Presentation - Eaton - Arc Flash Solutions
Presentation - Eaton - Arc Flash Solutions
Presentation - Eaton - Arc Flash Solutions
2
2
What is an Arc Flash?
An Arc Flash is a dangerous condition associated
with explosive release of energy caused by an
electrical arc due to either a phase to earth or
phase to phase fault.
3
3
Research studies say ….
4
4 4
Arc Flash – a real danger
5
5
Electrical injuries cost more than other injuries
6
6
Injury costs can last a lifetime
7
7
National Fire Protection Association
NFPA 70E-2009
Will this become a global Standard?
8
8
National Fire Protection Association
NFPA 70E-2009 Article 130.3
9
9
Electrical Workplace Safety Standards Summary
10
10
IEEE 1584-2002
“Guide for Performing Arc
Flash Calculations”
Provides guidance for the calculation of
incident energy and arc flash protection
boundaries.
It presents formulas for numerically quantifying
these values.
The IEEE 1584 Guide also includes an Excel
Spreadsheet “Arc-Flash Hazard Calculator”
which performs the actual calculations using
the formulas stated in the Guide.
11
11
How Do You Fix the Problems
Discovered?
12
12
Label Equipment and
Restrict Access (Keep People Away)
• By Qualified Engineer
• IEEE 1584
• Incident Energy Calcs
• AF protection boundaries
• Includes spreadsheet
• Standardized Data
Collection Templates
• Labels, Training,
Recommendations
Based upon maximum energy for a 2nd degree burn (1.2 cal/cm2)
17
17
Understand “Good” Safety Practices
Bad – Exposed Back of Neck, Head and Hair Good – All of Body Protected
18
18
Remember
19
19
Heat Stress Warning
Just as this clothing
blocks heat energy
from the outside, it
also slows the
escape of heat from
you body. This may
quickly cause a you
to overheat and
develop heat stress
problems.
20
20
This is uncomfortable. . .
21
21
This is REALLY uncomfortable……
22
22
Another Category of Methods …
1. Label Equipment & Train Personnel on Good
Safety Practices
2. Move People Further Away
3. Redirect Blast Energy
4. Prevent Fault
5. Reduce Available Fault Current
6. Shorten Clearing Time
23
23
Remote Racking and Control Options
Method 20 Method 21
Remote
Remote Racking (new
Racking Device
equipment)
Method 22 Method 23
Remain physically outside the flash protection boundary.
Therefore NO ARC FLASH HAZARD protection required!
How Do I Reduce Available Fault Current?
• Operate with a Normally Open Tie During
Maintenance Method 8
• Change Out Transformer – Smaller KVA and/or
Higher Impedance, if possible Method 9
25
25
Use High Speed Molded Case Breakers
Incident Energy at
Bolted Fault Current
IEEE 1584 Generic
Min Mid Max Equation
225 A MCCB with Thermal-Magnetic Trip Unit 15x 156x 444x
Bolted fault current 3.4 kA 35 kA 100 kA IEEE 1584 Using Time
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm 2) N/A1 1.7 4.7 Current Curve Input
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm 2) 59.6 1.1 2.3
Measured Incident Energy (Cal/cm 2) 0.08 0.1 0.11 Tested Value
1200 A MCCB with Electronic Trip Unit 16x 29x 83x
Bolted fault current 20 kA 35 kA 100 kA 1
2
N/A = Not Applicable
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm ) N/A1 3.5 9.4
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm 2) 218 3.5 5.8 because it is outside the
Measured Incident Energy (Cal/cm 2) 1.86 1.2 1.64 range of the IEEE 1584
Generic Equation
• 1584 predicts higher than actual incident energy for breakers and lower
than possible incident energy for fuses
• Incident energy release from Eaton MCCB protected circuit will be HRC 1 or
less for any current above 15x handle rating up to and including 100 kA
Method 12
26
26
Use High Speed Molded Case Breakers
Incident Energy at
Bolted Fault Current
IEEE 1584 Generic
Min Mid Max Equation
225 A MCCB with Thermal-Magnetic Trip Unit 15x 156x 444x
Bolted fault current 3.4 kA 35 kA 100 kA IEEE 1584 Using Time
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm 2) N/A1 1.7 4.7 Current Curve Input
IEEE
Inc. Energy via IEEE 1584 &1584 Predicted
Trip Curve (Cal/cm 2) 59.6 1.1 2.3
Measured Incident EnergyActual
2
(Cal/cmMeasured
) 0.08 0.1 0.11 Tested Value
1200 A MCCB with Electronic Trip Unit 16x 29x 83x
Bolted fault current 20 kA 35 kA 100 kA 1
2
N/A = Not Applicable
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm ) N/A1 3.5 9.4
IEEE
Inc. Energy via IEEE 1584 &1584 Predicted
Trip Curve (Cal/cm 2) 218 3.5 5.8 because it is outside the
Measured Incident Energy 2
(Cal/cmMeasured
Actual ) 1.86 1.2 1.64 range of the IEEE 1584
Generic Equation
• 1584 predicts higher than actual incident energy for breakers and lower
than possible incident energy for fuses
• Incident energy release from Eaton MCCB protected circuit will be HRC 1 or
less for any current above 15x handle rating up to and including 100 kA
Method 12
27
27
Low Voltage Power Circuit Breakers
28
28
For Even Better AF Performance, try …
M1
Method 14
SD= SD= SD=
0.3S 0.3S 0.3S
29
29
Keep Blast Away From People …
1. Label Equipment & Train Personnel on Good
Safety Practices
2. Move People Further Away
3. Redirect Blast Energy
4. Prevent Fault
5. Reduce Available Fault Current
6. Shorten Clearing Time
30
30
5/15/27/38 kV Arc Resistant Switchgear
Arc Flaps
Control
Section
2000A or
3000A breaker
with Vent
VT
drawer
Manual Close /
1200A can be 1
Open Push Buttons
high or 2 high
Method 24
LV Arc Resistant Switchgear
Arc Flaps
Method 25
MV Arc Resistant Motor Control Center
Arc Plenum
(available side
or rear exhaust)
Method 26
Arcflash Resistant Motor Control Center
Bucket Position Racking Tool Receiver Internal Shutter
Connected 3/8” Square Position
Test Open
Withdrawn Closed
Handle
Mechanism
Breaker
Device Island
• Start, Stop, Auto, Man
Starter
Method 27
You Can Also …
1. Label Equipment & Train Personnel on Good
Safety Practices
2. Move People Further Away
3. Redirect Blast Energy
4. Prevent Fault
5. Reduce Available Fault Current
6. Shorten Clearing Time
35
35
Transformer Bushing Monitoring
• Monitor Transformer Bushings
• Capacitance
• Power Factor
Method 28
36
36
Partial Discharge Monitoring
• Monitor Insulation Integrity
• Switchgear
• Generators
• Motors
37
37
Enable Safer Inspection
• Infrared Scanning Windows
for LV/MV Assemblies
38
38
Continuous Thermal Monitoring
• Monitoring connecting joints on a • Monitoring Individual
computer room power distribution Connections
unit (PDU) switchboard, utilizing
plastic bracket system
IR Sensor
39
39
Or You Can …
1. Label Equipment & Train Personnel on Good
Safety Practices
2. Move People Further Away
3. Redirect Blast Energy
4. Prevent Fault
5. Reduce Available Fault Current
6. Shorten Clearing Time
Both work to
Reduce Energy
40
40
Faster Clearing Times
ARMSTM (Arc Flash Reduction Maintenance System)
41
41
ARMS Maintenance Mode
ACB Application
42
42
Design the Hazard Out (Safety by Design)
PowerXpert CX with ARMS
43
43
Design the Hazard Out (Safety by Design)
PowerXpert CX with ARMS
44
44
Arcflash Reduction Maintenance System
Lockout
Switch
Battery
Circuit
Breaker
3/4” Diameter Copper
Electrodes
Line
Conductors 7
Calorimeter
Array
18 AWG Shorting
Wire between 3
Phase Electrodes
Output =
Arc Flash Energy
Open Side of
20”x20”x20” Enclosure Enclosure
46
46
Eaton Testing to Validate ARMS
Results of Eaton Moulded-Case Breaker Testing
Incident Energy at
Bolted Fault Current
Min Mid Max
225 A MCCB with Thermal-Magnetic Trip Unit
Bolted fault current 3.4 kA 35 kA 100 kA
2
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm ) N/A1 1.7 4.7
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm 2) 59.6 1.1 2.3
2
Measured Incident Energy (Cal/cm ) 0.08 0.1 0.11
1200 A MCCB with Electronic Trip Unit
Bolted fault current 20 kA 35 kA 100 kA
Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm 2) N/A1 3.5 9.4
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm 2) 218 3.5 5.8
2
Measured Incident Energy (Cal/cm ) 1.86 1.2 1.64
47
47
Arcflash Reduction Maintenance System
(ARMS™)
48
48
Arcflash Reduction Maintenance System:
Reduces Hazard Risk Category
Example:
• Normal settings –
HRC = 3 (10.7 cal)
49
49
ARMS Maintenance Mode
600A Interruption Devices (5kA @ 480V)
50
50
How is the ARMS system used to
reduce incident energy?
51
51
Incident energy varies with fault
duration times
Bolted Arcing Fault Incident Hazard
Fault Fault Duration Energy Risk
(kA) (kA) (secs) (cal/cm²) Category
_________________________________________________________
40 20 2 89 >4
40 20 0.5 22 3
40 20 0.3 13 3
40 20 0.1 4.4 2
40 20 0.05 2.2 1
________________________________________________________
40 20 0.04 1.8 1
_________________________________________________________
52
52
Hazard Analysis, Risk Estimation and Risk
Evaluation Procedure (NPFA 70E, Annex F)
53
53
Conclusion: Safety By Design
Moving Electrical Safety & Reliability Upstream
Prevention Protection
54
54
Conclusion of different methods you can
employ to make your facility safer
55
55
Questions?
Questions?
56
56
57
57