SIA-B Standard CT’s

OC&EF Dual & Self Powered Protection Relay

RMUs, MRMUs, and SF6 Insulated Switchgears


Secondary Distribution Protection
SELF-POWERED
TECHNOLOGY

• The SIA-B is an OC&EF protection relay with self powered and RS485 port (Modbus RTU or DNP3.0 protocol, selectable by
dual powered (self-powering + auxiliary power) options. general settings) on the rear side.
• The relay is self powered using the operating current through • The SIA-B is provided with a trip output for low power coil
three /1 (<2VA) standard current transformers fitted on the (24 Vdc – 135 mJ), 3 configurable inputs and 3 configurable
lines. These transformers are also used to obtain current outputs.
measurements. Besides, SIA-B can be used with auxiliary • The SIA-B is fitted with the demand of current (Load Data
power supply (24-230Vac/dc). The relay can be also supplied Profiling) with the following characteristics:
by a USB cable connected to the laptop, with the USB KITCOM » Number of records: 168
adapter or a standard power bank. » Recording mode circular
• Internal commissioning battery included as optional (Lithium » Sampling rate (interval): configurable through
battery: 20 years lifetime). communications 1-60 min
• Metallic box with high electromagnetic compatibility level • The SIA-B is provided with non-volatile RAM memory in order to
(EMC) and wide range of operating temperature. store up to 1.024 events and disturbance fault recording (DFR-
• Really low start-up levels in self powered mode: 75mA in three 20 fault reports and 10 oscillographic records in COMTRADE
phase system /160 mA in single phase system. format), maintaining date & time thanks to its internal RTC (Real
• Test menu allows the trip circuit to be tested before the Time Clock) even without power supply.
transformation centre is powered up. • Each oscillographic record contains 4 analogue channels and
• There are 4 configurable LEDs. When the relay is switched off, up to 32 digital channels. The oscillography is downloaded by
their previous states can be checked by powering the relay communications port. The SICom communications program
up (by self-powering the relay, through USB cable, auxiliary allows the oscillography record to be downloaded and saved
voltage or pressing commissioning battery). in COMTRADE format (IEEE C37.111-1991).
• Self-diagnosis of the relay status (WATCHDOG) through the • The installation and subsequent maintenance of external
configurable LEDs and outputs. batteries is eliminated. The operating costs of the centre are
• Low power consumption. reduced.
• To allow communication, relays are provided with a local • Its compact size makes SIA-B easy to install and its light weight
micro USB front port and with optional remote communication helps the customer to save costs in transport.

10
Functions diagram SIA-B

BUS SIA-B
Standard CT’s

3
50 50* 51 49 SHB TB* 50BF* CLP* 46*

1
50G 50G* 51G

52 52 68

CNT RTC PGC HMI SER DFR

LDP MET STTG CMMD


LINE

* Optional

1 1

RS485* USB

ANSI CODE PROTECTIONS ADDITIONAL FUNCTIONS

50 Instantaneous phase overcurrent CNT Counters

51 Inverse time phase overcurrent RTC Real Time Clock

50G Instantaneous measured neutral overcurrent PGC Programmable Logic Control

51G Inverse time measured neutral overcurrent HMI Human Machine Interface

SHB Second Harmonic Blocking SER Sequential Event Recording

49T External trip DFR Disturbance Fault Recording

46 Phase balance current protection LDP Load Data Profiling

49 Thermal overload MET Metering

CLP Cold Load Pickup STTG Settings Groups

52 Breaker wear monitoring CMMD Commands

50BF Circuit Breaker Failure

68 Zone selection interlocking

TB Trip block for switch disconnector

PGC Programmable logic control

11
Technical parameters SIA-B

Function Enable: No/Yes/SHB Function Enable: No/Yes/SHB


Current Tap: 0.07 to 30.00 xIn (step 0.01 xIn) Curve Type: IEC 60255-151 and IEEE curves.
Time Delay: 0.02 to 300.00 s (step 0.01 s)
IEC (Definite time, standard inverse, very inverse,
Activation level: 100% extremely inverse, long time inverse) and IEEE
(Moderately inverse, very inverse, extremely inverse).
Function 50-1 Deactivation level: 95%
Instantaneous deactivation Time delay: 0.02 to 300.00 s (step 0.01 s)
Function 50-2 (*)
Timing accuracy: Time Dial (TMS): 0.01 to 1.50 (step 0.01)
Without SHB permitted: ± 30 ms or ± Current Tap: 0.05 to 15.00 xIn (step 0.01 xIn)
0.5% (greater of both).
Function 51G Curve, current activation level: 110%
With SHB permitted: ± 50 ms or ± 0.5% Curve, current deactivation level: 100%
(greater of both).
Defined time, current activation level: 100%
Function Enable: No/Yes/SHB
Defined time, current deactivation level: 95%
Current Tap: 0.05 to 15.00 xIn (step 0.01 xIn)
Instantaneous deactivation
Time Delay: 0.02 to 300.00 s (step 0.01s)
Timing accuracy for IEC and IEEE curves selection:
Activation level: 100%
± 30 ms or ± 5% (greater of both)
Function 50G-1 Deactivation level: 95%
Timing accuracy for defined time curve selection:
Instantaneous deactivation
Function 50G-2 (*) ± 35 ms or ± 0.5% (greater of both)
Timing accuracy:
Function enable: No/Yes
Without SHB permitted: ± 30 ms or ±
0.5% (greater of both). Current Tap: 5 to 50% (step 1%)
Reset Time: 0.00 to 300.00 (step 0.01 s)
With SHB permitted: ± 50 ms or ± 0.5% Function SHB Block Threshold: 0.07 to 30.00 xIn (step 0.01 xIn)
(greater of both).
Activation level: 100%
Function Enable: No/Yes/SHB
Deactivation level: 95%
Curve Type: IEC 60255-151 and IEEE curves.
Temporized deactivation
IEC (Definite time, standard inverse, very inverse, External trip through configurable inputs. Activated
extremely inverse, long time inverse) and IEEE Function 49T by short circuiting the terminals (without auxiliary
(Moderately inverse, very inverse, extremely inverse). voltage)
Function enable: No/Yes
Time delay: 0.02 to 300.00 s (step 0.01 s)
Current tap: 0.10 to 2.40 In (step 0.01xIn)
Time Dial (TMS): 0.01 to 1.50 (step 0.01)
Current Tap: 0.07 to 30.00 xIn (step 0.01 xIn) ζ heating: 3 to 600 min (step 1 min)

Curve, current activation level: 110% ζ cooling: 1 to 6 x ζ heating (step 1)


Function 49
Curve, current deactivation level: 100% Alarm: 20 to 99% (step 1%)

Defined time, current activation level: 100% Trip level: 100%

Defined time, current deactivation level: 95% Deactivation level: 95% of alarm level
Function 51
Instantaneous deactivation Timing accuracy: ± 5% respect of theorical value.

Timing accuracy for IEC and IEEE curve selection: Maximum number of openings: 1 to 10.000 (step 1)
Maximum accumulated amperes: 0 to 100.000
Without SHB permitted: ± 30 ms or ± (M(A²)) (step 1)
5% (greater of both).
Opening time: 0.02 to 30.00 s (step 0.01 s)
With SHB permitted: ± 50 ms or ± 5% Function 52 Closing time: 0.02 to 30.00 s (step 0.01 s)
(greater of both).
Excessive repeated openings: 1 to 10.000 (step 1)
Timing accuracy for defined time selection: Repetitive openings/Time: 1 to 300 min (step 1 min)
Open breaker activation and reset threshold: 0.6%
Without SHB permitted: ± 30 ms or ±
In
0.5% (greater of both).
Function Enable: No/Yes
With SHB permitted: ± 50 ms or ± 0.5% Function TB (*)
(greater of both). Tap: 1.50 to 30.00 xIn (step 0.01 xIn)

12
Technical parameters SIA-B

Function enable: No/Yes/SHB Demand of current with the following characteristics:


Curve Type: IEC 60255-151 and IEEE curves. - Number of records: 168
Load Data Profiling
(LDP) - Recording mode circular
IEC (Definite time, standard inverse, very inverse,
extremely inverse, long time inverse) and IEEE - Sampling rate (interval): configurable through
(Moderately inverse, very inverse, extremely inverse). communications (1-60 min)
24 Vdc; 135 mJ (activation of the striker or low
Trip output
Time delay: 0.02 to 300.00 s (step 0.01 s) powered coil)
Time Dial (TMS): 0.01 to 1.50 (step 0.01) 3 configurable outputs (output 1, output 2 and
output 3):
Current tap: 0.07 to 10.00 xIn (step 0.01xIn)
Curve, current activation level: 110% 250 Vac – 8 A
Outputs
Curve, current deactivation level: 100%
30 Vdc – 8 A
Defined time, current activation level: 100%
(*) For the model with UL certification, the maximum
Function 46 (*) Defined time, current deactivation level: 95% current is 4 A
Instantaneous deactivation 3 inputs: they are activated by short-circuiting the
Inputs
terminals without external supply.
Timing accuracy for IEC and IEEE curve selection:
Fundamental values (DFT)
Without SHB permitted: ± 30 ms or ± Sampling: 16 samples/cycle
5% (greater of both).
±2% in a band of ± 20% the nominal current and ±4% or ±
With SHB permitted: ± 50 ms or ± 5% Current 5 mA in the rest of the band.
(greater of both). measurements
Phase measurement range: 0.07 to 30 times the
nominal current
Timing accuracy for defined time curve selection:
Neutral measurement range: 0.05 to 16 times the
Without SHB permitted: ± 30 ms or ± nominal current
0.5% (greater of both). Local port (micro USB): Modbus RTU
Communications
RS485 rear port: Modbus RTU or DNP3.0 Serial (*)
With SHB permitted: ± 50 ms or ± 0.5%
(greater of both). Self powering from
Three phase self-powering level: I > 75 mA
current
Function Enable: No/Yes
Power supply (*) 24-230 Vac/Vdc (-20/+10%)
Settings groups: 1 to 4 (step 1)
With USB KITCOM adapter or standard powerbank
No load Time: 0.02 to 300.00 s (step 0.01 s) Battery Supply
Function CLP (*)
Commissioning internal battery
Cold load Time: 0.02 to 300.00 s (step 0.01 s)
Power supply and measurement with standard CTs
Open breaker activation 0.6% In and reset Transformers
/1
threshold: 0.8% In
Operating temperature: -40 to 70ºC
Function Enable: No/Yes
Environmental
Storage temperature: -40 to 80ºC
Time Delay: 0.02 to 1.00 s (step 0.01 s) conditions
Function 50BF (*)
Relative humidity: 95%
Open breaker activation and reset threshold: 0.6%
In Metallic box
Available through configurable inputs and outputs Panel mounted
Function 68
thanks to the programmable logic (PGC).
Mechanical Height x Width: 90 mm x 245 mm
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP,
characteristics Depth: 139.4 mm
OR4_PULSE, NOR4, NOR4_TIMERUP, NOR4_
Programmable logic
PULSE, NOR4_PULSES, AND4, AND4_PULSES,
control (PGC) Weight: 3 kg
AND4_TIMERUP, AND4_PULSE, AND4_LATCH,
NAND4, NAND4_TIMERUP, NAND4_PULSE IP-54 panel mounted
4 settings groups (*) Optional depending on model
Settings tables
Selectable by input or general setting.

SER 1024 events

16 samples/cycle
4 analog channels and 32 digital channels

Disturbance fault 20 fault reports, 16 events in each.


recording (DFR)
10 disturbance records in COMTRADE format (50
cycles each).
COMTRADE IEEE C37.111-1991

13
Connections diagram SIA-B

• 3 CT power supply-measurement
• Rigid neutral

L1
A
L2
LINE B
L3
C
C B N

STRIKER
<24v
A1 A2 A3 A4 A5 A6 A7 A8 +- <135mj

A B C N
Measure Measure Measure Measure
& Power & Power & Power & Power

CURRENT INPUTS

+
B8
TRIP

-
B7
AC/DC

B1
POWER
AUX.

B2

B3
C
LOCAL PORT

INPUTS

B4
micro USB

B5
Digital Protection
B6
Self power

B9
OUTPUT 1

B10
WARNING
B11
Ground PC to relay ground
B12
OUTPUT 2

B13

B14

B15
OUTPUT 3

B16

B17

+ B18
RS485

GND
SAFETY
GROUND
- B19

(*) Example of connections diagram

14
Dimensions and cutout SIA-B

CUT-OUT
PATTERN

15
Kema Standards SIA-B

TEST TEST STANDARD LEVEL 0,15 - 80 MHz


IEC 60255-26
2.2.6. Conducted dis- 10 V
1. DIELECTRIC TESTS
turbance induced (IEC 61000-4-6)
IEC60255-27 5 kV by RF fields 27, 68 MHz
1.1. Impulse voltage Clause 7.2.8
Clause 10.6.4.2 1 kV 10 V

IEC60255-27 2 kV  Zone A
1.2. Dielectric voltage
Clause 10.6.4.3 0,5 kV 150 V DM
IEC 60255-26
IEC60255-27 300 V CM
1.3. Insulation resis- 2.2.7. Power frequency
500 VDC (IEC 61000-4-16)
voltage (50 Hz)
tance Clause 10.6.4.4
Clause 7.2.9
□ Zone B
2. ELECTROMAGNETIC COMPATIBILITY (EMC) tests 100 V DM
2.1. EMISSION 300 V CM
IEC 60255-26 IEC 60255-26
2.2.8. Power frequency 30 A/m cont.
CISPR11 (IEC 61000-4-8)
H- field (50 Hz) 300 A/m 1-3 s
2.1.1. Radiated CISPR22 class A Clause 7.2.10
emission table 1 class A IEC 60255-26 100%; 10-1000 ms
table 6 2.2.9. D.C. Voltage dips (IEC 61000-4-29) 60%; 200 ms
table 7 Clause 7.2.11 30%; 500 ms
IEC 60255-26 100%;
IEC 60255-26
2.1.2. Conducted CISPR22 0,5 – 25 c.
class A 2.2.10. A.C. voltage dips (IEC 61000-4-11)
emission table 2 60%; 10/12 c.
Clause 7.2.11
table 2/4 30%; 25/30 c.
2.2. IMMUNITY IEC 60255-26
2.2.11. D.C. voltage
2,5 kV CM (IEC 61000-4-29) 100%; 5s
IEC 60255-26 interruptions
2.2.1. Slow damped 1,0 kV DM Clause 7.2.11
oscillatory wave (IEC 61000-4-18)
(1 MHz) 1 kV CM IEC 60255-26
Clause 7.2.6 2.2.12. A.C. voltage 100%;
0 kV DM (IEC 61000-4-11)
interruptions 250/300 c
IEC 60255-26 Clause 7.2.11
2.2.2. Electrostatic 6 kV cont.
(IEC 61000-4-2) IEC 60255-26
discharges 8 kV air 15% Ut_dc
Clause 7.2.3 2.2.13. D.C. Ripple (IEC 61000-4-17)
100/120 Hz
80 - 1000 MHz Clause 7.2.12
10 V/m Shut-down ramp 60 s
2.2.14. D.C gradual shut- IEC 60255-26
1,4 – 2,7 GHz 5 min off
down/start-up Clause 7.2.13
IEC 60255-26 10 V/m Start-up ramp 60 s
2.2.3. Radiated radio
frequency mag- (IEC 61000-4-3) 80, 160, 380,  Zone A
netic field 2.2.15. Damped oscil-
Clause 7.2.4 450, 900, 100 A/m (peak)
latory magnetic
IEC 61000-4-10
1850, 2150 field (100 kHz
and 1 MHz)
□ Zone B
MHz
30 A/m (peak)
10 V/m
2.2.16. Pulse magnetic
IEC 61000-4-9 1000 A/m
 Zone A field
4 kV CM 3. MECHANICAL ENVIRONMENTAL CONDITIONS
IEC 60255-26
2 kV CM IEC 60255-1
2.2.4. Fast transient/
(IEC 61000-4-4)
burst
Clause 7.2.5
□ Zone B 3.1. Vibration response (IEC 60255-21-1) class 1

2 kV CM Clause 6.13.1

1 kV CM IEC 60255-1
3.2. Vibration endu-
 Zone A (IEC 60255-21-1) class 1
rance
to 4 kV LE Clause 6.13.1
IEC 60255-26 IEC 60255-1
to 2 kV LL
2.2.5. Surge (IEC 61000-4-5) 3.3. Shock response (IEC 60255-21-2) class 1
Clause 7.2.7
□ Zone B
Clause 6.13.2
to 2 kV LE
IEC 60255-1
to 1 kV LL
3.4. Shock withstand (IEC 60255-21-2) class 1
Clause 6.13.2

16
Kema Standards SIA-B

IEC 60255-1
3.5. Bump (IEC 60255-21-2) class 1
Clause 6.13.2
IEC 60255-1
3.6. Seismic (single axis
(IEC 60255-21-3) class 1
sweep)
Clause 6.13.3
4. CLIMATIC ENVAIRONMENTAL CONDITIONS
IEC 60255-1
4.1. Dry heat opera- (IEC 60068-2-2, test
+70°C; 72h
tional Bd)
Clause 6.12.3.1
IEC 60255-1
4.2. Cold operational (IEC 60068-2-1, test Ad) -40°C; 72h
Clause 6.12.3.2
IEC 60255-1
(IEC 60068-2-2, test
4.3. Dry heat storage +80°C; 72h
Bb)
Clause 6.12.3.3
IEC 60255-1
4.4. Cold storage (IEC 60068-2-1, test Ab) -40°C; 72h
Clause 6.12.3.4
IEC 60255-1
-40°C; +70°C
4.5. Change of tempe- (IEC 60068-2-14, test
3 hours
rature Nb)
5 cycles
Clause 6.12.3.5
IEC 60255-1
4.6. Damp heat, steady (IEC 60068-2-78, test +40°C; 93%
state Cab) 10 days
Clause 6.12.3.6
IEC 60255-1
+25°C; 40°C
(IEC 60068-2-30, test
4.7. Damp heat, cyclic 97%; 93%
Db)
6 cycles
Clause 6.12.3.7

17
Selection & Ordering data SIA-B

SIA-B Standard CT’s


Overcurrent & Earth Fault Protection Relay – Dual & Self-powered
PHASE CURRENT MEASUREMENT
1 1A

NEUTRAL CURRENT MEASUREMENT


1 1A

NET FREQUENCY
0 Defined by General Settings

POWER SUPPLY
A Self-powered + Commissioning battery
F Self-powered + 24-230 Vac/dc (Dual) + Commissioning battery

ADDITIONAL FUNCTIONS
C + 49 + SHB + 4 Settings groups + LDP + DFR + 52
D + 49 + SHB + 4 Settings groups + LDP + DFR + 52 + 46 + Trip Block +
50_2 + 50G_2 + CLP + 50BF

COMMUNICATIONS
0 USB (Modbus RTU)
2 USB (Modbus RTU) + RS485 (Modbus RTU or DNP3.0 Serial)

INPUTS AND OUTPUTS


3 4 LEDs + Trip (Striker) + 3 Outputs + 3 Inputs

MECHANICAL ASSEMBLY
2 Extended Horizontal Assembly
6 Extended Horizontal Assembly with anticorrosive treatment
7 Extended Horizontal Assembly with red LED for IRF and ring lug current
connector

LANGUAGE
A English, Spanish and German
B English, Spanish and Turkish
C English, Spanish and French
D English, Spanish and Russian
F English, French and Dutch

ADAPTATION
C 50_1 + 51 + 50G_1 + 51G + PGC
U 50_1 + 51 + 50G_1 + 51G + PGC + UL certification

Example of ordering code:

1 1 0 F C 0 3 2 A C SIA B 1 1 0 F C 0 3 2 A C

SIA-B