Unit 1 2022 EEE Updated
Unit 1 2022 EEE Updated
Consider a coil of n turns placed in a magnetic field of maximum value m wb, produced
by two poles N & S.
Initially the coil is along the reference axis. Field is perpendicular to the plane of the coil. Let
the coil be rotated in the anticlockwise direction with an angular velocity of radian /Sec as
shown in fig(2.1)
When the coil is along the ref avis at wt=0, called zero emf position. This is because of the
movement of the coil at this instant wt = 0 along the field.
If coil relates making an angle =wt with ref. axis, a this instant the normal component of
magnetic flue w.r.t the plane of the coil is equal to m cos ( = wt)
The effective value or r.m.s value of an alternating quantity is equal to that steady
current, which produces the same heat as produced by the alternating current when
passed through the same resistance for the same time.
Divide the time base of an a.c wave form into “n” equal parts so that each interval is
equal to t/n secs.
H = (i12+i22+-----------+in2) Rt =I2Rt
(i12 + i 22 +.................. + i 2n )
I =
n
Average value of an alternating current is equal to that steady current, which transfers
the same amount of charge, as, transferred by the alternating current across the same
circuit anal in the same time.
Average value is considered for one half a cycle, as the avg. value for complete cycle
is zero.
π π
1 1 I
Iav = idθ = I msinθdθ = m -cosθ π0
π0 π0 π
2
= I m = 0.637Im
π
The average value of an alternating current is 0.637 times its maximum value.
r.m.s value
Kf = Form Factor =
Average value
I 0.7071m
Kf = = = 1.11, (for sine wave)
Iav 0.6371m
maximum value
Kp = Peak Factor =
r.m.s. value
Im I
Kp = = = 1.414, for a sine wave.
I 0.7071m
The phase of an alternating quantity at any instant is the angle through in which the
routing vector representing alternating quantity has related through from the reference axis.
Phase difference between two alternating quantities is the angle between the two rotating
vectors, representing the two alternating quantities as shown in fig(2.4)
Phase
Phase of an alternating quantity at any particular instant as the fractional part of a period
or cycle through which the quantity has advanced from the selected origin. Taking an example,
in fig: 5, the phase of current at point A is T/4 second, where T is the time period or expressed
in terms of angle, it is /2 radians.
2
ωt
0 A
Figure 5
Phase Difference
When two alternating quantities are considered, the frequency being the same, they may
not pass through a particular point at the same instant. These two quantities are said to have a
phase difference. It is specified either in degrees or in radians. Phase is measured by the angular
difference between the points where the two curves cross the base or reference line in the same
direction.
The quantity ahead in phase is said to lead behind the other quantity whereas the second
quantity is said to lag behind the first one. In fig: 6, the leading current i1 goes through its zero
and maximum values first and current i1 goes through its zero and maximum values after time
angle .
i1
i2
2
ωt i1
0
i2
Figure 6
Two quantities are said to be in phase with each other if they pass through zero values at the
same instant and rise in the same direction. If two quantities pass through zero values at the
same instant by rise in opposite direction, they are said to be in opposition or out of phase.
Illustrative Examples
1. An alternating voltage has amplitude of 100V. Find its i) rms value and ii) average value.
Ans: Irms=Im/2=100/2=70.7A
Iav=0.637Im=63.7
2. An alternating current has an effective value of 200A. if its frequency is 25Hz, find its
average value and write down the expression for the current.
frequency, f=82.8 Hz
t1= 0.68ms
t2= T/2-t1=2.65ms
Analysis of AC circuits
i
i v
Let the voltage vector be taken as the reference. Then, the angle of lead/lag, Φ = 0
By Ohm’s law, instantaneous value of current through the circuit is given by,
v Vm sin (ωt)
i =R= = Im sin (ωt)
R
From the above equations, the phase difference between between v and i = 0. i.e,
i is in phase with v.
Vm 2 2 Vm 2 (1 − cos2ωt)
p= sin (ωt) =
R R 2
Vm 2 Vm 2 cos2ωt
p= −
R 2R 2
The second term represents a periodically varying quantity whose frequency is twice that of
the applied voltage v and therefore its Average value taken over its one full cycle = 0.
Vm 2 Vm Vm Vrms
Pavg = −0= . = . Im
2R √2 √2 R √2
Pavg = Vrms . Irms
Average power consumed, P = V.I for a pure resistive circuit
e v
i
di v
=
dt L
v Vm sin (ωt) Vm −cosωt Vm
i=∫ dt = ∫ dt = [ ]= [−sin (90 − ωt)]
L L L ω ωL
Vm Vm
i= [sin (ωt − π⁄2)] where 𝐗 𝐋 = 𝛚𝐋 = 𝟐𝛑𝐟𝐋 and Im =
XL XL
sin (2ωt)
p = −Vm Im
2
This represents a periodically varying quantity whose frequency is twice that of the applied
voltage v and therefore its Average value taken over its one full cycle = 0.
Therefore, Average Power consumed by pure L is,
Pavg = 0
i
i
v
v
Let v = Vm sin (ωt) (v is taken as the reference vector)
dv d[Vm sinωt]
i=C =C = Vm . ωC. sin(90 + ωt)
dt dt
Vm Vm
i= [sin (ωt + π⁄2)] where 𝐗 𝐂 = 𝟏⁄𝛚𝐂 = 𝟏⁄𝟐𝛑𝐟𝐂 and Im =
XC XC
From the above equation, i leads v by 𝛑⁄𝟐 radians or 90 degrees for pure C circuit.
Vm Im
p = Vm Im sin ωt cosωt = sin2ωt
2
This represents a periodically varying quantity whose frequency is twice that of the applied
voltage v and therefore its Average value taken over its one full cycle = 0.
Therefore, Average Power consumed by pure C is,
Pavg = 0
R L
ER EL E EL
I
Φ I
ER
E
⃗ and I are the RMS values of the applied voltage and the current respectively.
E
⃗ = ⃗⃗⃗⃗
E ER + ⃗⃗⃗⃗
EL
We know that for pure R circuit, voltage is in phase with current. Therefore ⃗⃗⃗⃗
ER is in phase
with I
We know that for a pure L circuit, current lags voltage by 90 degrees or ⃗⃗⃗⃗
EL leads I by 90
degrees. The vector sum of ⃗⃗⃗⃗
ER and ⃗⃗⃗⃗
EL gives ⃗E.
Em Im
p = e. i = Em Im sin(ωt) sin ωt (ωt − ∅) = [cos∅ − cos (2ωt − ∅)]
2
𝐏𝐚𝐯𝐠 = 𝐄. 𝐈. 𝐜𝐨𝐬∅
Power triangle
P: Real power
P=
Q: Reactive power
S: Apparent power
Q=
S2 = P2 + Q2
S=
It is defined as the power which is actually dissipated in the circuit resistance in Watts (W).
It is also called Active power or Wattful component of power or True power.
It is given by,
P = I2R = V I cosΦ Watts.
It is defined as the power developed in the inductive reactance of the circuit in Volt-Amperes-
Reactive (VAR).
It is also called Wattless component or Quadrature component of power.
It is given by,
Q = I2XL = I2.Z sinΦ = V I sinΦ Volt-Amperes-Reactive.
It is given by the product of rms values of applied voltage and circuit current in Volt-Amperes
(VA).
S = I2.Z = V I Volt-Amperes
Power factor
R C ER
Φ
I
ER EC
i E
EC
E
⃗E = ⃗⃗⃗⃗
ER + ⃗⃗⃗⃗
EC
⃗⃗⃗⃗
ER is in phase with I. ⃗⃗⃗⃗
EC lags I by 90 degrees. The vector sum of ⃗⃗⃗⃗
ER and ⃗⃗⃗⃗ ⃗.
EC gives E
Em Im
p = e. i = Em Im sin(ωt) sin ωt (ωt + ∅) = [cos(−∅) − cos (2ωt + ∅)]
2
𝐏𝐚𝐯𝐠 = 𝐄. 𝐈. 𝐜𝐨𝐬∅
6. Analysis of R-L-C Series circuit:
R L C
ER EL EC ⃗ = ⃗⃗⃗⃗
i E ER + ⃗⃗⃗⃗
EL + ⃗⃗⃗⃗
EC
E
We shall take I as the reference vector. ⃗⃗⃗⃗
ER is in phase with I. ⃗⃗⃗⃗
EL leads I by 90 degrees. ⃗⃗⃗⃗
EC
lags I by 90 degrees. Consider the following 3 cases.
Case 1: 𝐗 𝐋 > 𝐗 𝐂
It can be seen from the vector diagram that V leads I by Φ radians or I lags E by Φ radians.
𝐏𝐚𝐯𝐠 = 𝐄. 𝐈. 𝐜𝐨𝐬∅
Case 2: 𝐗 𝐋 < 𝐗 𝐂
𝐏𝐚𝐯𝐠 = 𝐄. 𝐈. 𝐜𝐨𝐬∅
Case 3: 𝐗 𝐋 = 𝐗 𝐂
𝐏𝐚𝐯𝐠 = 𝐄. 𝐈
Power triangle
P: Real power
P=
Q: Reactive power
S: Apparent power
Q= S2 = P2 + Q2
S=
It is defined as the power which is actually dissipated in the circuit resistance in Watts (W).
It is also called Active power or Wattful component of power or True power.
It is given by,
P = I2R = V I cosΦ Watts.
It is defined as the power developed in the inductive reactance of the circuit in Volt-
Amperes-Reactive (VAR).
It is also called Wattless component or Quadrature component of power.
It is given by,
Q = I2XL = I2.Z sinΦ = V I sinΦ Volt-Amperes-Reactive.
It is given by the product of rms values of applied voltage and circuit current in Volt-
Amperes (VA).
S = I2.Z = V I Volt-Amperes
Power factor
Power factor plays an important role in AC circuits since power consumed depends upon it.
It is clear from the above that for fixed power and voltage, the load current is inversely
proportional to the power factor. Lower the power factor, higher is the load current and vice-
versa. A power factor less than unity results in greater conductor size, large copper losses and
poor voltage regulation.
The low power factor is mainly due to the fact that most of the power loads are inductive and
therefore, take lagging currents. In order to improve the power factor, some device taking
leading power should be connected in parallel with the load. One of such devices can be a
capacitor. The capacitor draws a leading current and partly or completely neutralizes the
lagging reactive component of load current. This raises the power factor of the load.
To illustrate the power factor improvement by a capacitor, consider a single phase load taking
lagging current I at a power factor cosϕ1 as shown.
The capacitor C is connected in parallel with the load. The capacitor draws current IC which
leads the supply voltage by 90 degrees. The resulting line current I’ is the phasor sum of I and
IC and its angle of lag is ϕ2 as shown in the phasor diagram. It is clear that ϕ2 is less than ϕ1, so
that cos ϕ2 is greater than cos ϕ1. Hence the power factor of the load is improved. The following
points are to be noted.
1) The circuit current I’ after pf. Correction is less than the original circuit current I.
2) The active power (kW) remains unchanged due to power factor improvement.
Three-phase circuits:
Consider an alternator which is a machine which generates 3 phase voltages. The stationary
part or the stator is cylindrical in shape and has uniform slots on its inner periphery. The
conductors which form a winding are placed in these slots and connected together such that
the emfs induced in a winding are always additive. There are 3 windings which are connected
either in star or delta. The rotating part or the rotor os represented by two poles of a magnet.
AA’, BB’ and CC’ are three independent coils which are electrically displaced by 120 degrees
with respect to one another. When the rotor rotates in the clockwise direction with a particular
speed Ns, the flux produced by it sweeps across the stator conductors and hence emfs are
induced in all the three phases, which have a phase displacement of 120 degrees with respect
to one another. The waveforms of the voltages generated are sinusoidal in nature and can be
represented by the waveforms as shown.
A 3 phase supply is said to be balanced when all the 3 voltages have the same magnitude but
differ in phase by 120ᵒ with respect to each other.
The waveforms of the sinusoidal voltages generated can be represented by the waveforms as
shown.
Ec
Ea
12 Ea
3 12
12 12
12
Ec Eb
Eb
Relationship between Line and Phase values in a balanced star connected system:
Iline= Iphase
P3∅
= 3 x power consumed by each phase
P3∅
= 3 x Eph Iph cos (∠ b⁄w Eph and Iph )
El
P3∅ = 3 x Il cos ϕ
√3
𝐏𝟑∅ = √𝟑 𝐄𝐥 𝐈𝐥 𝐜𝐨𝐬 𝛟
Relationship between Line and Phase values in a balanced delta connected system:
Vline= Vphase
Ebc
Applying KCL at node 1,
Ia = Iab- Ica
From vector diagram,
Iab=2. Iab. Cos 30
Il=2. Iab √3/2
P3∅
= 3 x power consumed by each phase
P3∅
= 3 x Vph Iph cos (∠ b⁄w Vph and Iph )
Il
P3∅ = 3 x Vl cos ϕ
√3
𝐏𝟑∅ = √𝟑 𝐕𝐥 𝐈𝐥 𝐜𝐨𝐬 𝛟
Here we analyze the measurement of power when the load is star connected. The following
assumptions are made.
i) The 3 phase supply to which the load is connected is balanced.
ii) The phage sequence is ABC
iii) The load is balanced
iv) The load is R-L in nature
For Wattmeter 1
But we know that 3VL I L cos = P3 = Total power consumed by the 3 load
Thus, total power absorbed in the three phase load is given by the sum of the two
wattmeter readings.
W1 − W2 V I sin 1
= L L = tan
W1 + W2 3VL I L cos 3
W − W2
tan = 3 1
W1 + W2
W − W2
= tan −1 3 1
W1 + W2
W − W2
Powerfactor = cos = cos tan −1 3 1
W1 + W2
One of the wattmeters reads –ve . i.e, it kicks back. Then either Potential coil or
Current coil terminals are interchanged and the wattmeter reading is taken as –ve.
Numericals:
Solution:
𝑋𝐿 = 2𝜋𝑓𝐿 =
15.7 𝛺
𝑍 = 𝑅 + 𝑗𝑋𝐿
= 20 + 𝑗15.7 𝛺
𝑍
= 25.42∠38.13° 𝛺
Let V be taken as
reference.
⃗ = 230∠0° 𝑉
𝑉
230∠0
𝐼 = 25.42∠38.13° =
𝟗. 𝟎𝟒∠𝟑𝟖. 𝟏𝟑°𝑨
|𝑅|
𝑐𝑜𝑠𝛷 = |𝑍|
=
20
=
25.42
𝟎. 𝟕𝟖𝟔 𝐥𝐚𝐠𝐠𝐢𝐧𝐠
P=I2R or
P=VIcosΦ
P=1634.4Watts
2. R=20 𝛺, 𝐿 = 0.2𝐻 𝑎𝑛𝑑 𝐶 = 100µ𝐹 are connected in series across 220 V, 50 Hz supply.
Calculate the current, power factor and power consumed in the circuit. Draw the vector
diagram.
Solution:
𝑋𝐿 = 2𝜋𝑓𝐿 = 62.83𝛺
𝑋𝐶 = 1/2𝜋𝑓𝐶 = 31.8𝛺
Here XL>XC
𝑍 = 𝑅 + 𝑗(𝑋𝐿 − 𝑋𝐶 )
= 20 + 𝑗(62.83 − 31.8) 𝛺
𝑍 = 36.9 ∠58.32 Ω
Taking ⃗E = 220∠0° V as
reference,
⃗E 220∠0
I= =
𝑍 36.9∠58.32°
P = I2R or P = VIcosΦ
= 𝟓. 𝟗𝟔∠𝟓𝟖. 𝟑𝟐 𝑨
P=7106 Watts
|𝑅| 20
𝑐𝑜𝑠𝛷 = =
|𝑍| 36.9
= 𝟎. 𝟓𝟒𝟐 𝐥𝐚𝐠𝐠𝐢𝐧𝐠
R + r = 6.389 Ω
XL = 4.814 Ω
𝑉𝑐𝑜𝑖𝑙 171
|𝑍𝑐𝑜𝑖𝑙 | = |𝑟 + 𝑗𝑋𝐿 | = =
𝐼 30
= 5.7 Ω
r 2 = Zcoil 2 − XL 2 = 3.87 Ω
R = 6.389 − 3.87 = 2.518 Ω
Numericals:
1) Two wattmeters measure total power in a 3 phase circuit and are correctly connected.
One wattmeter reads 4800 W and the other reads backwards. On reversing the
connection of the latter, it reads 400 W. What is the total power and power factor.
Solution:
2) Three identical coils having a resistance of 10 Ω and an inductance of 0.05 H each are
connected in star across a 3 phase, 400 V, 50 Hz., balanced supply. Calculate the load
current and power consumed. What will be the readings of the two wattmeters connected
to measure the total power?
Solution:
3) A 3 phase star connected load draws a load current of 25 A. The load kVA and kW are 20
and 16 respectively. Find the reading on each of the two wattmeters used to measure the
3 phase power.
Solution:
4) The power flowing in a 440 V, 3ϕ, 3 wire balanced load system is measured by 2
wattmeter method. The reading in the wattmeter A is 750 W and in wattmeter B is 1500
W. What is the power factor of the system and load current per phase?
Solution:
440
V ph = = 254.03V
3
W1 + W2 = P3 = 750 + 1500 = 2250W
W − W2
tan = 3 1 = −0.577
W1 + W2
cos = 0.866 lagging
P3 = 3Vl I l cos
I l = I ph = 3.409 A
5) Two wattmeters are connected to measure the input of a 15 H.P, 50 Hz, 3 phase Induction
motor at full load. The full load efficiency and power factor are 0.9 and 0.8 lagging
respectively. Find the readings of the 2 wattmeters.
Solution:
Power output by the 3 phase induction motor at full load = 15 H.P = 15 x 746W Power output
= 11.19kW
output 11.19 x1000
Power input = = = 12.433kW
0.9
P3 = W1 + W2 = 12.433kW − − − − − (1)
cos = 0.8lagging
W − W2
cos = cos tan −1 3 1
W1 + W2
W − W2
cos −1 0.8 = tan −1 3 1
12.433k
W1 − W2 = 5.378kW − − − − − (2)
W1 = 8.905kW , W2 = 3.527kW