• The SIA-B is an OC&EF protection relay with self powered and RS485 port (Modbus RTU or DNP3.0 protocol, selectable by
dual powered (self-powering + auxiliary power) options. general settings) on the rear side.
• The relay is self powered using the operating current through • The SIA-B is provided with a trip output for low power coil
three /1 (<2VA) standard current transformers fitted on the (24 Vdc – 135 mJ), 3 configurable inputs and 3 configurable
lines. These transformers are also used to obtain current outputs.
measurements. Besides, SIA-B can be used with auxiliary • The SIA-B is fitted with the demand of current (Load Data
power supply (24-230Vac/dc). The relay can be also supplied Profiling) with the following characteristics:
by a USB cable connected to the laptop, with the USB KITCOM » Number of records: 168
adapter or a standard power bank. » Recording mode circular
• Internal commissioning battery included as optional (Lithium » Sampling rate (interval): configurable through
battery: 20 years lifetime). communications 1-60 min
• Metallic box with high electromagnetic compatibility level • The SIA-B is provided with non-volatile RAM memory in order to
(EMC) and wide range of operating temperature. store up to 1.024 events and disturbance fault recording (DFR-
• Really low start-up levels in self powered mode: 75mA in three 20 fault reports and 10 oscillographic records in COMTRADE
phase system /160 mA in single phase system. format), maintaining date & time thanks to its internal RTC (Real
• Test menu allows the trip circuit to be tested before the Time Clock) even without power supply.
transformation centre is powered up. • Each oscillographic record contains 4 analogue channels and
• There are 4 configurable LEDs. When the relay is switched off, up to 32 digital channels. The oscillography is downloaded by
their previous states can be checked by powering the relay communications port. The SICom communications program
up (by self-powering the relay, through USB cable, auxiliary allows the oscillography record to be downloaded and saved
voltage or pressing commissioning battery). in COMTRADE format (IEEE C37.111-1991).
• Self-diagnosis of the relay status (WATCHDOG) through the • The installation and subsequent maintenance of external
configurable LEDs and outputs. batteries is eliminated. The operating costs of the centre are
• Low power consumption. reduced.
• To allow communication, relays are provided with a local • Its compact size makes SIA-B easy to install and its light weight
micro USB front port and with optional remote communication helps the customer to save costs in transport.
10
Functions diagram SIA-B
BUS SIA-B
Standard CT’s
3
50 50* 51 49 SHB TB* 50BF* CLP* 46*
1
50G 50G* 51G
52 52 68
* Optional
1 1
RS485* USB
51G Inverse time measured neutral overcurrent HMI Human Machine Interface
11
Technical parameters SIA-B
Defined time, current deactivation level: 95% Deactivation level: 95% of alarm level
Function 51
Instantaneous deactivation Timing accuracy: ± 5% respect of theorical value.
Timing accuracy for IEC and IEEE curve selection: Maximum number of openings: 1 to 10.000 (step 1)
Maximum accumulated amperes: 0 to 100.000
Without SHB permitted: ± 30 ms or ± (M(A²)) (step 1)
5% (greater of both).
Opening time: 0.02 to 30.00 s (step 0.01 s)
With SHB permitted: ± 50 ms or ± 5% Function 52 Closing time: 0.02 to 30.00 s (step 0.01 s)
(greater of both).
Excessive repeated openings: 1 to 10.000 (step 1)
Timing accuracy for defined time selection: Repetitive openings/Time: 1 to 300 min (step 1 min)
Open breaker activation and reset threshold: 0.6%
Without SHB permitted: ± 30 ms or ±
In
0.5% (greater of both).
Function Enable: No/Yes
With SHB permitted: ± 50 ms or ± 0.5% Function TB (*)
(greater of both). Tap: 1.50 to 30.00 xIn (step 0.01 xIn)
12
Technical parameters SIA-B
16 samples/cycle
4 analog channels and 32 digital channels
13
Connections diagram SIA-B
• 3 CT power supply-measurement
• Rigid neutral
L1
A
L2
LINE B
L3
C
C B N
STRIKER
<24v
A1 A2 A3 A4 A5 A6 A7 A8 +- <135mj
A B C N
Measure Measure Measure Measure
& Power & Power & Power & Power
CURRENT INPUTS
+
B8
TRIP
-
B7
AC/DC
B1
POWER
AUX.
B2
B3
C
LOCAL PORT
INPUTS
B4
micro USB
B5
Digital Protection
B6
Self power
B9
OUTPUT 1
B10
WARNING
B11
Ground PC to relay ground
B12
OUTPUT 2
B13
B14
B15
OUTPUT 3
B16
B17
+ B18
RS485
GND
SAFETY
GROUND
- B19
14
Dimensions and cutout SIA-B
CUT-OUT
PATTERN
15
Kema Standards SIA-B
IEC60255-27 2 kV Zone A
1.2. Dielectric voltage
Clause 10.6.4.3 0,5 kV 150 V DM
IEC 60255-26
IEC60255-27 300 V CM
1.3. Insulation resis- 2.2.7. Power frequency
500 VDC (IEC 61000-4-16)
voltage (50 Hz)
tance Clause 10.6.4.4
Clause 7.2.9
□ Zone B
2. ELECTROMAGNETIC COMPATIBILITY (EMC) tests 100 V DM
2.1. EMISSION 300 V CM
IEC 60255-26 IEC 60255-26
2.2.8. Power frequency 30 A/m cont.
CISPR11 (IEC 61000-4-8)
H- field (50 Hz) 300 A/m 1-3 s
2.1.1. Radiated CISPR22 class A Clause 7.2.10
emission table 1 class A IEC 60255-26 100%; 10-1000 ms
table 6 2.2.9. D.C. Voltage dips (IEC 61000-4-29) 60%; 200 ms
table 7 Clause 7.2.11 30%; 500 ms
IEC 60255-26 100%;
IEC 60255-26
2.1.2. Conducted CISPR22 0,5 – 25 c.
class A 2.2.10. A.C. voltage dips (IEC 61000-4-11)
emission table 2 60%; 10/12 c.
Clause 7.2.11
table 2/4 30%; 25/30 c.
2.2. IMMUNITY IEC 60255-26
2.2.11. D.C. voltage
2,5 kV CM (IEC 61000-4-29) 100%; 5s
IEC 60255-26 interruptions
2.2.1. Slow damped 1,0 kV DM Clause 7.2.11
oscillatory wave (IEC 61000-4-18)
(1 MHz) 1 kV CM IEC 60255-26
Clause 7.2.6 2.2.12. A.C. voltage 100%;
0 kV DM (IEC 61000-4-11)
interruptions 250/300 c
IEC 60255-26 Clause 7.2.11
2.2.2. Electrostatic 6 kV cont.
(IEC 61000-4-2) IEC 60255-26
discharges 8 kV air 15% Ut_dc
Clause 7.2.3 2.2.13. D.C. Ripple (IEC 61000-4-17)
100/120 Hz
80 - 1000 MHz Clause 7.2.12
10 V/m Shut-down ramp 60 s
2.2.14. D.C gradual shut- IEC 60255-26
1,4 – 2,7 GHz 5 min off
down/start-up Clause 7.2.13
IEC 60255-26 10 V/m Start-up ramp 60 s
2.2.3. Radiated radio
frequency mag- (IEC 61000-4-3) 80, 160, 380, Zone A
netic field 2.2.15. Damped oscil-
Clause 7.2.4 450, 900, 100 A/m (peak)
latory magnetic
IEC 61000-4-10
1850, 2150 field (100 kHz
and 1 MHz)
□ Zone B
MHz
30 A/m (peak)
10 V/m
2.2.16. Pulse magnetic
IEC 61000-4-9 1000 A/m
Zone A field
4 kV CM 3. MECHANICAL ENVIRONMENTAL CONDITIONS
IEC 60255-26
2 kV CM IEC 60255-1
2.2.4. Fast transient/
(IEC 61000-4-4)
burst
Clause 7.2.5
□ Zone B 3.1. Vibration response (IEC 60255-21-1) class 1
2 kV CM Clause 6.13.1
1 kV CM IEC 60255-1
3.2. Vibration endu-
Zone A (IEC 60255-21-1) class 1
rance
to 4 kV LE Clause 6.13.1
IEC 60255-26 IEC 60255-1
to 2 kV LL
2.2.5. Surge (IEC 61000-4-5) 3.3. Shock response (IEC 60255-21-2) class 1
Clause 7.2.7
□ Zone B
Clause 6.13.2
to 2 kV LE
IEC 60255-1
to 1 kV LL
3.4. Shock withstand (IEC 60255-21-2) class 1
Clause 6.13.2
16
Kema Standards SIA-B
IEC 60255-1
3.5. Bump (IEC 60255-21-2) class 1
Clause 6.13.2
IEC 60255-1
3.6. Seismic (single axis
(IEC 60255-21-3) class 1
sweep)
Clause 6.13.3
4. CLIMATIC ENVAIRONMENTAL CONDITIONS
IEC 60255-1
4.1. Dry heat opera- (IEC 60068-2-2, test
+70°C; 72h
tional Bd)
Clause 6.12.3.1
IEC 60255-1
4.2. Cold operational (IEC 60068-2-1, test Ad) -40°C; 72h
Clause 6.12.3.2
IEC 60255-1
(IEC 60068-2-2, test
4.3. Dry heat storage +80°C; 72h
Bb)
Clause 6.12.3.3
IEC 60255-1
4.4. Cold storage (IEC 60068-2-1, test Ab) -40°C; 72h
Clause 6.12.3.4
IEC 60255-1
-40°C; +70°C
4.5. Change of tempe- (IEC 60068-2-14, test
3 hours
rature Nb)
5 cycles
Clause 6.12.3.5
IEC 60255-1
4.6. Damp heat, steady (IEC 60068-2-78, test +40°C; 93%
state Cab) 10 days
Clause 6.12.3.6
IEC 60255-1
+25°C; 40°C
(IEC 60068-2-30, test
4.7. Damp heat, cyclic 97%; 93%
Db)
6 cycles
Clause 6.12.3.7
17
Selection & Ordering data SIA-B
NET FREQUENCY
0 Defined by General Settings
POWER SUPPLY
A Self-powered + Commissioning battery
F Self-powered + 24-230 Vac/dc (Dual) + Commissioning battery
ADDITIONAL FUNCTIONS
C + 49 + SHB + 4 Settings groups + LDP + DFR + 52
D + 49 + SHB + 4 Settings groups + LDP + DFR + 52 + 46 + Trip Block +
50_2 + 50G_2 + CLP + 50BF
COMMUNICATIONS
0 USB (Modbus RTU)
2 USB (Modbus RTU) + RS485 (Modbus RTU or DNP3.0 Serial)
MECHANICAL ASSEMBLY
2 Extended Horizontal Assembly
6 Extended Horizontal Assembly with anticorrosive treatment
7 Extended Horizontal Assembly with red LED for IRF and ring lug current
connector
LANGUAGE
A English, Spanish and German
B English, Spanish and Turkish
C English, Spanish and French
D English, Spanish and Russian
F English, French and Dutch
ADAPTATION
C 50_1 + 51 + 50G_1 + 51G + PGC
U 50_1 + 51 + 50G_1 + 51G + PGC + UL certification
1 1 0 F C 0 3 2 A C SIA B 1 1 0 F C 0 3 2 A C
SIA-B