• The SIA-B is an OC&EF protection relay with self powered and • Self-diagnosis of the relay status (WATCHDOG) through a LED.
dual powered (self-powering + auxiliary power) options. • Low power consumption.
• The relay is self powered using the operating current through • To allow communication, relays are provided with a local micro
three specific current transformers fitted on the lines. These USB front port and with optional remote communication RS485
transformers are also used to obtain current measurements. port (Modbus RTU protocol) on the rear side.
Besides, SIA-B can be used with auxiliary power supply (24- • The SIA-B is provided with a trip output for low power coil (24
230Vac/dc). The relay can be also supplied by a USB cable Vdc – 135 mJ) and depending on model, 1 external trip input
connected to the laptop, with the USB KITCOM adapter or a and 2 configurable outputs.
standard power bank. • The SIA-B is provided with non-volatile RAM memory in order
• Internal commissioning battery included (Lithium battery: 20 to store up to 100 events and disturbance fault recording (DFR
years lifetime), as optional. – 4 fault reports in data format), maintaining date & time thanks
• Metallic box with high electromagnetic compatibility level to its internal RTC (real Time Clock) even without power supply.
(EMC) and wide range of operating temperature. • The installation and subsequent maintenance of external
• In self powered mode, SIA-B starts-up from 0.4 times the batteries is eliminated. The operating costs of the centre are
minimum primary current of the CT (three phase current). reduced.
• Test menu allows the trip circuit to be tested before the • Its compact size makes SIA-B easy to install and its light weight
transformation centre is powered up. helps the customer to save costs in transport.
• Bistable magnetic indicator (flag) which indicates the trip
condition, maintaining its position even though the relay loses
the supply.
20
Functions diagram SIA-B
BUS SIA-B
Specific CT’s
3
50 51 50N 51N TB* 49* SHB*
52
49T*
* Optional
1 1
RS485* USB
51N Inverse time calculated neutral overcurrent SER Sequential Event Recording
21
Technical parameters SIA-B
Function Enable: Yes/No/SHB(*) External trip through a specific input. Activated by short
Function 49T (*)
circuiting the terminals (without auxiliary voltage)
Current Tap: 0.20 to 20.00 xIn (step 0.01 xIn)
Function enable: No/Yes
Time Delay: 0.02 to 300.00 s (step 0.01 s)
Current tap: 0.10 to 2.40 In (step 0.01xIn)
Function 50 Activation level 100%
ζ heating: 3 to 600 min (step 1 min)
Deactivation level 95%
ζ cooling: 1 to 6 xζ heating (step 1)
Instantaneous deactivation Function 49 (*)
Alarm: 20 to 99% (step 1%)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Trip level: 100%
Function Enable: Yes/No/SHB(*)
Deactivation level: 95% of alarm level
Current Tap: 0.20 to 20.00 xIn (step 0.01 xIn)
Timing accuracy: ± 5% respect of theorical value.
Time Delay: 0.05 to 300.00 s (step 0.01 s)
Function Enable: Yes/No
Function 50N Activation level 100% Function TB (*)
Tap: 1.50 to 20.00 xIn (step 0.01 xIn)
Deactivation level 95%
Function enable: No/Yes
Instantaneous deactivation
Current Tap: 5 to 50% (step 1%)
Timing accuracy: ± 30 ms or ± 0.5% (greater of both)
Reset Time: 0.00 to 300.00 (step 0.01 s)
Function Enable: Yes/No/SHB(*)
Function SHB (*) Block Threshold: 0.20 to 20.00 xIn (step 0.01 xIn)
Curve Type: IEC 60255-151 and IEEE curves.
Activation level: 100%
IEC (Definite time, standard inverse, very inverse,
Deactivation level: 95%
extremely inverse, long time inverse, short time inverse)
and IEEE (Moderately inverse, very inverse, extremely Temporized deactivation
inverse).
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP,
Programmable OR4_PULSE, NOR4, NOR4_TIMERUP, NOR4_PULSE,
Time delay: 0.02 to 300.00 s (step 0.01 s) logic control NOR4_PULSES, AND4, AND4_PULSES, AND4_
(PGC) (*) TIMERUP, AND4_PULSE, AND4_LATCH, NAND4,
Time Dial (TMS): 0.05 to 1.25 (step 0.01)
NAND4_TIMERUP, NAND4_PULSE
Function 51 Current Tap: 0.20 to 7.00 xIn (step 0.01 xIn)
2 settings groups
Curve, current activation level: 110% Settings tables
Selectable by general settings.
Curve, current deactivation level: 100%
SER 100 events
Defined time, current activation level: 100%
Defined time, current deactivation level: 95% Disturbance fault 16 samples/cycle
recording (DFR) 4 fault reports, 24 events in each.
Instantaneous deactivation
Timing accuracy: ± 30 ms or ± 5% (greater of both, 24 Vdc; 135 mJ (activation of the striker or low powered
Trip output
considering the operating time is influenced by the used coil)
CT) 2 configurable outputs (output 1 and output 2):
Function Enable: Yes/No/SHB(*)
250 Vac – 8 A (62.5 VA max)
Curve Type: IEC 60255-151 and IEEE curves.
Outputs (*)
IEC (Definite time, standard inverse, very inverse, 30 Vdc – 8 A (30 W max)
extremely inverse, long time inverse, short time inverse) (*) For the model with UL certification, the maximum
and IEEE (Moderately inverse, very inverse, extremely current is 4 A
inverse).
External trip input: it is activated by short-circuiting the
Inputs (*)
terminals without external supply.
Time delay: 0.05 to 300.00 s (step 0.01 s)
True RMS
Time Dial (TMS): 0.05 to 1.25 (step 0.01)
Function 51N Sampling: 16 samples/cycle
Current Tap: 0.20 to 7.00 xIn (step 0.01 xIn) Current
measurements Relay accuracy for triphasic current: <2%
Curve, current activation level: 110%
CT Accuracy depending on the used CT: <±5% with
Curve, current deactivation level: 100% CT-5 type and <±10% with CT-10 type.
Defined time, current activation level: 100% Local port (micro USB): Modbus RTU
Communications
Defined time, current deactivation level: 95% RS485 rear port: Modbus RTU (*)
Instantaneous deactivation Self powering
Three phase self-power level: I > 0,35 x Is min
Timing accuracy: ± 30 ms or ± 5% (greater of both, from current
considering the operating time is influenced by the used Power supply (*) 24-230 Vac/Vdc -20/+10%
CT)
22
Technical parameters SIA-B
23
Connections diagram SIA-B
L1
A
L2
LINE B
L3
C
C B N
t°
STRIKER
<24v
A1 A2 A3 A4 A5 A6 +- <135mj
A B C
CURRENT INPUTS +
C1
TRIP
-
C2
C3
* EXT.
TRIP
OC& EF Protection Dual & Self powered
C4
micro USB
+
POWER
C5
AC/DC
* AUX.
LOCAL PORT
-
micro USB
C6
+ D1
OUTPUT 1 RS485
- D2
D3
WARNING
SIA-B
D5
D6
OUTPUT 2
D7
SAFETY
GND
GROUND D8
24
Dimensions and cutout SIA-B
Vertical assembly
CUT-OUT
PATTERN
25
Dimensions and cutout SIA-B
Horizontal assembly
CUT-OUT
PATTERN
26
Kema Standards SIA-B
Clause 7.2.5
□ Zone B IEC 60255-1
2 kV CM 3.4. Shock withstand (IEC 60255-21-2) class 1
1 kV CM Clause 6.13.2
Zone A IEC 60255-1
to 4 kV LE 3.5. Bump (IEC 60255-21-2) class 1
IEC 60255-26
to 2 kV LL Clause 6.13.2
1.2.5. Surge (IEC 61000-4-5)
Clause 7.2.7
□ Zone B IEC 60255-1
3.6. Seismic (single axis
to 2 kV LE (IEC 60255-21-3) class 1
sweep)
to 1 kV LL Clause 6.13.3
0,15 - 80 MHz 4. CLIMATIC ENVAIRONMENTAL CONDITIONS
IEC 60255-26
1.2.6. Conducted distur- 10 V IEC 60255-1
bance induced by RF (IEC 61000-4-6)
fields 27, 68 MHz (IEC 60068-2-2,
Clause 7.2.8 4.1. Dry heat operational +70°C; 72h
test Bd)
10 V
Clause 6.12.3.1
Zone A
IEC 60255-1
150 V DM
IEC 60255-26 (IEC 60068-2-1,
300 V CM 4.2. Cold operational -25°C; 72h
1.2.7. Power frequency volt- test Ad)
(IEC 61000-4-16)
age (50 Hz and 60 Hz)
Clause 7.2.9
□ Zone B Clause 6.12.3.2
100 V DM
300 V CM
27
Kema Standards SIA-B
IEC 60255-1
(IEC 60068-2-2,
4.3. Dry heat storage +80°C; 72h
test Bb)
Clause 6.12.3.3
IEC 60255-1
(IEC 60068-2-1,
4.4. Cold storage -40°C; 72h
test Ab)
Clause 6.12.3.4
IEC 60255-1
-25°C; +70°C
(IEC 60068-2-14,
4.5. Change of temperature 3 hours
test Nb)
5 cycles
Clause 6.12.3.5
IEC 60255-1
4.6. Damp heat, steady (IEC 60068-2-78, +40°C; 93%
state test Cab) 10 days
Clause 6.12.3.6
IEC 60255-1
+25°C; 40°C
(IEC 60068-2-30,
4.7. Damp heat, cyclic 97%; 93%
test Db)
6 cycles
Clause 6.12.3.7
28
Selection & Ordering data SIA-B
0 0 0 F 0 0 1 B D B SIA B 0 0 0 F 0 0 1 B D B
SIA-B
29