This document provides performance specifications for a General Electric Model PG9171(E) gas turbine configured with a DLN combustor. It lists the turbine's design output, heat rate, heat consumption, exhaust flow rate, and exhaust temperature for both natural gas and distillate oil fuels. It also notes corrections that apply to the performance based on altitude, ambient temperature, inlet guide vane modulation, and humidity.

Uploaded by

karim karim
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
183 views

General Electric Model PG9171 (E) Gas Turbine: Estim A Ted Performance - Configuration: DLN Combustor

This document provides performance specifications for a General Electric Model PG9171(E) gas turbine configured with a DLN combustor. It lists the turbine's design output, heat rate, heat consumption, exhaust flow rate, and exhaust temperature for both natural gas and distillate oil fuels. It also notes corrections that apply to the performance based on altitude, ambient temperature, inlet guide vane modulation, and humidity.

Uploaded by

karim karim
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

General Electric M o d e l PG9171(E) Gas Turbine

E stim a ted Perform a n c e - Configuration: DLN Com b u s tor


Compressor Inlet Conditions 59F (15 C), 60% Relative Humidity
Atmospheric Pressure 14.7 psia (1.013 bar)

Fuel Natural Gas Distillate Oil


Design Output kW 122500 127300
Design Heat Rate (LHV) Btu (kJ)/kWh 10140 (10700) 10600 (11180)
Design Heat Cons (LHV)x10^6 Btu (kJ)/h 1242.2 (1310.2) 1349.4 (1423.3)
Design Exhaust Flow x 10^3 lb (kg)/h 3275 (1486) 3355 (1522)
Exhaust Temperature deg. F (deg.C) 1009 (542.8) 1003 (539.4)
Water Flow lb (kg)/h 66850 (30323)
LOAD Base Base
Notes:
1. Altitude correction on curve 416HA662.
2. Ambient temperature correction on curve 522HA353.
3. Effect of modulating IGV's on exhaust temperature and flow on curve 522HA354.
4. Humidity effects on curve 498HA697 - all performance calculated
with a constant specific humidtiy of .0064 or less so as not to exceed 100% relative humidity.
5. Plant Performance is measured at the generator terminals and includes allowances for the effects of
excitation power, shaft driven auxiliaries, inlet bleed heating, 3.5 in H2O (8.7 mbar) inlet and 5.0 in H2O
(12.5 mbar) exhaust pressure drops and a DLN Combustor.
6. Additional inlet and exhaust pressure loss effects:

% Effect on Effect on
Output Heat Rate Exhaust Temp.
4 in Water (10.0 mbar) inlet -1.40 0.42 2.0F (1.1 C)
4 in Water (10.0 mbar) exhaust -0.40 0.40 2.1F (1.2 C)
120
0 Deg F

110

100
Heat Consumption - Percent Design

120 Deg F

90 59 Deg F

80

70

60

50 Note: Solid line depicts operating conditions from FSNL


to Base Load at the design conditions stated above.
Dotted line represents base load operations over the
40
ambient temperature range.

30

20

0 10 20 30 40 50 60 70 80 90 100 110 120 130


T. Austin Generator Output - Percent Design 522HA352
07/14/2000 Rev - 3