Symmetra PX 48kW
Scalable from 16kW to 48kW
>
High Performance,
Right-Sized
3-Phase Power
Protection with
Industry-Leading
Efficiency, Availability,
and Performance for
Small Data Centers or
High Density Zones
and distribution in a
single frame
years)
Symmetra® PX
batteries.
center reliability.
Symmetra PX family.
Symmetra PX 48kW
Energy Efficiency
95% efficient to 30% loading, the PX 48kW saves power
and cooling costs, significantly reducing your overall Total
Cost of Ownership.
Power Distribution
When demand rises and expansion becomes
necessary, there is no need to schedule
downtime to add a breaker. Power
distribution modules plug into a touch-safe
backplane that shields users from dangerous
amperage. The power distribution system
simplifies power management by including
output metering, branch current/circuit
monitoring, and auto-detection by the
InfraStruXure suite of management options.
Multiple power ratings and power cord
lengths for low to high power guarantee
compatibility and convenient installation.
Management Cards
Two SmartSlot positions can be used to expand the monitoring
capabilities of the UPS with these APC management cards:
> Network Management Card: One Management Card is included with
the UPS; it enables you to monitor and control the UPS over the
network. Optionally, install a second Management Card for
redundancy.
> Dry Contact/Environmental Cards: Monitor the conditions of the UPS
and its environment using external devices such as sensors.
> Building Management System (Modbus/Jbus) Card: Enable a Building
Management System to monitor the UPS.
I thd < 5%
Nominal input current 77A @ 380V, 73A @ 400V, or 70A @ 415V
Maximum input current
84.4A @ 380V, 80.2A @ 400V, or 77.3A @415V
(Nominal Vin, 10% charging batteries)
Input current limit 98.3A @ 380V / 400V / 415V
Maximum overload input current 84.4A @ 380V; 80.2A @ 400V; 77.3A @ 415V
Output
Power rating 48kW
V thd < 2% from 0 to 100% linear load, < 6% full non-linear load according to IEC/EN62040-3
Efficiency
Normal operation ≥ 95% at 35% - 100% load; ≥90% @ 15% - 34% load
Battery operation ≥ 94% at 25% - 100% load; ≥90% @ 15% - 34% load
Mechanical
Maximum dimensions (HxWxD) 1991 x 600 x 1070mm
Net weight 796kg
Shipping weight 858kg
UPS Frame Maximum Capacity
Regulatory Compliance
CE, UL1778, EN/IEC62040-1-1, EN/IEC/UL60950-1, EN50091-2 / IEC62040-2 (class A), FCC15A, EN/IEC62040-3