the same update process as the first chassis.
h. Power off the second chassis.
6. Designate the primary chassis. See Designate the Primary and Secondary
Chassis on page 61.
a. Verify that power is removed from both chassis.
b. Apply power to the chassis you want designated as the primary. Wait for
the status indicator to display PRIM.
c. Apply power to the chassis you want designated as the secondary.

44 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Install the Hardware Follow these steps to configure and install the hardware components of your
system.

Install the First Chassis

When you install a redundancy system, install one chassis, and its necessary
components, at a time.

Module Placement and Partnering

Each pair of controllers and communication modules must be composed of


compatible partner modules. Two modules in the same slot are considered as
compatible partners only if they contain compatible hardware and firmware and
other rules that the module can enforce. Either the module in the primary chassis
or its partner in the secondary chassis determines the compatibility status
(Compatible or Incompatible).

The redundancy module pair must occupy the same slots in their respective
chassis. The redundancy module pair does not consider the chassis pair to be
partnered if the redundancy modules are placed in different slots. This outcome
is true even if the partners of other modules are present in the same slot.

The redundancy module prevents certain redundancy operations, such as


Qualification, if incompatible modules reside in the redundant-control chassis
pair.

IMPORTANT For best performance, place the redundancy module in the chassis as close
as possible to the controller.

Complete these tasks to install the first chassis in the redundant chassis pair:
• Install the Redundancy Module

TIP Do not apply power to the system until both chassis and their components
are installed.

Then follow the steps that are described in Update Redundant Firmware on
page 58 to determine when to power each chassis.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 45


Chapter 3 Install the Redundancy System

Install the Redundancy Module

You must install one redundancy module in each chassis that is planned for your
system. Available modules are as follows:
• 1756-RM2
• 1756-RM2XT
• 1756-RM/A
• 1756-RM/B
• 1756-RMXT

IMPORTANT Redundancy bundles version 24.052 and greater support only 1756-RM2 and
1756-RM2XT modules.

IMPORTANT 1756-RM2 or 1756-RM2XT modules can only be used with other


1756-RM2 or 1756-RM2XT modules. You cannot mix 1756-RM2 and
1756-RM2XT modules with 1756-RM/A, 1756-RM/B, or 1756-RMXT
modules.

Installation Requirements

Before you install the module, be sure to note the following:


• Understand redundant systems and redundant media
• Verify that the planned modules for each redundant chassis of the pair are
identical - including firmware revisions
• Verify that your redundancy firmware revision is compatible with your
planned redundant chassis modules
• The 1756-RM/B module offers a higher level of performance than a
1756-RM/A module. Both modules can coexist in a redundant system,
but the highest system performance is achieved when the 1756-RM/B
modules are used together when used with a ControlLogix® 5570
controller.
• The 1756-RM2 module, when used with a ControlLogix 5570 controller,
offers higher crossload speeds than the 1756-RM/B module.

46 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage
Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio
communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if
nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure type ratings that are required to comply with
certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional
installation requirements
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosure

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal
operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wrist strap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.

Removal and Insertion Under Power (RIUP)

WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could
cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive
wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can
affect module operation.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 47


Chapter 3 Install the Redundancy System

European Hazardous Location Approval

The following applies when the product bears the Ex Marking.


This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to
comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in
Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.

WARNING:
• This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2
environments.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• This equipment must be used only with ATEX certified Rockwell Automation backplanes.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

Safety-related Programmable Electronic Systems

ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware
of the safety requirements in the application of the system and shall be trained in using the system.

Optical Ports

ATTENTION: Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed under some
conditions, the optical port may expose the eye beyond the maximum permissible-exposure recommendations.

Small Form-factor Pluggable

WARNING: When you insert or remove the small form-factor pluggable (SFP) optical transceiver while power is on, an electrical
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

48 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

North American Hazardous Location Approval


The following information applies when operating this equipment in hazardous Informations sur l'utilisation de cet équipement en environnements
locations. dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I qu'à une utilisation en environnements de Classe I Division 2
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous Groupes A, B, C, D dangereux et non dangereux. Chaque produit
locations only. Each product is supplied with markings on the rating est livré avec des marquages sur sa plaque d'identification qui
nameplate indicating the hazardous location temperature code. When indiquent le code de température pour les environnements
combining products within a system, the most adverse temperature dangereux. Lorsque plusieurs produits sont combinés dans un
code (lowest "T" number) may be used to help determine the overall système, le code de température le plus défavorable (code de
temperature code of the system. Combinations of equipment in your température le plus faible) peut être utilisé pour déterminer le
system are subject to investigation by the local Authority Having code de température global du système. Les combinaisons
Jurisdiction at the time of installation. d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: EXPLOSION HAZARD AVERTISSEMENT: RISQUE D’EXPLOSION –
• Do not disconnect equipment unless power has • Couper le courant ou s'assurer que
been removed or the area is known to be l'environnement est classé non dangereux
nonhazardous. avant de débrancher l'équipement.
• Do not disconnect connections to this • Couper le courant ou s'assurer que
equipment unless power has been removed or l'environnement est classé non dangereux
the area is known to be nonhazardous. Secure avant de débrancher les connecteurs. Fixer
any external connections that mate to this tous les connecteurs externes reliés à cet
equipment by using screws, sliding latches, équipement à l'aide de vis, loquets
threaded connectors, or other means provided coulissants, connecteurs filetés ou autres
with this product. moyens fournis avec ce produit.
• Substitution of components may impair • La substitution de composants peut rendre
suitability for Class I, Division 2. cet équipement inadapté à une utilisation en
• If this product contains batteries, they must only environnement de Classe I, Division 2.
be changed in an area known to be • S'assurer que l'environnement est classé non
nonhazardous. dangereux avant de changer les piles.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 49


Chapter 3 Install the Redundancy System

Laser Radiation Ports

ATTENTION: Class 1 laser product. Laser radiation is present when the system is open and interlocks bypassed. Only trained and
qualified personnel are allowed to install, replace, or service this equipment.

A redundant system is composed of two ControlLogix redundancy


modules working together that supervise the operating states and state
transitions that establish the basic framework for redundancy operations.
The redundant pairs provide a bridge between chassis pairs that let other
modules exchange control data and synchronize their operations. This
illustration identifies the external features of the module.

Figure 11 - 1756-RM2 or 1756-RM2XT Modules


1756-RM2 Module Top View 1756-RM2XT Module
Top View

Front View Front View

Status Indicators Status Indicators

Side View
Side View

CH2 CH1 CH2 CH1


Backplane
Connector
Backplane
Bottom View Bottom View
Connector

SFP transceivers are pre-installed in the redundant fiber ports

50 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Figure 12 - 1756-RM/A or RM/B and 1756-RMXT Modules


1756-RM/A or 1756-RM/B Module 1756-RMXT Module
Top View Top View

Front View
Front View
Status Indicators
Status Indicators
Redundancy Module

PRI COM OK

Side View Side View

LC Single- LC Single-
mode Backplane mode
Connector Connector Connector Backplane
Connector
Bottom View Bottom View

To install the redundancy module, follow these steps.

1. Align the circuit board with top and bottom guides in the chassis.
2. Slide the module into the chassis and make sure that the module backplane
connector properly connects to the chassis backplane.

The module is properly installed when it is flush with other installed modules.

IMPORTANT To remove the module, push the locking clips at the top and bottom of each
module and slide the module out of the chassis.

IMPORTANT If you are adding redundancy to an already operational ControlLogix system,


shut off your process to install the redundancy module. The first chassis that
you install the redundancy module into and turn on, becomes the primary
chassis.
You can also have to do the following:
• Use RSNetWorx™ software to configure keeper information in the
secondary ControlNet communication module if the master keeper for
ControlNet communication is in the primary chassis
• Enable redundancy in the programming software and remove any I/O
modules from the chassis

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 51


Chapter 3 Install the Redundancy System

The first chassis and its components are now installed. Chassis power must
remain off.

Install the Second Chassis

Once the first chassis and its components are installed, you can install the second
chassis of the redundant chassis pair.

See Install the Redundancy Module on page 45 to install the second chassis.

IMPORTANT The components that are used in the first and second chassis must match
exactly for the system to synchronize.

Connect the Redundancy Once the first and second chassis and their components are installed, you
Modules connect the redundancy modules via the 1756-RMCx fiber-optic
communication cable. The cable is not included with the redundancy module.
Before installation, order this fiber-optic communication cable separately.

Redundancy cables available from Rockwell Automation include the following.


Table 2 - Fiber-optic Cable Length
Fiber Cable Cat. No. Length
1756-RMC1 1 m (3.28 ft)
1756-RMC3 3 m (9.84 ft)
1756-RMC10 10 m (32.81 ft)

IMPORTANT Longer cables can be user-made and are supported based on the optical power
budget of the system. See Fiber-optic Cable on page 56.

52 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

The cable connection is made at the bottom of the module in a downward


orientation. There is enough space between the transmit and receive connectors
so you can use the LC connector coupler. The use of this coupler keeps the fiber-
optic cable from bending so you can connect and disconnect the cable without
removing the module from the chassis.

ATTENTION: Consider these points when connecting the fiber-optic cable:


• The redundancy module communication cable contains optical fibers. Avoid
making sharp bends in the cable. Install the cable in a location where it will
not be cut, run over, abraded, or otherwise damaged.
• The redundancy module contains a single-mode transmitter. Connecting this
module to a multi-mode port will damage any multi-mode devices.
• Media redundancy is achieved by installing modules with redundant ports
and installing a redundant fiber cable system. If a cable failure occurs, or cable
is degraded, the system uses the other cable.
• When using redundant media, route the two trunk cables (A and B) so that
damage to one cable will not damage the other cable. This reduces the risk of
both cables being damaged at the same time.
• Redundant cabling can tolerate one or more faults on a single channel. If a
fault were to occur on both channels, the network operation would be
unpredictable.

ATTENTION: Under certain conditions, viewing the optical port can expose the
eye to hazard. When viewed under some conditions, the optical port can expose
the eye beyond the maximum permissible exposure recommendations.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 53


Chapter 3 Install the Redundancy System

Connect the Fiber-optic Communication Cable to Redundant


Channels
Follow this procedure to install the communication cable to redundant channels
for the 1756-RM2 module.

IMPORTANT The redundancy module communication cable contains optical fibers. Avoid
making sharp bends in the cable. Install the cable in a location where it is
not cut, run over, abraded, or otherwise damaged.

1. Remove the protective plug on the first redundancy module in the


redundant chassis pair.
2. Remove the protective caps from the cable.
3. Plug the cable connectors into the first redundancy module.

The ends must be inserted opposite each other.


4. If redundant fiber crossload cable is required, install the second fiber cable
into the remaining port.
5. Plug the first end of the fiber cable into the CH1 port on the first chassis
and plug the matching end into the matching CH1 port on the second
chassis.

Logix5563 Redundancy Module

54 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Connect the Fiber-optic Communication Cable to Single Channels

Follow this procedure to install the communication cable.

IMPORTANT The redundancy module communication cable contains optical fibers. Avoid
making sharp bends in the cable. Install the cable in a location where it is
not cut, run over, abraded, or otherwise damaged.

1. Remove the protective plug on the first redundancy module in the


redundant chassis pair.
2. Remove the protective caps from the cable.
3. Plug the cable connector into the first redundancy module.
4. Plug the remaining cable-connector end to the second redundancy
module.

Logix5563 Redundancy Module

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 55


Chapter 3 Install the Redundancy System

Fiber-optic Cable

If you choose to make your own fiber-optic cables, consider the following:
• Fiber-optic Communication Cable Specifications:

Attribute 1756-RM2 1756-RM2XT 1756-RM/A or 1756-RM/B 1756-RMXT


Temperature, 0…60 °C (32…140 °F) -25…70 °C (-13…158 °F) 0…60 °C (32…140 °F) -25…70 °C (-13…158 °F)
operating
Connector type LC-type (fiber-optic)
Cable type 8.5/125 micron single-mode fiber-optic cable
Channels 1 (transmit and receive fiber)
Length, max 10 km (10,000 m, 10936.13 yd 4 km (4000 m, 4,374.45 yd)(1)
Transmission 1000 Mbps Less than or equal to 100 Mbps
Wavelength 1310 nm 1300 nm
SFP transceiver Transceiver Rockwell Automation PN-91972 — —
Connector/cable: LC duplex connector, 1000BASE-LX-compliant
(1) Longer distances are supported based on the optical power budget of the system. See the Optical Power Budget Ranges for 1756-RM2 and 1756-RM2XT Modules on page 56.

• Determine Optical Power Budget

You can determine the maximum optical-power budget in decibels (dB)


for a fiber-optic link by computing the difference between the minimum
transmitter-output optical power (dBm avg) and the lowest receiver
sensitivity (dBm avg). As shown in Table 3 , the maximum optical power
budget for the 1756-RM2 module is -9.5 - (-19) or 9.5 dB.

The optical-power budget provides the necessary optical-signal range to


establish a working fiber-optic link. You must account for the cable lengths
and the corresponding link penalties. All penalties that affect the link
performance must be accounted for within the link optical power budget.
Table 3 - Optical Power Budget Ranges for 1756-RM2 and 1756-RM2XT Modules
Transmitter Min Typical Max Unit
Output optical power -9.5 — -3 dBm
Wavelength 1270 — 1355 nm
Receiver Min Typical Max Unit
Receiver sensitivity — — -19 dBm
Receiver overload — — -3 dbm
Input operating wavelength 1270 — 1355 nm

56 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Use Dual Fiber Ports with the 1756-RM2 Redundancy Module

The dual fiber ports of the 1756-RM2 module constitute a redundant pair of
communication channels between the partner 1756-RM2 modules in a
redundant chassis pair. One of the channels is termed as 'ACTIVE', while the
other channel is termed as 'REDUNDANT'. All data communication between
the partner redundancy modules is conducted exclusively over the ACTIVE
channel. If or when the ACTIVE channel fails, a 'Fiber Channel Switchover' is
initiated automatically and all data communication shifts to the REDUNDANT
channel, which then becomes the new ACTIVE channel.

Fiber Channel Switchover

Due to the fiber channel switchover, the redundant chassis pair remains
synchronized even after a failure of the ACTIVE channel. Any of the following
failures of the ACTIVE channel trigger an automatic fiber channel switchover to
the REDUNDANT channel, provided the REDUNDANT channel is still
operating in a normal condition:
• Signal attenuation along the fiber cable path that is routed between the
partner redundancy modules
• A broken or damaged fiber cable that is routed between the partner
redundancy modules
• Improper or loosely fit cable connector
• SFP transceiver fault
• Removal or loose connection of the SFP transceiver
• Data communication error (signaled by a failed CRC check)

Chassis synchronization is lost only when both of the channels have failed or are
disconnected.

The fiber channel switchover can occasionally extend the completion of data
communication packets between the partner redundancy modules. Therefore,
the scan time of the controller can occasionally experience a delay of 10 ms or less.

Configuration

The use of dual fiber ports is entirely ‘plug and play’. There is no user
configuration that is needed for any of the operations of the active and redundant
channels. The firmware automatically manages the selection of active and
redundant channels. The dual fiber cables between the partner redundancy
modules can be crossed over between CH1 and CH2 without any restriction.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 57


Chapter 3 Install the Redundancy System

Monitoring and Repair

Synchronization is preserved if the REDUNDANT channel has failed or is being


repaired. The repair of the REDUNDANT channel can be performed online
while the redundant chassis pair is running synchronized. To aid online repairs,
the fiber cable connections and SFP transceiver can be removed and inserted
under power.

It is not mandatory to have the REDUNDANT channel that is connected


between the two redundancy modules. The redundant chassis pair can be
synchronized with just one of the channels connected. The REDUNDANT
channel can be installed later while the chassis is running synchronized.

The status indicators on the front panel and the indicators and counters that are
displayed in the RMCT provide monitoring of the channel status.

Update Redundant Use ControlFLASH or ControlFLASH Plus software to upgrade the firmware
Firmware of each module in each chassis.

IMPORTANT Apply power ONLY to the chassis that contains modules on which you are
upgrading firmware.

IMPORTANT Redundancy module firmware that is contained in the redundancy system


firmware bundle is designed for use with the 1756-RM, 1756-RM2,
1756-RMXT, and 1756-RM2XT redundancy modules.

Upgrade the Firmware in the First Chassis

Complete these steps to upgrade the firmware in the first chassis.

1. Apply power to the chassis.

Logix5563 Redundancy Module

58 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

2. Set the mode switch on the controller to REM.

Logix 55xx

RUN FORCE SD
OK

3. Wait for the redundancy module to complete its start-up scroll messages.
Check the module’s status indicators. Wait 45 seconds before you begin
updating the 1756-RM/1756-RM2 firmware. During this time, the
redundancy module conducts internal operations to prepare for an update.

Power Supply
indicator is green. Alphanumeric Display Redundancy Module

CH2 CH1 OK
Logix5563 Redundancy Module

OK indicator is red during self-


test, and turns green if
firmware is already
downloaded.

TIP If it is a new module, wait until APPLICATION UPDATE REQUIRED is


displayed. The status indicator flashes red.

4. Launch ControlFLASH or ControlFLASH Plus software and click Next


to begin the update process.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 59


Chapter 3 Install the Redundancy System

5. Select the catalog number of the module (upgrade the redundancy module
first) and click Next.

IMPORTANT The 1756-RM2 module uses different firmware than the 1756-RM and
1756-RMXT modules.

6. Expand the network driver to locate the redundancy module or module


you are upgrading.

7. Select the module and click OK.


8. Select the firmware revision that you want to update to and click Next.
9. Click Finish.
10. On the confirmation dialog box that appears click Yes.

IMPORTANT This process can take a few minutes. The system can look like it is not doing
anything, but it is. When the update is complete, the Update Status dialog
box appears and indicates that the update has successfully completed.

11. Click OK.


12. Verify that the redundancy module status displays PRIM, which indicates
a successful upgrade.
13. Complete steps 4…12 for each module in the chassis.

IMPORTANT Power off the first chassis after you have verified a successful update of each
module.

60 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Upgrade the Firmware in the Second Chassis

Complete these steps to update the firmware for the modules in the second
chassis.

1. Apply power to the second chassis.


2. Complete steps 3…12 in section Upgrade the Firmware in the First Chassis
beginning on page 58 for the modules in the second chassis.
3. Power off the second chassis after you have verified the successful upgrade
of each module.

Designate the Primary and Power on the chassis you want to designate as the primary chassis first. After you
Secondary Chassis have applied power, qualify the system so that all module pairs are at compatible
firmware revision levels.

IMPORTANT Do not apply power to the chassis until you have read the instructions for
designating the primary chassis. Applying power to the chassis in the
correct order is crucial to designating the primary and secondary chassis.
Do not attempt to designate a primary chassis before loading in an
application image.
Before you designate the primary chassis and qualify the system, make
sure that you have the latest firmware installed.
See Update Redundant Firmware on page 58.

Complete these steps to designate the primary and secondary chassis of a


redundant pair.

1. Verify that power is removed from both chassis.


2. Apply power to the chassis you want to designate as the primary chassis
and wait for the status indicators of the module to display PRIM.
3. Apply power to the chassis you want to designate as the secondary chassis.
4. Verify primary and secondary chassis designations by viewing the module
status display and the PRI indicator.

See Redundancy Module Status Indicators on page 209 for specific


redundancy module display information.

IMPORTANT If both modules have power applied to them simultaneously, the module
with the lowest IP address is designated as the primary chassis and displays
PRIM on the four-character display of the module. In addition, the PRI status
indicator on the primary redundancy module is green. The secondary chassis
displays either DISQ or SYNC, depending on the state of the secondary
chassis. In addition, the PRI status light on the secondary redundancy
module is not illuminated.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 61


Chapter 3 Install the Redundancy System

After Designation

When you first apply power to the designated primary and secondary chassis,
compatibility checks are carried-out between the redundant chassis. Then, if the
Auto-Synchronization parameter is set at Conditional, qualification begins.

TIP While the qualification occurs, the module status display transitions from DISQ
(disqualified) to QFNG (qualifying) to SYNC (synchronized). The qualification s
complete in 1…3 minutes and then module status display indicates the
qualification status.

Use this table as a reference when interpreting the qualification status of the
modules that are displayed on the module status display.

Module Status Display Interpretation


QFNG Qualification processes are in progress.
SYNC SYNC displays after qualification processes are complete.
This indicates that chassis configuration and the firmware revision levels are
compatible and that the secondary chassis is ready to assume control if there is a
major fault in the primary chassis.
DISQ…QFNG…DISQ If DISQ continues to display after about 3 minutes, one of these anomalies exists:
• Incorrect chassis configuration. That is, incompatible hardware is used.
• Incompatible firmware revisions are used between the primary and secondary
modules.
• Keeper parameters between ControlNet module partners are not the same.
• The partnered ControlNet modules are not set to the same node address.
• The partnered EtherNet/IP modules are not set to the same IP Configuration.
• The Auto-Synchronization parameter within the Redundancy Module
Configuration Tool is set to Never or Conditional (default setting).

Conversion from a Non-redundant to a Redundant System

To upgrade the standalone chassis to a redundant chassis pair:

1. Insert a redundancy module in a spare slot in the standalone chassis, and


2. Configure an identical chassis with compatible modules in the same slot as
the standalone chassis (including the redundancy module).

A partnered chassis that is designated as the secondary chassis stops functioning if


it contains:
• non-redundancy-compliant modules;
• or, modules not compatible with Enhanced redundancy;
• or, non-redundancy-compliant firmware

For more information, see Convert from a Non-redundant System on page 219.

62 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Install the Redundancy System Chapter 3

Qualification Status Via the RMCT

To view the qualification attempt, access the Synchronization or Synchronization


Status tabs of the RMCT. These tabs provide information about qualification
attempts and redundant chassis compatibility.

For more information on how to use the RMCT, see Chapter 6, Configure the
Redundancy Modules on page 89.

Figure 13 - RMCT Synchronization Status Tab

Figure 14 - Synchronization Status Tab for Chassis Compatibility

In addition, you can view events specific to qualification in the Event Log of the
RMCT.

Figure 15 - Event Log with Qualification Events

Reset the Redundancy Module

There are two ways to reset the module.


• Cycle power to the chassis.
• Remove the module from the chassis and reinsert the module.

IMPORTANT Do not choose to cycle power to the chassis if it causes you to lose control
of your process.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 63


Chapter 3 Install the Redundancy System

Remove or Replace the Redundancy Module

To remove or replace the redundancy module, follow these steps.

1. To disengage the upper and lower module tabs, push them.


2. Slide the module out of the chassis.
3. Insert the replacement in the same slot and move the fiber cable(s) to the
new module.

IMPORTANT If you want to resume system operation with an identical module, you
must install the new module in the same slot.

64 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 4

Configure the EtherNet/IP Network

Topic Page
Requested Packet Interval 65
IP Address Swapping 66
CIP Sync 69
Produce/Consume Connections 72
Configure EtherNet/IP Communication Modules in a Redundant System 75
Use a Redundancy System with Device Level Ring 76
Use a Redundancy System with Parallel Redundancy Protocol 77

Requested Packet Interval When using revisions earlier than 20.054, the RPI for I/O connections in a
redundancy-enabled controller tree must be less than or equal to 375 ms. When
using revision 20.054 or later, the RPI can be the same as a non-redundant
chassis.

CPU Usage

Table 4 describes CPU usage for EtherNet/IP™ communication modules.


Table 4 - System Resource Utilization Table
If the CPU utilization Then
rate is
0…80% No action is required.
Important: This range is the optimal rate.
Greater than 80% • Take steps to reduce your CPU utilization. See the EtherNet/IP Network
Configuration User Manual, publication ENET-UM001.
• Adjust the requested packet interval (RPI) of your connection.
• Reduce the number of devices that are connected to your module.
Important: Your EtherNet/IP communication module can function at 100% CPU
capacity, but at or near this rate, you run the risk of CPU saturation and performance
problems.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 65


Chapter 4 Configure the EtherNet/IP Network

IP Address Swapping IP address swapping is a feature available to EtherNet/IP communication


modules in a redundancy system where a partnered set of EtherNet/IP
communication modules swap IP addresses during a switchover.

IMPORTANT You must use IP address swapping to use remote I/O and produce/consume
connections of an EtherNet/IP network.

Determine Use of IP Address Swapping

Depending on your EtherNet/IP network configuration, you can choose to use


IP address swapping between your partnered EtherNet/IP communication
modules in the event of a switchover.

If you want to Then


Minimize data server communication recovery time during switchover(1)
Do not use IP address swapping
Have your partnered EtherNet/IP communication modules on different subnets
Use Remote I/O or produce/consume.
Use IP address swapping
Have your partnered EtherNet/IP communication modules on the same subnet
(1) For more information, see Data Server Communication Recovery Time Reduction During a Switchover on page 17.

If you are using different subnets, you are responsible for programming your
system to use the address and subnet of the new primary chassis in the event of a
switchover.

Do Not Use IP Address Swapping

If you do not use IP address swapping, assign unique values for these
configuration parameters at minimum on both EtherNet/IP communication
modules in the partnered set:
• IP address

IMPORTANT The IP address cannot be of the following format between the partner
EtherNet modules: aaa.bbb.ccc.ddd & aaa.bbb.ccc.(ddd+1)

Use IP Address Swapping

If you use IP address swapping, assign the same values for these configuration
parameters on both EtherNet/IP communication modules in the partnered set:
• IP address
• Subnet mask
• Gateway address

Figure 16 shows a partnered set of EtherNet/IP communication modules during


initial configuration.

66 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

Figure 16 - IP Addresses of EtherNet/IP Communication Modules During System Configuration

Assigned IP Address: 192.168.1.3

Primary chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK

1756-L64
1756-L64

When a redundancy system begins operating, the primary EtherNet/IP


communication module uses the IP address that is assigned during initial
configuration. The secondary EtherNet/IP communication module
automatically changes its IP address to the next highest value. When a switchover
occurs, the EtherNet/IP communication modules swap IP addresses.

For example, if you assign IP address 192.168.1.3 to both EtherNet/IP


communication modules in a partnered set, on initial system operation, the
secondary EtherNet/IP communication module automatically changes its IP
address to 192.168.1.4.

Figure 17 shows a partnered set of EtherNet/IP communication modules after


system operation begins.

Figure 17 - IP Addresses of EtherNet/IP Communication Modules After System Operation Begins

IP Address: 192.168.1.3 IP Address: 192.168.1.4

Primary Chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK


1756-L64
1756-L64

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 67


Chapter 4 Configure the EtherNet/IP Network

TIP Do not assign IP addresses to EtherNet/IP communication modules outside


the partnered set to values that conflict with those values that are used in
the partnered set.
In the previous example, the partnered set uses 192.168.1.3 and
192.168.1.4. Use 192.168.1.5 or higher for all EtherNet/IP communication
modules outside the partnered set.

Figure 18 shows the partnered set of EtherNet/IP communication modules in


RSLinx® Classic software after system operation begins.

Figure 18 - IP Addresses in RSLinx Classic Software

Static Versus Dynamic IP Addresses

We recommend that you use static IP addresses on EtherNet/IP communication


modules in redundancy systems.

ATTENTION: If you use dynamic IP addresses and a power outage, or other


network failure occurs, modules that use dynamic IP addresses can be
assigned new addresses when the failure is resolved. If the IP addresses
change, your application could experience a loss of control or other serious
complications with your system.

You cannot use dynamic IP addresses with IP address swapping.

Reset the IP Address for an EtherNet/IP Communication Module


If necessary, you can reset the IP address of a 1756-EN2x communication
module to the factory default value. To return to the factory default, set the
rotary switches on the module to 888 and cycle power.

After you cycle power to the EtherNet/IP communication module, you can
either set the switches on the module to the desired address, or set the switches to
999 and use one of these methods to set the IP address:
• BOOTP-DHCP server
• RSLinx Classic communication software
• Programming software

68 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

CIP Sync With redundancy system revision 19.052 or greater, you can use CIP Sync™
technology. CIP Sync technology provides a mechanism to synchronize clocks
between controllers, I/O devices, and other automation products in your
architecture with minimal user intervention.

CIP Sync technology uses Precision Time Protocol (PTP) to establish a Master/
Slave relationship among the clocks for each CIP Sync-enabled component in
the system. One master clock, which is known as the Grandmaster, sets the clock
to which all other devices on the network synchronize their clocks.

IMPORTANT Before you use this enhancement in a redundancy system, revision 19.052 or
later, see these publications for a full understanding of CIP Sync technology
in any system:
• Integrated Architecture™ and CIP Sync Configuration Application
Technique, publication IA-AT003
• ControlLogix® System User Manual, publication 1756-UM001

Consider these points when you use CIP Sync technology in a redundancy
system, revision 19.052 or later:

• If you enable CIP Sync Time Synchronization in the controllers in a


redundant chassis pair, you must also enable Time Synchronization in the
EtherNet/IP communication modules in the redundant chassis pair so all
devices have one path to the Grandmaster. To enable Time
Synchronization in the EtherNet/IP communication modules, change the
Time Sync Connection from None (default) to Time Sync and Motion.

If time synchronization is enabled in any controller in the primary chassis


of a disqualified redundant chassis pair, and no other devices in the
primary chassis have time synchronization enabled, the redundant chassis
pair attempts to qualify. However, in these application conditions, the
attempt to qualify fails.

• While CIP Sync technology can handle multiple paths between master
and slave clocks, it resolves mastership most effectively if you configure the
redundant paths so that Time Synchronization is enabled in only the
minimum required number of EtherNet/IP communication modules.

For example, if your redundant chassis pair has three 1756-EN2T


communication modules and all are connected to the same network,
enable Time Synchronization in only one of the modules.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 69


Chapter 4 Configure the EtherNet/IP Network

• If the primary controller is the Grandmaster, the redundancy system


automatically manages the CIP Sync clock attributes so that the controller
in the primary chassis is always set to be the Grandmaster instead of the
secondary controller. This clock management makes sure of a change to a
new Grandmaster when the redundancy system switches over.

• When a switchover occurs, these events take place:

– The Grandmaster status transfers from the original primary controller


to the new primary controller. This transfer can take longer to
complete than if Grandmaster status was transferred between devices
in a non-redundant system.
– After the switchover is complete, system synchronization can take
longer in a redundancy system, revision 19.052 or later, which uses
CIP™ technology than one that does not.

• If you attempt to use the Redundant System Update (RSU) feature to


update a redundancy system, revision 16.081 or earlier, which uses
Coordinated System Time (CST), the redundancy system, revision
19.052 or later, does not permit a locked switchover and the update fails to
complete.

To work around this restriction, first disable CST Mastership in the


original redundancy system and then use RSU to update the redundancy
system to revision 19.052 or later.

Figure 19 on page 71 shows an example redundancy system, revision 19.052 or


later, that uses CIP Sync technology.

70 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

Figure 19 - Redundancy System, Revision 19.052 or greater, Using CIP Sync Technology

Supervisory

Stratix® 5700 Stratix 5700

EtherNet
CIP Sync
CIP Sync
M S S M
Primary Chassis Secondary Chassis

P1 P1
G M S

Fiber Optic Cable

CIP Sync EtherNet CIP Sync

CIP Sync
CIP Sync
CIP Sync CIP Sync
S M M S S S

P2
S S
S S

CIP Sync
CIP Sync CIP Sync
CIP Sync
CIP Sync M S S S

G = Grandmaster (time source) S


M = Master
S = Slave
P1 and P2 = Priorities
CIP Sync CIP Sync

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 71


Chapter 4 Configure the EtherNet/IP Network

Produce/Consume With redundancy system revision 19.052 or later, you can use produce/consume
Connections connections over an EtherNet/IP network. Controllers let you produce
(broadcast) and consume (receive) system-shared tags.

IMPORTANT Sockets are supported in the 1756-EN2T, 1756-EN2TR and 1756-EN2F


modules, firmware revision 5.008 or later. For additional information, see
the EtherNet/IP Socket Interface Application Technique,
publication ENET-AT002.

IMPORTANT Unicast functionality in redundancy systems supports produced tags.


Unicast consumed tags are not supported.

TIP When using ControlLogix 5570 controllers in your system, you must use
revision 19.053 or greater.

Figure 20 - Example System Using Produced and Consumed Tags

Primary Chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK


1756-L64

1756-L64

Controller 1
Produced Tag
1756-L64

Controller 2
Consumed Tag

These requirements exist when you use produced and consumed connections
over an EtherNet/IP network in a redundancy system, revision 19.052 or
greater:
• You cannot bridge produced and consumed tags over two networks. For
two controllers to share produced or consumed tags, both must be
attached to the same network.
• Produced and consumed tags use connections in both the controllers and
the communication modules being used.

72 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

• Because the use of produced and consumed tags uses connections, the
number of connections available for other tasks, such as the exchange of
I/O data, is reduced.
The number of connections available in a system depends on controller
type and network communication modules used. Closely track the
number of produced and consumed connections to leave as many as
necessary for other system tasks.

• Produced and consumed tags must be configured in both the producing


controller and the consuming controller. Produced tags in a redundant
ControlLogix controller can be configured as either multicast or unicast.
Consumed tags by a redundant ControlLogix controller must be
configured as multicast in the producing controller.

• When you add an Ethernet module for the redundancy chassis to the I/O
tree of a remote consuming controller, change the Connection setting
from Rack Optimized to None. If this setting is not changed the
configured connection can briefly drop during a switchover.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 73


Chapter 4 Configure the EtherNet/IP Network

Produced/Consumed Tags between Primary Controllers and Nonredundant Controllers

The connection from the remote controller to the redundant controller can
briefly drop during a switchover. This condition can occur if the EtherNet/IP
communication modules of the remote chassis do not use specific firmware
revisions. The controllers in the redundant chassis pair must also produce tags
over the EtherNet/IP network that the controllers in the remote chassis consume.

Use these firmware revisions for EtherNet/IP communication modules in the


remote chassis to maintain connections during a switchover.

Table 5 - Minimum Firmware Revision for Communication Modules in Remote Chassis


Communication Module in Remote Chassis Minimum Firmware Revision
1756-EN2F 5.008 (unsigned)
5.028 (signed)
1756-EN2T
4.002
1756-EN2TR
1756-EN3TR
1756-EN4TR
1756-ENBT 6.001
1768-ENBT 4.001
1769-L2x
19.011
1769-L3xE
1788-ENBT 3.001
CompactLogix 5380 controllers
28.011
ControlLogix 5580 controllers
CompactLogix 5480 controllers 32.012

IMPORTANT The minimum firmware revisions that are listed in Table 5 apply only to
EtherNet/IP communication modules in the remote chassis.
In a redundant chassis pair, you can use only the ControlLogix modules that are
listed in the respective bundle's release notes

74 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

Configure EtherNet/IP Use these procedures to configure EtherNet/IP communication modules that
Communication Modules in are used in redundant chassis.

a Redundant System
Before You Begin

Before you begin configuring the EtherNet/IP communication modules in the


redundant chassis, verify that these tasks have been completed:
• The redundancy modules are installed and connected in the redundant
chassis.
• A plan for IP address use has been executed:
– If you are using IP address swapping, plan for the use of two
consecutive IP addresses in the partnered set.
– If you are not using IP address swapping, plan for the use of two IP
addresses.
• Know the subnet mask and gateway address for the Ethernet network the
redundant modules are to operate on.

Options for Setting the IP Addresses of EtherNet/IP Communication


Modules

By default, ControlLogix EtherNet/IP communication modules ship with the IP


address set to 999 and with Bootstrap Protocol (BOOTP)/Dynamic Host
Configuration Protocol (DHCP)-enabled.

Use one of these tools to set the IP addresses for your EtherNet/IP
communication modules:
• Rotary switches on the module
• RSLinx Classic communication software
• Programming software
• BOOTP/DHCP utility

Half/Full Duplex Settings

The redundancy system uses the duplex settings of the EtherNet/IP


communication module that is the primary. After a switchover, the duplex
settings of the new primary EtherNet/IP communication module are used. By
default, the duplex setting is automatic. We recommend that you use this setting
whenever possible.

To avoid communication errors, configure both the primary and secondary


EtherNet/IP communication modules with the same duplex settings. If you use
different duplex settings on partnered EtherNet/IP communication modules,
then messaging errors can occur after a switchover.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 75


Chapter 4 Configure the EtherNet/IP Network

Use a Redundancy System Device Level Ring (DLR) is an EtherNet/IP protocol defined by ODVA, Inc.
with Device Level Ring DLR provides a means for detecting, managing, and recovering from single faults
in a ring-based network.

A DLR network includes the following types of ring nodes.

Node Description
Ring supervisor A ring supervisor provides these functions:
• Manages traffic on the DLR network
• Collects diagnostic information for the network
A DLR network requires at least one node to be configured as ring supervisor.
IMPORTANT: By default, the supervisor function is disabled on supervisor-capable
devices, so they are ready to participate on a linear or star network or as a ring node on a
DLR network.
In a DLR network, you must configure at least one of the supervisor-capable devices as
the ring supervisor before physically connecting the ring. If you do not, the DLR network
does not work.
We recommend to assign at least one supervisor outside of the redundant chassis pair to
prevent losing supervision of the DLR during switchover.
For more information on DLR operation see the EtherNet/IP Device Level Ring
Application Technique, publication ENET-AT007.
Ring participants Ring participants provide these functions:
• Process data that is transmitted over the network.
• Pass on the data to the next node on the network.
• Report fault locations to the active ring supervisor.
When a fault occurs on the DLR network, ring participants reconfigure themselves and
relearn the network topology.
Redundant gateways Redundant gateways are multiple switches connected to a single DLR network and also
(optional) connected together through the rest of the network.
Redundant gateways provide DLR network resiliency to the rest of the network.

Depending on their firmware capabilities, both devices and switches can operate
as supervisors or ring nodes on a DLR network. Only switches can operate as
redundant gateways.

For more information about DLR, see the EtherNet/IP Device Level Ring
Application Technique, publication ENET-AT007.

76 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the EtherNet/IP Network Chapter 4

Use a Redundancy System Parallel Redundancy Protocol (PRP) is defined in international standard
with Parallel Redundancy IEC 62439-3 and provides high-availability in Ethernet networks. PRP
technology creates seamless redundancy by sending duplicate frames to two
Protocol independent network infrastructures, which are known as LAN A and LAN B.

A PRP network includes the following components.

Component Description
LAN A and LAN B Redundant, active Ethernet networks that operate in parallel.
Double attached node (DAN) An end device with PRP technology that connects to both LAN A and LAN B.
Single attached node (SAN) An end device without PRP technology that connects to either LAN A or LAN B.
A SAN does not have PRP redundancy.
Redundancy box (RedBox) A switch with PRP technology that connects devices without PRP technology to
both LAN A and LAN B.
Virtual double attached node An end device without PRP technology that connects to both LAN A and LAN B
(VDAN) through a RedBox.
A VDAN has PRP redundancy and appears to other nodes in the network as a DAN.
Infrastructure switch A switch that connects to either LAN A or LAN B and is not configured as a RedBox.

For more information about PRP topologies and configuration guidelines, see
the EtherNet/IP Parallel Redundancy Protocol Application Technique,
publication ENET-AT006.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 77


Chapter 4 Configure the EtherNet/IP Network

Notes:

78 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 5

Configure the ControlNet Network

Topic Page
Produce/Consume Connections 79
Network Update Time 81
Scheduled or Unscheduled Network 83
Schedule a New Network 84
Update an Existing Scheduled Network 87
Check the Network Keeper States 88

Produce/Consume You can use produce/consume connections over a ControlNet® network.


Connections Controllers let you produce (broadcast) and consume (receive) system-shared
tags.

Figure 21 - Example System Using Produced and Consumed Tags


Primary chassis Secondary Chassis

CH2 CH1 OK CH2 CH1 OK

Controller 1
Produced Tag

Controller 2
Consumed Tag

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 79


Chapter 5 Configure the ControlNet Network

Keep these points in mind when you use produced and consumed connections
over a ControlNet network in a redundancy system:

• During a switchover, the connection for tags that are consumed from a
redundant controller can drop briefly.

– The data does not update.


– The logic acts on the last data that it received.

After the switchover, the connection is re-established and the data begins
to update again.

• You cannot bridge produced and consumed tags over two networks. For
two controllers to share produced or consumed tags, both must be
attached to the same network.

• Produced and consumed tags use connections in both the controllers and
the communication modules being used.

• Because the use of produced and consumed tags uses connections, the
number of connections available for other tasks, such as the exchange of
I/O data, is reduced.

The number of connections available in a system depends on controller


type and network communication modules used. Closely track the
number of produced and consumed connections to leave as many as
necessary for other system tasks.

80 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the ControlNet Network Chapter 5

Network Update Time The network update time (NUT) that you specify for your redundant system
affects your system performance and your switchover response time. Typical
NUTs used with redundant systems range from 5…10 ms.

NUTs with Multiple ControlNet Networks

You can choose to use multiple ControlNet networks with your redundancy
system.

Figure 22 - Example of Two ControlNet Networks

CH2 CH1 OK CH2 CH1 OK

Redundant Chassis Pair


1756-L63

1756-L63
ControlNet Network 1
NUT = 5 ms
ControlNet Network 2
NUT =  21 ms

When you use multiple ControlNet networks, the networks must use compatible
NUTs. Compatible NUTs are determined based on the network that uses the
smallest NUT.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 81


Chapter 5 Configure the ControlNet Network

Use Table 6 to determine the compatible NUTs for your system.


Table 6 - Compatible NUT Values for Multiple ControlNet Networks
If the smallest NUT of a Then the largest NUT of any other network must be less
network is (ms) than or equal to (ms)
2 15
3 17
4 19
5 21
6 23
7 25
8 27
9 29
10 31
11 33
12 35
13 37
14 39
15 41
16 43
17 46
18 48
19 50
20 52
21 55
22 57
23 59
24 62
25 64
26 66
27 68
28 71
29 73
30 75
31 78
32 80
33 82
34 84
35 87
36 89
37…90 90

82 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the ControlNet Network Chapter 5

Scheduled or Unscheduled It is up to you to if you want to use a scheduled or unscheduled network.


Network
Use a Scheduled Network
Schedule or reschedule your ControlNet network when you execute these tasks:

• Commission a new redundant system.

• Add a chassis of remote ControlLogix® I/O that is set to use the


Rack Optimized communication format.

• Add any remote I/O besides ControlLogix I/O. For example, if you add
FLEX™ I/O modules, you must schedule the network.

• Use produced/consumed data. If you add a produced/consumed data tag,


you must reschedule the ControlNet network.

To schedule or reschedule your ControlNet network, you put your redundant


system in Program mode.

Use an Unscheduled Network

You can use an unscheduled network when you:

• Add a remote I/O chassis of ControlLogix I/O that does not use the
Rack Optimized communication format. That is, direct connections to
the I/O are used.

• Add a ControlLogix I/O module to a chassis that has already been


scheduled and uses the Rack Optimized communication format.

• Add some drives that support adding I/O while online.

• Use ControlNet to monitor HMI or the controller program execution


online.

You can add those components to the unscheduled network while your
redundant system is online and in Run mode. We recommend that you do not
use an unscheduled network for all of your I/O connections.

The use of 1756-CN2, 1756-CN2R, and 1756-CN2RXT modules provide


increased capacity for adding I/O while online compared to 1756-CNB or
1756-CNBR modules. With this increased capacity, you can easily add I/O and
increase ControlNet connections that are used without affecting your redundant
system performance.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 83


Chapter 5 Configure the ControlNet Network

Add Remote ControlNet Modules While Online

If you are adding a remote I/O chassis that is composed of a ControlLogix


ControlNet module and ControlLogix I/O while your redundant system is
running (online), make these considerations:

• Do not use Rack Optimized communication formats. The ControlNet


module and I/O must be configured for direct connections.

• For each remote I/O module used, plan for one direct connection to be
used.

Schedule a New Network Complete these steps to schedule a new ControlNet network for a redundancy
system.

IMPORTANT Before you schedule a ControlNet network, turn on the power to both
redundant chassis.
If you schedule a ControlNet network while the secondary chassis is off,
the keeper signature of a 1756-CN2 or 1756-CN2R module can mismatch
its partner. This action can cause the secondary chassis to fail to
synchronize.

1. Turn on the power to each chassis.


2. Start RSNetWorx™ for ControlNet software.
3. From the File menu, choose New.
4. At the New File dialog box, choose a configuration type.
This example uses ControlNet Configuration.

5. From the Network menu, choose Online.


6. Select your ControlNet network and click OK.

84 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the ControlNet Network Chapter 5

7. From the Network menu, choose Enable Edits.

8. From the Network menu, choose Properties.


9. In the Network Parameters tab, enter the parameters that are appropriate
for your system.

Parameter Specify
Network Update Time (ms) The minimum repetitive interval when data is sent over the ControlNet
network.
Max Scheduled Address The highest node number that uses scheduled communication on the
network.
Max Unscheduled Address The highest node number that you use on the network.
Media Redundancy The ControlNet channels that you are using.
Network Name A name for identifying the ControlNet network.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 85


Chapter 5 Configure the ControlNet Network

10. On the Media Configuration tab, add repeaters, fiber, and coax to
accurately represent your the worse case path between any two ControlNet
nodes.

If the media configuration does not accurately represent the maximum


propagation delay between any two nodes, your network may experience
errors.

11. Click Apply.


12. Click OK.
13. From the Network menu, choose Single Pass Browse.
14. From the File menu, choose Save.
15. Type a name for the file that stores the network configuration, then
click Save.
16. Click Optimize and rewrite Schedule for all Connections (default) and
click OK.

You have finished scheduling your new ControlNet network.

86 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the ControlNet Network Chapter 5

Update an Existing If you are adding the redundant chassis to an existing ControlLogix system that
Scheduled Network uses a ControlNet network, complete these steps to update the existing
ControlNet network.

1. Turn on the power to each chassis.


2. Start RSNetWorx for ControlNet software.
3. From the File menu, choose Open.
4. Select the file for the network and click Open.
5. From the Network menu, choose Online.
6. From the Network menu, choose Enable Edits.

7. From the Network menu, choose Properties.


8. In the Network Parameters tab, update the parameters specific to your
system.

9. Click OK.
10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 87


Chapter 5 Configure the ControlNet Network

12. Click Optimize and rewrite schedule for all connections and click OK.

13. Click OK.

You have completed updating your scheduled ControlNet network.

Check the Network Keeper After you schedule your ControlNet network, check the states of keeper-capable
States nodes. Checking the status of keeper-capable nodes is important because if a
major network disruption occurs, the keepers provide network configuration
parameters that are required to recover.

For more information about keepers and their function in a ControlNet


network, see the ControlNet Network Configuration User Manual,
publication CNET-UM001.

To check the status of keepers on the ControlNet network, complete these steps.

1. In RSNetWorx for ControlNet software, from the Network menu choose


Keeper Status.

2. Verify that one keeper-capable device outside the redundant chassis is


indicated as active and valid.

88 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the ControlNet Network Chapter 5

3. Verify that all keeper-capable devices on the network are valid.

Active and valid keeper


device.

Keeper-capable devices are valid.

4. Verify that all nodes on the network have the same keeper signature.

Keeper signatures are the same.

TIP If the keeper signatures of partnered ControlNet modules are different,


your redundant chassis can fail to synchronize.
If the keeper signatures of your partnered ControlNet modules are
different, update the keepers of the redundant ControlNet modules.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 89


Chapter 5 Configure the ControlNet Network

Save the Project for Each Primary Controller

After you have scheduled your ControlNet networks, go online with each
controller in your primary chassis, and upload and save the project. This process
makes downloading a project easier in the future because you won’t be required
to reschedule the network after completing the download.

Automatic Keeper Crossloads


The 1756-CN2, 1756-CN2R, and 1756-CN2RXT ControlNet modules have
an Automatic Keeper Crossload feature that makes replacing a ControlNet
module in a redundant chassis easier. The Automatic Keeper Crossload feature
also reduces the need to use RSNetWorx for ControlNet software once the
system is running.

With the Automatic Keeper Crossload feature, ControlNet modules can


automatically upload the keeper signature and network parameters from the
active keeper of a ControlNet network.

To replace a ControlNet module that has been configured and scheduled on the
ControlNet network, remove the existing module and insert a
1756-CN2, 1756-CN2R, or 1756-CN2RXT module. The module that you are
inserting must be unconfigured or have a keeper signature of all zeros.

TIP To clear the keeper signature of a 1756-CN2, 1756-CN2R, or


1756-CN2RXT module, complete these steps.

1. Disconnect the module from the ControlNet network and remove it


from the chassis.
2. Set the node address switches to 00.
3. Insert the module back into the chassis and wait for the status
display to indicate Reset Complete.
4. Remove the module and set the node address switches to the
intended node address.
5. Insert the module into the chassis.

After being inserted and connected to the ControlNet network, the


unconfigured 1756-CN2, 1756-CN2R, and 1756-CN2RXT modules crossload
the appropriate configuration from the active keeper on the ControlNet
network. The modules then become configured with the appropriate keeper
signature.

90 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 6

Configure the Redundancy Modules

Topic Page
About the Redundancy Module Configuration Tool (RMCT) 91
Determine If Further Configuration Is Required 92
Use the RMCT 93
Module Info Tab 96
Configuration Tab 98
Synchronization Tab 101
Synchronization Status Tab 104
System Update Tab 105

About the Redundancy The Redundancy Module Configuration Tool (RMCT) is used to configure the
Module Configuration Tool redundancy modules and to determine the status of the redundancy system.

(RMCT) Use the RMCT to complete these configuration-related tasks:


• Set Auto-Synchronization parameters.
• Set the time and date of redundancy modules.
• View and set module information.
• View and set Chassis ID parameters (Chassis A, Chassis B).
• Lock the redundant system for an update.
• Conduct a test switchover.

You can also use this functionality available with the RMCT to determine the
status of the redundant system:
• View error diagnostics specific to redundant chassis.
• View qualification and compatibility status of partnered modules.
• Identify noncompliant modules for removal.
• View redundant system event history.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 91


Chapter 6 Configure the Redundancy Modules

Determine If Further The default configuration of the redundancy modules lets you synchronize your
Configuration Is Required redundant chassis without additional configuration if you are using a basic
redundant chassis pair.

However, some applications and uses of the redundancy system can require
additional configuration. For example, you must use the RMCT for additional
configuration if you must complete any of these tasks:
• Set the redundancy modules to a different time or date (recommended).

TIP If you set the time and date of a redundancy module per the workstation time
and date, it can be helpful in analyzing redundancy logs in the future.

• Program your controller to control the redundant system.


• Change the redundancy synchronization options of the redundant system.
• Change the synchronization states of your redundant chassis.
• Conduct a test switchover.
• Complete a firmware update of a module in the redundant chassis while
the system is online.

If you must complete any of these tasks, see the sections that follow.

92 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Use the RMCT To access and begin using the RMCT, launch RSLinx® Classic software and
browse to your redundancy module. Right-click the redundancy module and
choose Module Configuration.

TIP If you cannot see the Module Configuration option in the list, then the
compatible version of the RMCT is not installed.

When you access the RMCT, the dialog box always indicates the status of the
redundancy chassis in the bottom-left corner.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 93


Chapter 6 Configure the Redundancy Modules

Identify the RMCT Version

You must use a version of the RMCT that is compatible with your redundancy
module firmware.

Beginning with version 20.054, the redundancy module firmware reports back to
the Redundancy Module Configuration Tool (RMCT) as to which version of
the RMCT is compatible. If there is an incompatibility, the RMCT shows only
the Module Info tab and indicates the version that the firmware is compatible
with.

For more information on the RMCT compatibility, see Knowledgebase Article


Redundancy Module Configuration Tool (RMCT).

To find the latest firmware bundle on the website, follow these steps.

1. The Redundancy Module Configuration Tool (RMCT) can be


downloaded from the Product Compatibility and Download Center
under the Firmware Downloads.
2. Search by the redundancy bundle used with your system to locate the
proper RMCT. The bundle is named by the firmware that is on the
processor in the redundancy system.
3. Depending on the version of the bundle, the RMCT may be included with
the firmware bundle or separate:

94 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Complete these steps to check or verify the version of the Redundancy Module
Configuration Tool (RMCT) that you have installed.

TIP The RMCT launches at the version that is compatible with the 1756
redundancy module firmware that is installed.
If you have not updated your 1756 redundancy module firmware after
upgrading your RMCT version, the RMCT version that is indicated can
differ from version you updated to. You can also check the RMCT version
that you have installed by using Add or Remove Programs in the Control
Panel.

1. Launch RSLinx Classic software.


2. Click the RSWho icon.

3. Right-click your redundancy module and choose Module Configuration.

The Module Configuration dialog box opens.


4. Right-click the title bar and choose About.

The About dialog box opens and indicates the RMCT version.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 95


Chapter 6 Configure the Redundancy Modules

This should show the version you need based on your bundle or higher.
The RMCT always shows the latest version installed, and later versions are
backwards compatible with earlier versions.

Update the RMCT Version

The RMCT version that is compatible with your redundancy module firmware is
included in the downloads for most redundancy bundles.
• For redundancy bundles that use firmware revision 20.009 or later for
1756-RM2 modules, the RMCT is included in the redundancy bundle
and is not available for separate download.
• For redundancy bundles that use firmware revision earlier than 20.009,
you can download the RMCT separately as a product add-on.

To launch the installation of the RMCT, open the folder that contains the
redundancy firmware revision and double-click the executable file titled
Redundancy_Module_CT.exe.

The RMCT Installation Wizard opens and prompts you with the steps to install
the RMCT.

Module Info Tab The Module Info tab of the RMCT provides a general overview of the
identification and status information of the redundancy module. This status
information is updated approximately once every two seconds.

TIP Not all indicators are shown for 1756-RM/A and 1756-RM/B modules.

96 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

These parameters are indicated in the Module Info tab.

Table 7 - Module Info Tab - Parameters Indicated


Parameter Description
Vendor Name of the vendor of the redundancy module.
Product Type General product type of the redundancy module.
Product Code CIP™ product code for the redundancy module.
Revision Major and minor revision information for the redundancy module.
Redundancy Module Serial Serial number of the redundancy module.
Number
Product Name Predefined catalog name of the redundancy module.
General Status General state of the redundancy module. Possible values include Startup, Load,
Fault, and OK.
Major Fault The major fault status of a redundancy module. When a major fault is detected,
the system does not provide redundancy support.
Minor Fault The minor fault status of a redundancy module. When a minor fault is detected,
the system continues to provide redundancy support.
Error Code Error code that is related to the fault if one exists.
Error Message Text-based message that describes the error if a fault exists.
Recovery Message Text-based message that indicates the recovery from a fault.
Total Indicates the number of channel switchovers that have occurred from CH1 to CH2
and vice versa on the module since its last powerup. It is reset to 0 automatically
by firmware on a power cycle.
Periodic Indicates the number of switchovers that have occurred between CH1 and CH2
over the last 10-second interval. The counter is constantly updated to reflect the
value that is recorded at every 10-second interval. The counter is automatically
reset to 0 on a power cycle.
Max Periodic Switchovers The maximum number that is recorded in the Periodic counter. The time of the
update is recorded every time that the counter is updated. The counter is
automatically reset to 0 on a power cycle and can also be reset by clicking the
Reset button.(1)
CH1 Status Fiber Channel 1 status.
The status shows the operating condition of the respective fiber channels in terms
of one of the following values:
– Unknown - Operating state is not yet determined
– Active - Channel is operating normally as the ACTIVE channel
– Redundant - Channel is operating normally as the REDUNDANT channel
– Link Down - Channel is disconnected. Causes can be: the cable is
disconnected/broken/damaged; signal is attenuated, connector is loose,
the partner 1756-RM2 module is power down or in a major fault state
– No SFP - No transceiver was detected, it has failed, it is loosely connected, it
is not installed
– SFP !Cpt - Transceiver is not a Rockwell Automation supported unit
– SFP Fail - Transceiver is in a failed state
CH2 Status Fiber Channel 2 status. See CH1 Status on page 97.
Chassis Platform Configuration Indicates configuration (version 19.05x and later always displays ‘enhanced’).
(1) The Periodic counters can be used to identify a burst of switchovers that can take place due to intermittent channel failures
within a few seconds. The recorded time can be helpful to correlate the switchover occurrences with any external failures that
have occurred on the fiber cables.

In addition, you can click Change to edit the User-Defined Identity parameters
to meet your application needs.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 97


Chapter 6 Configure the Redundancy Modules

Configuration Tab Use the Configuration tab to set redundancy options and the internal clock of
the redundancy module. After you modify a parameter, the Apply Workstation
Time button becomes active.

98 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Auto-synchronization

The first parameter in the Configuration tab is the Auto-Synchronization


parameter. The value that you chose for this parameter determines a significant
part of your redundant system behavior.

TIP Verify that your Auto-Synchronization parameter is at the proper value


before you modify your redundant system. This verification helps
prevent system errors.
For example, if you are upgrading your redundant system firmware,
verify that this parameter is set to Never or Conditional before
disqualifying your secondary chassis. If this parameter is Always, you
cannot properly disqualify your chassis and conduct the update.

Use the following table to determine the Auto-Synchronization setting that best
suits your application.

If you use this parameter This synchronization behavior results


Never The system remains in the same state, that is, either synchronized or
disqualified, until one of these events takes place:
• A command is issued from the RMCT to either synchronize or disqualify.
• The controller commands synchronization or disqualification by using a
MSG instruction. For this action to occur, Enable User Program Control must
be checked.
• A fault on the primary causes a switchover.
Always The system automatically synchronizes regularly.
If you attempt to disqualify the system by using the Disqualify Secondary
command in the RMCT, the resulting disqualification is temporary as the
system automatically qualifies and synchronizes again.
If the controller program disqualifies the system, the resulting disqualification
is also temporary.
Conditional The system behavior with this setting is dependent on the Auto-
Synchronization state of your system, found in the lower left portion of the
RMCT window after setting the Auto-Synchronization parameter to
Conditional:
• If your Auto-Synchronization parameter is set to Conditional and your
Auto-Synchronization state is 'Conditional, Enabled', then the system
continually attempts to synchronize.
• If your Auto-Synchronization parameter is set to Conditional and your
Auto-Synchronization state is 'Conditional, Disabled', then the system does
not automatically attempt to synchronize.
To change from 'Conditional, Enabled' to 'Conditional, Disabled', click
Disqualify Secondary on the Synchronization tab.
To change from 'Conditional, Disabled' to 'Conditional, Enabled', click
Synchronize Secondary on the Synchronization tab.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 99


Chapter 6 Configure the Redundancy Modules

Chassis ID

The chassis ID parameter is used to assign a generic label to the chassis that house
the redundancy modules. The available chassis labels are Chassis A and Chassis B.

If you change the chassis label in the RMCT of the primary redundancy module,
the secondary module and chassis are automatically assigned the other chassis
label.

The chassis label that is assigned to the module remains associated with the same
physical chassis, regardless of its primary or secondary control designation.

Enable User Program Control

Check Enable User Program Control in the Configuration tab if you plan to use
MSG instructions in your controller program to initiate a switchover, change the
redundancy module time, or synchronize.

If you leave Enable User Program Control unchecked, the redundancy modules
do not accept any commands from the controller.

Redundancy Module Date and Time

The Redundancy Module Date and Time parameters can be applied separate
from the Redundancy Module Options parameters. The time that is specified
with these parameters is the time that the event logs reference when a redundant
system event occurs.

To change the redundancy module time settings, use the pull-down menu or type
your changes then click Set to implement time changes. Or, to set the time of the
redundancy module to match that of the workstation, click Apply Workstation
Time.

IMPORTANT We recommend that you set the redundancy module date and time when
you commission a system. We also recommend that you periodically check
the date and time settings to make sure that they match the settings of the
controller.
If a power failure occurs on the redundant chassis, you must reset the date
and time information of the redundancy modules. The modules do not
retain those parameters when power is lost.

100 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Synchronization Tab The Synchronization Tab has commands for these options:
• Change the synchronization state of the system (synchronize or disqualify)
• Initiate a switchover
• Force the disqualified secondary to become the primary

The commands are described in the Commands in the Synchronization Tab


section on page 102.

This tab also has information about the last four synchronization attempts in the
Recent Synchronization Attempts log. N or N-X identify synchronization
attempts in the log. If the redundant chassis fail to synchronize, a cause is
identified in the Recent Synchronization Attempts log.

The causes and their interpretations are described in the Recent Synchronization
Attempts Log section on page 103.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 101


Chapter 6 Configure the Redundancy Modules

Commands in the Synchronization Tab

These sections explain each redundancy command and the system conditions
that are required for the command to be available.

Command Description
Synchronize Secondary This command forces the primary redundancy module to attempt synchronization with its partner. This command is
available in specific conditions:
• Available only when the chassis redundancy state is as follows:
– Primary with Disqualified Secondary
– Disqualified Secondary
• Unavailable (dimmed) in all other chassis states
Synchronization is asynchronous with the execution of this command. Successful execution of this command begins with
synchronization, which can take several minutes. Monitor the chassis status that is displayed at the bottom of the RMCT
to determine when synchronization has completed.
Disqualify Secondary This command forces the primary redundancy module to disqualify its partner.

ATTENTION:
• Disqualifying the secondary chassis makes it unable to assume control functions, that is,
redundancy is lost.
• If you disqualify the secondary and a major fault occurs on the remaining primary, a switchover
does not occur.

This command is available in specific conditions:


• Available only when the chassis redundancy state is as follows:
– Primary with Synchronized Secondary
– Synchronized Secondary
• Unavailable (dimmed) in all other chassis states
If you use the Disqualify Secondary command when the Auto-Synchronization parameter is set to Always, a
synchronization attempt occurs immediately after the secondary chassis becomes disqualified.
To keep the secondary disqualified after issuing a Disqualify Secondary command, set the Auto-Synchronization
parameter to Conditional or Never before disqualifying the secondary.
Initiate Switchover This command forces the system to initiate an immediate switchover from the primary chassis to the secondary chassis.
This command can be used when you upgrade redundancy system firmware or when you complete maintenance on one
chassis of the redundant pair.
This command can also be used to perform a realistic test of your redundant system behavior by simulating a failure that
is detected in the primary control chassis.
This command is available in specific conditions:
• Available only when the chassis redundancy state is as follows:
– Primary with Synchronized Secondary
– Synchronized Secondary
• Unavailable (dimmed) in all other chassis states
Become Primary This command forces a disqualified secondary system to become a primary system and is available in specific conditions:
• Available only when the chassis redundancy state is Secondary with No Primary.
• Unavailable (dimmed) in all other chassis states

102 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Recent Synchronization Attempts Log

This table describes the possible result and causes of synchronization states.

Table 8 - Recent Synchronization Attempts Log - Result Interpretations


Result Result Interpretation
Undefined The result of the synchronization is unknown.
No attempt since last powerup Synchronization has not been attempted since power was applied to
the module.
Success Full synchronization was successfully completed.
Abort The synchronization attempt failed. See Table 9 for further
information.

If the Synchronization Attempts log indicates that the Synchronization attempt


was aborted, use Table 9 to diagnose the cause.
Table 9 - Synchronization Interpretation
Cause Cause Interpretation
Undefined The cause of synchronization failure is unknown.
Module Pair Incompatible Synchronization was aborted because one or more module pairs are incompatible.
Module Configuration Error Synchronization was aborted because one of the modules is improperly configured.
Edit Session In Progress Synchronization was aborted because an edit or session is in progress.
Crossloading Failure An undetermined failure occurred during synchronization between redundancy modules.
Comm Disconnected The cable between the redundancy modules was disconnected.
Module Insertion Synchronization was aborted because a module was inserted into a chassis.
Module Removal Synchronization was aborted because a module was removed from a chassis.
Secondary Module Failed Synchronization was aborted because of a failure in the secondary module.
Incorrect Chassis State Synchronization was aborted due to an incorrect chassis state.
Comm Does Not Exist Synchronization could not be performed because the communication link between redundancy modules does not exist.
Non-redundant Compliant Module Exists Synchronization could not be performed because one or more non-redundancy modules are present in one of the chassis.
Sec Failed Module Exists A module in the secondary chassis has asserted the SYS_FAIL line, which indicates that it has faulted or failed.
Local Major Unrecoverable Fault Synchronization was aborted because of a local major unrecoverable fault.
Partner Has Major Fault Synchronization was aborted because the partner module has a major fault.
Sec SYS_FAIL_L Subsystem Failed The test of the SYS_FAIL line in the secondary chassis failed.
Sec RM Device Status = Comm Error Synchronization was aborted because the status of the secondary redundancy module indicates a communication error.
Sec RM Device Status = Major Recoverable Synchronization was aborted because the status of the secondary redundancy module indicates a major recoverable fault.
Fault
Sec RM Device Status = Major Unrecoverable Synchronization was aborted because the status of the secondary redundancy module indicates a major unrecoverable fault.
Fault
Incorrect Device State Synchronization was aborted because the device is in the wrong state.
Primary Module Failed Synchronization was aborted because of a failure in the primary module.
Primary Failed Module Exists A module in the primary chassis has asserted the SYS_FAIL line, which indicates that it has faulted or failed.
Auto-Sync Option Synchronization was aborted because the Auto-Synchronization parameter of one of the redundancy modules was changed during
synchronization.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 103


Chapter 6 Configure the Redundancy Modules

Table 9 - Synchronization Interpretation


Cause Cause Interpretation
Module Qual Request Synchronization was aborted because another synchronization request was received. The current synchronization has stopped so
that the new synchronization request can be serviced.
SYS_FAIL_L Deasserted Synchronization was aborted because one of the modules came out of a faulted or failed state.
Disqualify Command Synchronization was aborted because the redundancy module received a disqualify command from another device. The
originating device sends this command when it can no longer perform in the qualified state.
Disqualify Request Synchronization was aborted because the redundancy module received a disqualify command from another device. The
originating device sends this command when it can no longer perform in the qualified state.
Platform Configuration Identity Mismatch There are modules in the primary or secondary chassis that do not belong to the platform.
Detected
Application Requires Enhanced Platform A redundant controller is running an application that contains a feature that is qualified to run only on an enhanced redundant
platform, for example, Alarms.
ICPT Asserted A test line on the backplane is asserted.
Unicast Not Supported A unicast connection is configured in the redundant controller, and redundancy systems do not support Unicast.
PTP Configuration Error The PTP clock of a redundant controller is not synchronized or the partner controller pair is synchronized to another Grandmaster.
Secured Module Mismatch A mismatch was detected between a primary and secondary secured module.

Synchronization Status Tab The Synchronization Status tab provides a module-level view of these items:

• Synchronization state (for example, Synchronized or Disqualified)

• Chassis designation (Primary or Secondary)

• Module compatibility with its partner (for example, Full or Undefined)

Each module that is installed in the chassis is identified and information


regarding its partner and compatibility are provided.
Synchronization State Chassis Designation Module-partner Compatibility

104 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

System Update Tab Use of the commands in the System Update tab lets you perform firmware
updates in the secondary chassis while the primary chassis remains in control.
Reference the lock and switchover logs in this tab for update information when
completing a firmware update.

ATTENTION: When performing firmware updates by using


commands in the System Update tab, redundancy is lost. In the event
of a fault on the operating primary chassis, the system cannot switch
control to the secondary chassis.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 105


Chapter 6 Configure the Redundancy Modules

System Update Commands

The three system update commands are available only when accessing a primary
redundancy module. These commands are not available when accessing the
secondary redundancy module.

TIP While you are completing tasks to update the system by using the
system update commands, you cannot access these tabs in the RMCT:
• Configuration
• Synchronization
• Synchronization Status
If you attempt to access any of these tabs while the system is locked or is
completing a locked switchover, it results in an error dialog box.

Lock For Update

The Lock for Update command lets you synchronize a redundant chassis pair
under these conditions:

• The secondary redundancy module uses updated firmware and an updated


programming software application program version.

• The running primary redundancy module uses a previous firmware


revision and previous programming software application program version.

The Lock for Update command is available only when all modules in the primary
chassis have no compatibility anomalies. Before issuing the lock command, verify
that you have completed these tasks:

• Set the Auto-Synchronization option in the Configuration tab to Never.

• Disqualify the secondary chassis by using the Disqualify Secondary


command in the Synchronization tab of the RMCT of the secondary
redundancy module.

• Updated the primary and secondary redundancy modules to compatible


firmware revisions.

• Updated all other modules in the secondary chassis to their intended


firmware revisions.

• Configured the controller project that as required to accommodate the


update and replacement of modules if needed.

For details about how to complete those tasks, see Update Redundant Firmware
on page 58.

106 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

Click the Lock for Update command to initiate the locking process. The lock can
take several minutes to finish. Monitor the System Update Lock Attempts log to
determine when the lock is complete. In addition, the chassis status that is shown
at the bottom-left of the dialog box changes from Primary with Disqualified
Secondary to Primary Locked for Update.

Figure 23 - Lock for Update Status Updates

Lock initiated.

Lock complete.

Lock complete.

Abort System Lock

The Abort System Lock command can be used to stop the system lock. It is
available as soon as a lock for update is initiated.

Click Abort System Lock to return the redundant chassis status to Primary with
Disqualified Secondary. This action also causes the system update to stop and the
program in the secondary controller to clear. If you click Abort System Lock, you
must download the program to the secondary controller before reattempting a
Lock for Update.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 107


Chapter 6 Configure the Redundancy Modules

Initiate Locked Switchover

The Initiate Locked Switchover command is available only when the chassis
redundancy state is Primary with Locked Secondary. That is, the Initiate Locked
Switchover is available only after the lock for update is complete.

If you click Initiate Locked Switchover, your secondary chassis assumes control
and becomes the new primary. The old primary is now the new secondary chassis
and you can update the firmware of the modules in the new secondary chassis.

Figure 24 - Illustration of Switchover

Chassis A Chassis B

CH2 CH1 OK
CH2 CH1 OK

Secondary

1756-L63
1756-L63

1756-L63
1756-L63
Primary

Chassis B Chassis A

CH2 CH1 OK CH2 CH1 OK


Secondary

1756-L63

1756-L63
1756-L63

1756-L63
Primary

The difference between a locked switchover and a normal switchover is that you
initiate the locked switchover. You or a fault in the primary chassis initiate a
normal switchover.

108 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Configure the Redundancy Modules Chapter 6

System Update Lock Attempts

The System Update Lock Attempts is where attempts to lock the system are
logged. This log displays the last four lock attempts and provides this information
specific to each attempt:
• Time and date
• Status (for example, Locked or Abort)
• Result (for example, System Locked or Invalid Response Received)

The status indicated in the System Update Lock Attempts log can be any one of
the states that are listed in Table 10.

Table 10 - System Update Lock Attempts Log Statuses


Status Interpretation
Not Attempted A system lock has not been attempted since the last
powerup.
In Progress A lock is in progress.
Locked The lock was successfully completed.
Abort The lock attempt failed. The reason for the failure is
indicated in a Result field.

If your status is indicated as Abort, one of these conditions can exist:


• An error occurred while communicating with the partner redundancy
module.
• A module in the secondary chassis does not have a partner in the primary
chassis.
• A module pair is incompatible.
• The SysFail test was unsuccessful in the primary redundancy module.
• A Major Recoverable Fault occurred in primary redundancy module.
• A Major NonRecoverable Fault occurred in primary redundancy module.
• A module was inserted into the chassis.
• A module was removed from the chassis.
• A failed module exists in the secondary chassis.
• A failed module exists in the primary chassis.
• An Abort System Update command received.
• Invalid response was received from a module.
• A module rejected the state change.
• A platform mismatch was detected.

For more information on Lock for Update Failures, see the Knowledgebase
Article Lock for Update Fails.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 109


Chapter 6 Configure the Redundancy Modules

Locked Switchover Attempts

The Locked Switchover Attempts log provides information about the status of
the last four locked switchover attempts. This log includes this information about
each attempt:
• Time and date
• Status
• Result

The status indicated in the Locked Switchover Attempts log can be any one of the
states that are listed in Table 11.

Table 11 - Locked Switchover Event Log Statuses


Status Description
Not Attempted A locked switchover has not been attempted since the last
powerup.
In Progress A locked switchover is in progress.
Success A locked switchover was successfully completed.
Abort The locked switchover attempt failed. The cause of the failure is
indicated in a Result field.

If a locked switchover is aborted, it can be because of the following:


• A module declined a locked switchover readiness request.
• An invalid response was received from the locked switchover readiness
request.
• After an initiate switchover prompt, a module rejected the command.
• After an initiate switchover prompt, a module replied with an invalid
response.

110 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 7

Program the Redundant Controller

Topic Page
Configure the Redundant Controller 112
Crossloads, Synchronization, and Switchovers 116
Crossloads and Scan Time 121
Program to Minimize Scan Times 123
Program to Maintain Data Integrity 130
Optimize Task Execution 134
Conduct a Test Switchover 139
Program Logic to Run After a Switchover 141
Use Messages for Redundancy Commands 142
Set the Task Watchdog 146
Download the Project 148
Store a Redundancy Project to Nonvolatile Memory 149
Online Edits 152

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 111


Chapter 7 Program the Redundant Controller

Configure the Redundant Both controllers in the ControlLogix® redundancy system operate by using the
Controller same program. You do not need to create a project for each controller in the
redundant system.

IMPORTANT When programming your redundancy system, you should only interface with
the controller in the primary rack unless a specific workflow dictates that the
controller in the secondary rack should be the target of modification.

To configure your controllers to operate in a redundant system, complete these


steps.

1. Open or create a project for your redundant controller.


2. Access the Controller Properties dialog box for the controller.

3. Click the redundancy tab and check Redundancy Enabled.

4. If you are going to complete edits to your redundant controller while


online, see these sections for information about the parameters available in
the Advanced settings:
• Plan for Test Edits on page 153
• Reserve Memory for Tags and Logic on page 158
5. Click the Advanced tab.

6. Verify that Match Project to Controller is unchecked.

112 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

IMPORTANT Do not use Match Project to Controller property with redundant


controllers.
If you use the Match Project to Controller property available in the
Advanced tab of the Controller Properties dialog box, you cannot go
online with, download to, or upload from the new primary controller
after a switchover. This is because the serial number of the new primary
controller is not the same as the serial number of the old primary
controller and the project cannot be matched to the newly switched to
controller.

Verify that this option is


not checked.

7. Click Apply.
8. Click OK.

You have completed the minimum configuration that is required for your
redundant controllers.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 113


Chapter 7 Program the Redundant Controller

Enable Time Time synchronization is not required for redundancy to function. If your
Synchronization application requires Time synchronization, then follow these steps.

1. At the Date/Time tab in Controller Properties, make sure that Enable


Time Synchronization is checked.

Verify that this option is


checked.

2. Click Apply.
3. Click OK.
4. Access the Module Properties dialog box for the Ethernet module.
5. At the General tab of the Module Properties dialog box of the Ethernet
module, click Change.

114 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

6. In the Module Definition dialog box from the Time Sync connection pull-
down menu, select Time Sync and Motion.

7. Click OK to close the dialog box.


8. At the warning dialog box, click Yes.
9. Click Apply.
10. Click OK to close the Module Properties dialog box.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 115


Chapter 7 Program the Redundant Controller

Crossloads, Crossloading and synchronization points are points where the primary controller
Synchronization, and transfers data to the secondary controller. Crossload and synchronization points
keep the secondary controller ready to assume control in the event of a fault on
Switchovers the primary.

Before you begin programming your redundant controller, be aware of the impact
of crossloads and synchronization on the execution of a program after a
switchover. If you understand these concepts, it helps you to create programming
that best meets the needs for your redundant application.

Continue reading the sections that follow for explanations of crossloads and
synchronization and their relationship to switchovers and program execution.

Changing Crossload and Synchronization Settings

In the redundancy system, crossload and synchronization points for programs


within the Studio 5000 Logix Designer® project are configurable. You can limit
which programs data crossloading and synchronization follow. In many
applications, changes to this setting can reduce the overall impact to the task scan
time by reducing the number of times data is crossloaded.

If you reduce the number of crossload and synchronization points, the switchover
time becomes longer. This increase in switchover time is because more programs
can be rescanned after the switchover.

Synchronization is performed at the end of the last program in the program list of
the task, regardless of the Synchronize Data after Execution setting for the
program.

To change the synchronization setting of a program, open the Program Properties


dialog box of the program and check or uncheck Synchronize Data after
Execution.

Use this setting to change crossload and


synchronization points.

116 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Default Crossload and Synchronization Settings

The default setting for a program in a redundant project is for a crossload to


occur at the end of each program execution. However, for an equipment phase,
the default is that the crossload not execute at the end of the phase.

Before you change the default crossload and synchronization settings, read the
sections that follow so you have a complete understanding of the implications.
For information about how to change the point in a task where a crossload
occurs, see Changing Crossload and Synchronization Settings on page 116.

Recommended Task Types

To avoid anomalies after a switchover occurs, we recommend that you use only
one of these task configurations when programming your redundant controllers.
Use either of the following:
• One continuous task
• Multiple periodic tasks, each with unique priorities and periods

Only the single highest-priority periodic task can ensure bumpless output
switching on switchover. The sections that follow explain the impact of
crossloads and synchronization after a switchover based on the task structure you
use.

Continuous Task After Switchover

After a switchover occurs within a controller project that contains only a


continuous task, the new primary begins executing at the last crossload and
synchronization point. Depending on your crossload and synchronization
setting, the program that the new primary controller begins with can be
the following:
• The program that the switchover interrupted
• The program that immediately follows the last crossload and
synchronization point

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 117


Chapter 7 Program the Redundant Controller

Continuous Task with Crossloads at Each Program End

This diagram demonstrates how programs set to crossload and synchronize at


each program-end are executed after a switchover. As is shown, the new primary
controller begins executing at the beginning of the program that the switchover
interrupted. This process is the switchover execution that occurs if you use the
default crossload and synchronization setting for a program.

Figure 25 - Program Execution After a Switchover (Crossload After each Program)


New Primary Controller

Program 2 Program 3 Program 1


Switchover
Primary Controller
Program 1 Program 2 Program 3

Crossload Crossload Crossload

Continuous Task with Varying Crossloads at Program End

This diagram demonstrates how programs set to crossload and synchronize at


various intervals are executed after a switchover. As is shown, the new primary
controller begins executing the program that follows the last crossload and
synchronization point.

Figure 26 - Program Execution After a Switchover (no Crossload After each Program)
New Primary Controller
Program 2 Program 3 Program 1
Switchover
Primary Controller
Program 1 Program 2 Program 3

Crossload Crossload

For information about how to change the point in a task where a crossload
occurs, see Changing Crossload and Synchronization Settings on page 116.

118 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Multiple Periodic Tasks

ATTENTION: If you use multiple periodic tasks, program all crucial


outputs within the highest-priority task. Failure to program outputs
in the highest-priority task can result in outputs changing state if a
switchover occurs.

In a project where multiple periodic tasks are used, the point where program
execution begins after a switchover depends on the following:
• Crossload and synchronization settings
• Task priority settings

As with the continuous task, the controller begins executing at the program that
follows the last crossload and synchronization point.

In addition, a higher priority task can interrupt a lower priority task. If a


switchover occurs during or just after the higher priority task executes and the
lower priority task has not been completed, then the lower priority task and
programs are executed from the point at which the last crossload occurred.

This diagram demonstrates how tasks at different priorities execute if a


switchover occurs while a lower priority task is executing. The crossload and
synchronization points in this example are set to occur only at the end of the last
program within the tasks. The points are not set to occur at the end of each
program.

Figure 27 - Normal Periodic Task Execution (no switchover)


Crossload Crossload
Task - Priority 1 Task - Priority 1

Program 1 Program 2 Program 3 Program 1 Program 2 Program 3

Task - Priority 2 Task - Priority 2


Program 1 Progra am 2 Program 3

Higher-priority Lower-priority Crossload


Task Interrupts Task Resumes

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 119


Chapter 7 Program the Redundant Controller

The following diagram shows a lower priority task that has not been completed
and a switchover occurs. The lower priority task and programs are executed from
the beginning of the program where the switchover occurred. This result is
because the program uses the default configuration and crossloads and
synchronization points occur at the end of each program.

Figure 28 - Periodic Task Execution After Switchover When Configured to Crossload After
Programs
New Primary

Task - Priority 1
Program 1 Program 2 Program 3

Task - Priority 2
Crossload Program 2 Program 3

Crossload
Task - Priority 1
Program 2 Program 3 Crossload
Crossload Switchover
Task - Priority 2 Task - Priority 2
Primary

Program 1 Program m2 Program 3

Higher-priority Lower-priority
Task Interrupts Task Resumes Crossload

The following diagram shows a lower priority task that has not been completed
and a switchover occurs. The lower priority task and programs are executed from
the beginning and not at the program where the switchover occurred. This result
is because the crossloads and synchronization points were not configured to
occur at the end of each program.

Figure 29 - Periodic Task Execution After Switchover When Configured Not to Crossload After
Programs
New Primary

Program 1 Program 2 Program 3


Task - Priority 2
Crossload Program 1 Program 2 Program 3

Program 1 Program 2 Program 3


Switchover
Task - Priority 2 Task - Priority 2
Primary

Program 1 Progra am 2 Program 3

Higher-priority Lower-priority
Task Interrupts Task Resumes Crossload

For more information about programs and tasks with controllers, see the Logix
5000 Controllers Tasks, Programs, and Routines Programming Manual,
publication 1756-PM005.

120 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Crossloads and Scan Time It is important to plan for controller crossloads because the length of the
crossloads affects the scan time of your program. A crossload is a transfer of data
from the primary controller to the secondary controller. The crossload can occur
at the end of each program or at the end of the last program in a task.

The scan time of your program or phase is a total of the program execution time
and the crossload time. The following diagram demonstrates this concept.

Figure 30 - Crossload and Scan Time

Execution of Program Crossload

Program Scan Time

Estimate the Crossload Time

The amount of time that is required for a crossload is primarily dependent upon
the amount of data being crossloaded. During a crossload, any tag that has been
written to during the program execution is crossloaded. Even if a tag has not
changed, but has been rewritten during the program execution, it is crossloaded.

The crossload requires time to transfer tag value changes. The crossload also
requires a small amount of overhead time to communicate information about the
program being executed

Redundancy Object Attributes for Crossload Times

Before you complete calculations to estimate the crossload time, you must use a
Get System Value (GSV) instruction to read certain attributes of the redundancy
object. These attributes are data transfer sizes that are measured in DINTs (4-byte
words) and are used to calculate the estimated crossload time.

TIP To get these attributes, you do not need to have the secondary chassis
installed or operating. If you do not have the secondary chassis
operating, the attribute values read indicate what data sizes would be
transferred if the secondary chassis was in use.

This table indicates the two attributes that you can choose to get specific to the
crossload data transfer size. Get the attribute value that meets your application
requirements.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 121


Chapter 7 Program the Redundant Controller

If you need the Then get this attribute value


Data size of the last data that is transferred during the last LastDataTransferSize
crossload
Data size of the largest crossload of data MaxDataTransferSize

The LastDataTransferSize attribute refers to the transfer size of the previous


crossload and synchronization point, which occurred before the program that
contains the GSV instruction.

If you must measure the crossloaded data from the last program in the program
list of the task, add an additional program at the end of the task that acquires the
LastDataTransferSize value from the program that was formerly at the end of the
task.

Equation for Estimating Crossload Times

Use this equation to estimate the crossload time of your controllers for each
program after you have either of the following:
• The size of the last data transfer
• The maximum size of data that is transferred

ControlLogix 5560 Controllers

Crossload time per sync point (ms) = (DINTs  0.00091) + 0.6 ms

ControlLogix 5570 Controllers

The following equations apply when a ControlLogix 5570 controller is paired


with a redundancy module in both chassis in a redundancy system.
Table 12 - Crossload Times for ControlLogix 5570 Controllers
Controller Paired with Redundancy Module Crossload Time(1)
ControlLogix 5570 1756-RM2 Crossload time per sync point (ms) = (DINTs * 0.000550) + 0.39 ms
1756-RM/B Crossload time per sync point (ms) = (DINTs 0.00043) + 0.3 ms
1756-RM/A Crossload time per sync point (ms) = (DINTs  0.00091) + 0.6 ms
Where DINTs is the size of the data transferred measured in 4-byte words.
(1) Crossload time equations are derived from tests that are performed on the latest supported firmware revisions.

TIP A sync point is a mechanism that the primary controller uses to keep the secondary controller in sync.
By default, at the end of each program scan, the primary controller sends the secondary controller
the sync point and the secondary controller responds by moving its execution pointer to match the
primary controller.
The default for phases is not to send a sync point.
In revision 16.05x and later, the option exists to manipulate the sync points for faster program execution.

122 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Program to Minimize Scan There are several aspects of your program that must be as efficient as possible to
Times facilitate the fastest possible switchover because total program scan time impacts
system switchover time. The sections that follow describe methods to make your
program more efficient to minimize your program scan time.

These methods make your program more efficient and minimize program scan
times:
• Use a ControlLogix 5570 Controller with a 1756-RM2 Redundancy
Module
• Use Multiple Controllers
• Minimize the Number of Programs
• Manage Tags for Efficient Crossloads
• Use Concise Programming

Use a ControlLogix 5570 Controller with a 1756-RM2 Redundancy


Module

In redundancy system revision 19.053 and later, you can use ControlLogix 5570
controllers in your application. Relative to the redundancy module being used,
the ControlLogix 5570 controllers scan the controller program faster than
ControlLogix 5560 controllers. The ControlLogix 5570 controllers also scan the
controller program fastest if the redundancy system uses the 1756-RM2/A
redundancy module.

IMPORTANT Only the 1756-L72, 1756-L73, 1756-L74, and 1756-L75 controllers can be
used with the 1756-RM2 redundancy modules and revision 19.053.

If your application needs better controller performance, we recommend that you


update from ControlLogix 5560 controllers to ControlLogix 5570 controllers
and use 1756-RM2 redundancy modules.

Use Multiple Controllers

If you have a non-PlantPAx(1) system, consider using two controllers per


redundant rack. If you use multiple controllers, you can strategically program
between the controllers so the program execution and scan times are faster.

(1) PlantPAx guidelines recommend only one controller per ControlLogix redundancy chassis. Non-PlantPAx ControlLogix 5570
redundancy applications support as many as two controllers in each redundant chassis

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 123


Chapter 7 Program the Redundant Controller

Minimize the Number of Programs

When programming a redundant controller, use the fewest programs possible.


Use of the fewest programs possible is especially important if you plan to
crossload data and synchronize the controllers after the execution of each
program.

If you must crossload data at the end of each program, make these programming
considerations to minimize the crossload impact on the program scan time:

• Use only one or a few programs.

• Divide each program into the number of routines that is appropriate for
your application. A routine does not cause a crossload or increase the scan
time.

• Use the main routine of each program to call the other routines of the
program.

• If you want to use multiple tasks for different scan periods, use only one
program in each task.

Figure 31 - Use of Multiple Routines (preferred) Figure 31 - Use of Multiple Programs (not
preferred)

Manage Tags for Efficient Crossloads

Manage your data tags as the following sections recommend to program for more
efficient crossloads of data and reduce the amount of time that is required for a
crossload to execute.

124 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Delete Unused Tags

If you delete unused tags, it reduces the size of the tag database. A smaller
database takes less time to crossload.

Use Arrays and User-Defined Data Types

If you use arrays and User-Defined Data Types, the tags use smaller 4-byte
(32-bit) words for all data in the type or array. If you create an individual tag, the
controller reserves 4 bytes (32 bits) of memory even if the tag uses only 1 bit.

Arrays and User-Defined Data Types help conserve the most memory with
BOOL tags. However, we also recommend that you use them for your SINT,
INT, DINT, REAL, COUNTER, and TIMER tags.

Figure 32 - Example Savings with the Use of an Array


12 bytes of data to crossload (4
bytes for each tag).

4 bytes of data to crossload.

TIP If you have already created individual tags and programming that uses
those tags, consider changing the individual tags to alias tags that
reference the elements in an array.
If you choose this method, your programming can still reference the
individual tag names, but the crossload transfers the base array.

For more information about how to work with arrays, User-Defined Data Types,
and alias tags, see the Logix 5000 Controllers I/O and Tag Data Programming
Manual, publication 1756-PM004.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 125


Chapter 7 Program the Redundant Controller

Group Data Types Together in User-Defined Data Types

When you create a User-Defined Data Type for use in your redundancy program,
group like data types together. Grouping like data types compresses the data size
and helps reduce the amount of data that is transferred during a crossload.

Figure 33 - Example of Bytes Saved by Grouping Like Data


Data Types Ungrouped
Data Types Grouped

Group Data into Arrays of User-Defined Data Types by Frequency of Use

To update the secondary controller, the primary controller divides its memory
into blocks of 256 bytes. Anytime an instruction writes a value, the primary
controller crossloads the entire block that contains the value. For example, if your
logic writes only 1 BOOL value to a block, the controller crossloads the entire
block (256 bytes).

To minimize crossload time, group your data by how frequently your program
uses it.

126 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

For example, if your application uses DINTs that you use only as constants to
initialize your logic, BOOLs that you update every scan, and REALs that you
update every second, you can create a separate User-Defined Data Type for each
type of tag that is used at different points in the application. Using separate User-
Defined Data Types for each group, rather than grouping all tags together in one
User-Defined Data Type, helps to minimize the amount of data that is transferred
during the crossload.
Tags Grouped into User-Defined Data Types by Frequency of Use Tags in One User-Defined Data Type

Use DINT Tags Instead of SINT or INT Tags when Possible

We recommend that you use the DINT data type instead of the SINT or INT
data types because the controller usually works with 32-bit values (DINTs or
REALs). When processing, the controller converts SINT or INT tag values to
DINT or REAL values. When processing is complete, the controller converts the
value back to a SINT or INT value.

The controller automatically converts these data types while executing and
processing a program. No additional programming is required. However, while
this conversion process is transparent to you, it does require additional processing
time that impacts your program scan time and your switchover time.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 127


Chapter 7 Program the Redundant Controller

Use Concise Programming

Use these recommendations to create concise programming. Using concise


programming makes your program execute faster and reduces your program scan
time.

Execute an Instruction Only when Needed

We recommend that you execute instructions only when needed because each
time an instruction writes a value to a tag, the tag is crossloaded to the secondary
controller. Even if the tag values is the same, it is rewritten and is therefore
crossloaded.

Because many instructions write tag values whenever executed, strategic and
economical use of instructions is needed. Strategic programming techniques
include the following:
• Using preconditions to limit the execution of instructions
• Combining preconditions when possible
• Dividing programming into subroutines that are called only when required
• Running noncritical code every 2 or 3 scans instead of during every scan

For example, precondition an ADD instruction to run only when the controller
gets new data. As a result, the Dest_Tag is crossloaded only when the ADD
instruction produces a new value.

Figure 34 - Precondition Used with ADD Instruction

128 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

In combination with using preconditions, try to group instructions together that


the same instructions precondition. In this example, the four preconditions that
are used in the two branches can be combined to precede the two branches.
Doing so reduces the number of precondition instructions from four to two.

Figure 35 - Efficient Precondition Use

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 129


Chapter 7 Program the Redundant Controller

Program to Maintain Data When programming your redundant controllers, there are some instructions and
Integrity techniques that can cause data loss or corruption when used. These instructions
and techniques include the following:
• Array (File)/Shift Instructions
• Scan-dependent Logic

Array (File)/Shift Instructions

Interruptions to Array (File)/Shift Instructions by a higher priority task and then


switchover can result in an incomplete data shift and corrupted data.

The following Array (File)/Shift instructions can result in corrupt data in the
event of a switchover:
• Bit Shift Left (BSL)
• Bit Shift Right (BSR)
• FIFO Unload (FFU)

If Array (File)/Shift Instructions are used, these system behaviors can result:

1. If a higher priority task interrupts one of the Array (File)/Shift


instructions, the partially shifted array values are crossloaded to the
secondary controller.
2. If a switchover occurs before the instruction completes its execution, data
remains only partially shifted.
3. After a switchover, the secondary controller starts its executing at the
beginning of the program. When it reaches the partially executed
instruction, it shifts the data again.

130 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Buffering Critical Data

If you cannot place Array (File)/Shift instructions in the highest-priority task,


consider using a buffer with Copy File (COP) and Synchronous Copy File (CPS)
instructions to maintain the integrity of the array of data.

The programming example that is shown here shows the use of a COP
instruction to move data into a buffer array. The BSL instruction uses the data in
that buffer array. The CPS instruction updates the array tag and maintains data
integrity because a higher priority task cannot interrupt it. If a switchover occurs,
the source data (that is, the array tag) remains unaffected.

Figure 36 - Using a Buffer to Maintain Data During Shift

For more information about BSL, BSR, FFU, COP, and CPS instructions see the
Logix 5000 Controllers General Instructions Reference Manual,
publication 1756-RM003.

Scan-dependent Logic

If you program a lower priority task so that one instruction is dependent on


another instruction that occurs elsewhere in your program, a task interrupt and
switchover can disrupt your programming. The disruption can occur because the
higher priority task can interrupt the lower priority task and then a switchover
can occur before the lower priority task is completed.

When the lower priority task is executed from the beginning by the new primary
controller after the switchover, the dependent instruction can fail to execute at
the most recent value or state.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 131


Chapter 7 Program the Redundant Controller

For example, if a higher priority task interrupts the logic that is shown in this
example, the value of scan_count.ACC is sent to the secondary controller at the
end of the program in the higher priority task. If a switchover occurs before the
primary controller completes the EQU instruction, the new primary controller
starts its execution at the beginning of the program and the EQU instruction
misses the last value of scan_count.ACC. As a result, any programming that uses
the Scan_Count_Light tag can also execute by using incorrect data.

Table 13 - Scan-dependent Logic

Switchover
Interrupt by higher
priority task.

Use a Counter instruction to count each scan of the program.

An Equal To instruction uses the accumulated scan_count value as a reference to turn on an indicator when the
thousandth scan is complete.

132 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Bind Dependent Instructions with UID and UIE Instructions

If you cannot place scan-dependent instructions in the highest priority task,


consider using the User Interrupt Disable (UID) and User Interrupt Enable
(UIE) to prevent a higher priority task from interrupting the scan-dependent
logic.

For example, if you bind the scan-dependent logic that is previously shown, a
higher priority task would not interrupt the dependent instructions and a
switchover would not result in inconsistent data.

Figure 37 - Scan-dependent Instructions Bound with UID and UIE Instructions

Use a Counter instruction to count each scan of the program.


UID and UIE keep
higher priority tasks
from interrupting
the logic.
An Equal To instruction uses the accumulated scan_count value as a reference to turn on an indicator when the
thousandth scan is complete.

For more information about UID and UIE instructions, see the Logix 5000
Controllers General Instructions Reference Manual,
publication 1756-RM003.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 133


Chapter 7 Program the Redundant Controller

Optimize Task Execution To make synchronization, crossloads, and HMI updates as fast as possible,
consider following these task-related best practices:
• Use periodic tasks; avoid using a continuous task.
• Use the fewest number of tasks possible.

These recommendations are made to simplify the configuration and


management of the redundant controller's time dedicated to task execution vs.
servicing communications.

Table 14 lists some of the different communication types that take place during
task execution and service communication periods.

Table 14 - Communication Types during Scheduled and Unscheduled Periods


During These types of communication occur
Task execution Update I/O data (not including block-transfers)
Produced/consumed tags
Service Communication with programming devices (for example, Studio 5000 Logix Designer)
communication
Communication with HMI devices
Execution of Message (MSG) instructions, including block-transfers
Responses to messages from other controllers
Synchronization of the redundant system
Reestablishment and monitoring of I/O connections, such as Removal and Insertion Under
Power conditions. This process excludes normal I/O updates that occur during the execution
of logic
Bridging of communication from the serial port of the controller to other ControlLogix
devices via the ControlLogix backplane

In order to make synchronization, crossloads, and HMI updates as fast as


possible, you can optimize the configuration of each task. The methods used to
increase the time dedicated to servicing communications depends on the type of
tasks used in your program. See Table 15 for more information.

Table 15 - Methods to Increase the Time Dedicated to Servicing Communications


If your project contains Then see On Page
One or more periodic tasks with no continuous task . Periodic Task Configuration Optimization 135
This is the recommended best practice.
A continuous task with no other tasks. Continuous Task Configuration 137
Optimization
A continuous task with one or more periodic tasks. See the Knowledgebase Article
This task implementation is not recommended. The System Overhead Time Slice Explained.

134 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Periodic Task Configuration Optimization

If you have one or more periodic tasks with no continuous task, you can increase
the time dedicated to service communication by adjusting the priority and period
of each periodic task. If you do not have a continuous task in your project,
changing the System Overhead Time Slide has no affect.

TIP While you can use multiple periodic tasks in your redundant controller
program, use the fewest number of tasks possible.

If you use periodic tasks, communication is serviced any time that a task is not
running. For example, if you configure your task period at 80 ms and the task
executes in 50 ms, the controller has 30 ms out of every 80 ms to service
communication.

Figure 38 - Periodic Task Execution and Service Communication


50 ms 50 ms 50 ms
Task Execution
30 ms 30 ms 30 ms
Service Communication
Periodic Task Periodic Task Periodic Task

If you use multiple periodic tasks, verify the following:


• The execution time of a highest priority task is smaller than its period.
• The total execution time of all your tasks is less than the period of the
lowest priority tasks.

Verifying those settings generally leaves enough time to service communication.


The example configuration of tasks that are shown here demonstrates those
configuration settings.

Example of Periodic Task Configurations

Task Priority Execution Time Period Specified


1 Higher 20 ms 80 ms
2 Lower 30 ms 100 ms
Total execution time: 50 ms

In this example, the execution time of the highest priority task (Task 1) is smaller
than its period. 20 ms is less than 80 ms. The total execution time of all tasks is
less than the specified period of the lowest priority task. 50 ms is less than 180 ms.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 135


Chapter 7 Program the Redundant Controller

Tuning the Period Specified

You must tune the period you specify for your periodic tasks to balance the
controller time dedicated to program execution versus servicing communication.

TIP The crossloading of data during synchronization points extends task scan
times in redundancy systems. We recommend that you balance program
execution and service communication when the system is synchronized.

To check for overlaps, go online with the controller and access the Task
Properties dialog box. In the Monitor tab, note the maximum scan time. Verify
that the maximum scan time is smaller than the period you specified for the
periodic task.

136 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Continuous Task Configuration Optimization

If your project only contains a continuous task with no other tasks, you can adjust
the System Overhead Time Slice setting to change the percentage of time the
controller devotes to servicing communication versus executing the continuous
task.

IMPORTANT If there is no continuous task, adjusting the System Overhead Time Slice setting
has no effect. When there is no continuous task, all controller time not used for
other tasks will be used for servicing communications.

Table 16 shows the ratio between executing the continuous task and servicing
communication at various system overhead time slices. Consider the following:

• When the system overhead time slice setting is between 10% and 50%, the
time that is allocated for servicing communication is fixed at 1 ms. The
continuous task time slice changes to produce the desired ratio.

• When the system overhead time slice is greater than 50…90%, the time
that is allocated to the continuous task is fixed at 1 ms. The time that is
allocated to servicing communication changes to produce the desired ratio.

Table 16 - System Overhead Time Slice


At this time slice The continuous tasks runs for And service communication occurs for
as long as
10% 9 ms 1 ms
20% 4 ms 1 ms
25% 3 ms 1 ms
33% 2 ms 1 ms
50% 1 ms 1 ms
66% 1 ms 2 ms
75% 1 ms 3 ms
80% 1 ms 4 ms
90% 1 ms 9 ms

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 137


Chapter 7 Program the Redundant Controller

System Overhead Time Slice Examples

This diagram illustrates a system where the system overhead time slice is set to
20% (default). With this percentage, communication is serviced after every 4 ms
of continuous task execution. Communication is serviced for up to 1 ms before
the continuous task is restarted.

Figure 39 - System Overhead Time Slice Set to 20%


Legend:
Task executes.

Task is interrupted (suspended).

1 ms 1 ms 1 ms 1 ms 1 ms
Service Communication
4 ms 4 ms 4 ms 4 ms 4 ms
Continuous Task

This diagram illustrates a system where the System Overhead Time Slice is set to
33%. With this percentage, communication is serviced after every 2 ms of
continuous task execution. Communication is serviced for up to 1 ms before the
continuous task is restarted.

Figure 40 - System Overhead Time Slice Set to 33%


1 ms 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms
Service Communication
2 ms 2 ms 2 ms 2 ms 2 ms 2 ms 2 ms 2 ms 2 ms
Continuous Task

Change the System Overhead Time Slice

To change the System Overhead Time Slice, access the Controller Properties
dialog box and click the Advanced tab. From this tab, you can enter your System
Overhead Time Slice value.

138 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Options for During the Unused System Overhead Time Slice

Enable the Run Continuous Task option (default setting) if you want the
controller to revert to running the continuous task as soon as the communication
servicing task has no pending activity. This setting results in only using the
allocated communication servicing time if there is a need for it.

IMPORTANT We do not recommend that you use the Reserve for System Task option for
production. The option was developed to simulate systems with high
communication requirements.

Use the Reserve for System Task option to allocate the entire 1 ms of the system
overhead time slice to service communication - even if no service communication
or background tasks must be executed. You can choose to use this option without
service communication or background tasks to simulate a communication load
on the controller during design and programming. Use this setting for testing
only.

Conduct a Test Switchover Complete these steps to verify that your redundant system switches over as
expected. Your system must be fully qualified before you begin.

1. In RSLinx® Classic software, access the RMCT for the primary


redundancy module.

2. Click the Synchronization tab.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 139


Chapter 7 Program the Redundant Controller

3. Click Initiate Switchover.

The Redundancy Configuration Tool dialog box opens.

4. Click Yes.

The switchover begins.


5. To verify that the switchover was successful, monitor the RM2 status
indicators or the RMCT. You can also view your HMI or other status-
monitoring device.

Synchronization After a Switchover


TIP If your Auto-Synchronization parameter is set to Always, your system
begins synchronizing immediately after the switchover.

To monitor the synchronization of your system after you initiate the test
switchover, you can monitor the synchronization process by using these methods:
• Click the Synchronization Status tab and monitor the
Secondary Readiness column. The states No Partner, Disqualified,
Synchronizing, and Synchronized indicate the stages of synchronization.
• View the module status display of a primary communication module. The
states PwNS, PsDS, PwQg, and PwQS indicate the stages of
synchronization.
• View the module status display of the secondary redundancy module. The
states DISQ, QFNG, and SYNC indicate the stages of synchronization.
• Run a second test switchover where you power off the primary chassis to
initiate the switchover.

140 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Program Logic to Run After If your application requires certain logic or instructions to be executed after a
a Switchover switchover, then use programming and tags similar to the values shown in this
example.

Figure 41 - Precondition Used to Run Logic After Switchover - Ladder Logic

This GSV instruction obtains the chassis ID of the primary chassis (that is, the chassis that is in control).

If this is the first program scan, then use the current primary chassis ID as the chassis ID for the last scan.

If a switchover occurs, the chassis ID changes. The NEQ instruction compares the current and last primary chassis ID values. If the
values are different, the Switchover_Occurred bit is turned on. In addition, the current primary chassis ID is moved into the last
chassis ID.

If the Switchover_Occurred bit is on, then the instructions added to this rung are executed and the Switchover_Occurred bit is
reset.

Add your switchover-dependent instructions here.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 141


Chapter 7 Program the Redundant Controller

Use Messages for For some applications, consider programming the controller to issue redundancy
Redundancy Commands system commands via the redundancy modules. The sections that follow explain
how to configure a MSG instruction to issue a redundancy command.

Verify User Program Control

For a MSG instruction to issue a command via the redundancy modules, the
redundancy modules must be configured for user program control.

To verify that the modules are enabled for user program control, access the
Configuration tab of the RMCT and verify that Enable User Program Control is
checked.

Figure 42 - Enable User Program Control in the RMCT

Use an Unconnected Message

When you add your MSG instruction for issuing the command through the
redundancy modules, configure it as an unconnected message.

142 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Configure the MSG Instruction

Use the MSG configuration settings that correspond to the command you intend
to issue to the redundancy modules.

If you must See page


Initiate a Switchover 143
Disqualify the Secondary Chassis 145
Synchronize the Secondary Chassis 145
Set the Redundancy Module Date and Time 146

Initiate a Switchover

To initiate a switchover, use the MSG instruction parameters that are listed in
Table 17.
Table 17 - MSG Instruction to Initiate a Switchover
In this tab Edit this element To use this value
Configuration Message Type CIP™ Generic
Service Type Custom
Service Code 4e
Class bf
Instance 1
Attribute None - no value needed
Source Element INT tag with a value of 1
Source Length 2
Destination Element None - no value needed.
Communication Path 1 - the slot number of the 1756-RM, 1756-RM2,
1756-RMXT, or 1756-RM2XT module.
Connected box Leave the Connected checkbox unchecked.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 143


Chapter 7 Program the Redundant Controller

Use Table 18 when using MSG instructions during a switchover.


Table 18 - MSG Instruction Behavior During a Switchover
If the MSG instruction is Then
From a redundant controller In a redundant controller, any MSG instruction that is in progress during a switchover experiences an error.
(The ER bit of the instruction turns on.) After the switchover, normal communication resumes.
To a redundant controller For any MSG instruction from a controller in another chassis to a redundant controller, cache the connection:
Properties of the Message to the Redundant Controller
Configured Message Instructions
If the MSG instruction Then
originates from a
redundant controller
During a switchover The message instructions status bits are updated asynchronously to the program scan. Consequently, you cannot crossload your
message instructions status bits to a secondary controller.
During a switchover, any active message instructions become inactive. When this change occurs, you must reinitialize the execution
of your message instructions in the new primary controller.
During qualification The scrolling display changes from CMPT for compatible to QFNG for qualifying.
• If a configured message is cached, the primary controller automatically establishes a connection with no errors.
• If a configured message is uncached or unconnected, the primary controller receives Error 1 Extended Error 301, No Buffer
Memory.
If the message is targeted to a Then
redundant controller
During the erroring out of a message All backplane communication ceases. This stoppage lets the redundant controller receive the message instruction that is required to
perform a switchover or any diagnostics.
Important: If any of your messages are active during a switchover, you can expect one of these things to happen:

• Cached and connected messages cause the message instruction to pause for 7.5 seconds because the initiating controller has
not received a response from the targeted controller. For cached messages, the message instruction tries to execute three more
times, each attempt followed by a pause of 7.5 seconds. If, after 30 seconds pass, the targeted controller does not respond to the
initiating controller, then the switchover errors out with connected timeout Error 1 Extended Error 203.
An example of a connected message would be CIP data table read-and-write messages after a
connection has been established.

• Uncached messages error out after 30 seconds if you have initiated them because the initiating controller never received a reply
to the forward-open request. The error is Error 1F Extended Error 204, an unconnected timeout.
Examples of uncached messages would include CIP generic messages and messages that are captured during the
connection process.
During qualification Cached messages that run with no errors. A connection has been established.
Connected, but uncached, messages or unconnected messages error out with Error 1 Extended Error 301, No
Buffer Memory.

144 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Disqualify the Secondary Chassis

To disqualify the secondary chassis, use the MSG instruction parameters that are
listed in Table 19.
Table 19 - Disqualify the Secondary Chassis
In this tab Edit this element To use this value
Configuration Message Type CIP Generic
Service Type Custom
Service Code 4d
Class bf
Instance 1
Attribute None - no value needed
Source Element INT tag with a value of 1
Source Length 2
Destination Element None - no value needed.
Communication Path 1 - the slot number of the 1756-RM, 1756-RM2,
1756-RMXT, or 1756-RM2XT module.
Connected box Leave the Connected checkbox unchecked.

Synchronize the Secondary Chassis

To disqualify the secondary controller, use the MSG instruction parameters that
are listed in Table 20.
Table 20 - Synchronize the Secondary Chassis
In this tab Edit this element To use this value
Configuration Message Type CIP Generic
Service Type Custom
Service Code 4c
Class bf
Instance 1
Attribute None - no value needed
Source Element INT tag with a value of 1
Source Length 2
Destination Element None - no value needed.
Communication Path 1 - the slot number of the 1756-RM, 1756-RM2,
1756-RMXT, or 1756-RM2XT module.
Connected box Leave the Connected checkbox unchecked.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 145


Chapter 7 Program the Redundant Controller

Set the Redundancy Module Date and Time

To set the WallClockTime of the 1756-RM module, use the MSG instruction
parameters that are listed in Table 21.
Table 21 - Set WallClockTime
In this tab Edit this element To use this value
Configuration Message Type CIP Generic
Service Type Custom
Service Code 10
Class 8b
Instance 1
Attribute b
Source Element WallClockTime[0]
WallClockTime is a DINT[2] array that stores the
CurrentValue of the WallClockTime object
Source Length 8
Destination Element None - no value needed.
Communication Path 1 - the slot number of the 1756-RM, 1756-RM2,
1756-RMXT, or 1756-RM2XT module.
Connected box Leave the Connected checkbox unchecked.

Set the Task Watchdog Watchdog times set for tasks in redundancy applications must be larger than
watchdog times set for tasks in non-redundancy applications because more time
is required to conduct crossloads and synchronization.

An increase in the required watchdog time is also a result of the way programs are
executed in the event of a switchover. A program or programs can be executed a
second time after switchover. This action depends on when in the task or
program the switchover occurs and where in the task crossload and
synchronization occurs.

If a program is executed a second time, the length of time that is required for the
program scan is increased. However, the watchdog timer is not reset and
continues to countdown from the beginning of the task that the old primary
controller started. Therefore, the watchdog timer must be configured to account
for the potential of additional program scans.

146 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

We recommend that you reevaluate the watchdog times in your application if


either of these events occur:

• A second controller is added to a redundancy chassis.

• The application in a second controller that is already in the system is


modified.

Figure 43 - Watchdog Configured for Redundancy Switchover

Program 2 Program 3
Switchover
Task Crossload
Program 1 Program 2 Program 3

Crossload Crossload

Task Watchdog

In the event of a watchdog timeout, a major fault (type 6, code 1) results. If this
fault occurs after a switchover, the control system fails-to-safe or to the
configured hold state.

Figure 44 - Watchdog Not Configured for Redundancy Switchover

Program 2 Program 3
Switchover
Task
Crossload
Program 1 Program 2 Program 3

Crossload Crossload

Task Watchdog

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 147


Chapter 7 Program the Redundant Controller

Minimum Value for the Watchdog Time


To set Watchdog time for your ControlLogix 5560 controllers, use this table to
determine which equation to use to calculate the time for each task.

If Then use this equation


Using ControlNet® I/O ms (2 * maximum_scan_time) + 150
Using Ethernet I/O ms (2 * maximum _scan_time) + 100

The maximum_scan_time is the maximum scan time for the entire task when the
secondary controller is synchronized.

To set the initial task tuning of the ControlLogix 5570 controller, follow these
steps.

IMPORTANT This process works only when there is no Continuous task that is configured in the
Logix application.

1. Monitor the Max Scan Time for each task while the redundant chassis pair
is synchronized.
2. Set the Watchdog times for each task to three times the Max Scan Time.
3. To configure each Task Period, use the Logix 5000™ Task Monitor Tool.(1)
a. Adjust the Task periods of each so that the maximum scan time is less
than 80% of the task period rate.
b. Adjust the Task periods so that the Logix CPU % utilization is never
above 80%.
c. While performing these tests, the HMI and any other external systems
must be connected to the Logix controller.

IMPORTANT Verify that there are no task overlaps.

Download the Project Download the project only to the primary controller. When the secondary
controller is synchronized, the system automatically crossloads the project to the
secondary controller.

IMPORTANT If the secondary chassis was qualified and becomes disqualified after you
download the project, verify that you have enabled the controller for
redundancy.

(1) See the PlantPAx® DCS Configuration and Implementation User Manual Manual, publication PROCES-UM100.

148 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Store a Redundancy Project Use this procedure to store an updated project and firmware to the nonvolatile
to Nonvolatile Memory memory card of the controller.

This section describes how to store a project to nonvolatile memory in either of


these conditions:
• Store a Project While the Controller is in Program or Remote Program
Mode
• Store a Project While a System is Running

IMPORTANT We recommend that you store the same project on the nonvolatile memory
cards of both controllers. By doing so, you can be assured that if a controller,
primary or secondary, loses the project from its internal memory, you can
load the most recent project back onto that controller.
If you store the same project on the nonvolatile memory cards of both
controllers, while the process is running, you must save the project on the
controllers while they are in the secondary controller state. To do so, you
save the project on the secondary controller, conduct a switchover, and save
the project on the new secondary controller. Even if you do not plan to use
the SD card, leave the card installed in the controller to collect diagnostic
information that you can provide to Rockwell Automation Technical
Support.
For more information, see the steps in Store a Project While the Controller is
in Program or Remote Program Mode on page 150 or Store a Project While a
System is Running on page 151.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 149


Chapter 7 Program the Redundant Controller

Store a Project While the Controller is in Program or Remote Program


Mode
If you want to store your controller project in nonvolatile memory while your
redundant system is not running, complete these steps. Before you begin, verify
that a controller communication path has been specified and that you are able to
go online with the primary controller.

1. Verify that the redundant chassis are synchronized. If they are not
synchronized, synchronize them.
2. To put the primary controller into Program or Remote Program mode, use
programming software or the mode switch.
3. In RSLinx Classic communication software, right-click the redundancy
module and choose Module Configuration to open the RMCT.

4. In the Configuration tab, set the Auto-Synchronization parameter to


Conditional.

5. On the Synchronization tab, click Disqualify Secondary.

6. In the programming software, access the Controller Properties dialog box


and click the Nonvolatile Memory tab.
7. Click Load/Store.
8. Click <-- Store and then click Yes.

When the store is complete, go online with the secondary controller.

150 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

9. Complete steps 6…8 to store the project in nonvolatile memory of the


secondary controller.
10. In RSLinx Classic software, open the RMCT for one of the redundancy
modules in the redundant pair.
11. In the Synchronization tab, click Synchronize Secondary.

12. In the Configuration tab, set the Auto-Synchronization option to your


desired setting.

Store a Project While a System is Running

If you want to store your controller project in nonvolatile memory while your
redundant system is running, complete these steps.

1. Verify that the redundant chassis are synchronized.

2. In the RMCT, access the Configuration tab and set the Auto-
Configuration parameter to Never.
3. In the Synchronization tab, click Disqualify Secondary.
4. Go online with the secondary controller.

IMPORTANT Do not go online with the primary controller until you have completed
this procedure.

5. Open the Controller Properties dialog box and click the Nonvolatile
Memory tab.
6. To store the project in nonvolatile memory, click Load/Store then <--
Store.
7. In the RMCT, click the Synchronization tab.
8. Click Synchronize Secondary and wait for the system to synchronize.
9. Click Initiate Switchover.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 151


Chapter 7 Program the Redundant Controller

10. Go online with the new secondary controller.


11. Complete step 5 and step 6 to store the project.
12. In the RMCT, click the Configuration tab and set the Auto-
Configuration to your desired setting.
13. In the Synchronization tab, click Synchronize Secondary.
You have completed the steps that are required to store your project while
online.

Load a Project

If you must load a project from nonvolatile memory, you must first disqualify
your redundancy system. You then load the project from the nonvolatile memory
card to the primary controller, and resynchronize the redundant chassis once the
load is complete.

For details about loading a project from nonvolatile memory, see the Logix 5000
Controllers Nonvolatile Memory Card Programming Manual,
publication 1756-PM017.

Online Edits You can edit the redundant controller program while the system is online and
running. However, considerations specific to redundancy must be made with
considerations described in the Logix 5000 Controllers Quick Start,
publication 1756-QS001.

Support for Partial Import Online

Beginning with redundancy system revision 19.052 or later, you can use the
Partial Import Online (PIO) feature available in the programming software.

Consider these points when using PIO with redundancy systems at revision
19.052 or later:
• If you select Import Logix Edits as Pending or Accept Program Edits
when executing a PIO, the primary controller treats the PIO feature as a
set of multiple test edits where, after the import is complete, you can
switch between testing the edits or not.
• We recommend that you do not use Finalize All Edits in Program when
you import edits. If you use this option, any failure due to the import
causes a failure on the new primary controller after a switchover.
• If edits exist in the primary controller due to a PIO, they are treated the
same as normal test edits regarding the ‘Retain Test Edits at Switchover’
selection and Redundancy System Update.
• If a PIO is in progress, the primary controller rejects any attempt to
qualify.
• If you attempt to initiate a PIO on a primary controller in the process of
qualifying the system, that PIO is rejected.

152 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

• If a switchover occurs while the PIO is still in process, a PIO to a primary


controller can fail.

When the anomaly occurs and the PIO fails, you can see any of these
errors:
– Failed to import file 'c\...\xxx.L5x
Object already exists

– Failed to import file 'c\...\xxx.L5x


Already in request mode/state

– CIP error: Problem with a semaphore

– Internal Object Identifier (IOI) destination unknown

After switchover is complete, reattempt the PIO and it completes


successfully.

There are additional considerations necessary to performing online edits:


• Plan for Test Edits
• Assemble Edits with Caution
• Reserve Memory for Tags and Logic

Plan for Test Edits

Before you begin editing your redundant program while your system is running,
verify that the Retain Test Edits on Switchover setting meets your application
requirements.

IMPORTANT We recommend that you leave the Retain Test Edits on Switchover
setting at the default (that is, unchecked) to avoid faulting both
controllers when testing your edits.

If you enable the system to retain the test edits on a switchover (that is, you check
Retain Test Edits on Switchover), faults that result from the test edits can also
occur on the new primary controller after a switchover.

If you do not enable the system to retain the test edits on a switchover (that is,
you leave Retain Test Edits on Switchover unchecked), faults that result from the
test edits are not carried over to the new primary controller in the event of a
switchover.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 153


Chapter 7 Program the Redundant Controller

Use this table to determine the Retain Test Edits on Switchover setting that suits
your application.

If you must Then


Prevent a test edit from faulting both the primary and secondary Leave Retain Test Edits on Switchover
controller unchecked
Keep test edits active, even in the event of a switchover and at the Check Retain Test Edits on Switchover
risk of faulting both controllers

To change the Retain Test Edits on Switchover setting, click the Redundancy tab
in the Controller Properties then click Advanced.

Figure 45 - Retain Test Edits on Switchover

154 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

Assemble Edits with Caution

When you assemble edits to your program while online, the original program
that existed before the changes were made is deleted. As a result, if the edits you
assemble cause a fault on the primary controller, the new primary controller also
faults after the switchover. Also, when you assemble edits in the primary
controller, the edits are also assembled in the secondary controller.

Before you assemble any edits to your program, test the edits to verify that faults
do not occur.

1. In the Controller Organizer, open the routine you must edit.


2. Make the appropriate changes to your routine.
3. Click the Verify Routine button.
4. Click the Accept Pending Program Edits button.

Figure 46 - Test Edits Before Finalizing

Accept Pending Program Edits Verify Routine

TIP Even if you have not enabled the Retain Test Edits on Switchover
property, faults can still occur on the primary and secondary controllers if
the edits are assembled.
The Retain Test Edits on Switchover property affects only edits that are
being tested. The Retain Test Edits on Switchover does not affect the
redundant controllers that are running assembled edits.
5. At the Accept the Pending Edits dialog box, click Yes.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 155


Chapter 7 Program the Redundant Controller

6. Click Test Accepted Program Edits.

Test Accepted Program Edits

7. At the dialog box, click Yes.

156 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Program the Redundant Controller Chapter 7

8. Click Assemble Accepted Program Edits.

Finalize All Edits

9. At the dialog box, click Yes.

Your edits are now assembled.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 157


Chapter 7 Program the Redundant Controller

Reserve Memory for Tags and Logic

IMPORTANT Do not change the Memory Usage settings for Tags and Logic unless
Rockwell Automation Technical Support instructs you to change the
settings.

Depending on your redundant application, you may need to change the memory
usage property for your redundant controller. The setting that you specify
impacts how the controller divides memory for tags and logic to be stored to the
buffer during a crossload to the secondary controller. Table 22 indicates when
you can consider changing the memory usage setting
.

Table 22 - Possible Memory Usage Setting Change


If your online edits are primarily changes to Then move the Memory Usage slider towards
Tags with little or no changes to logic Tags
Logic with little or no new tags created Logic

IMPORTANT Do not set the Memory Usage slider to only Tags or Logic:
• Moving the slider to only Tags can block you from performing edits while online and OPC
communication can fail.
• If you move the slider to only Logic, you cannot create or edit any tags while online.

IMPORTANT When using a ControlLogix 5570 redundancy controller using version 19


software, and the Memory Usage slider is set to the far left for Tags, the first
synchronization attempt is successful. However, after switchover or
disqualification, the next qualification attempt fails, and one or more entries
appear in the secondary redundancy module event log with the following
description: ‘(14) Error Setting Up Data Tracking.’
To recover from this issue, move the slider slightly to the right. This change
must be made offline or in Program mode. Additionally, you must download
the updated application to the disqualified secondary to update its
configuration. The next qualification attempt is successful.

Memory Usage Slider

158 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 8

Monitor and Maintain a Redundancy System

Topic Page
Controller Logging 159
Monitor System Status 161
Verify Date and Time Settings 163
Verify System Qualification 164
Check the EtherNet/IP Module Status 166
Check the ControlNet Module Status 168

This chapter describes some of the key tasks to complete to monitor and
maintain your redundancy system.

Controller Logging Beginning with redundancy system revision 19.052, you can use the controller
logging feature. This feature provides a way to detect and log changes. These
changes include programming software and controller mode switch interactions,
made to ControlLogix® 5560 and ControlLogix 5570 controllers, without
adding any auditing software.

With controller logging, the controller can perform these tasks:

• Detect changes and create logs entries that contain information about the
changes.

• Store the log entries to a CompactFlash (CF) card or Secure Digital (SD)
card for later review.
• Provide programmatic access to log entry counters to provide change
detection information remotely.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 159


Chapter 8 Monitor and Maintain a Redundancy System

Controller Log

A controller log is the record of changes. The log is stored on the NVS memory of
the controller automatically. You can move the log to a CF card or SD card on an
as needed basis or automatically at predefined times. The NVS memory of the
controller and each external memory card type has a maximum number of entries
that they can store.

Specific events are stored in the log of the controller.

For more information on controller logging, see the Logix 5000 Controllers
Information and Status Programming Manual, publication 1756-PM015.

Controller Logging in Redundancy Systems


Because redundancy systems operate with partnered controllers, there are
considerations that you must consider regarding controller logging:

• The primary and secondary controllers maintain separate logs.

• You do not need to synchronize the logs.


• On the primary controller, controller logging occurs exactly as it does on a
controller in a non-redundant system, regardless of whether the system is
qualified and synchronized or disqualified.

• A secondary controller logs the removal or insertion of removable storage


components, that is, a CF or SD card, in any operating state. Otherwise,
the secondary controller only logs events that occur when the controller is
in a disqualified state.

Component Change Detection

Component tracking allows you to determine whether tracked routines,


Add-On Instructions, and constant tags have been changed. The Studio 5000
Logix Designer® application creates a tracked value to indicate the current state of
all components.

For more information, see the Logix 5000 Controllers Information and Status
Programming Manual, publication 1756-PM015.

160 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Monitor and Maintain a Redundancy System Chapter 8

Monitor System Status IMPORTANT When programming your redundancy system, program so your
redundancy system status is continually monitored and displayed on
your HMI device.
If your redundancy system becomes disqualified or a switchover occurs,
the change in status is not automatically annunciated. You must program
the system to communicate the change in status via your HMI or other
status-monitoring device.

For most redundant applications, you must program to obtain the status of the
system. Program to obtain system status when you do the following:
• Program HMI to display the system status
• Precondition logic to execute based on the system status
• Use the diagnostic information to troubleshoot the system

To obtain the status of your redundant system, use a Get System Value (GSV)
instruction in your program and plan for the tags you are writing the values to.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 161


Chapter 8 Monitor and Maintain a Redundancy System

In the following example, the GSV instruction is used to obtain the chassis ID
(that is, the chassis A or B designation) of the chassis that is functioning as the
primary. The PhysicalChassisID value is stored in the PRIM_Chassis_ID_Now
tag. The PhysicalChassisID value that is retrieved matches the Chassis ID
indicated in the Controller Properties dialog box.

If the Physical Chassis ID Value is Then the Chassis ID is


0 Unknown
1 Chassis A
2 Chassis B

Figure 47 - GSV Instruction to Get Chassis ID

Ladder Logic

Structured Text

Chassis ID in Controller
Properties

For more information about the REDUNDANCY object attributes, see


Appendix B, Redundancy Object Attributes on page 227.

162 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Monitor and Maintain a Redundancy System Chapter 8

Verify Date and Time Verify that the Redundancy Module Date and Time information matches the
Settings date and time of your system after you have configured and downloaded your
redundant system to the controller.

TIP Consider checking the Redundancy Module Date and Time as a part of
your regular maintenance procedures. Regular verification of the date
and time information keeps the event logs of the redundancy modules
accurate.

If the date and time are not correct, the redundant system event logs do not
match the date and time information for the rest of the system. Incorrect date and
time information complicates troubleshooting if an event or error occurs on your
redundant system.
2

Verify Date and Time


Settings

IMPORTANT If power to one of the redundancy modules is cycled, the redundancy


module powers up with the time set to when the power was lost. If the
partner redundancy module has remained active during this time, the
time set in that module is automatically transferred to the powering-up
module. If a power failure event happens so that both modules are shut
off, reset the time and date in the RMCT.
If you set and verify the date and time settings after a power loss, it helps
with troubleshooting if an error or event occurs.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 163


Chapter 8 Monitor and Maintain a Redundancy System

Verify System Qualification After you have completed programming your redundant system and have
downloaded your program to the primary controller, check the system status to
verify that the system is qualified and synchronized.

TIP The system qualification process can take several minutes. After a
qualification command or a switchover, allow time for qualification to
complete before acting based on the qualification status.

Check Qualification Status Via Module Status Displays

You can view qualification status by using the status displays and indicators of the
secondary redundancy module and the primary and secondary ControlNet® and
EtherNet/IP™ communication modules.

Table 23 - Synchronized System


Primary Chassis Display Secondary Chassis Display
Redundancy Module Communication Redundancy Module Communication
Module Module
PRIM PwQS SYNC QS

Table 24 - Qualifying System


Primary Chassis Display Secondary Chassis Display
Redundancy Module Communication Redundancy Module Communication
Module Module
PRIM and QFNG PQgS QFNG QgS

Table 25 - System with a Primary and Disqualified Secondary


Primary Chassis Display Secondary Chassis Display
Redundancy Module Communication Redundancy Module Communication
Module Module
PRIM PwDS DISQ Either:
• CMPT (modules are
compatible)
• DSNP (no partner is
present)

164 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Monitor and Maintain a Redundancy System Chapter 8

Example of Qualified and Disqualified Status Indicators

This example shows status display messages and status indicators that can appear
differently depending on the qualification status of the redundant chassis. The
following are only two examples of status display message and indicator
combinations for both the qualified and disqualified states.
Qualified Redundant Chassis Disqualified Redundant Chassis

Primary Chassis Primary Chassis


1756-L63

1756-L63
Secondary Chassis Secondary Chassis

1756-L63
1756-L63

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 165


Chapter 8 Monitor and Maintain a Redundancy System

Check Qualification Status Via the RMCT

To determine the qualification status of your system by using the RMCT, open
the RMCT and view the qualification status in the bottom-left corner of the tool.

Check the EtherNet/IP After you have programmed your redundant system and configured your
Module Status EtherNet/IP network, check two statistics specific to your EtherNet/IP modules.
These statistics include the CPU usage and the connections used.

To view the CPU usage and the number of connections that are used, complete
these steps.

1. In RSLinx® Classic software, open the Module Statistics for the EtherNet/
IP module.
2. Click the Connection Manager tab.

166 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Monitor and Maintain a Redundancy System Chapter 8

EtherNet/IP Module CPU Usage

The CPU usage of the EtherNet/IP modules must be at 80%, or less. CPU usage
below 80% reserves enough CPU functionality for the EtherNet/IP module to
facilitate a switchover.

If the CPU usage is above 80%, the secondary chassis can fail to synchronize with
the primary chassis after a switchover occurs. In addition, unscheduled
communication can be slowed.

If you must reduce the CPU usage of your EtherNet/IP modules, consider
making the following changes:
• Increase the Requested Packet Interval (RPI) of your connections.
Increasing the RPI rate of a connection reduces the loading on the
associated communications modules
• Reduce the number of devices that are connected to your module.

For additional details about reducing the CPU utilization of your EtherNet/IP
modules, see EtherNet/IP Network Devices User Manual, publication
ENET-UM006.

EtherNet/IP Module Connections Used

If the connections of your EtherNet/IP modules that are used are near the limits
of the module, you can experience difficulty when attempting to go online with
the system. This difficulty arises because going online with a processor also
consumes a connection, if the attempts to go online are through the
communication module that is near the limit. You can also experience difficulty
when attempting to add modules to the system.

Monitor the EtherNet/IP Network

For most redundant applications, monitoring the status of the EtherNet/IP


network is important for maintenance and troubleshooting.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 167


Chapter 8 Monitor and Maintain a Redundancy System

Check the ControlNet After you have programmed your redundant system and configured your
Module Status ControlNet network, check two statistics specific to your ControlNet modules.
These statistics include the CPU usage and the connections used.

To view the CPU usage and the number of connections that are used, complete
these steps.

1. In RSLinx Classic software, open the Module Statistics for the ControlNet
module.

2. Click the Connection Manager tab.

168 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Monitor and Maintain a Redundancy System Chapter 8

ControlNet Module CPU Usage

The CPU usage of the ControlNet modules must be at 80%, or less. CPU usage
below 80% reserves enough CPU functionality for the ControlNet module to
facilitate a switchover.

If the CPU usage is above 80%, the secondary chassis can fail to synchronize with
the primary chassis after a switchover occurs. In addition, unscheduled
communication can be slowed.

If you must reduce the CPU usage of your ControlNet modules, consider making
the following changes:
• Increase the Network Update Time (NUT) of the ControlNet network.
• Increase the Requested Packet Interval (RPI) of your connections.
• Reduce the number of connections through the ControlNet modules.
• Reduce the number of messages that are used in the program.

ControlNet Module Connections Used

If the connections of your ControlNet modules that are used are near the limits
of the module, you can experience difficulty when attempting to go online with
the system. This difficulty arises because going online with a processor also
consumes a connection. You can also experience difficulty when attempting to
add modules to the system.

For information about connections available with ControlNet modules, see


ControlNet Network Requirements on page 30.

Monitor the ControlNet Network


For most redundant applications, monitoring the status of the ControlNet
network is important for maintenance and troubleshooting.

For programming samples to monitor the ControlNet network, visit the


Rockwell Automation® Sample Code Library. Applicable sample programs
include the following:
• ME Faceplates for ControlNet Diagnostics
• ControlNet Connection and Media Status

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 169


Chapter 8 Monitor and Maintain a Redundancy System

Notes:

170 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Chapter 9

Troubleshoot a Redundant System

Topic Page
General Troubleshooting Tasks 171
Check the Module Status Indicators 172
Use Programming Software to View Errors 173
Use the RMCT for Synchronization Attempts and Status 176
Use the RMCT Event Log 178
Event Log Tab 187
System Event History 197
Keeper Status Causing Synchronize Failure 201
Partner Network Connection Lost 204
Redundancy Module Connection Lost 206
Redundancy Module Missing 207
Qualification Aborted Due to a Non-redundant Controller 208
Redundancy Module Status Indicators 209

General Troubleshooting When an error or other event occurs on the redundancy system, several tasks can
Tasks be executed to determine the cause. After an error or event, you can perform these
tasks:

• Check the module status indicators.

• View diagnostic information in the programming software.

• Access status and event information in the RMCT.

• Use RSLinx® Classic software to view network status.

• Use RSNetWorx™ for ControlNet® software to view ControlNet network


status.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 171


Chapter 9 Troubleshoot a Redundant System

Check the Module Status If an error or event occurs in the redundancy system, check the module status
Indicators indicators to determine which module is causing the error or event.

If any of the modules have status indicators that are steady or flashing red, then
examine that module status display and the RMCT or other software to
determine the cause.

Figure 48 - Steady or Flashing Red Indicators Indicate Errors on 1756-RM2 or 1756-RM2XT


Modules

CH2 CH1 OK

Figure 49 - Steady of Flashing Red Indicators Indicate Errors on 1756-RM/1756-RMXT Modules

For more information about module status indicators, see Redundancy Module
Status Indicators on page 209.

Figure 50 - Module Status Displays for Chassis with ControlLogix 5560 and ControlLogix 5570
Controllers
ControlLogix® 5560 Controller and 1756-RM Module ControlLogix 5560 Controller and 1756-RM2 Module

PRI COM OK CH2 CH1 OK

ControlLogix 5570 Controller and 1756-RM Module ControlLogix 5570 Controller and 1756-RM2 Module

PRI COM OK CH2 CH1 OK

172 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Use Programming Software To view redundancy status by using programming software, complete these steps.
to View Errors 1. Go online with the redundant controller.

2. Either click Primary or Secondary, depending on the controller you are


online with.

Primary Controller

Secondary Controller

The redundant controller ID and status are displayed.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 173


Chapter 9 Troubleshoot a Redundant System

3. If further information is required, click Controller Properties.

4. Click the Redundancy tab.

5. If controller fault details are needed, click the Major Faults and Minor
Faults tabs to view fault types and codes.
These fault bits are status bits that the controller sets. You can set these
fault bits for testing, but that is not the main purpose of these bits.

Fault details display


here:

6. If necessary, reference these resources:


• Redundant Controller Major Fault Codes
• Logix 5000™ Controllers Major and Minor Faults Programming
Manual, publication 1756-PM014 (describes all major and minor fault
codes)

174 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Redundant Controller Major Fault Codes

The fault codes that are listed and described in Table 26 are specific to redundant
controllers. For information about all controller major and minor fault codes, see
the Logix 5000 Controllers Major, Minor, and I/O Faults Programming Manual,
publication 1756-PM014.
Table 26 - Redundant Controller Major Fault Codes
Type Code Cause Recovery Method
12 32 A disqualified secondary controller was power cycled and no Verify that these conditions exist:
partner chassis or controller was found upon power-up.
• A partner chassis is connected.
• Power is applied to both redundant chassis.
• Partnered controllers have the same:
– Catalog number
– Slot number
– Firmware revision
12 33 An unpartnered controller has been identified in the new Use either of these methods:
primary chassis after a switchover.
• Remove the unpartnered controller and troubleshoot the
cause of the switchover.
• Add a partner controller to the secondary chassis,
troubleshoot the cause of the switchover, and synchronize
the system.
12 34 Before switchover, a mode switch mismatch was present. The Use either of these methods:
old primary controller was in Program mode and the mode
switch of the secondary partner was in the Run position. • Change the mode switches from Run mode to Program
mode and back to Run mode twice to clear the fault.
Instead of the switchover transitioning the new primary
controller to go to Run mode, the new primary controller Make sure that the mode switch positions for both
transitions to a faulted state after the switchover. controllers in a partnered set match.
• Use the programming software to go online with the
controllers. Then, clear the faults and change the mode
switch positions for both the controllers in the partnered
set to Run.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 175


Chapter 9 Troubleshoot a Redundant System

Use the RMCT for When troubleshooting your redundant system for anomalies with qualification
Synchronization Attempts and synchronization, check the Synchronization and Synchronization Status tabs
of the RMCT.
and Status
Recent Synchronization Attempts

The Synchronization tab provides a log of the last four synchronization attempts.
If a synchronization command was unsuccessful, the Recent Synchronization
Attempts log indicates a cause.

For more information about how to resolve the synchronization conflict, click
the attempt and view the Description in the lower box.

Figure 51 - Example of an Unsuccessful Synchronization Attempt

For more information about how to interpret the Recent Synchronization


attempts log, see Recent Synchronization Attempts Log on page 103.

176 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Module-level Synchronization Status

The Synchronization Status tab provides a module-level view of redundant


chassis and can be used to identify what module pair can be causing a
synchronization failure.

Depending on the type of synchronization failure, you may need to open the
Synchronization Status tabs for the primary and secondary redundancy modules.
• If there is a difference between major revisions of the controllers or
modules, the Compatibility column shows Incompatible, as shown in this
graphic.
Primary Chassis

Secondary Chassis

• If there is a difference between minor revisions of the controllers or


modules, the Compatibility column also shows Incompatible, as shown in
the following graphic.

Primary Chassis

Secondary Chassis

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 177


Chapter 9 Troubleshoot a Redundant System

Use the RMCT Event Log When troubleshooting your redundant system, access the Event Log to
determine the cause of an event, error, switchover, or major fault.

Interpret Event Log Information

Use this procedure to view and interpret Event Log information.

1. Open the RMCT and click the Event Log tab.

Primary Chassis

Secondary Chassis

178 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

2. If an event occurred, open the Event Log for both chassis (A and B).
3. Locate the Event line that shows the qualification code, start date, and
time of the event, in the A chassis event log.
This entry is the last time the redundancy module was working properly.
Multiple codes could be displayed if multiple errors occurred.
Additionally, if a secondary redundancy module is not present, then a code
can fail to b e seen at all. See Table 27 on page 181.
4. Then, locate the matching time entry in the B chassis event log. This entry
displays the disqualification code on the Event line.
Chassis A

PwQS and start date and start time in Chassis A.


This is the last time the redundancy module was
working properly.

Chassis B

QSwP and start date and start time in Chassis B.


This is the last time the redundancy module was
working properly, and by time, must match up
with Chassis A.

5. Work back in time (up the lines of preceding events), to locate the point
that a switchover or disqualifying event occurred.
This is the end date and time of the event, and is indicated on the Event
line in the A chassis event log, with a disqualification code that the
secondary has been disqualified, and a corresponding disqualification code
in the B chassis event log. Again, if no secondary is present, the event log
can display no secondary disqualification codes at all. See Table 27 on
page 181.
Chassis A

PwDS and end date and end time in Chassis A.


This is the time the redundancy module
experienced a disqualifying event or switchover.

Chassis B

DSwP and matching end date and end time in


Chassis B. This is the time the redundancy
module experienced a disqualifying event or
switchover.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 179


Chapter 9 Troubleshoot a Redundant System

6. To find the error that caused the disqualification, examine the range of
time in between the start of the event and the end of the event.

IMPORTANT This range of time can be large depending on how much time has passed
since the last disqualifying event.

End

Error
Start

End

Error

Start

TIP You can also use the Log Time column to identify a significant event. Scan
within a time range that corresponds to the time an event was reported or
annunciated.
In addition, you can also attempt to identify events by finding differences
between times logged. Such gaps in time often identify events that require
troubleshooting. When troubleshooting by identifying gaps in the time
entries, remember that gaps in months, days, or minutes can indicate a
significant change to the system.
Not all events that are logged are indicative of an anomaly that must be
corrected. For example, events that are classified as Minor Faults do not
warrant corrective behavior unless they occur just before a switchover,
major fault, or state change and can be identified as contributing to
successive events.

180 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

7. After you have located an event entry that is related to the anomaly you are
troubleshooting, double-click the event to view Extended Event
Information.

Double-click to view more information.

The Description provides more


information about the state change that
occurred.

No recovery method is described. This


indicates that action is not required in
response to this event.

8. View the Description and Extended Data Definitions.

The Description and Extended Data Definitions can be used to obtain


further event information and can indicate a recovery method.
Table 27 - Possible Qualification Status Indicators
Status Code Description
PwQS Primary with qualified (synchronized) secondary partner
QSwP Qualified (synchronized) secondary with primary partner
DSwP Disqualified secondary with primary partner
DSwNP Disqualified secondary with no partner
PwDS Primary with disqualified secondary partner
PwNS Primary with no secondary partner

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 181


Chapter 9 Troubleshoot a Redundant System

Export All Event Logs

To export event logs with the RMCT version 8.3.1.0 or later, follow these steps.

1. Open the RMCT on the redundancy module in the primary chassis and
click the Event Log tab.
2. Click Export All.

The Export All dialog box appears.

3. Click OK.
4. Select the communication path to the partner redundancy module with
RSLinx Classic.
The Export Event Log configuration screen appears.

5. To change the file name or save location to something other than the
default, select the Browse button.
6. Click Export.

182 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

7. Select the redundancy module in the secondary chassis.

In the following example, chassis B is the secondary chassis.

The primary chassis exports first.


In the following example, chassis A is the primary chassis.
The status displays during export.

The secondary chassis then exports.


In the following example, chassis B is the secondary chassis.

A confirmation dialog box displays when the export completes.

8. Click OK.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 183


Chapter 9 Troubleshoot a Redundant System

Export Diagnostics

IMPORTANT Only Export Diagnostics when requested to do so by Rockwell Automation


Technical Support.

You can also click Export Diagnostics if there is a module fault in the redundancy
module. Click Export Diagnostics to collect and save diagnostic data from the
redundancy module and its partner, if an unrecoverable firmware fault occurs. A
red ‘OK’ light on the front of the redundancy module indicates a nonrecoverable
fault, and a fault message scrolls across the marquee display. When you click
Export Diagnostics, information is recorded that Rockwell Automation
engineering can use to determine the cause of the fault.

Because diagnostic information is recorded for the redundancy module and its
redundancy partner, a communication path to the partner redundancy module is
also part of the process to obtain the diagnostics.

Follow these steps.

1. Click Clear Fault if it is enabled, as it can first be necessary to clear any


faults before using Export Diagnostics.
2. Click Export Diagnostics.

184 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

The Export Diagnostics dialog box appears and asks you to continue
specifying a communication path.

3. Click OK to specify the communication path via RSWho software.

The RSWho window appears.

4. Select the communication path to the partner or secondary module and


click OK.

The Export Diagnostics dialog box appears and prompts you to specify a
location to save the export file.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 185


Chapter 9 Troubleshoot a Redundant System

5. Name and save the export file.


6. Click Export.

It can take several minutes to export the data.

The Export Diagnostic Complete dialog box appears once the export has
completed.

7. Click OK.

Forward this diagnostics file to Rockwell Automation Technical Support only if


requested to do so.

Contact Rockwell Automation Technical Support

If you tried to use the event logs to troubleshoot your redundant system and are
unsuccessful, prepare to contact Rockwell Automation Technical Support by
exporting the event logs of both the primary and secondary redundancy
modules. The technical support representative who assists you uses those files to
help determine the cause of a switchover or other anomaly.

For more information about how to export the event logs, see Export Event Log
Data on page 191.

Controller Events

Occasionally, controller-related events can be logged in the RMCT Event Log. In


some cases, the events are strictly status updates and are not indicative of an
anomaly that requires troubleshooting.

In other cases, the event description can indicate Program Fault Cleared, or a
similar description of a resolved anomaly. If state changes or switchovers do not
follow these types of events, then they are not indicative of an anomaly that
requires additional troubleshooting.

If a state change or switchover follows an event that is logged for a controller in


the redundant system, use the programming software to go online with the
controller and determine the cause of the fault. For more information about how
to use programming software to troubleshoot a fault, see the section titled Use
Programming Software to View Errors on page 173.

186 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Event Log Tab


IMPORTANT Messages in the Event Log are esoteric. These messages are for Rockwell
Automation development engineering to debug redundancy system events
after the fact. Anyone who is not part of the development engineering team
can have difficulty interpreting the meaning of many of the events in the
Event Log. For user facing messages, see System Event History on page 197.

The Event Log tab provides a history of events that have occurred on the
redundant chassis.

These system events are indicated in the event logs:


• Qualification stages that are entered and completed
• Module insertion/removal
• Firmware errors
• Communication events and errors
• Configuration changes
• Other system events that affect qualification and synchronization

IMPORTANT The events that are logged in this tab are not always indicative of an error.
Many of the events that are logged are informational only.
To determine if additional action or troubleshooting is required in response
to an event, see Table 29 on page 188.

The Event Log tab can be customized to view the log specific to only one chassis
or the event logs of both redundant chassis. You can alter your view of the event
logs by changing the Auto-Update and Partner Log parameters.

Table 28 - Settings for Event Log Views


Use This Setting To
Auto-Update Keep the log from updating while you are viewing it.
Partner Log View only the event log for the module you are accessing.

Figure 52 - Settings for Event Log Views

Check On to keep the log updating automatically. Check Close to view only the log of one redundancy module.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 187


Chapter 9 Troubleshoot a Redundant System

Event Classifications

Each event that is identified and logged is classified. You can use these
classifications to identify the severity of the event and determine if additional
action is required.

Figure 53 - Event Classifications in the Event Log Tab

Event Classifications

Use Table 29 to determine what an event classification indicates and if corrective


action is required.
Table 29 - Classification Types
Classification Type Description Action Required
Configuration A redundancy module configuration parameter has been changed. No corrective action is required.
For example, if you change the Auto-Synchronization parameter from This event is provided for informational purposes and does not indicate
Always to Never, an event that is classified as Configuration is logged. serious anomaly with the redundancy system.
Command An event that is related to commands that are issued to the redundant No corrective action is required.
system has occurred. This event is provided for informational purposes and does not indicate
For example, if you change the Redundancy Module Date and Time serious anomaly with the redundancy system.
parameters, a WCT time change event of the Command classification is
logged.
Failure A failure on the redundancy module has occurred. Action can be required to determine the cause of the failure.
For example, an internal Firmware error event that is classified as a If Switchover or Major Fault event does not precede a failure, then the
Failure can be indicated in the event log. module could have corrected the error internally and additional action is
not required.
To determine if corrective action is required, double-click the event to see
Extended Event Information and the suggested recovery method, if
applicable.
Major Fault A major fault has occurred on one of the redundancy modules. Action can be required to determine the action that is necessary to correct
the fault.
Double-click the event to see Extended Event Information and the
suggested recovery method, if applicable.

188 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Table 29 - Classification Types


Classification Type Description Action Required
Minor Fault A minor fault has occurred on one of the redundancy modules. No corrective action is required.
This event is provided for informational purposes and does not indicate a
serious anomaly with the redundancy system.
Starts/Stops Various internal chassis and module processes have started or stopped. No corrective action is required.
However, if an event that is classified as a Failure, State Change, or Major
Fault occurs after the Starts/Stops event, view the Extended Event
Information of both events to determine if the events are related.
State Changes A chassis or module state change has occurred. No corrective action is required.
For example, if the chassis designation changes from being a However, if an event that is classified as a Failure, or Major Fault occurs
disqualified secondary to a qualified secondary, a State Change event after the State Changes event, view the Extended Event Information of
is logged. both events to determine if the events are related.
Switchover An event that is related to a chassis switchover has occurred. Action can be required to determine the cause of the switchover and
For example, if an Initiate Switchover command is issued, an event potential correction methods.
that is classified as Switchover is logged. Double-click the event to see Extended Event Information and the
suggested recovery method, if applicable.
Synchronization An event that is related to chassis synchronization has occurred. No corrective action is required.
For example, if the Synchronization command has been issued, a This event is provided for informational purposes and does not indicate a
Network Transitioned to Attached event is logged and classified as serious anomaly with the redundancy system.
Synchronization.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 189


Chapter 9 Troubleshoot a Redundant System

Access Extended Information about an Event

Events that are logged in the Event Log tab can have additional information
available. To access additional information about an event, double-click an event
that is listed in the log.

Double-click to open extended information.

Scroll to view
details of other
events.

View the Description


and Extended Data
Definitions.

190 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Interpret Extended Information for an Event

The information that is listed in this table can be provided (depending on the
type of event) after you have accessed the Extended Information Definition
dialog box.
.

Information Type Description


Event Information The redundancy system assigns this event information:
• Event number
• Date and time the event occurred
• Event classification
Submitter Information This information reflects information specific to the module that reported the
event. Information that is provided in this section includes the:
• Name of the module that originated the event
• Slot number of the module that originated the event
• Serial number of the module that originated the event
Event Details This section provides these additional details about the event:
• Description of the event
• Examine the Extended Data Definition, which provides an explanation of the
event and bytes, for errors
• Extended Data Bytes (in Hexadecimal) that provides further details the
event

Export Event Log Data

After you have viewed extended information about an event, you could need to
export event data. You can export data with either of these features:

• Export Selection

• Export All - Available with redundancy system, Revision 19.052 or later

Export Selection

Use this feature to export event log data for single or multiple events that occur
on a primary or secondary redundancy module.

Complete these steps to export event data for an event.

TIP If the redundancy modules are not available in RSLinx Classic software
after a fault, you must apply the recovery method that the module
indicates before attempting to export the Event Log data.

1. Launch RSLinx Classic communication software and browse to the


redundancy modules.
2. Right-click the primary redundancy module and choose
Module Configuration.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 191


Chapter 9 Troubleshoot a Redundant System

3. In the Auto-Update area, click Off to keep the log from updating.

4. In the Partner Log area, click Close.

This action closes the event log of the partner module.

5. Select one event or multiple events for which you want to export data. To
select multiple events, select a start event, press and hold SHIFT, and select
an end event.

6. Click Export Selection.

The Export Event Log dialog box opens.


7. Complete these steps on the Export Event Log dialog box.
a. Specify a file name and location or use the default name and location.
b. Check CSV (Comma-Separated Value).

TIP If you are sending the exported Event Log files to Rockwell Automation
Technical Support, you must use the CSV file type.

c. Check Include Extended Information.

TIP If you are sending the exported Event Log files to Rockwell Automation
Technical Support, include the diagnostic data and extended
information.
If you include this data, Rockwell Automation Technical Support can
analyze module and system failures more effectively.

192 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

8. Click Export.

The event log is exported. The log can take a few minutes to export.

9. If you want to export the secondary redundancy module log for a complete
system view complete step 1…step 8.

IMPORTANT If you are exporting event data to provide to Rockwell Automation Technical
Support to troubleshoot an anomaly, you must obtain the event logs for
both the primary and secondary redundancy modules. Rockwell
Automation Technical Support needs the event logs to troubleshoot the
anomaly.
If you cannot access the event log for the secondary redundancy module,
export it from the partner event log via the primary redundancy module.
We recommend that you get the logs by choosing export all with the CSV
file type.
Keep in mind, though, that the view the primary redundancy module has of
the event log of the secondary redundancy module is typically limited. To
troubleshoot an anomaly with Rockwell Automation Technical Support, you
must obtain the event log of the secondary redundancy module from the
view of the module itself.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 193


Chapter 9 Troubleshoot a Redundant System

Export All

Use this feature to export all available event log data for events in both of the
redundancy modules of the redundant chassis pair automatically.

We recommend that you use this feature when troubleshooting system-related


anomalies, where the location of a fault could have occurred a lengthy period
before the current event.

Complete these steps to export event log data for one event.

TIP If the redundancy modules are not available in RSLinx Classic software
after a fault, you must apply the recovery method that the module
indicates before attempting to export the Event Log data.

1. Launch RSLinx Classic communication software and browse to the


redundancy modules.
2. Right-click the primary redundancy module and choose
Module Configuration.
3. On the Event Log tab, click Export All.

4. At the Export All dialog box, click OK.


5. At the RSLinx Classic window, select the redundancy module in the
partner redundant chassis.
6. Complete these steps on the Export Event Log dialog box and click OK.
a. Specify a file name and location or use the default name and location.
b. Check CSV (Comma-Separated Value).

TIP If you are sending the exported Event Log files to


Rockwell Automation Technical Support, you must use the
CSV file type.

c. Check Export Diagnostic Data.


d. Check Include Extended Information.

TIP If you are sending the exported Event Log files to


Rockwell Automation Technical Support, include the
diagnostic data and extended information.
If you include this data, Rockwell Automation Technical
Support can analyze module and system failures more
effectively.

194 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

7. Click Export.

The event log is exported. The log can take a few minutes to export.

Wait for this dialog box to appear.

8. Click OK.

A .csv and a .dbg file is in the folder location specified. Make sure to
provide the .csv file to Rockwell Automation Technical Support when
troubleshooting an anomaly.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 195


Chapter 9 Troubleshoot a Redundant System

Clear a Fault

You can use the Clear Fault feature on the Event Log tab to clear major faults that
occur on a redundancy module.

With this feature, you can remotely restart the redundancy module without
physically removing and reinserting it from the chassis. The module restart clears
the fault.

IMPORTANT Export all event and diagnostic data from the module before you clear major
faults from the module. Clear Fault is active only when the redundancy
module is in a major faulted state.

Module faults are displayed on the Module Info tab. This example graphic shows
information for a module that has experienced a minor fault.

Fault details display


here:

196 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

System Event History The System Event History tab is designed to give a user with limited knowledge
of ControlLogix Redundancy systems an event history.

These events include the following:


• Qualification - The ControlLogix Redundancy system can now
switchover to the secondary redundancy chassis if necessary.
• Disqualification - The secondary redundancy chassis is not ready to accept
control of the system. The ControlLogix Redundancy system cannot
switchover.
• Switchovers - The secondary chassis has now become the primary chassis
and is now controlling the system.
• Module faults - A module has faulted in the ControlLogix Redundancy
system.

The last 20 events are logged in the System Event History tab. There are 10
events from each redundancy module.

System Event History Column Descriptions

For each event logged, this information is provided:


• Attempt - Event count, this will from N to N-19 for the maximum of 20
events.
• Initiation Time - The time and date of the event from the redundancy
module clock
• Event Class - Qualification, Disqualification, or RM FAULT
(Redundancy Module fault)
• Basic Info - Information about the origin of the event (for example,
Commanded or Auto Qualification)
• Extended Info-A - A short text description of the event
• Extended Info-B - Additional details on the event
• User Comment - An editable user comment for the event

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 197


Chapter 9 Troubleshoot a Redundant System

Edit a User Comment for a System Event

To edit the User Comment that is associated with a system event, complete these
steps.

1. Select the event.


2. Click Edit.
3. In the Description field, type your event description.

4. Click Accept Edit.


5. At the Accept Edit dialog box, click OK.

Save System Event History


If you want to save the system event log to the nonvolatile memory of the
redundancy module, click Save System History at the bottom of the System Event
tab. If you save this history, it can assist with troubleshooting the system later.

198 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Event Examples

This section contains System Event History records for typical system events.
The examples in this section are from Firmware Enhanced Redundancy Bundle
V20.056_kit1, RMCT version 8.2.1.0.
Table 30 - Manual Switchover
Event Class Basic Info Extended Info-A Extended Info-B
Switchover Commanded – –

Table 31 - Disqualify Secondary


Event Class Basic Info Extended Info-A Extended Info-B
Disqualification Commanded – –

Table 32 - Qualification Successful


Event Class Basic Info Extended Info-A Extended Info-B
Qualification Auto-Qualification Synchronized Qualification Complete
Qualification Auto-Qualification In Progress –

Table 33 - Qualification Failed Due to Incompatible Module


Event Class Basic Info Extended Info-A Extended Info-B
Qualification Auto-Qualification In Progress –
Qualification – Qual Abort Cause: module pairs are incompatible

Table 34 - Switchover Due to Module Removal from Primary


Event Class Basic Info Extended Info-A Extended Info-B
Disqualification Module Fault Chassis B SYS_FAIL_L Asserted in Secondary Chassis
Switchover Module Removal Chassis B - Slot No:2 –

Table 35 - Switchover Due to Network Cable Removal in Primary


Event Class Basic Info Extended Info-A Extended Info-B
Switchover Module Fault Chassis B - Slot No: xx(1) Possible Causes:
1. Network cable removal
2. Controller program fault
(1) xx = module slot number.

Table 36 - Switchover Due to Chassis Power Fault in Primary Chassis


Event Class Basic Info Extended Info-A Extended Info-B
Switchover Partner RM Power Failure – –

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 199


Chapter 9 Troubleshoot a Redundant System

Table 37 - Disqualification Due to Network Connection Lost between Primary and Secondary Chassis
Event Class Basic Info Extended Info-A Extended Info-B
(1)
Switchover Module Fault Chassis B - Slot No: xx Possible Causes:
1. Network Cable Removal(2)
2. Controller Program Fault
(1) xx = module slot number.
(2) This lost connection is not a network cable removal issue. The communication modules not being able to see each other over the network has caused the lost connection.

Table 38 - Disqualification Due to Partner Chassis Power Fault


Event Class Basic Info Extended Info-A Extended Info-B
Disqualification Partner RM Power Failure – –

Table 39 - Disqualification Due to Partner Chassis Module Removal


Event Class Basic Info Extended Info-A Extended Info-B
Disqualification Module Removal Chassis A - Slot No: xx(1) –
(1) xx = module slot number.

Table 40 - Disqualification Due to Partner Chassis Redundancy Module Fault


Event Class Basic Info Extended Info-A Extended Info-B
RM FAULT Major Fault Fault Code: EE05 Reset
Disqualification Partner RM Power Failure – –

Table 41 - Disqualification Due to Redundancy Module Fiber Cable Disconnected or Faulted


Event Class Basic Info Extended Info-A Extended Info-B
Disqualification RM Fiber Cable Disconnect – –

200 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Keeper Status Causing To determine if a keeper status anomaly is causing a synchronization failure, you
Synchronize Failure can view the module status display of the ControlNet modules. You can also
check the keeper status by using RSNetWorx for ControlNet software.

TIP To avoid anomalies with the Keeper Status, always reset the ControlNet
module configuration of a module being used as a replacement before
inserting and connecting the module in a ControlNet network.
For more information about how to reset the ControlNet module
configuration, see Automatic Keeper Crossloads on page 88.

Check the Module Status Display


If the module status display of the ControlNet modules in the redundant chassis
indicates these errors, you must take corrective action:
• Keeper: Unconfigured
• Keeper: Unconfigured (data format changed)
• Keeper: Unconfigured (slot changed)
• Keeper: Unconfigured (net address changed)
• Keeper: Signature Mismatch
• Keeper: None Valid on Network

Check Keeper Status in RSNetWorx for ControlNet Software

To check the status of keepers on the ControlNet network, open RSNetWorx for
ControlNet access the Keeper Status from the Network menu.

Figure 54 - Network Keeper Status

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 201


Chapter 9 Troubleshoot a Redundant System

Valid Keepers and Signatures

This example shows a Keeper Status dialog box where the ControlNet network is
composed of valid keepers and signatures.

Valid Keeper Status and Signatures

Unconfigured Keeper

The following example shows the Keeper Status dialog box where a module has
an unconfigured status. Besides the status that is shown, the module status display
indicates Keeper: Unconfigured (node address changed).

This error results when the node address of the module has been changed. After
changing the node address, the module was used as a replacement and inserted
into the redundant chassis.

Figure 55 - Keeper Status - Unconfigured

To correct this anomaly, do one of the following:


• Select the unconfigured module and click Update Keeper.
• Reschedule the ControlNet network.

202 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Keeper Signature Mismatch

This example shows ControlNet modules in the redundant chassis that do not
have the same keeper signatures. With this anomaly, the ControlNet module
display indicates Keeper: Signature Mismatch.

This anomaly can result if a ControlNet module configured for the same node of
another network is used to replace a ControlNet module with the same node
address in the redundant chassis.

Figure 56 - Keeper Status - Signature Mismatch

ControlNet modules in the redundant chassis


with different keeper signatures.

To correct this anomaly, do one of the following:


• Select the unconfigured module and click Update Keeper.
• Reschedule the ControlNet network.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 203


Chapter 9 Troubleshoot a Redundant System

Partner Network If a partner network connection between a redundant chassis pair is lost, a state
Connection Lost change or switchover can occur. These state changes can result:
• Primary with qualified secondary changes to primary with disqualified
secondary
• Qualified secondary with primary to disqualified secondary with primary

To use the Event Log to determine if a lost partner network connection caused a
state change, complete these steps.

IMPORTANT This example shows a connection that is lost over a ControlNet network. The
same steps apply if the connection is lost over an EtherNet/IP™ network.

1. Open RSLinx Classic software and access the RMCT of the primary
redundancy module.

This chassis is the chassis that was previously the secondary but is now the
primary.

Primary Chassis

Secondary Chassis

2. Locate the last event that indicates successful qualification and status.
Primary Chassis
Event Log

A switchover is
initiated.

Event indicates that


chassis state is as a
qualified secondary.

3. Open the Event Log for the secondary chassis because the cause of the
switchover is not apparent.
4. Use the time of the switchover event that is found in the primary chassis to
identify the corresponding event in the secondary chassis.

204 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

The switchover indicated in the primary chassis log occurred at 04:37:22.


Secondary Chassis Event Log

The corresponding events in the secondary chassis log indicate that the
network is not attached and that the SYS_FAIL_LActive backplane signal
is active. Both these events indicate an error in the connection of the
ControlNet module to the network.
5. Confirm the ControlNet connection error by browsing the network in
RSLinx Classic software.

This node is no longer


connected.

An attempt to access the


secondary RMCT fails and this
error is indicated.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 205


Chapter 9 Troubleshoot a Redundant System

To recover from a ControlNet network disconnection, perform the following:


• Check all ControlNet tap and trunkline connections. Correct any
disconnections or other connection anomalies.
• If the Auto-Synchronization parameter is not set to Always, use the
commands in the Synchronization tab of the RMCT to synchronize your
chassis.

For more information about troubleshooting ControlNet network anomalies, see


the ControlNet Network Configuration User Manual,
publication CNET-UM001.

To recover from a EtherNet/IP network disconnection, perform the following:


• Check all EtherNet/IP network and switch connections.
• If the Auto-Synchronization parameter is not set to Always, use the
commands in the Synchronization tab of the RMCT to synchronize your
chassis.

For more information about troubleshooting EtherNet/IP network anomalies,


see the EtherNet/IP Network Devices User Manual, publication ENET-UM006.

Redundancy Module To determine if the connection between the redundancy modules caused a
Connection Lost switchover or state change, open the Event Log of the redundancy module that is
the primary.

The Event Log clearly indicates that one of the redundancy modules has been
disconnected. In addition, the dimmed secondary chassis log indicates that the
module is not connected.

To resolve this anomaly, check the intermodule cable that connects the
redundancy modules. Verify that it is properly connected and is not severed.

Also, if the Auto-Synchronization parameter of this system is not set to Always,


use the commands in the Synchronization tab to synchronize that chassis once
the anomaly is resolved.

206 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Redundancy Module To determine if a missing redundancy module caused a state change and
Missing switchover, access the Event Log of the chassis that is the primary chassis.

Figure 57 - Event Log with Partner RM Screamed Event

RM Screamed event indicates


module removal.

Last normal event


logged.

Dimmed secondary
chassis log indicates
issue with redundancy
module.

The redundancy module logs the Partner RM Screamed event just before it is
disconnected. Depending on the cause of the missing module, the Partner RM
Screamed event can fail to be logged before the module is lost.

You can also browse to the redundancy module in RSLinx Classic software to
determine if it is connected to the network. A red X over the redundancy module
indicates that RSLinx cannot communicate with the module.

Figure 58 - Missing Redundancy Module in RSLinx Classic Software

To correct the missing module anomaly, first verify that the redundancy module
is correctly installed in the chassis and it is properly powered. Then check the
intermodule cable that connects the redundancy modules.

After you have verified that the module is installed and powered, you can need to
synchronize the chassis by using the synchronization commands in the
Synchronization tab. Use the synchronization commands if your Auto-
Synchronization parameter for the chassis is not set to Always.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 207


Chapter 9 Troubleshoot a Redundant System

Qualification Aborted Due If you place a controller that is not enabled for redundancy into the redundant
to a Non-redundant chassis, the qualification and synchronization fail. To determine if your
synchronization failure is due to a non-redundant controller, complete these
Controller steps.

1. If not already open, open the RMCT of the primary module.


2. Click the Synchronization tab and view the Recent Synchronization Status
Attempts log.
The log indicates that there is a Module Configuration Error.
3. To view the description, select the aborted attempt.

4. Click the Synchronization Status tab to check the compatibility between


modules.

All modules are indicated as being fully compatible.

5. Open the programming software and go online with the primary


controller in your system.
6. Open the controller properties and verify that Redundancy Enabled is
checked.

This controller is not


enabled for use in a
redundant system.

208 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

If Redundancy Enabled is not selected, then perform the following:


• Do one of the following:
–Remove the controllers that are not Redundancy Enabled.
–Enable the controller for redundancy and make other program
changes to accommodate redundancy.

• After you remove or correct the Redundancy Enabled setting, attempt


to synchronize your redundant system again.

Redundancy Module Status The redundancy modules have these diagnostic status indicators.
Indicators
1756-RM2 and 1756-RM2XT Status Indicators
Figure 59 - Redundancy Module Status Indicators for 1756-RM2 and 1756-RM2XT Modules

PR I M
CH2 CH1 OK
CH2 CH1 OK

Module Status Display

The module status display provides diagnostic information.


Table 42 - Module Status Display
Module Status Display Description
Four-character display executing self-test at power-up.
No action necessary.
Txxx The redundancy module is executing a self-test at power-up. (xxx represents a
hexadecimal test identification number.)
Wait for self-test to finish. No action is required.
XFER Application firmware update is in progress.
Wait for firmware update to finish. No action is required.
ERAS Boot mode - Erasing current redundancy module firmware
PROG Update mode - Updating redundancy module firmware
Wait for firmware update to finish. No action is required.
???? Resolving initial redundancy module state
Wait for state resolution to finish. No action is required.
PRIM Primary redundancy module.
The module is operating as the primary module. No action is required.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 209


Chapter 9 Troubleshoot a Redundant System

Table 42 - Module Status Display


Module Status Display Description
DISQ Disqualified secondary redundancy module.
Check the type and revision of the secondary partner module.
QFNG Qualifying secondary redundancy module.
Redundant system status. No action is required.
SYNC Qualified secondary redundancy module.
Redundant system status. No action is required.
LKNG Secondary redundancy module that is in process of locking for update.
LOCK Secondary redundancy module that is locked for update.
Exxx Major fault has occurred (xxx represents an error or fault code, with the two least-
significant characters in decimal).
Use the Error ID code to diagnose and address the error. For more information on
error codes, see Redundancy Module Fault Codes and Display Messages on
page 216.
EEPROM Update Required Onboard EEPROM is empty.
Replace the module.
BOOT Erase Error Error in erasing NVS device while updating boot image.
Cycle power to the module. If the error persists, replace the module.
BOOT Program Error Error in writing in NVS device while updating boot image.
Cycle power to the module. If the error persists, replace the module.
APP Erase Error Error in erasing NVS device while updating application image.
Cycle power to the redundancy module. If the error persists, replace the module.
APP Program Error Error in writing in NVS device while updating application image.
Cycle power to the redundancy module. If the error persists, replace the module.
CONFIG Erase Error Error in erasing NVS device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
CONFIG Program Error Error in writing in NVS device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
EEPROM Write Error Error in writing in EEPROM device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
Application Update Required The module is running boot firmware. Download the application firmware that is
obtained from the respective redundancy bundle.
ICPT A test line on the backplane is asserted. Check if the error message goes away after
removing each module, one at a time. If error persists, cycle power to the chassis, or
replace the chassis.
!Cpt All modules in the chassis do not belong to the same redundancy platform.
Untrusted Certificate Error The 1756-RM2 and 1756-RM2XT modules use signed firmware. This error appears
when either the contents of the downloaded certificate or its signature for the
downloaded firmware is invalid.
Unknown(1) Operating state is not yet determined.
Active(1) Channel is operating normally as the active channel.
Redundant(1) Channel is operating normally as the redundant channel.
Link Down(1) Channel is disconnected. Several causes could be:
– The cable is disconnected, broken, or damaged
– The signal is attenuated
– The connector is loose
– The partner 1756-RM2 module is powered down or in a major fault state

210 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

Table 42 - Module Status Display


Module Status Display Description
(1)
No SFP No transceiver was detected. Several causes could be:
– It has failed
– It is loosely connected
– It is not installed

SFP !Cpt(1) Rockwell Automation does not support the transceiver.


(1)
SFP Fail The transceiver is in a failed state.
(1) Can be present for either CH1 or CH2, but not both simultaneously.

SFP Error Message

Use only Rockwell Automation approved small form pluggable (SFP).

When an incompatible SFP is installed in the 1756-RM2 module, the


CH1/CH2 status indicator shows steady red and the RMCT software displays
the following error message in the status bar at the bottom of the screen:
‘SFP !Cpt.’

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 211


Chapter 9 Troubleshoot a Redundant System

OK Status Indicators

The OK status indicator reveals the current redundancy module state.


Table 43 - OK Status Indicator
Indicator State Description
Off No power is applied to the redundancy module.
If necessary, apply power.
Steady red One of these conditions exists:
• The redundancy module is conducting a self-test during power-up. No action
necessary.
• The redundancy module has experienced a major shutdown fault.
Cycle power to clear the fault. If the major fault does not clear, replace the
module.
Flashing red One of these conditions exists:
• The redundancy module is updating its firmware. No action necessary.
• The redundancy module has been configured improperly. Check the module
configuration and correct any issues.
• The redundancy module has experienced a major fault that can be cleared
remotely using the RMCT.
Steady green The redundancy module is operating normally. No action is required.
Flashing green The redundancy module is operating normally but is not communicating with the
other redundancy modules in the same chassis.
If necessary, establish communication with the other redundancy module.

CH1 and CH2 Status Indicators

The CH1 and CH2 status indicators reveal the following module states.
Table 44 - CH1 and CH2 Status Indicators
Indicator State Description
Off One of these conditions exists:
• No power
• RM major fault
• NVS update
Steady green(1) Channel is operating as the active channel.
Steady red One of these conditions exists:
• No transceiver plugged in
• Faulted or failed transceiver detected
• Transceiver with incorrect or vendor ID detected
Intermittent red For 1 s, then off, indicates power-up.
Flashing red One of these conditions exists:
• Redundant channel error
• No cable connection
Intermittent green(1) On for 256 ms for each packet that is received, then off. Active operating channel.
(Channel that is used for data communication between the partner 1756-RM2
modules.)
Flashing green(1) Indicates that this channel is operating as the back-up channel and is ready to
become the active channel if the current active channel fails.
(1) Can be present for either CH1 or CH2, but not both simultaneously.

212 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

1756-RM/A and 1756-RM/B Status Indicators


Figure 60 - Redundancy Module Status Indicators for 1756-RM and 1756-RMXT Modules

PR I M Module Status Display

Status Indicators
PRI COM OK
PRI COM OK

Module Status Display

The module status display provides diagnostic information.


Table 45 - Module Status Display
Module Status Display Description
Four-character display executing self-test at power-up.
No action necessary.
Txxx The redundancy module is executing a self-test at power-up. (xxx represents a
hexadecimal test identification number.)
Wait for self-test to finish. No action is required.
XFER Application firmware update is in progress.
Wait for firmware update to finish. No action is required.
ERAS Boot mode - Erasing current redundancy module firmware.
PROG Boot mode - Updating redundancy module firmware.
Wait for firmware update to finish. No action is required.
???? Resolving initial redundancy module state.
Wait for state resolution to finish. No action is required.
PRIM Primary redundancy module.
The module is operating as the primary module. No action is required.
DISQ Disqualified secondary redundancy module.
Check the type and revision of the secondary partner module.
QFNG Qualifying secondary redundancy module.
Redundant system status. No action is required.
SYNC Qualified secondary redundancy module.
Redundant system status. No action is required.
LKNG Secondary redundancy module that is in process of locking for update.
LOCK Secondary redundancy module that is locked for update.
Exxx Major fault has occurred (xxx represents an error or fault code, with the two least-
significant characters in decimal).
Use the Error ID code to diagnose and address the error. For more information on
error codes, see Redundancy Module Fault Codes and Display Messages on
page 216.
EEPROM Update Required Onboard EEPROM is empty.
Replace the module.
BOOT Erase Error Error in erasing NVS device while updating boot image.
Cycle power to the module. If the error persists, replace the module.
BOOT Program Error Error in writing in NVS device while updating boot image.
Cycle power to the module. If the error persists, replace the module.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 213


Chapter 9 Troubleshoot a Redundant System

Table 45 - Module Status Display


Module Status Display Description
APP Erase Error Error in erasing NVS device while updating application image.
Cycle power to the redundancy module. If the error persists, replace the module.
APP Program Error Error in writing in NVS device while updating application image.
Cycle power to the redundancy module. If the error persists, replace the module.
CONFIG Erase Error Error in erasing NVS device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
CONFIG Program Error Error in writing in NVS device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
EEPROM Write Error Error in writing in EEPROM device while updating configuration log image.
Cycle power to the redundancy module. If the error persists, replace the module.
Application Update Required The module is running boot firmware. Download the application firmware that is
obtained from the respective redundancy bundle.
ICPT A test line on the backplane is asserted. Check if the error message goes away after
removing each module, one at a time. If error persists, cycle power to the chassis, or
replace the chassis.
!Cpt All modules in the chassis do not belong to the same redundancy platform.

214 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

OK Status Indicators

The OK status indicator reveals the current redundancy module state.


Table 46 - OK Status Indicator
Indicator State Description
Off No power is applied to the redundancy module.
If necessary, apply power.
Steady red One of these conditions exists:
• The redundancy module is conducting a self-test during power-up.
• No action necessary.
• The redundancy module has experienced a major fault.
Cycle power to clear the fault. If the major fault does not clear, replace the
module.
Flashing red One of these conditions exists:
• The redundancy module is updating its firmware.
• No action necessary.
• The redundancy module has been configured improperly.
• Check the module configuration and correct any issues.
• The redundancy module has experienced a minor failure.
Cycle power to clear the fault. If the major fault does not clear, replace the
module.
Steady green The redundancy module is operating normally. No action is required.
Flashing green The redundancy module is operating normally but is not communicating with the
other redundancy module.
If necessary, establish communication with the other redundancy module.

Communication Status Indicator

The communication status indicator indicates activity on the redundancy


module communication between chassis in the redundant chassis pair.
Table 47 - Communication Status Indicator
Indicator State Description
Off One of these conditions exist:
• No power is applied to the module.
• Apply power to the module.
• There is no communication between redundancy modules in the redundant
chassis pair.
Diagnose the redundancy configuration to determine why no communication is
taking place.
Red < 1 second The module has been started and has established partner communication.
No action is required.
Steady red The module has experienced a critical communication failure.
Cycle power to clear the fault. If the major fault does not clear, replace the module.
Flashing green > 250 ms Communication activity is present.
No action is required.

Chassis State Status Indicator

The Chassis State (PRI) status indicator identifies whether the chassis is primary.
The PRI status indicator on the primary redundancy module remains steady
green, and the PRI status indicator on the secondary redundancy module
remains off.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 215


Chapter 9 Troubleshoot a Redundant System

Redundancy Module Fault Codes and Display Messages

Redundancy modules can experience any of these faults.


Table 48 - Module Fault Codes
Fault Type Description
Minor Recoverable This fault type results in these conditions:
• The fault does not stop redundancy operations and provides you with a recovery
mechanism.
• The module can clear some minor recoverable faults on its own.
Minor This fault type results in these conditions:
Nonrecoverable • The fault does not stop redundancy operations.
• No recovery mechanism is available.
Major Recoverable The fault impacts redundancy operations, although the effect is not always
immediate.
For example, if the fault occurred in the secondary redundancy module, the
secondary chassis disqualifies and is not able to take over control if the primary
redundancy module fails
Major This fault type results in these conditions:
Nonrecoverable • This is a critical fault. Redundancy operations cease.
• A switchover can occur.
• No recovery mechanism is available.
• The module can require replacement.

When the redundancy module experiences a fault, indication of that fault type is
presented in these methods:

• Event log

• Module Status Display

IMPORTANT This section describes a subset of module fault codes you can see in the
event log or Module Status Display.
If you see a fault code that is not included in this chapter, contact Rockwell
Automation for assistance in troubleshooting that fault.

Event Log When Redundancy Module Experiences Fault

The redundancy module logs the fault type in its event log in NVS memory. You
access the event log through the RMCT to troubleshoot the fault yourself or with
assistance from Rockwell Automation Technical Support for troubleshooting the
fault.

Module Status Display

A character string scrolls across the Module Status Display to indicate the fault
type. The character string displays the fault type in either of these ways:

• Two to four-character word abbreviations

• Alpha numeric codes

216 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Troubleshoot a Redundant System Chapter 9

This table describes the two to four-character word abbreviations.


Table 49 - Major Fault Code Messages
1st Word 2nd Word 3rd Word 4th Word Error Description
CFG LOG ERR Configuration log error. No action is required.
COMM RSRC ERR Communication resource error. Reset the redundancy
module.
COMM RSRC ERR PRT1 Port1 Communication resource error on Backplane.
Reset the redundancy module and check the chassis.
COMM RSRC ERR PRT2 Port2 Communication resource error on redundancy
link. Complete these tasks:
1. Reset the module.
2. Check the cable.
COMM ERR PRT1 Port1 Communication error, Backplane
communication. Check or replace the chassis.
COMM ERR PRT2 Port2 Communication error on the redundancy link.
Check or replace the single-mode cable.
COMM ERR General Communication Error. No action is required.
DUPL RM Duplicate redundancy module. This module is not in
control. Remove this redundancy module.
EVNT LOG ERR Event Log Error. No action is required.
FRMW ERR Firmware error. Update the firmware.
HDW ERR Hardware failure. Replace the module.
OS ERR Operating system error. Replace the module.
RM PWR DOWN The redundancy module Power Down, Module
detected a DC_Fail condition.
Check the other modules in the chassis.
WDOG ERR Watchdog time out. Reset the module.
WDOG FAIL Watchdog task failed its status check. Replace the
module.

The fault code is a four-character alphanumeric string. Valid characters are 0…9
and A through Z, except S and O. The first character is always E. Each firmware
subsystem within the redundancy module is assigned a range of fault codes. Each
subsystem assigns fault codes within its range.

If you encounter one of these error codes, record the Exxx code and contact
Rockwell Automation Technical Support.

Recovery Messages
For certain faults, the module status display provides recovery instructions. Up to
four, four-character words are displayed.
Table 50 - Recover Messages
Recovery Instruction Code Description
RPLC MOD Replace the redundancy module only.
RSET RM2 or RSET MOD Reset the redundancy module only.
REMV MOD Remove the redundancy module only.
SEAT MOD Reinsert only the redundancy module into the chassis.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 217


Chapter 9 Troubleshoot a Redundant System

Notes:

218 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Appendix A

Convert from a Non-redundant System

Topic Page
Update the Configuration in Programming Software 220
Replace Local I/O Tags 222
Replace Aliases to Local I/O Tags 223
Remove Other Modules from the Controller Chassis 224
Add an Identical Chassis 225
Upgrade to Redundancy Firmware 225
Update the Controller Revision and Download the Project 225

When converting from a non-redundant to a redundant system, first consider the


following:
• You can use only Studio 5000 Logix Designer® versions 16, 19, 20, 24, 30,
31, 32, or 33 in a redundancy system.
• The redundant chassis pair has controller, communication module and
I/O module restrictions.

See Chapter 1, About ControlLogix Redundancy Systems for additional


information.

Complete the tasks in this section to convert a non-redundant ControlLogix®


system to a redundancy system.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 219


Appendix A Convert from a Non-redundant System

Update the Configuration These steps provide an overview of the process that is required to update the
in Programming Software I/O Configuration tree in the programming software.

1. If you have I/O in the chassis with the controller, add a ControlLogix
communication module to the appropriate network because I/O modules
are not permitted in a redundant chassis.

You can now move the I/O modules to the new chassis in the I/O
Configuration tree.

The I/O can be placed in


this chassis.

220 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Convert from a Non-redundant System Appendix A

2. Copy the I/O modules and paste them into the chassis of the newly added
communication module.

Paste I/O into the new


ControlNet® chassis.

3. Delete the I/O modules from the controller chassis configuration.

4. Continue by completing the procedures to Replace Local I/O Tags and to


Replace Aliases to Local I/O Tags.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 221


Appendix A Convert from a Non-redundant System

Replace Local I/O Tags If you have moved I/O modules out of the local controller chassis and into the
remote I/O chassis, complete these steps to find and replace the local I/O tags in
your program.

1. Open the routine where the local I/O tags must be updated.
2. Press CTRL+H to open the Replace in Routines dialog box.

3. From the Find What pull-down menu, choose Local:.


4. From the Replace With pull-down menu, choose the name of the
communication module where the remote I/O was placed.
5. From the Find Where pull-down menu, choose All Routines.
6. Click Find Within >>.
7. Select Ladder Diagrams.
8. Check Instruction Operands.

9. Click Replace All.

The find/replace is completed and the results are indicated in the Search
Results tab.

222 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Convert from a Non-redundant System Appendix A

Replace Aliases to Local I/O If your program uses alias tags for the I/O modules that you are moving,
Tags complete these steps to replace alias tags.

1. In the programming software, open the Controller Tags.


2. Press CTRL+H to open the Replace Tags dialog box.

3. From the Find What pull-down menu, choose Local:.


4. From the Replace With pull-down menu, choose the name of the
communication module where the remote I/O was placed.
5. From the Find Where pull-down menu, choose All Tags.
6. Click Find Within >>.
7. Select Alias and click Replace All.

The Search Results tab indicates the changed tags.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 223


Appendix A Convert from a Non-redundant System

Remove Other Modules If modules other than those modules listed in Table 1 are in the controller chassis,
from the Controller Chassis you must remove them. You can use these modules in ControlLogix redundancy
systems. Not all components are compatible with all redundancy system
revisions. To make sure of component compatibility, see the release notes specific
to your redundancy system revision in the PCDC at:
http://www.rockwellautomation.com/global/support/pcdc.page.
Table 1 - Components Available for Use in a Redundant Chassis Pair
Module Type Cat. No. Available with Available with Available with Available with Available with
Redundancy System: Redundancy System: Redundancy System: Redundancy System: Redundancy System:
Revision 31.05x, Revision 24.05x, Revision 20.05x Revision 19.05x Revision 16.08x
Revision 32.05x Revision 30.05x
Revision 33.05x
Communication 1756-CN2(1) x x x x x
modules
1756-CN2R(1) x x x x x
1756-CN2RXT x x x x x
1756-EN2F x x x - -
1756-EN2T x x x x x
1756-EN2TR x x x x -
1756-EN2TP x - - - -
1756-EN2TXT x x x x x
Controllers 1756-L61, 1756-L62, - - x x x
1756-L63, 1756-L64
1756-L63XT - - x x x
1756-L65 - - x x -
1756-L71 x x x - -
1756-L72, 1756-L73, x x x x -
1756-L74, 1756-L75
1756-L73XT x x x x -
Redundancy 1756-RM - - x x x
modules
1756-RMXT - - x x x
1756-RM2 x x x x x
1756-RM2XT x x x x x
(1) You can use series B or later modules.

224 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Convert from a Non-redundant System Appendix A

Add an Identical Chassis After you have configured your primary chassis with the modules that are listed
in Table 1, add an identical chassis that contains the same modules with the same
module-placement.

For more information about chassis configuration, see the section titled
Redundant Chassis on page 21.

Upgrade to Redundancy Once you have made the appropriate changes to your system configuration and
Firmware program, and have added the identical chassis, upgrade your system firmware.

For information about how to upgrade the redundant system firmware, see
Update Redundant Firmware on page 58.

Update the Controller After you upgrade the firmware, use programming software to access the
Revision and Download the controller properties and update the controller major revision to match the
redundancy firmware major revision you are using.
Project

Once you have updated the controller firmware revision and saved the changes,
download the updated program to the controller.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 225


Appendix A Convert from a Non-redundant System

Notes:

226 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Appendix B

Redundancy Object Attributes

Table of Redundancy Use this table of redundancy object attributes as a reference when programming
Object Attributes to obtain the status of your redundancy system.

For this information Get this attribute Data GSV/SSV Description


Type
Redundancy status of the entire ChassisRedundancyState INT GSV If Then
chassis.
16#2 Primary with synchronized secondary
16#3 Primary with disqualified secondary
16#4 Primary with no secondary
16#10 Primary locked for update
Redundancy state of the partner PartnerChassis INT GSV If Then
chassis. RedundancyState
16#8 Synchronized secondary
16#9 Disqualified secondary with primary
16#E No partner
16#12 Secondary locked for update
Redundancy status of the controller. ModuleRedundancy State INT GSV If Then
16#2 Primary with synchronized secondary
16#3 Primary with disqualified secondary
16#4 Primary with no secondary
16#6 Primary with synchronizing secondary
16#F Primary locking for update.
16#10 Primary locked for update
Redundancy state of the partner. PartnerModule INT GSV If Then
RedundancyState
16#7 Synchronizing secondary
16#8 Synchronized secondary
16#9 Disqualified secondary with primary
16#E No partner
16#11 Secondary locking for update
16#12 Secondary locked for update
Results of the compatibility checks CompatibilityResults INT GSV If Then
with the partner controller.
0 Undetermined
1 No compatible partner
2 Fully compatible partner

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 227


Appendix B Redundancy Object Attributes

For this information Get this attribute Data GSV/SSV Description


Type
Status of the synchronization Qualification InProgress INT GSV If Then
(qualification) process.
-1 Synchronization (qualification) is not in progress.
0 Unsupported
1...99 For modules that can measure their completion percentage, the
percent of synchronization (qualification) that is complete.
50 For modules that cannot measure their completion percentage,
synchronization (qualification) is in progress.
100 Synchronization (qualification) is complete.
Mode switch settings of the KeyswitchAlarm DINT GSV If Then
controller and its partner match or
do not match. 0 • The mode switches match
OR
• No partner is present.
1 Mode switches do not match
Position of the mode switchmode PartnerKeyswitch DINT GSV If Then the mode switch is in
switch of the partner.
0 Unknown
1 RUN
2 PROG
3 REM
Status of the minor faults of the PartnerMinorFaults DINT GSV This bit Means this minor fault
partner (if the
ModuleRedundancyState indicates 1 Power-up fault
that a partner is present).
3 I/O fault
4 Problem with an instruction (program)
6 Periodic task overlap (watchdog)
9 Problem with the serial port
10 Low battery or issue with the energy storage module
Mode of the partner. PartnerMode DINT GSV If Then
16#0 Power up
16#1 Program
16#2 Run
16#3 Test
16#4 Faulted
16#5 Run-to-program
16#6 Test-to-program
16#7 Program-to-run
16#8 Test-to-run
16#9 Run-to-test
16#A Program-to-test
16#B Into faulted
16#C Faulted-to-program

228 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Redundancy Object Attributes Appendix B

For this information Get this attribute Data GSV/SSV Description


Type
In a pair of redundant chassis, PhysicalChassisID INT GSV If Then
identification of a specific chassis
without regard to the state of the 0 Unknown
chassis.
1 Chassis A
2 Chassis B
Slot number of the 1756-RM module SRMSlotNumber INT GSV
in this chassis.
• Size of the last crossload. LastDataTransfer Size DINT GSV This attribute gives the size of data that was or would have been crossloaded in
• Size of the last crossload if you the last scan in the number of DINTs (4-byte words).
had a secondary chassis. The secondary chassis does not have to be connected or online. If you do not have
a secondary chassis, the number of DINTs that would have been crossloaded are
indicated.
• Size of the biggest crossload. MaxDataTransfer Size DINT GSV This attribute gives the biggest size of the LastDataTransfer Size attribute in DINTs
• Size of the biggest crossload if SSV (4-byte words).
you had a secondary chassis. The secondary chassis does not have to be connected or online. If you do not have
a secondary chassis, the largest number of DINTs that would have been
crossloaded are indicated.
If you must reset this value, use an SSV instruction with a Source value of 0.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 229


Appendix B Redundancy Object Attributes

Notes:

230 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Appendix C

Redundancy System Checklists

Topic Page
Chassis Configuration Checklist 231
Remote I/O Checklist 232
Redundancy Module Checklist 232
ControlLogix Controller Checklist 233
ControlNet Checklist 234
EtherNet/IP Module Checklist 235
Project and Programming Checklist 236

Chassis Configuration Checklist


 Requirement
Chassis that is used for the redundant pair are the same size, for example, both are 1756-A7, 7-slot chassis.
Only these modules are used in the redundant chassis:
• ControlLogix® controllers, catalog numbers 1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73, 1756-L73XT,
1756-L74, 1756-L75
– ControlLogix 5560 and ControlLogix-XT™ 5560 controllers are not compatible with redundancy systems that have firmware revision 24.50 or greater.
• ControlNet® communication modules, catalog numbers 1756-CN2, 1756-CN2R, and 1756-CN2RXT
• EtherNet/IP™ communication modules, catalog numbers 1756-EN2F(1), 1756-EN2T, 1756-EN2TP(2), 1756-EN2TR(3), and 1756-EN2TXT.
• Redundancy modules, catalog numbers 1756-RM, 1756-RMXT, 1756-RM2, 1756-RM2XT
Each chassis of the pair is composed of identical modules that are of identical redundancy firmware revisions and catalog numbers(4).
Partner modules are placed in same slots of both chassis of the redundant pair (for example, the 1756-L63 is placed in slot 0 of both chassis).
I/O modules are not placed in the redundant chassis.
Seven or fewer communication modules of any type or combination are used in each redundant chassis.
(1) You can use the 1756-EN2F module only with a redundancy system, revision 20.054 or later.
(2) You can use the 1756-EN2TP module only with a redundancy system, revision 31.052 or later.
(3) You can use the 1756-EN2TR module only with a redundancy system, revision 19.052 or later.
(4) There are some exceptions to this requirement. For more information, see Redundant Chassis on page 21.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 231


Appendix C Redundancy System Checklists

Remote I/O Checklist


 Requirement
I/O is not placed in redundant chassis.
I/O is connected to the redundant chassis by using one of these networking options:

• ControlNet connections to the same ControlNet network as the redundant controller chassis, without bridging.

• EtherNet/IP connections to the same EtherNet/IP network as the redundant controller chassis, without bridging. If in the I/O tree of the redundancy controller, all
I/O and consumed tag connections must be multicast connections. The I/O tree of the redundancy controller can contain produced unicast tags that remote devices
consume.

• A DeviceNet® network that is connected through a 1756-DNB DeviceNet communication module in a remote, that is, non-redundant, chassis.

• A universal remote I/O or Data Highway Plus™ network that is connected by using a 1756-DHRIO module in a remote (non-redundant) chassis.

Redundancy Module Checklist


 Requirement
One redundancy module is placed in the same slot of each redundant chassis.
Series A and B redundancy modules are fully compatible. Therefore, you can use any combination of them in a partnered set, for example, a 1756-RM/A module in the
primary chassis and a 1756-RM/B module in the secondary chassis. However, the best scan performance occurs when two Series B redundancy modules are used with
ControlLogix 5570 controllers.

IMPORTANT The scan time is slightly extended when you downgrade a Series B redundancy module to a Series A module with a ControlLogix 5570
controller in the redundant chassis pair. In this case, raise the task watchdog limits by a factor of ~2x before downgrading. Thereafter, you can
retune the limits that are based on the updated scan time numbers.

ControlLogix 5560 controllers that are used with a combination of Series A and Series B redundancy modules in the redundant chassis pair
have the same performance a as if only Series A redundancy modules are used in the redundancy chassis pair. This result is regardless of the
primary or secondary redundancy state.

A fiber-optic cable connects the redundancy modules in the redundant chassis pair. The following are catalog numbers of fiber-optic cable you can order from
Rockwell Automation:
• 1756-RMC1 (1 m, 3.28 ft)
• 1756-RMC3 (3 m, 9.84 ft)
• 1756-RMC10 (10 m, 32.81 ft)
If necessary, you can make your own fiber-optic cable that is up to 4 km (13,123.36 ft) for the 1756-RM/B module or 10 km (32,808.40 ft) for the 1756-RM2 module.

232 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Redundancy System Checklists Appendix C

ControlLogix Controller Checklist


 Requirement
Identical ControlLogix controllers are placed in the same slot of both chassis of the redundant pair.
Partnered controllers are identical in redundancy firmware revision.
Within each redundant chassis, one or two (maximum) of these controllers(1) are used:
• 1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64(2), 1756-L65
• 1756-L71, 1756-L72, 1756-L73, 1756-L73XT, 1756-L74, 1756-L75
Do not combine ControlLogix 5560 and ControlLogix 5570 controllers in a redundant chassis.
ControlLogix 5560 and ControlLogix-XT 5560 controllers are not compatible with redundancy systems that have firmware revision 24.052_kit1 or later.
Each controller in the redundancy chassis has enough memory to store twice the amount of controller data and I/O memory(3). See Knowledgebase Article,
Understanding ControlLogix Redundancy Memory Usage. A login is required to access the article.
Eight controller connections are reserved for redundancy use.
(1) The controllers can be of any series as long as the firmware revisions and catalog numbers are identical.
(2) When using ControlLogix redundancy system, revision 16.081 or earlier, you cannot use two 1756-L64 controllers in the same chassis. You can, however, use a 1756-L64 controller in the same chassis
as a 1756-L61, 1756-L62, or 1756-L63 controller.
(3) ControlLogix 5580 controllers that are enabled for redundancy do not have memory constraints.ControlLogix 5580 controllers that are enabled for redundancy experience no reduction in memory
from a standard use ControlLogix 5580 controller.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 233


Appendix C Redundancy System Checklists

ControlNet Checklist
 Requirement
ControlNet Module
Identical ControlNet modules are placed in the same slot of both chassis of the redundant pair.
ControlNet modules are identical in redundancy firmware revision and in catalog number.
Only the 1756-CN2, 1756-CN2R, or 1756-CN2RXT ControlNet modules are used.
Partnered ControlNet modules both have identical keeper information as explained in the ControlNet Network Configuration User Manual, publication CNET-UM001.
Three connections of the ControlNet module are appropriately reserved for redundancy system use.
ControlNet Network
USB ports of communication modules in the redundant chassis are not used while the system is running (online).
At least four ControlNet nodes are used on the ControlNet network. That is, at least two ControlNet nodes are on the ControlNet network along with the two
ControlNet modules in the redundant chassis.
These requirements apply to at least one ControlNet node:
• It is not in the redundant chassis pair.
• It uses a node address lower than the ControlNet node addresses of modules in redundant chassis pair.
ControlNet module partners in the redundant chassis have the following:
• Node address switches set to the same address (for example, the switches of both modules are set to node address 13).
• Two consecutive node addresses reserved (for example, nodes 13 and 14) to accommodate a switchover. The primary ControlNet module can have an even or odd-
numbered node address.
The ControlNet network is scheduled by using techniques that are described in the ControlNet Network Configuration User Manual, publication CNET-UM001.(1)
Devices on other communication networks are bridged to the ControlNet network appropriately.
ControlNet HMI
A ControlNet network or a ControlNet-to-EtherNet/IP gateway is used to connect to HMI because your system requires that HMI be updated immediately after a
switchover.
• PanelView™ Standard terminal, PanelView 1000e, or 1400e terminal
For an unscheduled network, 4 HMI terminals per controller are used.
For a scheduled network, any number of terminals within the limits of the ControlNet network are used.
• PanelView Plus terminal, VersaView® industrial computer that runs a Windows CE operating system
RSLinx® Enterprise software, version 5.0 or later, is used.
Within each controller and communication module, five connections for each PanelView Plus or VersaView terminal are reserved.
• FactoryTalk® View SE software with RSLinx communication software, version 2.52 or later, RSView®32 software, FactoryTalk Linx software, version 5.0
The number of RSLinx servers that a controller uses is limited to 1…4 (maximum).
(1) Unscheduled ControlNet networks can be used, however, certain use considerations must be made. See Chapter 5, Configure the ControlNet Network on page 79.

234 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Redundancy System Checklists Appendix C

EtherNet/IP Module Checklist


 Requirement
EtherNet/IP Module
Identical EtherNet/IP communication modules are placed in the same slot of both chassis of the redundant chassis pair.
EtherNet/IP communication modules are one of these catalog numbers:
• 1756-EN2F(1), 1756-EN2T, 1756-EN2TP(2), 1756-EN2TR(3), and 1756-EN2TXT
EtherNet/IP Network
With firmware revision 19.052 and later, you can use an EtherNet/IP network for I/O and produced/consumed tags.
With firmware revisions 16.081 and earlier, an EtherNet/IP network does not support I/O or produced/consumed tags.
Redundancy systems support unicast produced tags. Unicast consumed tags are not supported in redundancy systems.
USB ports of communication modules in the redundant chassis are not used while the system is running (online).
IP addresses of devices on the EtherNet/IP network are static and IP address swapping is enabled.(4)
EtherNet/IP HMI
Data server communication recovery time is the time during a switchover from primary to secondary, when tag data from the controller is unavailable for reading or
writing. See Data Server Communication Recovery Time Reduction During a Switchover on page 17.
IMPORTANT: This feature requires FactoryTalk Linx software, version 5.50.04 or later.
• PanelView Standard terminal
None (the use of the PanelView Standard terminal in a redundant system requires the same considerations as a non-redundant system).
• PanelView Plus terminal, VersaView industrial computer that runs a Windows CE operating system
FactoryTalk Linx software, version 3.0 or later, is used.
Within each of the controllers and communication modules, five connections for each PanelView Plus or VersaView terminal are reserved.
• FactoryTalk View SE software with FactoryTalk Linx software
FactoryTalk Linx software, version 3.0 or later is used.
IP address swapping is used.
HMI and both redundant chassis are on the same subnet.
• FactoryTalk View SE software with RSLinx software, version 2.x, RSView32 software, Any other HMI client software that uses RSLinx software, version 2.x
The number of RSLinx servers that a controller uses is limited to 1…4 (maximum).
(1) You can use the 1756-EN2F module only with a redundancy system, revision 20.054 or later.
(2) You can use the 1756-EN2TP module only with a redundancy system, revision 31.052 or later.
(3) You can use the 1756-EN2TR module only with a redundancy system, revision 19.052 or later.
(4) Other IP address configurations are permitted, but require additional considerations. For more information, see IP Address Swapping on page 66.

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 235


Appendix C Redundancy System Checklists

Project and Programming Checklist

Also see the ControlLogix Controller Checklist on page 233.

 Requirement
The Redundancy Module Date and Time has been set by using the RMCT (this in not required, but strongly recommended).
One project is created by using programming software and is downloaded to the primary controller.(1)
Redundancy is enabled within the Redundancy tab of the Controller Properties dialog box.
Time synchronization is not required for redundancy to function. If your application requires Time synchronization, then:
• Enable Time synchronization on the Date/Time tab of the Controller Properties dialog box.
• Select Time Sync and Motion on the Module Definition dialog box for the Ethernet module that is located in the local chassis.
Task configuration is either:
• One continuous task within the project.
or
• Multiple periodic tasks with only one task at the highest priority. Also, multiple tasks are structured at all different priorities and periods so that the fewest possible
separate tasks are used.
The redundant controller program does not contain:
• Event tasks.
• Inhibited tasks.
Programming specific to critical I/O that must be bumpless is placed in the highest-priority user task according to your task configuration.

If you use this task structure Then programming specific to bumpless I/O is in
One continuous task The continuous task.
One continuous task and one or more periodic tasks The highest-priority periodic task where only that one task is at the
highest priority.
Multiple periodic tasks The highest-priority periodic task where only that one task is at the
highest priority.

For ControlLogix 5560 controllers, the task watchdog is (2 * maximum_scan_time) + 150 ms when using ControlNet I/O and (2* maximum_scan_time) + 100 ms
when using Ethernet I/O, where maximum_scan_time is the maximum scan time for the entire task to complete when the redundant controllers are synchronized.
To calculate watchdog time for ControlLogix 5570 controllers, see Minimum Value for the Watchdog Time on page 148.
Scan time is minimized by using these techniques when possible:
• Unused tags are eliminated.
• Arrays and user-defined data types are used instead of individual tags.
• Redundancy data is synchronized at strategic points by using the Synchronize Data after Execution setting in the Program Properties dialog box.
• Programming is written as compactly and efficiently as possible.
• Programs are executed only when necessary.
• Data is grouped according to frequency of use.
• DINT tags are used instead of SINT or INT tags.
For produced/consumed data, the communication module in the remote chassis that holds the consuming controller uses the Comm Format: None.
Critical messages from a remote chassis to redundant chassis use cached connections.
Active tags on scan per controller are less than 10,000 tags/second.
(1) The project that is loaded on the primary controller is automatically crossloaded to the secondary controller when synchronization occurs.

236 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Index

Numerics configuration
1715 Redundant I/O systems 12, 14, 36 controller 112
EtherNet/IP modules 75
1756-CN2x modules 25 HMI 38
1756-EN2T remote I/O 36
sockets 72 RMCT
1756-EN2TR determine if needed 92
sockets 72 Configuration tab 98 - 100
1756-EN2Tx modules 25 connections
1756-RM communication 26
status indicators 172 controller 24
1756-RM and 1756-RMXT modules 24 continuous task
1756-RM2 46, 50 execution 117
recommended 117
1756-RM2/A
ControlFLASH 44, 59
ControlLogix 5570 123
crossload 122 controller 22
dual fiber ports 57 configure redundancy 112
status indicators 172, 209 connections 24
1756-RM2XT 46, 50 enable user program 100
event in Event Log 209
status indicators 209 save project 90
status 173
A troubleshoot
non-redundant 208
Array (File)/Shift instructions 130 use multiple 123
Auto-Synchronization 99 controller logging 159
ControlLogix 5560 233
ControlLogix 5570 233
B 1756-RM2/A 123
BOOTP/DHCP utility 75 memory usage slider 158
ControlNet
CPU usage 169
C keeper crossload 90
keeper status 88
calculate
module
task watchdog 148 check status 168
CH1 monitor CPU usage 169
status indicators 212 network update time 81
CH2 node requirements 30 - 32
status indicators 212 overview 30 - 33
chassis 44 produce/consume connections 79
designate 61 redundant media 33
ID 100 remote I/O 14
install 45 requirements 30 - 33
module placement 45 sample programs 167, 169
primary 15 schedule
secondary 15 existing network 87
chassis configuration list 231 new network 84
troubleshoot
CIP Sync technology 12, 69 keeper status 201
clearing a fault 196 lost connection 204
communication unscheduled 83
EtherNet/IP delay 28 conversion
module connections 26 non-redundant to redundant 62
modules 25 convert
communication module 44 nonredundant to redundant 219 - 225
unicast 19 CPU usage
components Ethernet/IP 65
overview 13
concise, program 128

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 237


Index

crossload 46 execution
1756-RM2/A 122 continuous task 117
ControlNet keepers 90 periodic task 119
default 117 export data for a single event 191 - 193
estimate 121 export data for all events 194 - 195
redundancy object attributes 121 export diagnostics button 184
redundant system 15
scan time 121 export event log 191 - 195
extended event information 190

D
Data Highway Plus 35 F
date and time 100 FactoryTalk software 12
designate fiber-optic cable 56
primary chassis 61 redundancy channels 54
designation fiber-optic communication cable 44
chassis 61 firmware 58
conduct 15 revision 41
qualification after 62 signed and unsigned 13
DeviceNet 35 update 58 - 61
DSwNP firmware bundle 43
qualification status indicators 181 flash upgrade 58
DSwP
qualification status indicators 181
dual fiber ports H
1756-RM2/A 57 hardware
duplex setting 75 install 45
Human-Machine-Interface (HMI) 38 - 40
use over ControlNet 39
E use over EtherNet/IP 38
electrostatic discharge 47
enable
user program control 100
I
environmental considerations 43 I/O
EtherNet/IP 1715 Redundant I/O systems 12, 36
1715 Redundant I/O systems 12 in redundancy system revisions 14
configure module 75 multicast 232
delay 28 over EtherNet/IP network 12
duplex setting 75 placement 14, 36
IP address swapping 66 - 68 install
overview 34 hardware 44, 45
produce/consume connections 72 power supply 45
remote I/O 12, 14 primary chassis 45 - 52
requested packet interval 65 redundancy module 46
requirements 34 secondary chassis 52
set address 75 installation instructions 51
troubleshoot IP address
lost connection 204 BOOTP/DHCP utility 75
use of CIP Sync technology 69 consecutive 66
with HMI 38 plan 75
Ethernet/IP programming software 75
CPU usage 65 RSLinx communication software 75
Event Log set 75
controller event 209 swap 66
qualification events 63 swapping 66 - 68
RMCT 178 switches 75
Event Log tab 187 - 196
clearing a fault 196
export data for all events 194 - 195 K
export single event data 191 - 193 keeper
extended event information 190 crossloads 90
status 88

238 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Index

mismatch 203 O
module status display 201
RSNetWorx for ControlNet software 201 online edits 152 - 158
unconfigured 202 finalize 155
valid 202 reserve memory 157, 158
troubleshoot 201 retain edits 154
test edits 153
operations
L chassis designation 15
laser radiation ports 50 crossload 15
qualification 15
log redundancy system 15
Recent Synchronization Attempts 102 switchover 15
logic, scan-dependent 131 synchronization 15
optical ports 48
M
memory usage slider P
ControlLogix 5570 158 parallel redundancy protocol 77
mode switch Partial Import Online 152
REM 59 periodic task
Module Info tab 96 - 97
execution 119
module placement recommended 117
chassis 45 power supply 27, 44
module status display 164 install 45
monitor primary chassis 15
ControlNet designate 61
sample programs 167, 169 designation 61 - 63
motion installation 45 - 52
unsupported feature 13 produce/consume connections
MSG instruction 144 over ControlNet 79
multicast over EtherNet/IP 72
I/O 232 produced tags
unicast 72
program
N crossload
network 83 default 117
scan time 121
ControlNet
enable user control 100
monitor CPU usage 169 finalize test edits 155
overview 30 - 33
logic after switchover 141
Data Highway Plus 35 maintain data integrity 130 - 133
DeviceNet 34, 35
manage tags 124
EtherNet/IP 34
messages for redundancy commands 142 -
overview 28 - 29
146
keeper 88
monitor system status 161
keeper crossload 90
online edits 152 - 158
Remote I/O 34
optimize task execution 134 - 136
schedule
Partial Import Online 152
existing 87
reserve memory 157, 158
new 84
scan time
Universal Remote I/O 35
minimize 123 - 129
update time 81
synchronization
network update time 81
default 117
non-redundant controller 208 tags 124
non-redundant to redundant task type 117
conversion 62 test edits 153
nonredundant, convert from 219 - 225 use concise 128
programming software 75
project
save 90
PsDS
qualification status indicators 181

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 239


Index

PwNS redundancy system


qualifcation status indicators 181 chassis 21
PwQS communication modules 25
qualification status indicators 181 components 13
controllers 22
features 12
Q operations 15
power supply 27
QSwP quick start 43
qualification status indicators 181 redundancy modules 24
qualification restrictions 19
after designation 62 using ControlNet 30 - 33
check in RMCT 166 using EtherNet/IP 28 - 29
check status 164 redundant chassis
description of 15 designate 61
status via RMCT 63 example 20, 21
troubleshoot redundant fiber cable 53
non-redundant controller 208 redundant fiber ports
qualification status indicators 181
single point of failure 12
DSwNP 181 redundant media
DSwP 181
PwDS 181 ControlNet 33
PwNS 181 redundant module
PwQS 181 qualify 63
QSwP 181 remove 64
qualify replace 64
redundant module 63 reset 63
quick start REM
redundancy system 43 mode switch 59
remote
1715 Redundant I/O systems 36
R communication modules 34
I/O 12
Recent Synchronization Attempts log 102 ControlNet 14
redundancy channels EtherNet/IP 14
fiber-optic cable 54 placement 36
redundancy module 24, 44 remove
date and time 100 redundant module 64
info 96 - 97 replace
install 46 redundant module 64
lost connection between modules 206 requested packet interval
troubleshoot over EtherNet/IP 65
missing 207 requirements
Redundancy Module Configuration Tab
ControlNet 30 - 33
qualification EtherNet/IP 34
status 63 firmware 41
Redundancy Module Configuration Tool 91 reset
additional configuration 92 redundant module 63
check qualification 166 restrictions 19
Configuration tab 98 - 100
Event Log tab 187 - 196 redundancy system 19
identify version 94 RIUP 47
Module Info tab 96 - 97 RMCT 43, 91
open 93 Event Log 178
Synchronization Status tab 104 troubleshoot 178
Synchronization tab 101 - 104 version 94
System Update tab 105 - 110 RSLinx Classic 43
update 96 RSLinx communication software 75
redundancy object attributes
for crossload time 121

240 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


Index

S synchronization 99
default 117
scan time description of 15
best performance 123 monitor after switchover 140
concise programming 128 Synchronization Status tab 104
crossload 121 Synchronization tab 101 - 104
efficient crossloads 124 - 127
minimize 123 - 129 attempts log 102
commands in 102
multiple controllers 123
system
number of programs 124
scan-dependent logic 131 qualification, system
synchronization 15
schedule system conversion 219
ControlNet 84 system overhead time slice 138
secondary chassis 15
System Update commands
designation 61 - 63
intallation 52 abort system lock 107
set IP address 75 initiate locked switchover 108
lock for update 106
SFP 211 System Update Lock Attempts 109
small form pluggable 56
System Update tab 105 - 110
transceiver 56
signed and unsigned commands 106 - 108
Locked Switchover Attempts 110
firmware 13
System Update Lock Attempts 109
SIL3
unsupported feature 13
single point of failure T
redundant fiber ports 12 tags
small form pluggable
manage 124
SFP 56
task 119
sockets
1756-EN2T 72 continuous, execution 117
optimize execution 134 - 136
1756-EN2TR 72
recommended 117
software
time and date 100
FactoryTalk Alarms and Events 41
FactoryTalk Batch 41 transceiver
FactoryTalk View Site Edition 41 SFP 56
optional 41 troubleshoot 171 - 209
programming software 75 check status indicators 172
RSLinx communication software 75 controller event 209
RSNetWorx for ControlNet 41 EtherNet/IP
RSNetWorx for EtherNet/IP 41 lost connection 204
RSView32 41 lost EtherNet/IP connection 204
status missing redundancy module 207
of qualification 63 qualification abort 208
via module status display 164 redundancy module
status indicators lost connection 206
missing 207
1756-RM 172 RMCT 178
1756-RM2/A 172, 209
synchronization
1756-RM2XT 209
keeper status 201
CH1 212
use
CH2 212
RSNetWorx for ControlNet software 201
use to troubleshoot 172
Studio 5000 Logix Designer 173
Studio 5000 Logix Designer 43
use to troubleshoot 173
subnet 66 U
switchover 15 unicast
description 16 communication module 19
example 108
locked attempts 110 produced tags 72
Universal Remote I/O 35
logic after 141
monitor synchronization after 140 unscheduled
test 166 ControlNet network 83
synchronization
automatic

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 241


Index

unsupported feature
motion 13
SIL3 13
update
RMCT 96
system commands 106 - 108
upgrade
firmware 58 - 61
user program control 100
utilities
BOOTP/DHCP 75

V
version
RMCT 94

W
watchdog time 148, 236
workstation software 43

242 Rockwell Automation Publication 1756-UM535I-EN-P - October 2020


ControlLogix 5570 Redundancy User Manual

Notes:

Rockwell Automation Publication 1756-UM535I-EN-P - October 2020 243


Rockwell Automation Support
Use these resources to access support information.

Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, ControlFLASH, ControlFLASH Plus, ControlLogix, ControlLogix-XT, Control Tower, Data Highway Plus, expanding human possibility, FactoryTalk, FLEX I/O, Integrated Architecture,
Logix5000, PanelView, PhaseManager, PlantPAx, POINT I/O, PowerFlex, Rockwell Automation, RSLinx, RSNetWorx, RSView, Stratix, Studio 5000 Automation & Engineering Design Environment,
Studio 5000 Logix Designer, and VersaView are trademarks of Rockwell Automation, Inc.
CIP, CIP Sync, ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 1756-UM535I-EN-P - October 2020


Supersedes Publication 1756-UM535H-EN-P - September 2019 Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like