EN FANOX DATA SIABSPECIFIC SELFPOWERED PlugConnectorsProtectionRelays R13

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

SIA-B Specific CT’s

OC&EF Dual & Self Powered Protection Relay

RMUs, MRMUs, and SF6 Insulated Switchgears


Secondary Distribution Protection
SELF-POWERED
TECHNOLOGY

• The SIA-B is an OC&EF protection relay with self powered and • Self-diagnosis of the relay status (WATCHDOG) through a LED.
dual powered (self-powering + auxiliary power) options. • Low power consumption.
• The relay is self powered using the operating current through • To allow communication, relays are provided with a local micro
three specific current transformers fitted on the lines. These USB front port and with optional remote communication RS485
transformers are also used to obtain current measurements. port (Modbus RTU protocol) on the rear side.
Besides, SIA-B can be used with auxiliary power supply (24- • The SIA-B is provided with a trip output for low power coil (24
230Vac/dc). The relay can be also supplied by a USB cable Vdc – 135 mJ) and depending on model, 1 external trip input
connected to the laptop, with the USB KITCOM adapter or a and 2 configurable outputs.
standard power bank. • The SIA-B is provided with non-volatile RAM memory in order
• Internal commissioning battery included (Lithium battery: 20 to store up to 100 events and disturbance fault recording (DFR
years lifetime), as optional. – 4 fault reports in data format), maintaining date & time thanks
• Metallic box with high electromagnetic compatibility level to its internal RTC (real Time Clock) even without power supply.
(EMC) and wide range of operating temperature. • The installation and subsequent maintenance of external
• In self powered mode, SIA-B starts-up from 0.4 times the batteries is eliminated. The operating costs of the centre are
minimum primary current of the CT (three phase current). reduced.
• Test menu allows the trip circuit to be tested before the • Its compact size makes SIA-B easy to install and its light weight
transformation centre is powered up. helps the customer to save costs in transport.
• Bistable magnetic indicator (flag) which indicates the trip
condition, maintaining its position even though the relay loses
the supply.

20
Functions diagram SIA-B

BUS SIA-B
Specific CT’s

3
50 51 50N 51N TB* 49* SHB*

52

49T*

tº RTC PGC* HMI SER

MET STTG CMMD DFR


*
LINE

* Optional

1 1

RS485* USB

ANSI CODE PROTECTIONS ADDITIONAL FUNCTIONS

50 Instantaneous phase overcurrent RTC Real Time Clock

51 Inverse time phase overcurrent PGC Programmable Logic Control

50N Instantaneous calculated neutral overcurrent HMI Human Machine Interface

51N Inverse time calculated neutral overcurrent SER Sequential Event Recording

SHB Second Harmonic Blocking DFR Disturbance Fault Recording

49T External trip MET Metering

49 Thermal overload STTG Settings Groups

TB Trip block for switch disconnector CMMD Commands

PGC Programmable logic control

21
Technical parameters SIA-B

Function Enable: Yes/No/SHB(*) External trip through a specific input. Activated by short
Function 49T (*)
circuiting the terminals (without auxiliary voltage)
Current Tap: 0.20 to 20.00 xIn (step 0.01 xIn)
Function enable: No/Yes
Time Delay: 0.02 to 300.00 s (step 0.01 s)
Current tap: 0.10 to 2.40 In (step 0.01xIn)
Function 50 Activation level 100%
ζ heating: 3 to 600 min (step 1 min)
Deactivation level 95%
ζ cooling: 1 to 6 xζ heating (step 1)
Instantaneous deactivation Function 49 (*)
Alarm: 20 to 99% (step 1%)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Trip level: 100%
Function Enable: Yes/No/SHB(*)
Deactivation level: 95% of alarm level
Current Tap: 0.20 to 20.00 xIn (step 0.01 xIn)
Timing accuracy: ± 5% respect of theorical value.
Time Delay: 0.05 to 300.00 s (step 0.01 s)
Function Enable: Yes/No
Function 50N Activation level 100% Function TB (*)
Tap: 1.50 to 20.00 xIn (step 0.01 xIn)
Deactivation level 95%
Function enable: No/Yes
Instantaneous deactivation
Current Tap: 5 to 50% (step 1%)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Reset Time: 0.00 to 300.00 (step 0.01 s)
Function Enable: Yes/No/SHB(*)
Function SHB (*) Block Threshold: 0.20 to 20.00 xIn (step 0.01 xIn)
Curve Type: IEC 60255-151 and IEEE curves.
Activation level: 100%
IEC (Definite time, standard inverse, very inverse,
Deactivation level: 95%
extremely inverse, long time inverse, short time inverse)
and IEEE (Moderately inverse, very inverse, extremely Temporized deactivation
inverse).
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP,
Programmable OR4_PULSE, NOR4, NOR4_TIMERUP, NOR4_PULSE,
Time delay: 0.02 to 300.00 s (step 0.01 s) logic control NOR4_PULSES, AND4, AND4_PULSES, AND4_
(PGC) (*) TIMERUP, AND4_PULSE, AND4_LATCH, NAND4,
Time Dial (TMS): 0.05 to 1.25 (step 0.01)
NAND4_TIMERUP, NAND4_PULSE
Function 51 Current Tap: 0.20 to 7.00 xIn (step 0.01 xIn)
2 settings groups
Curve, current activation level: 110% Settings tables
Selectable by general settings.
Curve, current deactivation level: 100%
SER 100 events
Defined time, current activation level: 100%
Defined time, current deactivation level: 95% Disturbance fault 16 samples/cycle
recording (DFR) 4 fault reports, 24 events in each.
Instantaneous deactivation
Timing accuracy: ± 30 ms or ± 5% (greater of both, 24 Vdc; 135 mJ (activation of the striker or low powered
Trip output
considering the operating time is influenced by the used coil)
CT) 2 configurable outputs (output 1 and output 2):
Function Enable: Yes/No/SHB(*)
250 Vac – 8 A (62.5 VA max)
Curve Type: IEC 60255-151 and IEEE curves.
Outputs (*)
IEC (Definite time, standard inverse, very inverse, 30 Vdc – 8 A (30 W max)
extremely inverse, long time inverse, short time inverse) (*) For the model with UL certification, the maximum
and IEEE (Moderately inverse, very inverse, extremely current is 4 A
inverse).
External trip input: it is activated by short-circuiting the
Inputs (*)
terminals without external supply.
Time delay: 0.05 to 300.00 s (step 0.01 s)
True RMS
Time Dial (TMS): 0.05 to 1.25 (step 0.01)
Function 51N Sampling: 16 samples/cycle
Current Tap: 0.20 to 7.00 xIn (step 0.01 xIn) Current
measurements Relay accuracy for triphasic current: <2%
Curve, current activation level: 110%
CT Accuracy depending on the used CT: <±5% with
Curve, current deactivation level: 100% CT-5 type and <±10% with CT-10 type.
Defined time, current activation level: 100% Local port (micro USB): Modbus RTU
Communications
Defined time, current deactivation level: 95% RS485 rear port: Modbus RTU (*)
Instantaneous deactivation Self powering
Three phase self-power level: I > 0,35 x Is min
Timing accuracy: ± 30 ms or ± 5% (greater of both, from current
considering the operating time is influenced by the used Power supply (*) 24-230 Vac/Vdc -20/+10%
CT)

22
Technical parameters SIA-B

With USB KITCOM adapter or standard powerbank


Battery Supply (*)
Internal Commissioning battery (*)
Transformers Power supply and measurement through specific CTs
Operating temperature: -40 to 70ºC
Environmental
Storage temperature: -40 to 80ºC
conditions
Relative humidity: 95%
Metallic box
Panel mounted
Horizontal assembly:

Height x Width x Depth:

Push-in spring plug connector:


102.7x185.8x69.6 (mm)

Screw type connector: 102.7x185.8x62.2


Mechanical
(mm)
characteristics
Vertical assembly:

Height x Width x Depth:

Push-in spring plug connector:


167.8x120.65x69.6 (mm)

Screw type connector:167.8x120.65x62.2


(mm)
IP-54 panel mounted
(*) Optional depending on model

23
Connections diagram SIA-B

L1
A
L2
LINE B
L3
C
C B N


STRIKER
<24v
A1 A2 A3 A4 A5 A6 +- <135mj

A B C

Measure Measure Measure

CURRENT INPUTS +
C1

TRIP
-
C2

C3
* EXT.
TRIP
OC& EF Protection Dual & Self powered

C4
micro USB

+
POWER

C5
AC/DC
* AUX.
LOCAL PORT

-
micro USB

C6

+ D1
OUTPUT 1 RS485

- D2

D3
WARNING
SIA-B

Ground PC to relay ground D4

D5

D6
OUTPUT 2

D7
SAFETY
GND
GROUND D8

(*) Example of connections diagram

24
Dimensions and cutout SIA-B

Vertical assembly

CUT-OUT
PATTERN

25
Dimensions and cutout SIA-B

Horizontal assembly

CUT-OUT
PATTERN

26
Kema Standards SIA-B

TEST IEC 60255-26


TEST LEVEL 1.2.8. Power frequency 30 A/m cont.
STANDARD (IEC 61000-4-8)
H- field 300 A/m 1-3 s
1. ELECTROMAGNETIC COMPATIBILITY (EMC) tests Clause 7.2.10
1.1. EMISSION  Zone A
IEC 60255-26 1.2.9. Damped oscillatory 100 A/m (peak)
magnetic field (100 IEC 61000-4-10
CISPR11 class A
1.1.1. Radiated emission kHz and 1 MHz) □ Zone B
CISPR22 class A
30 A/m (peak)
table 1
1.2.10. Pulse magnetic field IEC 61000-4-9 1000 A/m
IEC 60255-26
100%;
CISPR22 IEC 60255-26
1.1.2. Conducted emission class A 0,5 – 25 c.
table 2 1.2.11. A.C. voltage dips (IEC 61000-4-11)
60%; 10/12 c.
table 2/4 Clause 7.2.11
30%; 25/30 c.
1.2. IMMUNITY
IEC 60255-26
2,5 kV CM 1.2.12. A.C. voltage interrup- 100%;
IEC 60255-26 (IEC 61000-4-11)
tions 250/300 c
1.2.1. Slow damped oscilla- 1,0 kV DM
(IEC 61000-4-18) Clause 7.2.11
tory wave (1 MHz) 1 kV CM
Clause 7.2.6 2. DIELECTRIC TESTS
0 kV DM
IEC60255-27 5 kV
IEC 60255-26 2.1. Impulse voltage
6 kV cont. Clause 10.6.4.2 1 kV
1.2.2. Electrostatic dischar-
(IEC 61000-4-2)
ges 8 kV air IEC60255-27 2 kV
Clause 7.2.3 2.2. Dielectric voltage
Clause 10.6.4.3 0,5 kV
80 - 1000 MHz
IEC60255-27
10 V/m 2.3. Insulation resistance 500 VDC
Clause 10.6.4.4
1,4 – 2,7 GHz
3. MECHANICAL ENVIRONMENTAL CONDITIONS
IEC 60255-26 10 V/m
1.2.3. Radiated radio fre- IEC 60255-1
quency magnetic (IEC 61000-4-3) 80, 160, 380,
field 3.1. Vibration response (IEC 60255-21-1) class 1
Clause 7.2.4 450, 900,
Clause 6.13.1
1850, 2150
IEC 60255-1
MHz
3.2. Vibration endurance (IEC 60255-21-1) class 1
10 V/m
Clause 6.13.1
 Zone A
IEC 60255-1
4 kV CM
IEC 60255-26 3.3. Shock response (IEC 60255-21-2) class 1
2 kV CM
1.2.4. Fast transient/burst (IEC 61000-4-4) Clause 6.13.2

Clause 7.2.5
□ Zone B IEC 60255-1
2 kV CM 3.4. Shock withstand (IEC 60255-21-2) class 1
1 kV CM Clause 6.13.2
 Zone A IEC 60255-1
to 4 kV LE 3.5. Bump (IEC 60255-21-2) class 1
IEC 60255-26
to 2 kV LL Clause 6.13.2
1.2.5. Surge (IEC 61000-4-5)
Clause 7.2.7
□ Zone B IEC 60255-1
3.6. Seismic (single axis
to 2 kV LE (IEC 60255-21-3) class 1
sweep)
to 1 kV LL Clause 6.13.3
0,15 - 80 MHz 4. CLIMATIC ENVAIRONMENTAL CONDITIONS
IEC 60255-26
1.2.6. Conducted distur- 10 V IEC 60255-1
bance induced by RF (IEC 61000-4-6)
fields 27, 68 MHz (IEC 60068-2-2,
Clause 7.2.8 4.1. Dry heat operational +70°C; 72h
test Bd)
10 V
Clause 6.12.3.1
 Zone A
IEC 60255-1
150 V DM
IEC 60255-26 (IEC 60068-2-1,
300 V CM 4.2. Cold operational -25°C; 72h
1.2.7. Power frequency volt- test Ad)
(IEC 61000-4-16)
age (50 Hz and 60 Hz)
Clause 7.2.9
□ Zone B Clause 6.12.3.2
100 V DM
300 V CM

27
Kema Standards SIA-B

IEC 60255-1
(IEC 60068-2-2,
4.3. Dry heat storage +80°C; 72h
test Bb)
Clause 6.12.3.3
IEC 60255-1
(IEC 60068-2-1,
4.4. Cold storage -40°C; 72h
test Ab)
Clause 6.12.3.4
IEC 60255-1
-25°C; +70°C
(IEC 60068-2-14,
4.5. Change of temperature 3 hours
test Nb)
5 cycles
Clause 6.12.3.5
IEC 60255-1
4.6. Damp heat, steady (IEC 60068-2-78, +40°C; 93%
state test Cab) 10 days
Clause 6.12.3.6
IEC 60255-1
+25°C; 40°C
(IEC 60068-2-30,
4.7. Damp heat, cyclic 97%; 93%
test Db)
6 cycles
Clause 6.12.3.7

28
Selection & Ordering data SIA-B

SIA-B Specific CT’s


Overcurrent & Earth Fault Protection Relay – Dual & Self-powered
PHASE CURRENT MEASUREMENT
0 Defined by General Settings
NEUTRAL CURRENT MEASUREMENT
0 Internal measurement
NET FREQUENCY
0 Defined by General Settings
POWER SUPPLY
0 Self powered
A Self powered + Commissioning battery
5 Self powered + 24-230 Vac/dc (Dual)
F Self powered + 24-230 Vac/dc (Dual) + Commissioning battery
ADDITIONAL FUNCTIONS
0 -
1 + 49
2 + SHB + 49
3 + SHB + Trip block for switch disconnector
B + Trip Block for switch disconnector
COMMUNICATIONS
0 USB (Modbus RTU)
1 USB (Modbus RTU) + RS485 (Modbus RTU)
INPUTS AND OUTPUTS
0 Trip (striker)
1 Trip (striker) + External trip input (49T) + 1 magnetic indicator
2 Trip (striker) + External trip input (49T) + 1 magnetic indicator + 2 outputs
MECHANICAL ASSEMBLY
A Vertical Assembly with screw type plug connector
B Horizontal Assembly with screw type plug connector
C Vertical Assembly with screw type plug connector and anticorrosive
treatment
D Horizontal Assembly with screw type plug connector and anticorrosive
treatment
E Vertical Assembly with push-in spring plug connector
F Horizontal Assembly with push-in spring plug connector
G Vertical Assembly with push-in spring plug connector and anticorrosive
treatment
H Horizontal Assembly with push-in spring plug connector and
anticorrosive treatment
LANGUAGE
A English, Spanish and German
B English, Spanish and Turkish
C English, Spanish and French
D English, Spanish and Russian
ADAPTATION
B 50 + 51 + 50N + 51N + fast SOTF + microUSB port
T 50 + 51 + 50N + 51N + fast SOTF + microUSB port + UL Certification

Example of ordering code:

0 0 0 F 0 0 1 B D B SIA B 0 0 0 F 0 0 1 B D B

SIA-B

29