BS Panic Bar

Download as pdf or txt
Download as pdf or txt
You are on page 1of 62

BRITISH STANDARD BS EN

1125:2008

Building hardware —
Panic exit devices
operated by a
horizontal bar, for use
on escape routes —
Requirements and test
methods
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

ICS 91.190

12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:
Copyright British Standards Institution
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008

National foreword

This British Standard is the UK implementation of EN 1125:2008. It


supersedes BS EN 1125:1997 which is withdrawn.
The UK participation in its preparation was entrusted by Technical Committee
B/538, Doors, windows, shutters, hardware and curtain walling, to
Subcommittee B/538/4, Building hardware.
A list of organizations represented on this committee can be obtained on
request to its secretary.
This publication does not purport to include all the necessary provisions of a
contract. Users are responsible for its correct application.
Compliance with a British Standard cannot confer immunity from
legal obligations.

This British Standard was Amendments/corrigenda issued since publication


published under the authority
of the Standards Policy and
Strategy Committee Date Comments
on 31 March 2008

© BSI 2008

ISBN 978 0 580 62450 6

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
EUROPEAN STANDARD EN 1125
NORME EUROPÉENNE
EUROPÄISCHE NORM January 2008

ICS 91.190 Supersedes EN 1125:1997

English Version

Building hardware - Panic exit devices operated by a horizontal


bar, for use on escape routes - Requirements and test methods

Quincaillerie pour le bâtiment - Fermetures anti-panique Schlösser und Baubeschläge - Paniktürverschlüsse mit
manoeuvrées par une barre horizontale, destinées à être horizontaler Betätigungsstange, für Türen in Fluchtwegen -
utilisées sur des voies d'évacuation - Exigences et Anforderungen und Prüfverfahren
méthodes d'essai
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

This European Standard was approved by CEN on 30 November 2007.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1125:2008: E
worldwide for CEN national Members.

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Contents Page

Foreword............................................................................................................................................................. 4
Introduction ........................................................................................................................................................ 5
1 Scope ..................................................................................................................................................... 7
2 Normative references ........................................................................................................................... 7
3 Terms and definitions........................................................................................................................... 7
4 Requirements ...................................................................................................................................... 12
4.1 Design requirements .......................................................................................................................... 12
4.2 Performance requirements ................................................................................................................ 20
4.3 Requirements for product information............................................................................................. 25
5 Tests - General and test apparatus ................................................................................................... 26
5.1 General................................................................................................................................................. 26
5.2 Test apparatus .................................................................................................................................... 27
6 Test methods – Procedures............................................................................................................... 28
6.1 General................................................................................................................................................. 28
6.2 Test procedure - Test sample A – Environmental tests.................................................................. 29
6.3 Test procedure - Test sample B - Design and performance tests ................................................. 31
7 Classification....................................................................................................................................... 36
7.1 Category of use (1st character) ......................................................................................................... 36
7.2 Durability (2nd character) .................................................................................................................. 36
7.3 Door mass (3rd character) ................................................................................................................. 36
7.4 Suitability for use on fire/smoke doors (4th character) .................................................................. 36
7.5 Safety (5th character) ......................................................................................................................... 36
7.6 Corrosion resistance (6th character) ................................................................................................ 36
7.7 Security (7th character)...................................................................................................................... 37
7.8 Projection of horizontal bar (8th character) ..................................................................................... 37
7.9 Type of horizontal bar operation (9th character)............................................................................. 37
7.10 Field of door application (10th character) ........................................................................................ 37
7.11 Example of classification ................................................................................................................... 37
8 Marking ................................................................................................................................................ 38
8.1 On the product .................................................................................................................................... 38
8.2 On the packaging ................................................................................................................................ 38
8.3 On the installation instructions ......................................................................................................... 39
8.4 Mortise lock combined with a separate horizontal bar unit ........................................................... 39
9 Evaluation of Conformity ................................................................................................................... 39

2
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

9.1 Initial type test ..................................................................................................................................... 39


9.2 Sampling, testing and conformity criteria ........................................................................................ 40
9.3 Factory production control ................................................................................................................ 41
9.4 Periodic testing (for all products) ..................................................................................................... 45
9.5 Annual testing (for all products) ....................................................................................................... 46
Annex A (normative) Installation and fixing instructions ........................................................................... 47
Annex B (normative) Additional requirements for panic exit devices intended for use on
fire/smoke resisting door assemblies............................................................................................... 49
Annex C (normative) Maintenance instructions .......................................................................................... 50
Annex D (normative) Flow chart of test procedures ................................................................................... 51

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
Annex E (informative) Guidance for choosing relevant product standards for particular exit
door applications ................................................................................................................................ 52
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of EU Directive 89/106/EEC, EU Construction Products Directive ....................... 53
Bibliography ..................................................................................................................................................... 58

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Foreword
This document (EN 1125:2008) has been prepared by Technical Committee CEN/TC 33 “Doors, windows,
shutters, building hardware and curtain walling”, the secretariat of which is held by AFNOR.

This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by July 2008, and conflicting national standards shall be
withdrawn at the latest by July 2008.

Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.

This document supersedes EN 1125:1997.

This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).

For relationship with EU Directive 89/106/EEC, see informative Annex ZA which is an integral part of this
document.

It has been revised to incorporate clarification of the definitions, safety requirements and test procedures,
in particular for panic exit devices intended for use on double leaf doorsets, in order to allow for more
reproducible test methods.

It incorporates extension of the classification to avoid misuse of the products, extension of the limits of door
mass and dimensions as well as extension of the field of door application to cover products already
available on the market which were not covered by the 1997 edition of this European Standard.

A full contribution to the preparation of this European Standard has been made by The European
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Federation of Associations of Lock and Builders Hardware Manufacturers (ARGE).

This European Standard is part of a group of standards dedicated to building hardware products. It is one
of a group of standards for exit devices and exit systems developed by Technical Committee CEN/TC 33.

Wherever reference is made to classes, they are considered to be technical classes and not classes
according to Article 3(2) of the Construction Products Directive (89/106/EEC).

Verification or tests performed by mechanical test laboratory and fire test laboratory are listed in Table 1
summarizing performance characteristics and compliance criteria.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus,
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia,
Slovenia, Spain, Sweden, Switzerland and the United Kingdom.

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Introduction

Experience relating to escape from buildings, fire and/or smoke hazards and general safety has made it
desirable that doors, in public areas, public buildings, places of public entertainment, shops etc, or those
that have to be operated in a panic situation, be fitted with panic exit devices operated by a horizontal bar
to common European Standard specifications.

The main purpose of the performance requirements contained in this European Standard is to give safe
and effective escape through a doorway with one single operation by hand and/or body pressure to
release the panic exit device, with minimum effort and without prior knowledge of the panic exit device.

In this standard priority is given to the panic operation rather than pressure and resistance to the door
opening from seals, weather-stripping, multiple bolt heads etc. Precedence is given to the importance of
ease of opening by the young, elderly and infirm.

In a panic situation, a group of people will react differently from an individual. When two or more people are
rushing to an exit door located on an escape route, probably in darkness and/or smoke, it is possible that
the first one to reach the door will not necessarily operate the panic exit device, but can push the surface
of the door (door under pressure) while other people will be trying to operate the horizontal bar by hand or
body pressure. See Figure 1.

Whilst reasonable external security will be provided by the panic exit devices covered in this standard to
avoid potential misuse of the device (chains, bolts, etc.), the main objective is to enable a door to be
opened at all times by hand or body pressure along its inside face on the panic exit device and not
requiring the use of a key or any other object.

The performance tests incorporated in this European Standard are considered to be reproducible and, as
such, will provide a consistent and objective assessment of the performance of these panic exit devices.

Where emergency exit devices are required for situations in which people are familiar with the use of the
door hardware in their surroundings, where exit doors are required to be inwardly-opening, and/or where a
panic situation is unlikely to develop, reference can be made to EN 179, covering emergency exit devices.
See definition 3.19.

Where additional security is required for exit doors, reference should be made to prEN 13633 covering
electrically controlled panic exit systems, or to prEN 13637 covering electrically controlled exit systems, for
use on escape routes. See Bibliography.

Due to the wide range of panic exit devices, the reader is advised to refer to the scope and the detailed
contents of this European Standard for coverage but, for information and general guide, this revised
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

European Standard now deals with:

• panic exit devices designed to be used in panic situations;

• panic exit devices for use on hinged or pivoted door leaves only;

• range of panic exit devices including those for use on double doorsets (see 7.10);

• two specific types of horizontal bar operation: panic exit devices with "push-bar", type A (see 3.17
and Figure 2) and panic exit devices with "touch-bar", type B (see 3.19 and Figure 3);

• two categories of panic exit device projection in order to maximize the width of the escape route,
and minimize the projection from the door face where either or both of these criteria are of
importance (see 4.1.11);

• two specific designs of panic exit devices: those designed for use on single leaf doors only, and
those specifically designed for use on single leaf doors and/or double doorsets.

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

This European Standard does not cover the following:

• any particular design of panic exit devices, and only such dimensions as are required for safety
reasons are specified;

• specific panic exit devices intended for use by the severely disabled (due to the wide range of
disabilities, such panic exit devices and their performances should be agreed between specifier
and producer);

• emergency exit devices operated by a lever handle or push-pad (see EN 179) or electrically
controlled panic exit systems or electrically controlled exit systems (see prEN 13633 and prEN
13637).

Figure 1 — A panic situation

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

1 Scope
This European Standard specifies requirements for the manufacture, performance and testing of panic exit
devices mechanically operated by either a horizontal push-bar or a horizontal touch-bar, specifically
designed for use in a panic situation on escape routes.

The suitability of a panic exit device for use on fire/smoke resisting door assemblies is determined by fire
performance tests conducted in addition to the performance tests required by this European Standard.
Annex B indicates additional requirements for these products.

This European Standard covers panic exit devices which are either manufactured and placed on the
market in their entirety by one producer or produced by more than one producer and subsequently placed
on the market as a kit in a single transaction.

2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

EN 179, Building hardware - Emergency exit devices operated by a lever handle or push pad -
Requirements and test methods

EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows
and elements of building hardware - Part 1: Fire resistance test for doors and shutter assemblies and
openable windows

EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows
and elements of building hardware - Part 3: Smoke control test for door and shutter assemblies

EN 1670:2007, Building hardware - Corrosion resistance - Requirements and test methods


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

EN ISO 9001:2000, Quality management systems - Requirements (ISO 9001:2000)

3 Terms and definitions


For the purposes of this document, the following terms and definitions apply.

3.1
active leaf
first opening and last closing leaf of a rebated single swing double doorset

3.2
automatic relatching device
part of a panic exit device to enable the automatic securing of a door in the closed position, after it has
been operated

NOTE For example, a spring loaded latch bolt or an automatically thrown bolt head.

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

3.3
bolt head
portion of a panic exit device that engages with the keeper to secure the door in the closed position

3.4
dogging mechanism
part of a panic exit device for holding the bolt head(s) in the withdrawn position until manually reset

3.5
doorset
assembly consisting of a single leaf exit door being hinged or pivoted vertically in a frame

3.6
inactive leaf
last opening and first closing leaf of a rebated single swing double doorset

3.7
inside
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

face of the door on which the bar is situated for operating a panic exit device in order to exit

3.8
keeper
part of a panic exit device such as a strike, a socket or other fitting with which the bolt head(s) engages

3.9
push-bar
activating horizontal bar of a panic exit device (type A), designed to be fixed between pivoted support
brackets that operates in the direction of exit and/or in an arc downwards (See Figure 2)

3.10
producer
manufacturer, entity or organization that has legal responsibility for placing the product on the market

3.11
outside
face of the door opposite to the face on which the bar for operating the panic exit device is situated

3.12
outside access device
optional part of a panic exit device for opening an exit device from the outside

NOTE An outside access device can be supplied with optional re-entry function.

3.13
bar
horizontal part of a panic exit device which, when pushed, will operate the mechanism

3.14
double doorset
assembly consisting of two hinged or pivoted leaves within a single frame

NOTE 1 The meeting stiles can be either plain or rebated.

NOTE 2 A double doorset where only one leaf is equipped with a panic exit device is considered to be a single
panic exit doorset.

NOTE 3 A double doorset where the first opening leaf is equipped with a panic exit device conforming to EN 1125
and the second opening leaf is equipped with an emergency exit device conforming to EN 179 is considered to be a
double emergency exit doorset, or a single panic exit door.

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

3.15
touch-bar
activating horizontal bar of a panic exit device (type B), designed to be part of a chassis or other mounting
assembly, that operates in the direction of exit (see Figure 3)

3.16
release force
force applied to the bar in a direction perpendicular to the door face, which is necessary to withdraw or
release all the bolt head(s) from the keeper(s), such that the door can be opened

3.17
vertical rod
extension of the bolt head of a panic exit device that links it to the horizontal bar via the operating
mechanism

3.18
panic exit device
exit device conforming to EN 1125 intended to give safe and effective escape through a doorway with
minimum effort and without prior knowledge of the panic exit device allowing safe escape even in the event
of the door being under pressure such as by people being pushed against the door in the direction of
escape

NOTE 1 A panic exit device contains bolt head(s) that engage(s) with a keeper(s) in the surrounding door frame
and/or floor for securing a door when closed. The bolt head(s) can be released by the bar positioned horizontally
across the inside face of the door when it is moved anywhere along its effective length in the direction of travel and/or
in an arc downwards.

NOTE 2 Panic exit devices are intended for use where panic situations can arise. In a panic situation, a group of
people will react differently from an individual. When two or more people are rushing to an escape door, probably in
darkness and/or smoke, it is possible that the first one to reach the door will not necessarily operate the panic exit
device, but can push the surface of the door (door under pressure) while other people will be trying to operate the
horizontal bar by hand or body pressure.

NOTE 3 When a door opens in the direction of exit, a panic exit device can be used instead of an emergency exit
device subject to local regulations.

Figure 2 — Panic exit device with type A bar operation (push-bar)

9
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Figure 3— Panic exit device with type B bar operation (touch-bar)

3.19
emergency exit device
exit device conforming to EN 179, intended for emergency purposes where panic situations are not likely to
arise, to give safe and effective escape through a doorway with one single operation to release the
emergency exit device, although this can require prior knowledge of its operation

NOTE 1 An emergency exit device contains bolt head(s) that engage(s) with a keeper(s) in the surrounding door
frame and/or floor for securing a door when closed. The bolt head(s) can be released by the lever handle or the push
pad positioned on the inside face of the door.

NOTE 2 Exit devices conforming to EN 179 are intended for emergency purposes where panic situations are not
likely to arise. Where a pressure against the door caused by people in a panic is foreseen, then a panic exit device
conforming to EN 1125 should be used.

NOTE 3 Emergency exit devices are suitable also for inwardly opening single leaf exit doors, where local building
regulations allow.

3.20
double doorset panic exit device
panic exit device designed for use on the leaves of double doorsets, such that the operation of either
horizontal bar will release at least the door leaf to which it is fitted

3.21
deadbolt
part of a panic exit device that can be deadlocked manually by key or automatically and which is released
when the exit device is operated

NOTE A panic exit device can be designed to incorporate additional deadbolt(s) thrown by a key or thumbturn,
used only at certain periods of time for additional security.

3.22
exit door
door on an escape route equipped with an exit device conforming to EN 179 and/or EN 1125

3.23
effective length of bar
length of the bar (dimension X) including any member to which the bar is fixed and which will itself yield to
hand or body pressure thereby causing the panic exit device mechanism to operate (See Figure 4)

10
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

3.24
re-entry function
optional function that allows, for safety reasons, an individual to re-enter a room from outside without a key
once the inside operating element has been actuated. After having released the device from the inside,
any handle (or other means) to operate the exit device from outside remains unlocked until manually reset
by key

3.25
field of door application
door configurations for which the panic exit devices are designed and claimed by the producer

3.26
limits of door mass and dimensions
dimensional and mass limits of the doors for which the panic exit devices are designed

3.27
sub-assemblies
pre-assembled set of components that form one part of the panic exit device, for example: pullman catches,
operating boxes and lock cases

3.28
effective width of door opening
unobstructed width of the inside face of the door leaf (dimension Y) when the door is in the secured
position (See Figure 4)

3.29
visual inspection
assessment made with the naked eye, adjusted for normal vision and use of the appropriate measurement
equipment

3.30
functional test
assessment made by operating the test door (opening or closing) and/or operating any element of the exit
device

3.31
measurement
assessment made by using a measuring tool

11
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

4 Requirements

4.1 Design requirements

4.1.1 General

Compliance with the design requirements shall be as Table 1.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
4.1.2 Release function

A panic exit device shall be designed to release a door at all times from the inside in less than 1 s, when
the horizontal bar positioned horizontally across the inside of the door is operated by hand or body
pressure in one continuous movement in the direction of exit and/or in an arc downwards, anywhere along
its effective length and not requiring the use of a key or other similar object. It shall be designed to release
the door without any delay from the time the horizontal bar is operated to the released position of the
mechanism.

The operation of the horizontal bar shall enable immediate exit from the inside at all times regardless of
any auxiliary locking and/or unlocking means being incorporated, such as a deadbolt or outside access
device.

Compliance shall be verified by visual inspection, functional tests and/or measurements.

4.1.3 Panic exit device mounting

A panic exit device, with the exception of the horizontal bar, shall be designed to be mounted either on the
inside face of, or within, a door.

Compliance shall be verified by visual inspection.

4.1.4 Corrosion resistance

The corrosion resistance shall comply with 4.2.9 or be at least grade 3 in accordance with
EN 1670:2007, 5.6.

4.1.5 Exposed edges and corners

A panic exit device shall have all edges and exposed corners, that are likely to cause injury to persons
using the exit, rounded to a radius of not less than 0,5 mm.

Compliance shall be verified by visual inspection and measurements.

4.1.6 Temperature range

Materials selected in the design of a panic exit device shall be suitable for the operation of the panic exit
device between temperatures of -10 °C and +60 °C. This requirement shall be verified by the test specified
in 6.2.2. The maximum operating force at -10 °C and at +60 °C shall not exceed 50 % in excess of the
operating forces measured at 20 °C.

4.1.7 Double doorset

The design of a panic exit device intended for use on double doorset leaves shall allow both leaves to be
opened simultaneously and to swing freely in the direction of exit once the door has been released.

12

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

NOTE 1 The construction and installation of a specific doorset assembly, including choice of hinges, leaf thickness
and leaf width, can have a significant effect on the ability of both leaves to open simultaneously. These issues are
beyond the scope of this European Standard. Additional guidance is given in A.5.

NOTE 2 For example, on rebated double doors, operating the panic exit device on the inactive leaf will release both
the inactive and the active leaf.

Compliance shall be verified by visual inspection and functional tests carried before and also after
durability test.

4.1.8 Suitability of panic exit devices for use on smoke/fire resisting doorsets

Panic exit devices that are suitable for use on smoke/fire resisting doorsets shall conform to the
requirements of 4.2.3, 4.2.4, Annex B and be classified according to 7.4.

4.1.9 Bar installation

Panic exit devices shall be designed such that the effective bar can be installed at 150 mm (dimension Z)
or less from the door stop at the leading edge of the door when the door is in the closed position. See
Figure 4.

Compliance shall be verified by visual inspection and measurements.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
13

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Z X Z X

Y Y

Type A panic exit device Type B panic exit device

Key
Z is the distance from door stop
X is the effective length of horizontal bar
Y is the effective width of door opening

Figure 4 — Type A and type B panic exit devices


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

4.1.10 Bar length

The design of a panic exit device shall be such that the effective length (dimension X) of the horizontal bar
shall be as near as possible to the effective width (dimension Y) of the door opening for which it is
recommended, but never less than 60 %. See Figure 4.

Compliance shall be verified by visual inspection and measurements.

4.1.11 Bar projection

No part of a panic exit device, when the door is in any position, shall project (dimension W) from the face of
the door more than:

a) category 1: projection up to 150 mm (large projection);

b) category 2: projection up to 100 mm (standard projection).

NOTE 1 See Figure 5 for illustration of dimension W (projection).

NOTE 2 Categories 1 and 2 apply to both type A and B operation.

Compliance shall be verified by visual inspection and measurements.

14

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

W W

Type A panic exit device Type B panic exit device

Key
W is the maximum projection of active horizontal bar

Figure 5 — Overall projection from door face


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

4.1.12 Bar end

The operating bar of a panic exit device shall not protrude beyond either of the end support brackets. In
the case of a double doorset panic exit device, the requirement shall apply to each end of each bar.

NOTE This is particularly important when the door is used for access as well as for egress.

Compliance shall be verified by visual inspection.

4.1.13 Operating bar face

For type A panic exit devices, when secured in position the vertical axis or height (dimension V) of the
operating face of the push-bar shall be not less than 18 mm. See Figure 6.

For type B panic exit devices, when secured in position the vertical axis or height (dimension V) of the
operating face of the touch-bar shall be not less than 18 mm. Where the operational member is situated
within the non-operational member, the height (dimension V) of the operating face of the touch-bar shall be
at least 60 % of the overall height (dimension U) of the panic exit device measured anywhere within the
effective length of the bar. When the touch-bar is fully depressed, the touch-bar face shall not protrude less
than 3 mm (dimension T) beyond any non-operable member, and not be less than 25 mm (dimension S)
from the face of the door. See Figure 7.

Compliance shall be verified by visual inspection and measurements.

15

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
V

Key
R is the minimum gap between the horizontal bar
and the surface of the door leaf
V is the vertical axis or height of the operating face

Figure 6 — Heights and projections for type A panic exit devices


U
V

Key
S is the minimum projection from the face of the door
T is the minimum projection from non operable member
U is the overall height
V is the height of the operating face

Figure 7— Heights and projections for type B panic exit devices

16

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

4.1.14 Test rod

To reduce the risk of trapping fingers and/or the blocking of the panic exit device, any gap shall not trap a
test rod (of 10 mm diameter by 100 mm in length) by its 10 mm diameter in any position during the
operation of the panic exit device. See Figure 8.

Compliance shall be verified by visual inspection and measurements.

Figure 8 — Example of test rod for type A panic exit devices

4.1.15 Door face gap

The gap between a horizontal bar and the door face or exit device support shall be not less than 25 mm
(dimension R) at any position of bar travel to reduce the risk of trapped fingers. To allow for particular
designs such as bracket supports, bushings, etc, the first 25 mm of each end of the bar length may have
any such gaps reduced to 20 mm. See Figure 6.

Where a type B panic exit device allows spacing between the operating bar and the door face, this spacing
shall not be less than 25 mm when the touch-bar is fully depressed (same as dimension R for type A
devices).

Compliance shall be verified by visual inspection and measurements.

4.1.16 Accessible gap

A panic exit device shall be designed such that the top surface of any operating element, touch-bar,
chassis or other mounting assembly does not contain any accessible gap that could inadvertently be
blocked by a foreign object, resulting in failure of the panic exit device to operate.

A steel test piece of 10 mm x 15 mm x 20 mm placed in any accessible gap and in any orientation shall not
prevent correct operation of the panic exit device.

Compliance shall be verified by visual inspection and measurements.

17
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

4.1.17 Door free movement

The design of a panic exit device shall be such that the bolt head(s), once the door has been released to
open, does not restrict or impede the free movement of the door.

The design of a panic exit device can include a dogging mechanism or an automatic relatching device. If
the exit device is equipped with a dogging mechanism or a device retaining the bolt(s) retracted, this shall
not impede the free movement of the door once released.

An exit device shall be designed to avoid accidental release of the bottom bolt, preventing the free opening
of the door.

Exit devices intended for use on smoke/fire resisting doors, shall comply with Annex B for additional
requirements.

Compliance shall be verified by visual inspection and functional tests carried before and also after
durability test.

4.1.18 Top vertical bolt


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

A panic exit device with top and bottom vertical rods shall include a mechanism to ensure that the
releasing and/or the manipulation of the bottom vertical rod bolt head does not release the top vertical rod
bolt head. This is verified by pushing the bottom bolt head up to its flush position with the bolt case.

Compliance shall be verified by visual inspection and functional tests carried before and also after
durability test.

4.1.19 Covers for vertical rods

If covers are provided to surface fixed vertical rods to achieve abuse resistance, they shall have secure
fixings and only be removable by means of a specific tool.

Compliance shall be verified by visual inspection and functional tests, or (if not removable by a specific
tool) the panic exit device shall meet the performance requirements of 4.2.6 with the covers removed.

The design of a panic exit device may provide for guide(s) to retain the vertical rods.

4.1.20 Keepers

The design of a panic exit device shall include a keeper(s) for engaging the bolt head(s) when the panic
exit device is in the secured position.

Keepers shall provide protection for any part of the door or frame that could be damaged by the panic exit
device during the opening and closing cycle of the door.

Compliance shall be verified by visual inspection and functional tests carried before and also after the
durability test.

4.1.21 Keepers dimensions

The design of a floor keeper shall be such that dust and dirt can easily be removed with a conventional
vacuum cleaner. If the keeper is not fitted flush, it shall not exceed 15 mm in height (dimension H) from the
finished floor level and shall be chamfered in the direction of escape at an angle (M) not exceeding 45°
from the horizontal, and any up stand (dimension P) shall not exceed 3 mm. See Figure 9.

Compliance shall be verified by visual inspection and measurements.

18

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

H
P
Key
H is the height of the floor keeper
M is the angle from the horizontal
P is the up stand of the floor keeper

Figure 9 — Floor keeper dimensions

4.1.22 Lubrication

Where periodic lubrication is required, it shall be possible to lubricate without dismantling the panic exit
device. No additional lubrication shall be required before 20 000 cycles have been attained and at no less
interval than 20 000 cycles thereafter. This requirement shall be verified in accordance with 6.3.4.

4.1.23 Door mass and dimensions

The door mass and door dimensions shall be limited to the following for the purposes of a panic exit device
tested on a test door in accordance with 5.2.2:

 maximum door mass: 100 kg or 200 kg according to the classification;

 maximum door height, excluding any rebates: up to a 20 % increase of the height of the test door (i.e.
maximum increased height = 2 520 mm);

 maximum door width, excluding any rebates: up to a 20 % increase of the width of the test door (i.e.
maximum increased width = 1 320 mm).

Beyond these limits a panic exit device shall be additionally tested, in accordance with the following:

1) door mass over 200 kg: repeat the durability test in accordance with 6.3.4 and the final
examination in accordance with 6.3.8, with the intended door mass;

2) door width over 1 320 mm: repeat the test in accordance with 6.3.2, the abuse resistance
test of operating element in accordance with 6.3.5 and the final examination in accordance with
6.3.8 with the intended door width;

3) door height over 2 520 mm: repeat the release test in accordance with 6.3.2, the abuse
resistance test of vertical rods in accordance with 6.3.6 and the final examination in accordance
with 6.3.8. Either perform the test with the intended door height or perform the test on test doors
2 100 mm high but with weights added to the vertical rods to ensure that the vertical rods have
the same mass that they would have on the door for which the device is specified. In this case the
longest unsupported length of surface fixed vertical rod, at the midpoint of which the abuse force
is applied, shall be not less than the one of the door for which the device is intended;

19
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

The forces shall be applied in accordance with 5.2.1.

A panic exit device may be used on a door with shorter dimensions and lower mass than the dimensions
and the mass of the door to which it has been tested.

4.1.24 Outside access device

The provision for a connection of an outside access device (key, cylinder, lever handle, knob, etc.) shall
not, in any way, render the panic exit device inoperable from the inside, whether the outside access device
is tested in the fully locked or unlocked position with the key removed. The installation instructions shall
clearly indicate the approved configurations for outside access.

An outside access device that is not specified by the producer as designed to be compatible with a specific
panic exit device shall not be considered to be in conformity with this document.

When an outside access device is intended for use with a thumbturn cylinder, the size and any positioning
of the thumbturn shall not interfere with the operation of the panic exit device from the inside.

Where National Building Regulations accept direct connection of the exit device mechanism with the
outside lever handle, which when being blocked at any position may render the exit device inoperable from
the inside, this shall be clearly stated in the installation instructions, as in 4.3.

Where an outside access device is intended for use with a cylinder, and a key left inside a cylinder at any
position may render the panic exit device inoperable from the inside, then this shall be clearly stated in the
installation instructions, as in 4.3 and Annex A.

Compliance is verified by a visual and mechanical examination, which shall include all the functions of the
outside access device which have been declared by the producer of the panic exit device.

Compliance shall be verified by visual inspection and functional tests.

The examination shall confirm that the release forces of the panic exit device are still within the limits of

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
6.3.2 with the outside access device installed.

4.1.25 Dangerous substances

Materials in products shall not contain or release any dangerous substances in excess of the maximum
levels specified in existing European material standards or any national regulations.

Compliance shall be verified by visual inspection of documents supplied by the producer.

4.2 Performance requirements

4.2.1 General

Panic exit devices shall be manufactured such that, when tested according to the specified test method,
the performance of the panic exit device (or components) shall demonstrate conformity to the specific
design requirements as specified in 4.1, and conformity to the requirements for product information as
specified in 4.3, Annex A and Annex C.

Panic exit devices shall demonstrate conformity to the characteristics according to Table 1.

A panic exit device whose performance is declared as compliant with this document shall conform to all the
requirements of Table 1.

20

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Table 1 – Performance characteristics and compliance criteria


Performance Function Clause number Compliance criteria
characteristic
a b
Mechanical Fire Requirement Test
Ability to release
(for locked doors on
escape routes)
Release function X X 4.1.2 4.1.2 Threshold (≤ 1 s)
Panic exit device X X 4.1.3 4.1.3 Pass/Fail
mounting
Exposed edges and X 4.1.5 4.1.5 Threshold (≥ 0,5 mm)
corners
Double doorset X X 4.1.7 4.1.7 Pass/Fail
Bar installation X 4.1.9 4.1.9 Threshold (Z ≤ 150 mm)
Bar length X 4.1.10 4.1.10 Threshold (≥ 60 %)
Bar projection X 4.1.11 4.1.11 Threshold ( W ≤ 100 or
150 mm)
Bar end X 4.1.12 4.1.12 Pass/Fail
Operating bar face X 4.1.13 4.1.13 Threshold ( V ≥ 18 mm)
Test rod X 4.1.14 4.1.14 Pass/Fail
Door face gap X 4.1.15 4.1.15 Threshold (R≥ 25 mm)
Accessible gap X 4.1.16 4.1.16 Threshold (20 mm)
Door free movement X X 4.1.17 4.1.17 Pass/fail
Top vertical bolt X 4.1.18 4.1.18 Pass/fail
Keepers X 4.1.19 4.1.19 Pass/fail
Keepers dimensions X 4.1.21 4.1.21 Threshold (H ≤ 15 mm;
M ≤ 45°; P ≤ 3 mm)

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
Door mass and X 4.1.23 6.3.2; 6.3.4; Threshold (Grade)
dimensions 6.3.5; 6.3.6;
6.3.8
Outside access X 4.1.24 4.1.24; 6.3.2 Pass/Fail
device
Release forces X 4.2.2 6.3.2 Threshold (≤ 80 N and
≤ 220N under pressure)
Security requirement X 4.2.7 6.3.7 Threshold (Grade)

Durability of
ability to release
(for locked doors on
escape routes)
Corrosion resistance X 4.1.4; 4.2.9 6.2.3 Threshold (Grade)
Temperature range X 4.1.6 6.2.2 Threshold (50 % in
excess)
Covers for vertical X 4.1.19; 4.2.6 4.1.19; 6.3.6 Threshold (500 N)
rods
Lubrication X 4.1.22 6.3.4 Threshold (20 000
cycles)
Re-engagement force X 4.2.3 6.3.3 Threshold (≤ 50 N)
Durability X 4.2.4 6.3.4 Threshold (Grade -
100 000 or 200 000
cycles)
Abuse resistance – X 4.2.5 6.3.5 Threshold (500 N and
Horizontal bar 1000 N)
Abuse resistance – X 4.2.6 6.3.6 or Threshold (500 N)
Vertical rod 4.1.19
Final examination X 4.2.8; 4.2.2; 6.3.2; 4.1.17 Threshold (≤ 80 N and
4.1.17
≤ 220 N under
pressure)

21

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Performance Function Clause number Compliance criteria


characteristic
a b
Mechanical Fire Requirement Test
Self closing ability
C (for fire/smoke
doors on escape
routes)
Re-engagement force X 4.2.3 6.3.3 Threshold (≤ 50 N)

Durability of Self
closing ability C
against aging and
degradation
(for fire/smoke
doors on escape
routes)
Durability X 4.2.4 6.3.4 Threshold (Grade -
100 000 or 200 000
cycles)
Re-engagement force X 4.2.3 6.3.3 Threshold (≤ 50 N)

Resistance to fire
E (integrity) and I
(insulation)
(for use on fire
doors)
Suitability of panic exit X 4.1.8; Annex B Annex B Threshold (Grade)
devices for use on fire
resisting doorsets
assemblies - -
Additional
requirements

Control of X 4.1.25 4.1.25 Pass/Fail


dangerous
substances.
a
Verification or tests performed by mechanical test laboratory
b
Verification or tests performed by fire test laboratory

4.2.2 Release forces

4.2.2.1 Release forces with door not under pressure

When a panic exit device is tested in accordance with 6.3.2.1, the force required to release the panic exit
device shall not exceed 80 N. See Figure 10.

4.2.2.2 Release forces with door under pressure

When a panic exit device is tested in accordance with 6.3.2.2, the door shall not open prior to the release
force being applied, and the force required to release the panic exit device shall not exceed 220 N. See
Figure 10.

22
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

1 000 N

80 N 220 N

Door not under pressure Door under pressure

Figure 10 — Release forces

4.2.3 Re-engagement force

When a panic exit device is tested in accordance with 6.3.3, the force required to release an automatic
relatching device in order to re-engage the panic exit device to the secured position shall not exceed 50 N.

The test in 6.3.3 may be omitted if the panic exit device does not include an automatic relatching device.

4.2.4 Durability

When a panic exit device is tested in accordance with 6.3.4, the cycling test shall consist of:

 100 000 cycles to achieve grade 6;

 200 000 cycles to achieve grade 7.

When a panic exit device equipped with a deadbolt only thrown by a key for additional security is tested in
accordance with 6.3.4.2, the cycling test of the deadbolt shall consist of:

 25 000 cycles to achieve grade 6;

 50 000 cycles to achieve grade 7.

A panic exit device may be designed to incorporate an additional deadbolt thrown by a key, used only at
certain period of time for additional security. The release function shall be tested with any deadbolt thrown.
The durability of the deadbolt does not need to be tested to same number of cycles as either the regular
latch bolt or an automatic relatching device, or an automatic deadbolt.

Panic exit devices intended for use only on the inactive leaf of a double doorset shall be tested in
accordance with 6.3.4.1 (Test 2); the cycling test shall consist of:

 10 000 cycles to achieve grade 6;

 20 000 cycles to achieve grade 7.

For rebated double doorsets, it shall not be necessary for panic exit devices used only on inactive leaves
to complete the same number of durability cycles as that required for the active leaf. However, when a
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

panic exit device is designed for use on either leaf of a double doorset, or for use on a single door, it shall
be tested to the complete number of cycles.

23

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

After the test, the panic exit device shall continue to be operable and meet the requirements of 4.1.17,
4.2.2 and 4.2.3.

4.2.5 Abuse resistance - Horizontal bar

When a panic exit device is tested in accordance with 6.3.5, the horizontal bar shall withstand a force of
1000 N. See Figure 11.

After the test, the panic exit device shall meet the requirements of 4.1.14 and 4.1.15 and continue to be
operable. The requirements of 4.1.15 shall be checked during the final examination by the tests given in
6.3.8.

A panic exit device with a dogging mechanism shall have the test of 4.2.5 repeated with the panic exit
device in the dogged position.

1 000 N

1 000 N 1 000 N

1 000 N

Figure 11— Abuse resistance test forces

4.2.6 Abuse resistance - Vertical rods

Vertical rods shall be resistant to abuse by either conformity to 4.1.19 or with the following test.

When a panic exit device is tested in accordance with 6.3.6, the surface fixed rods shall withstand a pulling
force of 500 N. See Figure 12.

After the test, the panic exit device shall continue to meet the requirements of 4.1.14 and 4.1.15 and
continue to be operable. This last requirement shall be checked during the final examination by the tests
given in 6.3.8.

500 N

Figure 12 — Abuse resistance test force


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

24

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

4.2.7 Security requirement

When a panic exit device is tested in accordance with 6.3.7 the device shall remain in the locked position
and shall keep the door closed when subjected to a force of 1 000 N. This requirement corresponds to
grade 2 for security in 7.7).

Panic exit devices conforming to this European Standard have a safety rather than a security function. It is
therefore considered essential that the panic exit device should continue to be operable after the
application of any abuse test forces. The test values in 4.2.7 reflect this requirement and indicate a level of
strength that should be achieved without impairing the escape function of the panic exit device.

4.2.8 Final examination

At the end of the test programme the panic exit device shall continue to be operable and meet the
requirements of 4.2.2 and 4.1.17.

4.2.9 Corrosion resistance

When a panic exit device is tested in accordance with 6.2.3, the force required to release the panic exit
device shall not exceed:

a) 80 N prior to the test;

b) 120 N after the test.

4.3 Requirements for product information

A panic exit device manufactured to this European Standard shall be supplied with clear and detailed
instructions for its installation and maintenance. See Annex A and Annex C.

These instructions shall contain the following:

a) The limitations on:

• intended use,
• door mass and door dimensions,
• maximum door distortion to enable safe exit at all times (see 5.2.2),
• minimum resistance of the door leaf against a pulling force of the recommended fixing screws,
• field of door application,
• fire/smoke door suitability.

Where an exit device is suitable for use on fire and smoke door assemblies based on a test in accordance
with EN 1634-1 (see 7.4 Grade B), the product information shall include:
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

• fire resistance time (i.e. 30 minutes, 90 minutes, etc.) for each door configuration approved
(i.e. single leaf door only, double exit door, etc.),
• type of door (timber, steel, others),
• reinforcements supplied with the exit device if any,
• any additional information such as fire test report or web site where to find updated information.

b) The following warning in a prominent position: "The safety features of this product are essential to its
compliance with EN 1125. No modification of any kind, other than those described in these
instructions, is permitted".

c) Installation and fixing instructions to ensure that the panic exit device can achieve the performance
requirements in this document, including any restriction in use, for example conditions under which the
exit device could be rendered inoperable. See 4.1.24 and Annex A.

25

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

d) Maintenance instructions to ensure that the panic exit device continues to achieve the performance
requirement in this document for a reasonably economic working life (see Annex C).

e) A list of all elements that are tested and approved for use with this panic exit device and which may be
packaged separately, e.g. mortise lock, horizontal bar, cylinder, keeper, etc.

Where an assembly is using different accessories, the producer shall clearly identify configurations that are
acceptable within the product family and those which are not (i.e. using a table).

It is of paramount importance that a panic exit device is installed as defined by the producer and equipped
with properly compatible components and/or accessories. Therefore this information shall be available in
the producer’s instructions.

If the producer allows a double doorset to be equipped with a combination of a panic exit device in
accordance with EN 1125 on the active (or first opening) leaf and an emergency exit device on the inactive
(or second opening) leaf, the installation instructions shall clearly indicate which specific EN 1125 panic
exit device on the active leaf is compatible in combination with which specific EN 179 emergency exit
device chosen on the inactive leaf. See Annex A.

Compliance shall be verified in accordance with 6.3.1.b).

5 Tests - General and test apparatus

5.1 General

Any panic exit device within any one product range having significantly different working components, or
working components of significantly different materials, shall be separately tested.

Panic exit devices intended for use with a mortise lock shall be tested together with the horizontal bar
specified by the producer.

Three test samples shall be used for testing in accordance with this European Standard:

 test sample A for environmental tests;

 test sample B for design and performance tests;

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
 test sample C for reference or further tests.

Alternatively, test sample C can be used also for environmental tests if it is necessary to split temperature
and corrosion test.

Failure of any one test within a sequence shall constitute failure of that particular test sample.

In the case of any one test sample failure the relevant test sequence may be repeated using sample C.

The panic exit device shall be fitted to the test door in accordance with the producer's instructions as in 4.3.

If a panic exit device is to be used on single leaf doors only, this panic exit device shall be tested on the
test door described in 5.2.2.1, or on the test door described in 5.2.2.2 by using only one of the two leaves,
with the unused leaf being clamped secured.

If a panic exit device is to be used on double doorsets, this panic exit device shall be tested only on the
test door described in 5.2.2.2.

NOTE It is recognized that such panic exit devices can also, in some circumstances, be used on single leaf doors.

26

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Throughout these tests, the following tolerances on values shall apply, unless otherwise stated:

- angular position, in degrees ± 2°;

- force, in Newtons ± 2 %;

- length, in millimetres ± 2 %;

- mass, in kilograms ± 5 %;

- temperature, in degrees Celsius ± 2 °C;

- time, in seconds ± 10 %.

The ambient temperature of the test environment shall be controlled throughout the tests to between
+15 °C and +30 °C. The environment shall be free from draughts.

5.2 Test apparatus

5.2.1 General

Instruments with an accuracy of 1,5 % of reading or better shall be used for measurements in accordance
with these test methods.

The forces required shall be applied as follows:

 release forces required in 6.2.3 and 6.3.2, shall be applied gradually at an average rate of 20 N/s ±
10 % from 30 N to the required value;

 abuse forces required in 6.3.5 and 6.3.6 shall be applied gradually at an average rate of 100 N/s ±
10 % from 100 N to the required value;

 security forces required in 6.3.7 shall be applied gradually at an average rate of 100 N/s ± 10 % from
500 N to the required value;

 operating forces required in 6.3.4, shall be applied gradually, in no less than 1 s.

 re-engagement force required in 6.3.3 shall be applied from 30 N to 50 N or to the required value
within 1 s.

For example, these rates are calibrated on a blocked door prior to carrying out the tests. Unless otherwise
stated in the relevant clause, all forces shall be applied by means of a polyamide or POM actuator of the
following dimensions:

a) release tests and cycling tests (horizontal bar operation): diameter 60 mm;

Where such a dimension cannot be applied due to design of the product, a minimum 15 mm diameter
actuator shall be used and its use shall be recorded in the test report.

b) door loading test: diameter 60 mm;

Pulling may be used as an alternative way to conduct the test.

c) abuse tests (all elements): diameter 15 mm.

All edges shall be radiused by 3 mm.

27
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

All cycle testing equipment shall include means of recording the number of cycles attained.

5.2.2 Test door

5.2.2.1 For a single leaf test door, the test door leaf shall be 2 100 mm high and 1 100 mm wide. It shall
have means of attaching weights so that the door mass is in accordance with the intended classification in
kilograms ± 2 %. The test door and its frame shall be made of material of sufficient rigidity (i.e. welded
steel or aluminium profiles) such that any distortion taking place during the test sequence shall be no more
than 5 mm at any position. Actuating means shall be provided to enable the door to be opened solely by
operating the horizontal bar of the panic exit device under test.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
5.2.2.2 For a double leaf test door, the test door leaves shall each be 2 100 mm high and 1 100 mm
wide. They shall have means of attaching weights so that the door mass is in accordance with the intended
classification in kilograms ± 2 %. The test door leaves and their frames shall be made of material of
sufficient rigidity (i.e. welded steel or aluminium profiles) such that any distortion taking place during the
test sequence shall be no more than 5 mm at any position. Actuating means shall be provided to enable
either door leaf to be opened solely by operating the respective horizontal bar of the panic exit device
under test. Provision shall be made for an astragal (or rebated edge) to be fitted to the external face of the
first opening leaf. The effective gap between the two leaves shall be 6 mm.

5.2.2.3 The position of the centre of gravity shall be nominally at the mid-height position of the test door
leaf and 500 mm from the vertical axis of the hinges.

5.2.2.4 The test door shall be mounted vertically on hinges or other bearings attached to the rigid frame.
The moment of friction shall not exceed 2 Nm in both directions. The axis of rotation shall be positioned
65 mm from the inside face of the test door leaf measured perpendicular to the leaf. See Figure 13.

Dimensions in millimetres

1 100
65

Figure 13 — Mounting of test door and frame

5.2.2.5 The producer may specify any reinforcement or special preparation to the door, according to the
installation instructions.

6 Test methods – Procedures

6.1 General

Test samples as in 5.1 shall be used for performance verification.

 test sample A for environmental tests;

 test sample B for design, product information and mechanical performance tests.

The Flow Chart described in Annex D shall be used for the test sequence.

28

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Alternatively, test sample C can be used also for environmental tests if it is necessary to split temperature
and corrosion test.

During installation, the positional details (i.e. keepers, bolts, gaps, etc.) shall be recorded in the test report.

Prior to each individual test, it shall be permitted to carry out the following adjustments: retightening of
fixing screws to the test door, and cleaning of bolts and keepers (only once after the durability test). Such
adjustments shall be recorded in the test report.

After installation and until the end of the test sequence, in the order detailed in 6.3.2 to 6.3.8, it shall not be
permitted to carry out the following adjustments: modification of the adjustment or positioning of keepers,
rods, bolts, latches, springs, and operating element.

For mortise panic exit devices, mortised locks shall be installed in a way that the vertical axis of the forend
is positioned 20 mm from the internal face of the test door leaf. If this requirement is in conflict with the
producer’s installation instructions, the producer’s installation instructions shall be followed. See Annex A.

6.2 Test procedure - Test sample A – Environmental tests

6.2.1 General

The environmental tests shall be carried out in the order detailed below.

6.2.2 Temperature test

6.2.2.1 Principle

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
The panic exit device shall be exposed in as assembled a state as possible to high and low temperatures
for sufficient time to allow temperature stability to be reached, and for functional tests to be conducted. For
the functional test, the forces required to withdraw the bolt head(s) shall be measured and compared
without using the keeper.

Tests may be carried out either as sub-assemblies or complete devices.

NOTE The humidity level is not critical during this test.

6.2.2.2 Test procedure

- Stabilize the panic exit device for a minimum of 4 h at a temperature of +20 °C.

- While still in the test chamber, measure relevant operating forces.

- Stabilize the panic exit device for a minimum of 4 h at a temperature of +60 °C.

- While still in the test chamber, measure relevant operating forces.

- Verify that the operating forces are no more than 50 % in excess of the operating forces measured at
+20 °C.

- Stabilize the panic exit device for a minimum of 4 h at a temperature of -10 °C.

- While still in the test chamber, measure relevant operating forces.

- Verify that the operating forces are no more than 50 % in excess of the operating forces measured at
+20 °C.

29

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

The operating force in this test shall be the force required to operate the panic exit device or any of its
critical components. Alternatively, where it is not possible to measure relevant operating forces inside the
test chamber, it is possible to assemble the device outside the test chamber in a maximum time of 5 min in
order to measure the operating forces.

6.2.3 Corrosion test

6.2.3.1 Pre-test release force

6.2.3.1.1 Single leaf test door

Install test sample A on the test door in accordance with the producer's instructions.

With no thrust on any part of the test door and with the test door secured, the horizontal bar shall be
actuated at its midpoint and within a maximum of 25 0+10 mm from each end of the operating bar.

This test shall be conducted three times. Verify each time that the panic exit device meets the
requirements of 4.2.9.a).

6.2.3.1.2 Double leaf test door

The test of 6.2.3.1.1 shall be carried out on each leaf, depending on the field of door application claimed.

6.2.3.2 Neutral salt spray test

Remove the panic exit device from the test door and, in as assembled a state as possible, subject to a
neutral salt spray test in accordance with 4.1.4.

Surfaces which are not exposed to the atmosphere in normal installation may be covered or protected
during this test. For example, mortise elements may be inserted into a suitable piece of material such as
"PMMA" or a non metal material.

6.2.3.3 Post-test release force

6.2.3.3.1 Single leaf test door

After completion of the test remove the panic exit device from the cabinet and rinse it gently in clean
running water at a temperature not exceeding 40 °C. Allow the device to dry for 3 h at a temperature of
between 15 °C and 30 °C and at a humidity of between 40 % RH and 70 % RH. At the end of the 3 h
drying period, and in a time of up to 2 h, re-install the panic exit device on the test door.

With no thrust on any part of the test door and with the test door secured, the horizontal bar shall be
actuated at its midpoint and within a maximum of 25 0+10 mm from each end of the horizontal bar.

This test shall be conducted 10 times. Verify that during each of the last three times, the panic exit device
meets the requirements of 4.2.9.b).

6.2.3.3.2 Double leaf test door

The test in 6.2.3.3.1 shall be carried out on each leaf, depending on the field of door application claimed.

30
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

6.3 Test procedure - Test sample B - Design and performance tests

6.3.1 General

a) Compliance with the design requirements given in 4.1 shall be verified by visual inspections, functional
tests or measurements. See 3.29, 3.30, 3.31.

b) Compliance with the requirements for product information in accordance to 4.3 shall be verified by
visual inspections and be recorded in the test report. This report shall include at least the following:

1. installation instructions and permitted adjustments;

2. limitation of the door size and mass and door configuration;

3. safety warning;

4. maintenance instructions;

5. list of approved components and accessories;

6. fire/smoke suitability information including type of door and fire resistance time.

Items 2, 5 and 6 may be obtained from the producer's web site, if available.

NOTE This is desirable to ensure that the latest product information is available.

c) The performance requirements shall be tested in the order detailed in 6.3.2 to 6.3.8.

Prior to the start of the test sequence of sample B (design and mechanical performance), it is permissible
to make any necessary installation adjustments to the panic exit device or its fixings in accordance with the
producer's instructions.

6.3.2 Release tests

6.3.2.1 Release tests door not under pressure

6.3.2.1.1 Single leaf test door

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
Prior to testing, the panic exit device shall be set to its most unfavourable configuration to verify that
reliable release is achieved in all expected situations. For example, when a deadbolt is available, it shall be
engaged prior to the release test. See Figure 10.

With no thrust on any part of the test door and with the test door secured, the horizontal bar shall be
actuated by a force at three successive positions along the bar, midpoint and within a maximum of 25
+10
0 mm from each end of the horizontal bar.

This test shall be conducted three times at each position.

Verify each time and at each position that the panic exit device meets the requirements of 4.2.2.1.

6.3.2.1.2 Double leaf test door

The test of 6.3.2.1.1 shall be carried out on each leaf, depending on the field of door application claimed.

31

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

6.3.2.2 Release tests door under pressure

6.3.2.2.1 Single leaf test door

Using the same installation as for 6.3.2.1.1 apply to the test door a force of 1 000 N at a position of 550
mm from the centre line of the hinges of the test door leaf and between 800 mm and 1 200 mm from the
bottom of the test door in the direction of exit.

With the test door secured, the horizontal bar shall be actuated by a force at three successive positions
along the bar, midpoint and within a maximum of 25 0+10 mm from each end of the horizontal bar.

This test shall be conducted three times at each position.

Verify each time and at each position that the panic exit device meets the requirements of 4.2.2.2.

6.3.2.2.2 Double leaf test door

a) Using the same installations as for 6.3.2.1.2 apply to the active leaf a force of 1 000 N at a position of
550 mm from the centre line of the hinges and between 800 mm and 1 200 mm from the bottom of the
active leaf in the direction of exit.

With both door leaves secured, the horizontal bar mounted on the active leaf shall be actuated by a
force at three successive positions along the bar, midpoint and within a maximum of 25 0+10 mm from
each end of the horizontal bar.

This test shall be conducted three times at each position.


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Verify each time and at each position that the panic exit device meets the requirements of 4.2.2.2.

b) Repeat test a) but apply the actuating force to the horizontal bar mounted on the inactive leaf.

c) Repeat test a) but apply the 1 000 N force to the inactive leaf and apply the actuating force to the
horizontal bar mounted on the inactive leaf.

d) Repeat test a) but apply the 1 000 N force to the inactive leaf and apply the actuating force to the
horizontal bar mounted on the active leaf.

6.3.3 Re-engaging test

With the test door open at 10°, apply a closing force of up to 50 N at right angles to the face of the test
door, at a position of 1 000 mm from the centre line of the hinges of the test door leaf and between 800
mm and 1 200 mm from the bottom of the test door to re-engage the panic exit device in the secured
position.

In the case of a double doorset, conduct this test on each leaf consecutively, in accordance with the
closing sequence of the panic exit device under test.

This test shall be conducted three times.

Verify each time that the panic exit device meets the requirements of 4.2.3.

32

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

6.3.4 Durability test

6.3.4.1 General

Panic exit devices shall be subjected to durability test cycles according to their field of application as in
Tables 2 and 3.

Some exit devices, especially those delivered in a modular way, are not suitable for certain type of doors
(i.e. two vertical rod devices on a rebated double doorset). It shall be clear in the installation instructions
which combination is suitable for use on which type of door. See Annex A.

The panic exit device under test shall be actuated by its operating element as follows:

- Measure and record the gap between the bolt head(s) and keeper(s);

- Measure and record the engagement of the bolt head(s) into the keeper(s);

- Prior to the cycling test, measure and record the force needed to release the exit device with 25 N load
on the test door;

- Apply the force needed to release the exit device, and open the door. The test door shall be opened by
solely actuating the horizontal bar at its midpoint;

- If the operating force is not enough during the durability test, then gradually increase the operating
force until it operates, and continue the cycling. The maximum force allowed to release the panic exit
device installed on the active leaf shall not exceed 25 % of the required release force in 4.2.2.1. This force
shall be recorded in the test report;

- At the end of the cycling test, measure and record the force needed with 25 N load on the test door to
release the device;

- Measure and record the gap between the bolt head(s) and keeper(s) at the end of the cycling test;
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

- Measure and record the engagement of the bolt head(s) into the keeper(s);

- Verify that the exit device meets the requirements of 4.1.17.

The full test sequence for sample B (initial release test, re-engaging test, durability test, release test, abuse
resistance test and security test) shall be performed with the same installation of the exit device according
to producer's instructions, to verify the durability of the performance of the exit device. No adjustment is
allowed because of wear of the product.

33

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Table 2 - Test method according to category

Category Field of Door applications covered Test method


A  Outwardly opening single door Test 1 + Test 2

 Outwardly opening double door: active or inactive


leaf,

B  Outwardly opening single door only Test 1

C  Outwardly opening double door: Inactive leaf only Test 2

Table 3 – Number of cycles

Test Test door Number of cycles


method
Test 1  Outwardly opening single leaf door 100 000 or 200 000
cycles
 Outwardly opening double door

Test 2  Outwardly opening double door (operate inactive leaf 10 000 or 20 000
in order to open both leaves) cycles

According to the producer’s installation instructions, the most unfavourable conditions (e.g. different
keepers or functions) shall be chosen in order to minimize the amount of testing required. This may be
done by preliminary testing or evaluation. See Annex A.
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Test 1:

The test door shall be opened to an angle of between 10° and 12° by solely actuating the operating bar.
Following a dwell period of not less than 0,5 s a closing force shall be applied to return the test door to the
secured position in a time of between 1,0 s and 2,0 s. The closing force shall be removed when the test
door reaches an open position of (5 ± 1)°, allowing the test door to latch by kinetic energy alone, and with
no residual closing moment. Following a dwell period in the latched position of not less than 0,5 s, cycling
shall continue for a total of 100 000 cycles for grade 6 or 200 000 cycles for grade 7.

In the case of testing a panic exit device on the inactive leaf, the active leaf shall be held open throughout
Test 1.

A force of 25 N shall be applied to the single leaf test door or to both leaves of a double leaf test door at a
position of 550 mm from the centre line of the hinges, and between 800 and 1 200 mm from the bottom of
the test door in the direction of door opening, to simulate a force caused by seals.

Test 2:

Both leaves of the test door shall be opened by solely actuating the operating element of the inactive leaf
to an angle of at least 10°, for a total of 10 000 cycles for grade 6, or 20 000 cycles for grade 7. Means
shall be provided to return each leaf in a time of between 3 s and 6 s to the secured position in the correct
sequence, with no residual closing moment, before the commencement of the next cycle.

The test door may be opened further than 10° if required by the construction of the panic exit device.

34

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

A force of 25 N shall be applied to both leaves of the double leaf test door at a position of 550 mm from the
centre line of the hinges, and between 800 and 1 200 mm from the bottom of the test door in the direction
of door opening, to simulate a force caused by seals.

After completing the total required number of cycles, verify that the panic exit device meets the
requirements of 4.2.4.

When an outside access device is supplied with optional re-entry function, then this function shall be tested
20 cycles every testing day or after not more than 20 000 cycles.

The test report shall record the specific types of door installation for which the panic exit devices tested are
approved.

Where periodic lubrication is recommended by the producer it shall not take place before 20 000 cycles
have been attained and at no less an interval than 20 000 cycles thereafter.

6.3.4.2 Panic exit devices with additional deadbolt

When a panic exit device is equipped with a deadbolt for additional security, the first 25 000 cycles for
grade 6, or 50 000 cycles for grade 7 shall be conducted with the deadbolt engaged each time before the
panic exit device is released.

6.3.5 Abuse resistance test – Horizontal bar

With the test door clamped in the closed position, apply a force of 1 000 N consecutively in each of four
directions at three positions along the horizontal bar, midpoint and within a maximum of 25 0+10 mm from
each end, at right angles to the bar, for not less than 10 s at each position. The forces shall be applied in
the most unfavourable order, according to the particular design of the panic exit device. See Figure 11.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
Verify that the panic exit device meets the requirements of 4.2.5.

If the design of a panic exit device does not permit a force to be applied in a given direction without
materially affecting the panic exit device (for example by drilling or clamping, etc), this part of the test may
be omitted. Any such omission shall be noted in the test report.

NOTE It is possible to use a specifically designed fixture in order to apply abuse forces where required.

6.3.6 Abuse resistance test - Vertical rods

With the test door secured in the closed position, apply a pulling force of 500 N at the midpoint on the
longest unsupported length of surface fixed vertical rods in a direction perpendicular to the door face for
not less than 10 s. See Figure 12.

Verify that the panic exit device meets the requirements of 4.2.6.

If the design of a panic exit device does not permit the force to be applied (see 4.1.19), this test may be
omitted. Any such omission shall be noted in the test report.

6.3.7 Security test

The force applied during the release test of 6.3.2.2 shall be considered to satisfy the security requirements
of 4.2.7.

6.3.8 Final examination

At the completion of tests 6.3.2 to 6.3.7, verify that the panic exit device meets the requirements of 4.2.8.

35

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

7 Classification

7.1 Category of use (1st character)

Only one grade of use shall be used:

 grade 3: high frequency of use where there is little incentive to exercise care, i.e. where there is a
chance of an accident occurring and of misuse.

EXAMPLE Doors to shops, hospitals, schools and other buildings which provide access to designated areas and
which are used by the public and others frequently carrying or propelling bulky objects.

7.2 Durability (2nd character)

Two grades of durability shall be used:

 grade 6: 100 000 test cycles;

 grade 7: 200 000 test cycles.

7.3 Door mass (3rd character)

Three grades of door mass shall be used:

 grade 5: up to 100 kg;

 grade 6: up to 200 kg;

 grade 7: over 200 kg;

7.4 Suitability for use on fire/smoke doors (4th character)

Three grades shall be used:

 grade 0: Not approved for use on fire / smoke door assemblies;

 grade A: Suitable for use on smoke door assemblies - based on the requirements of B.1.

 grade B: Suitable for use on fire and smoke door assemblies based on a test in accordance with EN
1634-1;

Annex B contains additional requirements for panic exit devices to this grade.

7.5 Safety (5th character)

Only one grade of safety shall be used:

 grade 1: all panic exit devices have a critical safety function, therefore only the top grade is identified
for the purpose of this European Standard.

7.6 Corrosion resistance (6th character)


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Two grades of corrosion resistance given in EN 1670: 2007, 5.6, shall be used:

 grade 3: 96 h (high resistance)

36

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

 grade 4: 240 h. (very high resistance)

7.7 Security (7th character)

Only one grade of security shall be used:

 grade 2: panic exit devices are primarily for the operation of a door from the inside and the security
requirements are secondary to those of safety.

NOTE Grade 2 is a minimum specification. If additional specific tests are made to prove a higher level of security,
the panic exit devices will be deemed to conform with this European Standard provided that all the requirements of this
European Standard are met.

7.8 Projection of horizontal bar (8th character)

Two grades of horizontal bar projection shall be used:

 grade 1: projection up to 150 mm (large projection);

 grade 2: projection up to 100 mm (standard projection).

7.9 Type of horizontal bar operation (9th character)

Two types of operation shall be used:

 type A: panic exit device with "push-bar" operation.

 type B: panic exit device with "touch-bar" operation.

7.10 Field of door application (10th character)

Three categories of fields of door application shall be used according to the end use of the panic exit
device (see 6.3.4). A panic exit device shall be characterised for one field of door application only.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
 category A: single door, double door: active or inactive leaf;

 category B: single door only;

 category C: double door, inactive leaf only;

NOTE Certain panic exit devices are restricted to particular doors within this broad categorization. The installer
should check the specific application according to the producer’s installation instructions.

7.11 Example of classification

1 2 3 4 5 6 7 8 9 10
3 7 5 B 1 3 2 2 A B

This classification denotes a panic exit device with the following characteristics:

(3) is suitable for use in high frequency applications;

(7) tested to 200 000 cycles;

(5) for door mass up to 100 kg;

37

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

(B) suitable for use on fire/smoke resisting door assemblies according to product information;

(1) is safe in use on escape route doors;

(3) with high corrosion resistance;

(2) with grade 2 security level 1000 N;

(2) with a horizontal bar projection of up to 100 mm;

(A) a "push bar" type A of panic exit device;

(B) suitable for use on a single door only.

8 Marking

8.1 On the product

A producer may only claim compliance with this European Standard if compliance can be demonstrated
with all the relevant clauses of this document for type "A" or type "B" panic exit devices.

Where the requirements of this clause are also required for regulatory marking, compliance with the
requirements for regulatory marking shall be deemed to satisfy the requirements of this clause. Voluntary
marking shall not be applied in such a manner that it could be confused with the regulatory marking. The
following information shall be marked on the product:

a) CE marking symbol; see Annex ZA for further requirements;

b) identification number of the certification body;

c) producer's name or trademark or other means of positive identification;

d) number and year of this European Standard, i.e. EN 1125: 2008;

e) full classification of the product;

f) month and year of manufacture.

Only item a) CE marking symbol and items b) and c) shall need to be visible after installation. Item f) may
be in coded form.

NOTE 1 For CE marking and labelling, see ZA.3.

NOTE 2 See Table 4.

8.2 On the packaging

The following information shall be marked on the packaging:

a) producer's name or trademark or other means of positive identification;

b) number and year of this European Standard, i.e. EN 1125:2008;

c) producer’s product reference number.

NOTE See Table 4.

38
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

8.3 On the installation instructions

The information given in Table 4 shall be marked on the installation instructions.

Table 4 - The marking requirements

On the product (device On the On the


Marking requirements
mechanism and/or operating packaging installation
element) instructions
Visible before Visible after
installation installation

CE marking symbol - X - X

Identification number of the certification body - X - X

The name or identifying mark of the producer - X X X

Registered address of the producer - - - X

The last two digits of the year in which the marking - - - X


was applied
The number of the EC certificate of conformity - - - X
a a
Reference to this European Standard (number and X - X X
year)
Classification Xa - - X

Month and year of assembly by producer X - - -

Category of projection - - - X

Field of door application - - - X

Door dimension suitability - - - X

Producer’s product reference number - - X X

Information on the only approved components for use - - - X


on escape/exit doors (operating elements, keepers,
etc.)
a If a product conforms to different standards with different classifications, then this additional marking may be omitted and
included in the Installation instructions. See Annex A.

8.4 Mortise lock combined with a separate horizontal bar unit


--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

If a panic exit device consists of a mortise lock combined with a separate horizontal bar unit, and the
mortise lock cannot be replaced without removing the bar unit first, then it is sufficient to apply the marking
requirements to the bar unit only.

9 Evaluation of Conformity

9.1 Initial type test

9.1.1 General

The conformity of the panic exit device to the requirements of this European Standard and with the stated
values (including classes) shall be demonstrated by:

39

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

 initial type testing;

 factory production control by the producer, including product assessment.

For the purposes of testing, panic exit devices may be grouped into families, where it is considered that the
results for one or more characteristics from any one product within the family are representative for those
same characteristics for all panic exit devices within that same family (a product may be in different
families for different characteristics).

An initial type test is the complete set of tests or other procedures, in respect of the characteristics to be
assessed, determining the performance of samples of products representative of the product type.

Initial type testing shall be performed to show conformity with this European Standard for panic exit
devices being put onto the market.

Initial type testing shall be repeated if a change in production process, in material, in supply of components
or in product design, could detrimentally affect the performance of the declared characteristics.

NOTE The producer should discuss such changes with the laboratory that conducted the original type testing in
order to evaluate the need for new initial type testing.

In the case of type testing of panic exit devices for which initial type testing in accordance with this
European Standard was already performed, type testing may be reduced if it has been established that the
performance characteristics compared with the already tested panic exit devices have not been affected.

Where kit components (e.g. sub assemblies) are used whose characteristics have already been
determined, by the component producer, on the basis of conformity with this or other appropriate European
technical specifications, these characteristics need not be reassessed provided that the components'
performance or method of assessment remain the same, that the characteristics of the component are
suitable for the intended end use of the finished product, and insofar as the manufacturing process does
not have a detrimental effect on the determined characteristics.

Products CE marked in accordance with appropriate harmonised European specifications may be


presumed to have the performances stated with the CE marking, although this does not replace the

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
responsibility of the kit producer to ensure that the kit as a whole is correctly designed (where the producer
himself undertakes the design) and its components have the necessary performance values to meet the
design.

9.1.2 Characteristics

All characteristics in 4.2 shall be subject to initial type testing.

Release of dangerous substances may be assessed indirectly by controlling the content of the substance
concerned.

9.1.3 Use of historical data

Tests previously performed on the same panic exit devices in accordance with the provisions of this
European Standard (same characteristic(s), test method, sampling procedure, system of attestation of
conformity, etc.) may be taken into account.

9.2 Sampling, testing and conformity criteria

Samples, selected in accordance with 6.1, representing the series, shall be subjected to the full test
sequence in accordance with 6.2 and 6.3 and, where relevant, Annex B.

The following rules shall be applied for the selection of test samples:

40

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

a) separate type tests shall be conducted where devices have different numbers of locking points;

b) separate type tests shall be conducted where significant components (which can affect its performance
to the standard) are of different design or material;

c) variations of model within a family that have not been selected for initial type test shall be covered
through the periodic and annual testing;

d) tests performed on samples that are not made from full production methods, processes and tooling
shall be repeated within the first six months of full production.

NOTE Item d) is a possibility offered to the producer to reduce time and cost to market. It is essential to be
able to verify that the product made from production tools has the same design characteristics and performance as the
samples that have been accepted.

Where devices in families have a different number of locking points, or where significant components that
could affect the performance to this European Standard are of a different design or material, the most
severe and/or unfavourable configuration of such devices shall be subjected to an initial type test or such
devices shall be subjected to separate initial type tests.

It may be possible to carry out pre-tests, to identify the worst case product/combination for type testing,
that is representative of the series. This shall include pre-release tests on different versions within the
series, including for example different keeper settings or outside access devices, to evaluate the most
unfavourable version to be tested.

9.3 Factory production control

9.3.1 General

The producer shall establish, document and maintain a factory production control (FPC) system to ensure
that the products placed on the market conform to the declared performance characteristics. The FPC
system shall consist of written procedures (works' manual), regular inspections and tests and/or
assessments and the use of the results to control raw and other incoming materials or components,
equipment, the production process and the product. Records shall remain legible, readily identifiable and
retrievable.

An FPC system conforming to the requirements of EN ISO 9001:2000, and made specific to the
requirements of this European Standard shall be considered to satisfy the above requirements.

The results of inspections, tests or assessments requiring action shall be recorded, as shall any action
taken. The action to be taken when control values or criteria are not met shall be recorded and retained for
the period specified in the producer’s FPC procedures.

9.3.2 Documents

The producer shall draw up and keep up-to-date documents defining the FPC that is applied. The
producer’s documentation and procedures shall be appropriate to the product and manufacturing process.
The FPC system shall achieve an appropriate level of confidence in the conformity of the product. This
involves:

a) preparation of documented procedures and instructions relating to FPC operations;

b) effective implementation of these procedures and instructions;

c) recording of these procedures and their results;

41
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

d) use of these results to correct any deviations, repair the effects of such deviations, treat any resulting
instances of non-conformity and, if necessary, revise the factory production control to rectify the cause of
non-conformities.

The producer shall establish procedures to ensure that the production tolerances allow for the panic exit
device’s performances to be in conformity with the declared values, derived from initial type testing.

The producer shall record the results of the tests specified above. These records shall at least include the
following information:

 identification of the panic exit device tested;

 date of sampling and testing;

 test methods performed;

 test results;

 frequency of product testing. See 9.4 and 9.5.

9.3.3 Traceability and marking

Individual products, product batches or packages shall be identifiable and traceable with regard to their
production origin. The producer shall have procedures ensuring that processes related to affixing
traceability codes and/or markings (see Clause 8) are inspected regularly. Compliance with EN ISO
9001:2000, 7.5.3 shall be deemed to satisfy the requirements of this sub-clause.

9.3.4 Non conforming products

The producer shall have written procedures which specify how non-conforming products shall be dealt with.
Any such events shall be recorded as they occur and these records shall be kept for the period defined in
the producer’s written procedures. Compliance with EN ISO 9001:2000, 8.3 shall be deemed to satisfy the
requirements of this sub-clause.

9.3.5 Corrective action

The producer shall have documented procedures that instigate action to eliminate the cause of non-
conformities in order to prevent recurrence. Compliance with EN ISO 9001:2000, 8.5.2 shall be deemed to
satisfy the requirements of this sub-clause.

As a minimum, the producer shall have procedures to treat non-conforming products as follows:

a) isolate and identify non-conforming products;

b) undertake the necessary corrective actions;

c) repeat tests as appropriate to prove that the product meets the specifications.

9.3.6 Handling, storage and packaging

The producer shall have procedures providing methods of product handling and shall provide suitable
storage areas preventing damage or deterioration.

9.3.7 Personnel

The responsibility, authority and the relationship between personnel that manages, performs or verifies
work affecting product conformity, shall comply with the appropriate clause of EN ISO 9001:2000.

42
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

9.3.8 Equipment

All weighing, measuring and testing equipment necessary to achieve, or produce evidence of, conformity
shall be calibrated or verified and regularly inspected according to documented procedures, frequencies
and criteria. Control of monitoring and measuring devices shall comply with the appropriate clause of
EN ISO 9001:2000.

All equipment used in the manufacturing process shall be regularly inspected and maintained to ensure
use, wear or failure does not cause inconsistency in the manufacturing process.

Inspections and maintenance shall be carried out and recorded in accordance with the producer’s written
procedures and the records retained for the period defined in the producer's FPC procedures.

9.3.9 Design process

The FPC system shall document the various stages in the design of the panic exit device, identify the
checking procedure and those individuals responsible for all stages of design.

During the design process itself, a record shall be kept of all checks, their results, and any corrective
actions taken. This record shall be sufficiently detailed and accurate to demonstrate that all stages of the
design phase, and all checks, have been carried out satisfactorily. Compliance with EN ISO 9001:2000,
7.3 shall be deemed to satisfy the requirements of this sub-clause.

9.3.10 Raw materials and components

The specifications of all incoming raw materials and components shall be documented, as shall the
inspection scheme for ensuring their conformity. The verification of conformity of the raw material with the
specification shall be in accordance with EN ISO 9001:2000, 7.4.3.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
In case supplied kit components are used, the attestation of conformity level of the component shall be at
least that given in the appropriate harmonised technical specification for that component. If this is not the
case, the inspection scheme shall be adequate to demonstrate their suitability.

9.3.11 In-process control

The producer shall plan and carry out production under controlled conditions. Compliance with EN ISO
9001:2000, 7.5.1 and 7.5.2 shall be deemed to satisfy the requirements of this sub-clause.

9.3.12 Unit checks during manufacture

The producer shall conduct as a minimum, the checks given in Table 5:

Table 5 – Minimum frequency of unit checks

Characteristics Clause, Threshold Minimum Minimum


indicating the value (if number of frequency of
relevant test any) and samples/ tests or
method (if any) tolerances tests inspection

Ability to release
(for locked doors on escape
routes)
Release function 4.1.2 Threshold (≤ 1 1 Every sub-
s) assembly
Panic exit device mounting 4.1.3 Pass/Fail 1 6 months
Exposed edges and corners 4.1.5 Threshold (≥ 1 Beginning of
0,5 mm) production

43

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Characteristics Clause, Threshold Minimum Minimum


indicating the value (if number of frequency of
relevant test any) and samples/ tests or
method (if any) tolerances tests inspection

Double doorset 4.1.7 Pass/Fail 1 6 months


Bar installation 4.1.9 Threshold (Z 1 Beginning of
≤ 150 mm) production
Bar length 4.1.10 Threshold (≥ 1 Beginning of
60 %) production
Bar projection 4.1.11 Threshold ( W 1 Beginning of
≤ 100 or 150 production
mm)
Bar end 4.1.12 Pass/Fail 1 Beginning of
production
Operating bar face 4.1.13 Threshold ( V 1 Beginning of
≥ 18 mm) production
Test rod 4.1.14 Pass/Fail 1 Beginning of
production
Door face gap 4.1.15 Threshold (R≥ 1 Beginning of
25 mm) production

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
Accessible gap 4.1.16 Threshold (> 1 Beginning of
20 mm) production
Door free movement 4.1.17 Pass/fail 1 6 months
Top vertical bolt 4.1.18 Pass/fail 1 6 months
Keepers 4.1.20 Pass/fail 1 Beginning of
production
Keepers dimensions 4.1.21 Threshold (H 1 Beginning of
≤ 15 mm; M ≤ production
45°; P ≤ 3
mm)
Door mass and dimensions 4.1.23 Threshold 1 Beginning of
(Grade) production
Outside access device 4.1.24 Pass/Fail 1 Beginning of
production
Release forces 4.2.2 Threshold (≤ 1 Every sub-
assembly batch
80 N and ≤ produced or
220 N under received
pressure)
Security requirement 4.2.7 Threshold 1 Beginning of
(Grade) production

Durability of ability to release


(for locked doors on escape
routes)
Corrosion resistance 4.1.4; 4.2.9 Threshold 1 Beginning of
(Grade) production
Temperature range 4.1.6 Threshold (50 1 Beginning of
% in excess) production
Covers for vertical rods 4.1.19; 4.2.6 Threshold 1 Beginning of
(500 N) production
Lubrication 4.1.22 Threshold 1 Beginning of
(20 000 production
cycles)
Re-engagement force 4.2.3 Threshold (≤ 1 6 months
50 N)
Durability 4.2.4 Threshold 1 Beginning of
(Grade - production
100 000 or
200 000
cycles)

44

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Characteristics Clause, Threshold Minimum Minimum


indicating the value (if number of frequency of
relevant test any) and samples/ tests or
method (if any) tolerances tests inspection

Abuse resistance – Horizontal bar 4.2.5 Threshold 1 Beginning of


(500 N and production
1000 N)
Abuse resistance – Vertical rod 4.2.6 Threshold 1 Beginning of
(500 N) production
Final examination 4.2.8; 4.2.2; 4.1.17 Threshold (≤ 1 Beginning of
production
80 N and ≤
220 N under
pressure)

Self closing ability C


(for fire/smoke doors on escape
routes)
Re-engagement force 4.2.3 Threshold (≤ 1 6 months
50 N)

Durability of Self closing ability


C against aging and
degradation
(for fire/smoke doors on escape
routes)
Durability 4.2.4 Threshold 1 6 months
(Grade -
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

100 000 or
200 000
cycles)
Re-engagement force 4.2.3 Threshold (≤ 1 6 months
50 N)

Resistance to fire E (integrity)


(for use on fire doors) and I
(insulation)
Suitability of panic exit devices for use 4.1.8; Annex B Threshold 1 ITT satisfactory
on fire resisting doorsets assemblies - (Grade) unless a change
- Additional requirements in materials or
components

Control of Dangerous 4.1.25 Pass/Fail 1 (continuous


substances monitoring of raw
material/compon
ents)

- Beginning of production means at the commencement of a production line following a successful ITT. A new ITT
means a new production line.
- Sub-assembly: see Clause 3

9.4 Periodic testing (for all products)

At intervals of no more than six months, samples taken from finished stock, selected in accordance with
6.1 and representative of the series shall be subjected to the following tests:

45

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

a) release tests in accordance with 6.3.2;

b) durability test in accordance with 6.3.4;

c) release tests in accordance with 6.3.2;

d) abuse resistance test on operating element 6.3.5.

Where particular products within a series (or family) of products have not been subjected to a specific initial
type test in accordance with 9.1, such products shall be chosen in sequence for the test of 9.3.1, so that
over time, all variations of the product family, shall have been tested.

9.5 Annual testing (for all products)

At intervals of no more than one year, three samples representative of the series shall be taken from
finished stock and subjected to the full sequence of testing specified in Clause 6.

46 --`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex A
(normative)

Installation and fixing instructions

The following shall be the minimum information and installation guidance to accompany the panic
exit device:

A.1 The producer shall specify the appropriate fixing arrangements for the door types for which the exit

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
device is designed.

A.2 Before fitting an exit device to a door, the door should be checked to ensure correct hanging and
freedom from binding.

It is not recommended, for example, that exit devices be fitted to hollow core doors unless specially
designed by the producer for this type of doors.

It is recommended to verify that the door construction allows the use of the device, i.e. to verify that offset
hinges and engaging leaves allow both leaves to be opened simultaneously (see A.4), or to verify that the
gap between door leaves does not differ from that defined by the exit device producer, or to verify that the
operating elements do not interfere, etc.

NOTE Panic exit devices manufactured in accordance with this European Standard will provide a high degree of
safety and reasonable security provided that they are fitted to doors and door frames that are in good condition.

A.3 Before fitting a panic exit device to a fire/smoke resisting door, the fire certification of the fire door
assembly on which the exit device has been tested to prove suitability for use on a fire door should be
examined. It is of utmost importance that an exit device is not used on a fire door assembly of a greater fire
resistance time than approved for. See Annex B.

A.4 Care should be taken to ensure that any seals or weather-stripping fitted to the complete door
assembly, does not inhibit the correct operations of the panic exit device.

A.5 On double doorsets with rebated meeting stiles and where both leaves are fitted with panic exit
devices, it is essential to check that either leaf will open when its panic exit device is activated and also
that both leaves will open freely when both panic exit devices are operated simultaneously.

The use of a carry bar to move the active leaf may be required for this application.

A.6 Where panic exit devices are manufactured in more than one size it is important that the correct size
is selected.

A.7 Category 2 (standard projection) panic exit devices should be used in situations where there is
restricted width for escape, or where the doors to be fitted with the panic exit devices are not able to open
beyond 90°.

A.8 Where a panic exit device is designed to be fitted to a glazed door, it is essential that the glazing is
tempered or laminated glass.

A.9 Different fixing may be necessary for fitting panic exit devices to wood, metal or frameless glass
doors. For more secure fixing, male and female through-door bolts can be used.

47

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

A.10 Panic exit devices are not intended for use on double action (double swing) doors unless specifically
designed by the producer.

A.11 The fixing instructions should be carefully followed during installation. These instructions and any
maintenance instructions should be passed on by the installer to the user. See Annex C.

A.12 The horizontal bar should normally be installed at a height of between 900 mm and 1 100 mm from
the finished floor level, when the door is in the secured position. Where it is known that the majority of the
occupants of the premises will be young children, consideration should be given to reducing the height of
the bar.

A.13 The horizontal bar should be installed so as to provide the maximum effective length.

A.14 The bolt heads and keepers should be fitted to provide secure engagement. Care should be taken to
ensure that no projection of the bolt heads, when in the withdrawn position, can prevent the door swinging
freely.

A.15 Where panic exit devices are to be fitted to double doorsets with rebated meeting stiles and self
closing devices, a door coordinator device in accordance with EN 1158 (see Bibliography) should be fitted
to ensure the correct closing sequence of the doors. This recommendation is particularly important with
regard to fire/smoke resisting door assemblies.

A.16 No devices for securing the door in the closed position should be fitted other than that specified in
this European Standard. This does not preclude the installation of self closing devices.

A.17 If a door closing device is to be used to return the door to the closed position, care should be
taken not to impair the use of the doorway by the young, elderly and infirm.

A.18 Any keepers or protection plates provided should be fitted in order to ensure compliance with this
European Standard.

A.19 A sign which reads "Push bar to open" or a pictogram should be provided on the inside face of the
door immediately above the horizontal bar, or on the bar if it has a sufficient flat face to take the size of
2
lettering required. The surface area of the pictogram should be not less than 8 000 mm and its colours
should be white on a green background. It should be designed such that the arrow points to the operating
element, when installed. The pictogram given in Figure A.1 can be used:

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Figure A.1—Pictogram

48

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex B
(normative)

Additional requirements for panic exit devices intended for use on


fire/smoke resisting door assemblies

B.1 A panic exit device intended for use on fire/smoke resisting door assemblies shall meet the following
requirements in accordance with its intended classification specified in 7.4.

Grade A: Grade A exit devices representative of their type shall have been subjected to a successful
evaluation proving their suitability for use on smoke resisting doors. For this, all parts of the exit device that
are responsible for keeping the door in its closed position shall be made out of material with a melting point
of not less than 300 °C. If the exit device is equipped with a latch bolt and the latch bolt could be the only
part of the exit device that keeps a smoke door in its closed position, then the projection of the latch bolt
shall be at least 10 mm. Alternatively, the suitability for use on smoke resisting doors shall be determined
by a successful test conducted in accordance with EN 1634-3.

Installation instructions shall ensure that the engagement of the latch bolt inside the locking plate is not
less than 6 mm.

Grade B: Grade B exit devices representative of their type and including any outside access devices
intended for fire door use shall have been subjected to a successful fire test conducted on both sides of
the door in accordance with EN 1634-1 to prove the contribution of the exit device to the fire resistance of
the complete door assembly. It should not be necessary for the exit device to be operable after such a fire
test.

NOTE Although the panic exit devices referred to in this annex are suitable for use with fire/smoke resisting door
assemblies, the safety aspect and ease of escape as described in the introduction to this European Standard remains
of the utmost importance.

B.2 A panic exit device intended for use on self-relatching fire resisting doors shall include an automatic
relatching device.

This requirement shall not apply where the panic exit devices are intended for use on self closing fire
resisting doorsets and where the fire test evidence required by B.1 has been obtained from unlatched fire
resisting doorset assemblies.

Details of the inclusion or otherwise of an automatic relatching device in the fire test samples shall form a
part of the final fire test report.

B.3 A panic exit device intended for use on self-relatching fire resisting doors shall not include a dogging
mechanism or other means of holding the bolt heads in the withdrawn position unless such means are
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

capable of reliable release of the bolt head(s) in conjunction with a smoke/fire alarm system.

This requirement shall not apply where the panic exit devices are intended for use on self closing
smoke/fire resisting doorsets and where the fire test evidence required by B.1 has been obtained from
unlatched smoke/fire resisting doorset assemblies. Regardless of whether a dogging mechanism is
operated or not, the device shall not prevent the door from self closing.

Details of the inclusion or otherwise of a dogging mechanism in the fire test samples shall form a part of
the final fire test report.

If a device intended for use on self-relatching smoke/fire resisting doors allows for automatic rebolting, it
shall be designed to avoid accidental rebolting while the door is opened which could prevent the self
closing of the door.

49

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex C
(normative)

Maintenance instructions

The following shall be the minimum information to accompany the product:

To ensure performance in accordance with this document, the following routine maintenance checks
should be undertaken at intervals of not more than one month (or the period recommended by the
producer):

a) Inspect and operate the panic exit device to ensure that all components are in a satisfactory working
condition; using a force gauge, measure and record the operating forces to release the exit device.

b) Ensure that the keeper(s) is (are) free from obstruction.

c) Check that the panic exit device is lubricated in accordance with the producer’s instructions.

d) Check that no additional locking devices have been added to the door since its original installation.

e) Check periodically that all components of the system are still correct in accordance with the list of
approved components originally supplied with the system.

f) Check periodically that the operating element is correctly tightened and, using a force gauge,
measure the operating forces to release the exit device. Check that the operating forces have not changed
significantly from the operating forces recorded when originally installed.

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

50

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex D
(normative)

Flow chart of test procedures

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Figure D.1 — Flow chart of test procedures

51

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex E
(informative)

Guidance for choosing relevant product standards for particular exit


door applications

The final choice of a product for a particular application depends upon a risk analysis of its intended use on
exit doors. Table E.1 indicates the main functions of the two exit hardware standards, to enable this risk
assessment to be undertaken.

In case of any doubt, a panic situation should be assumed, and therefore preference should be given to
panic exit devices and panic exit systems as these give precedence to safe exit from buildings through
additional requirements for release under loaded door conditions. These requirements simulate the forces
which may be applied by people in panic.

NOTE See Introduction to EN 1125:1997.

Table E.1 — Main functions of exit devices


Standards Î PANIC EMERGENCY
EXIT DEVICES EXIT DEVICES
Functions Ð mechanically operated mechanically operated
EN 1125 EN 179
EXIT PANIC situation: EMERGENCY situation:
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

from inside under panic


or emergency conditions * Exit at all times * Exit at all times
* Single operation of horizontal * Single operation of lever handle in
bar in the direction of exit to a downward direction or in a
release the door downward direction towards the
* No prior knowledge of device hinges, or single operation of push
operation needed pad in the direction of exit and/or in
* Loaded door release of device an arc downwards or to the side, to
release the door
* Prior knowledge of door situation
(e.g. inwardly opening) may be
required

IMPORTANT NOTE: No evaluation


of loaded door release of device
NORMAL EXIT * Egress authorized at all times * Egress authorized at all times
from inside with no panic * Precedence is given to the
or emergency conditions importance of ease of opening
by the young, elderly and infirm
ACCESS * Mechanical or electrical * Mechanical or electrical operation
from outside operation from outside when from outside when available
available * No influence on exit from inside
* No influence on exit from inside
SECURITY * NONE: immediate release of * NONE: immediate release of the
from inside the device without any delay device without any delay
SECURITY * Minimum level * Minimum level or higher grades
from outside possible

52

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Annex ZA
(informative)

Relationship between this European Standard and the Essential


Requirements of EU Directive 89/106/EEC, EU Construction Products
Directive

ZA.1 Clauses addressing the provisions of the EU Construction Products Directive

This European Standard has been prepared under Mandates M/101 and M/126 “External doors and
windows, roof openings and roof lights (including fire doors and shutters)” – amended, given to CEN by the
European Commission and the European Free Trade Association.

The clauses of this European Standard, shown in this annex meet the requirements of the mandate given
under the EU Construction Product Directive (89/106/EEC). Compliance with these clauses confers a
presumption of fitness of panic exit devices covered by this annex for their intended use.

CAUTION — Other requirements and other EU Directives, not affecting the fitness for intended use,
can be applicable to panic exit devices falling within the scope of this European Standard.

NOTE 1 In addition to any specific clauses relating to dangerous substances contained in this European Standard,
there may be other requirements applicable to the products falling within its scope (e.g. transposed European
legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the EU
Construction Products Directive, these requirements need also to be complied with, when and where they apply.

NOTE 2 An informative database of European and national provisions on dangerous substances is available at the
Construction web site on EUROPA (http://europa.eu.int/comm/enterprise/construction/index_en.htm).

This annex establishes the conditions for the CE marking of the panic exit devices intended for the uses
indicated in Table(s) ZA.1 and shows the relevant clauses applicable.
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

This annex has the same scope as Clause 1 of this standard and is defined by Table ZA.1

Table ZA.1 — Clauses of this European Standard applying to the essential characteristics
Product: Panic exit devices operated by a horizontal bar as covered by the scope of this European Standard.
Intended use: For doors on escape routes.
Essential characteristic Requirement clauses Mandated Notes
in this European levels and/or (expression of
Standard classes performance)
Ability to release 4.2.1 None Threshold values as
(for doors on escape routes) Table 1
Durability of ability to release against 4.2.1 None Threshold values as
aging and degradation Table 1
(for doors on escape routes)
Self closing ability C 4.2.1 None Threshold values as
(for fire/smoke doors on escape routes) Table 1
Durability of self closing ability C 4.2.1 None Threshold values as
against aging and degradation Table 1
(for fire/smoke doors on escape routes)
Resistance to fire E (integrity) and I 4.2.1 None Threshold (Grade)
(insulation)
(for fire doors on escape routes)
Control of Dangerous substances 4.1.25 None Clause ZA.3
Note 2 of clause ZA.1
above

53

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

The requirement on a certain characteristic is not applicable in those Member States (MSs) where there
are no regulatory requirements on that characteristic for the intended use of the product. In this case,
manufacturers placing their products on the market of these MSs are not obliged to determine nor declare
the performance of their products with regard to this characteristic and the option “No performance
determined” (NPD) in the information accompanying the CE marking (see ZA.3) may be used. The NPD
option may not be used, however, where the characteristic is subject to a threshold level.

ZA.2 Procedure for the attestation of conformity of panic exit devices

The system of attestation of conformity of panic exit devices indicated in Table ZA.1. in accordance with
the Decision of the Commission 95/204/EC amended 99/93/EC as given in Annex III of the mandate for
“External doors and windows, roof openings and roof lights (including fire doors and shutters)” amended, is
shown in Table ZA.2 for the indicated intended use(s) and relevant level(s) or class(es).

Table ZA.2 — System of attestation of conformity

Product Intended use Levels or System of attestation of


classes conformity

Building hardware For doors on escape routes. --- 1


related to doors and
gates

System 1: See CPD, Annex III point 2 (i), without audit-testing of samples

The attestation of conformity of the panic exit device in Table ZA.1 shall be according to the evaluation of
conformity procedures indicated in Table ZA.3 resulting from application of the clauses of this or other
European Standard indicated therein.

Table ZA.3 — Assignation of evaluation of conformity tasks for panic exit devices under system 1

Evaluation of
Tasks Content of the task conformity
clauses to apply

Tasks under Factory production control


9.3
the (FPC)
responsibility All characteristics of Table ZA.1
9.4
of the Further testing of samples
producer taken at factory 9.5

9.1
Initial type testing All characteristics of Table ZA.1
Tasks under
9.2
the
responsibility
Initial inspection of factory
of the 9.3
and of FPC
product
certification Parameters related to all
body Continuous surveillance, characteristics of Table ZA.1
assessment and approval 9.1
of FPC

54
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

When compliance with conditions of this annex is achieved, the certification body shall draw up a certificate
of conformity (EC Certificate of conformity), which entitles the producer to affix the CE marking.

The EC Certificate of conformity shall include the following information:

a) name, address and identification number of the certification body;

b) name and address of the producer, or an authorised representative established in the EEA, and
place of production;

c) description of the product (type, identification, use);

d) provisions to which the product conforms (e.g. Annex ZA of EN 1125:2008);

e) particular conditions applicable to the use of the product;

f) certificate’s number;

g) conditions and period of validity of the certificate, where applicable;

h) name of, and position held by, the person empowered to sign the certificate;

In addition, for each product covered by an EC Certificate of conformity, the producer shall draw up a
declaration of conformity (EC Declaration of conformity) including the following information:

1) name and address of the producer, or an authorised representative established in the EEA;

2) name and address of the certification body;

3) description of the product (type, identification, use, ...), and a copy of the information
accompanying the CE marking;

4) provisions to which the product conforms (i.e. Annex ZA of EN 1125:2008);

5) particular conditions applicable to the use of the product (e.g. provisions for use under certain
conditions);

6) number of the accompanying EC Certificate of conformity;

7) name of, and position held by, the person empowered to sign the declaration on behalf of the
producer or authorised representative.

It is essential that both documents are presented in the official language or languages acceptable to the
Member State in which the product is to be used.

ZA.3 CE marking and labelling

The manufacturer or authorised representative established within the EEA is responsible for the affixing of
the CE marking. The CE marking symbol to affix shall be in accordance with Directive 93/68/EC and shall
be shown on the panic exit device and/or on the accompanying commercial documents as below:

The CE marking symbol shall be accompanied by the following information:

a) identification number of the certification body;

b) name or identifying mark of the producer;

55
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

c) registered address of the producer;

d) last two digits of the year in which CE marking was affixed;

e) number of the EC certificate of conformity;

f) reference to this European Standard (EN 1125:2008) and product description;

g) full classification of the panic exit device (type).

The CE marking and items a) to g) above shall be included with the installation instructions accompanying
the product. An example of CE marking is given in Figure ZA.1.

Additionally, at least the CE marking symbol and item a), b), f), g) of this information shall be affixed to the
panic exit device. Only the CE marking symbol and items a) and b) shall need to be visible on the product
after installation.

CE conformity marking, consisting of the


“CE”-symbol given in Directive
93/68/EEC.

01234 Identification number of the certification


body
Easy-exit Ltd
Name or identifying mark of the producer

EN 1125: 2008 No. of European Standard

375B1322AB Classification of the product

(see example in 7.11)

Figure ZA.1 a) – Example of CE marking on a panic exit device

56
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

CE conformity marking, consisting of the


“CE”-symbol given in Directive
93/68/EEC.

01234 Identification number of the certification


body
EN 1125: 2008
No. of European Standard and product
Panic exit device description

Type-375B1322AB Classification of the product (see example


in 7.11)

Easy-exit Ltd, PO Box 21, B-1050 Name or identifying mark and registered
address of the producer

08 Last two digits of the year in which CE


marking was affixed

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
01234-CPD-00234 Certificate number (where relevant)
Ability to release : Pass (≤ 80 N unloaded / ≤ 220 N Essential characteristics (where relevant)
loaded)
Durability of ability to release : Pass (200 000
cycles / ≤ 50 N)
Fire resistance C – Self-closing; E – Integrity; I –
Insulation : Pass (Grade B)

Figure ZA.1b) – Example of CE marking on the installation instructions of a panic exit device

In addition to any specific information relating to dangerous substances shown above, the product should
also be accompanied, when and where required and in the appropriate form, by documentation listing any
other legislation on dangerous substances for which compliance is claimed, together with any information
required by that legislation.

NOTE European legislation without national derogation need not be mentioned.

57

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN 1125:2008
EN 1125:2008 (E)

Bibliography

EN 1158, Building hardware - Door coordinator devices - Requirements and test methods

prEN 1634-2, Fire resistance and smoke control tests for door and shutter assemblies, openable windows
and elements of building hardware - Part 2: Fire resistance characterisation test for elements of building
hardware

EN 13501-2, Fire classification of construction products and building elements - Part 2: Classification using
data from fire resistance tests, excluding ventilation services
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---

prEN 13633, Building hardware - Electrically controlled panic exit systems for use on escape routes -
Requirements and test methods

prEN 13637, Building hardware - Electrically controlled emergency exit systems for use on escape routes –
Requirements and test methods

CONSTRUCT 04/645 Rev.1 GUIDANCE PAPER D (concerning the Construction Products Directive -
89/106/EC), CE marking under the construction products directive European Commission - Enterprise
Directorate - General - Single Market : regulatory environment, standardisation and New Approach –
Construction - 27 May 2004

58

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`

Copyright British Standards Institution


blank
Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST
BS EN
1125:2008
BSI — British Standards Institution
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.

Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures

--`,,,`,,`,``,``,,``,``,`,`,,,``-`-`,,`,,`,`,,`---
that subscribers automatically receive the latest editions of standards.

Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001.
Fax: +44 (0)20 8996 7001. Email: [email protected]. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.

Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: [email protected].
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001.
Email: [email protected].
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.

Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
BSI written permission of BSI must be obtained.
389 Chiswick High Road Details and advice can be obtained from the Copyright & Licensing Manager.
London Tel: +44 (0)20 8996 7070. Fax: +44 (0)20 8996 7553.
Email: [email protected].
W4 4AL

Copyright British Standards Institution


Provided by IHS under license with BSI - Uncontrolled Copy Licensee=Atkins Global /5975177002, User=Mohamed, Amir
No reproduction or networking permitted without license from IHS Not for Resale, 01/18/2015 04:07:56 MST

You might also like