Series 500 Inline and insertion style flow meters accommodate virtually all
common installations requirements. The insertion style flow meters are available
with 1/2” OD probes in 6” to 24” lengths, The inline style are available for pipe sizes
SERIES 500 & 540 from 1/4” to 2”. The 3 1/2” long flow sections have MNPT ends as standard for easy
mounting in the process line. ValuMass flow meters accept 24VDC, 115VAC or
230VAC input power as specified at the time of purchase.
LOW COST/
HIGH VALUE
THERMAL GAS MASS FLOW MEASUREMENT APPLICATIONS-
www.epiflow.com
RTD’s (Resistance Temperature Detectors)
Specifications
Linear signal output 0–5 Vdc & 4–20 mA (Flow and Temperature)
Event Relays (Two) 1 Amp @ 30 Vdc event selectable functions (see Manual)
Communication Protocols RS232 & RS485 Modbus RTU, Optional BACnet, HART or Profibus DP
Display LCD 2-line 16-character Rate, Total, Milliwatts, Temperature, Event
Accuracy including linearity (Ref.: 21°C)* ±(1% of Reading + 0.5% of Full Scale + GTC)
Repeatability ±0.2% of Full Scale
Sensor response time 1 second to 63% of final value
Turn down ratio 100:1; 10 SFPM (0.05 NMPS) Minimum Reading
Withstands Ambient temperature (electronics) -40° to 158°F (-40° to 70°C)
Suitable Process Gas temperature range** -40° to 392°F (-40° to 200°C)
Gas temperature coefficient (GTC) 0.02% Full Scale/°C
Gas pressure effect Negligible over ± 50% of factory calibration pressure
Pressure rating maximum 500 PSIG (Stainless Steel ferrule), 25PSIG (Teflon ferrule)
Input power requirement 6 Watts
24 Vdc @ 250mA
120 Vac 50/60 Hz optional
240 Vac 50/60 Hz optional
Flow Meter power requirements 5 watts maximum
Date/Time RAM Back-up Lithium Button Cell, ten-year life, quantity 1
Wetted materials 316L Stainless Steel
Standard temperature & pressure (STP) 70°F & 29.92" Hg (Air 0.075 lb./cubic foot)
Optional 0°C & 1.0132 BarA (Air 0.081 lb./cubic foot)
Or user specified STP at time of order
NIST traceable calibration Yes
* EPI is not responsible for measurement errors due to flow profile irregularities caused by installation, piping configurations, surface corrosion or scale,
valve placement, etc.
** Specify average process operating temperature, with high & low limits.
NOTE: Specifications subject to change without notice. Consult our web site, www.epiflow.com, at time of order.
NOTE: Eldridge Terms & Conditions for sales available on our web site, www.epiflow.com.
www.epiflow.com
Series 500 & 540
Dimensional Specifications
500 540
INLINE INSERTION
2.75” 3.375” 2.00”
4.50”
0.5” FNPT
e P rod u c t s , e P rod u c t s ,
id g In id g
dr c. dr
In
c.
El El
1.7”
L”
NPT
FLOW
3.5” Length
NO AGENCY CERTIFICATIONS
Flow Transmitter: Manufacturer rated as flame proof Ex, type 4x, IP66
CE