Changes To The 2014 National
Changes To The 2014 National
Changes To The 2014 National
CODE
There were a number of changes made to Art. 250 in the 2014 edition of the
National Electrical Code (NEC). Most of the changes were either global issues,
such as the change made across the board moving the 600-V rule to 1000 V or
the changes that involved adding clarification to better explain existing code. But
in a few areas, we see some fairly big changes.
In particular, we see the addition of a new table, Table 250.102(C) (see Appendix
B), in the 2014 Code. This new table is intended to help in determining the proper
size of all types of bonding jumpers, and is very similar to Table 250.66 (see
Appendix B). We see in Part VI of Art. 250 a significant expansion of Art.
250.122(F) Conductors in Parallel, in an attempt to help clarify a fairly confusing
section of the Code. In Part VIII, we see a brand-new section of the Code, Art.
250.167, which adds the requirement for ground-fault detection systems on
certain direct current (DC) systems.
In Part X, for systems operating at over 1000 V, we actually have two entirely new
sections of code. The 2011 version of Art. 250.186 gets renumbered as Art.
250.187, giving us a new Art. 250.186 for 2014. The new Art. 250.186 is quite
large and extensive and deals with new regulations regarding the neutral
conductor. Additionally, this same section sees an entirely new area mandating
the bonding of metal fences for electrical systems operating at 1000 V and higher
in Art. 250.194.
Here is a list of each of the changes to Art. 250 by part. Only a few of the minor
wording changes regarding the global 1000-V change are mentioned below, as in
most cases this change had little impact on Art. 250.
15.1. PART I
15.2. PART II
There is a small change in this section to clarify the wording regarding the 50- to
1000-V specification.
There is a small change in this section to clarify the wording regarding the 50- to
1000-V specification.
There is a small change in this section to clarify the wording regarding the 50- to
1000-V specification.
There is a small change in this section to clarify the wording regarding the 50- to
1000-V specification.
The Code added overhead and underground service conductors to the existing
requirements.
There is a small change in this section to clarify the wording regarding the 1000-V
or less specification.
The Code added overhead and underground service conductors to the existing
requirements.
The Code added wording to confirm that multiple separately derived systems
connected in parallel must also meet the rules found in Art. 250.30.
There was a minor change in this section to improve the clarity of the wording.
There was a minor change in this section to improve the clarity of the wording.
The 2014 edition of the Code changed the order of sections A, B, and C to
improve clarity.
The Code clarified that this section applies to both services and separately
derived systems.
There was a minor change to include the provision that the ground bar
must be of sufficient length to accommodate the number of
terminations necessary for the installation.
This section of the Code was split into four subsections for clarity.
There was a minor change in this section to clarify that a combination of differing
types of electrodes or multiple electrodes of the same type could be used, but
that the same rules apply.
The title of this section was changed and permission to extend rebar or
conductors out and above of the concrete foundation, so as to allow an accessible
location for connecting the grounding electrode conductor to the concrete-
encased electrode, was added
15.4. PART V
The requirement to reference 505.5 and 506.5 was added to this section, and an
informational note with regard to special bonding requirements found in Arts.
501.30, 502.30, 503.30, 505.25, and 506.25 was also added.
15.5. PART VI
The size of the conductor in this rule was changed from 6 AWG to 4 AWG.
Article 250.122(B) Increased in Size
This section was expanded to improve clarity; the exception allowing design
changes by electrical engineers was also added.
A global change to the 600-V rule to 1000 V; this was changed in Exception no. 4.
The Code increased the DC voltage from 50 V to 60 V and required (in Exception
no. 1) that the source of power be adjacent or integral to the system.
The Code placed a maximum size of 3/0 copper or 250 kcmil aluminum for the
grounding electrode conductor on DC systems.
The Code placed a maximum size of 3/0 copper or 250 kcmil aluminum for the
grounding electrode conductor on DC systems.
15.8. PART IX
15.9. PART X
Article 250.194 Grounding and Bonding of Fences and Other Metal Structures
Citation
EXPORT
David R. Stockin: McGraw-Hill's National Electrical Code® 2014 Grounding and
Earthing Handbook. CHANGES TO THE 2014 NATIONAL ELECTRICAL CODE,
Chapter (McGraw-Hill Professional, 2014), AccessEngineering
This product incorporates part of the open source Protégé system. Protégé is
available at http://protege.stanford.edu//