Modicon M251 - TM251MESE
Modicon M251 - TM251MESE
Modicon M251 - TM251MESE
Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Modicon M251
Complementary
Maximum number of I/O 7 (local I/O-Architecture)
expansion module 14 (remote I/O-Architecture)
Data backed up 128 MB built-in flash memory for backup of user programs
Integrated connection type USB port with mini B USB 2.0 connector
Non isolated serial link serial with RJ45 connector and RS232/RS485 interface
Dual-port Ethernet 1 with RJ45 connector
Ethernet port Ethernet 2 with RJ45 connector
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for bus length of 3 m for USB
Electrical connection removable screw terminal blockpower supply (pitch 5.08 mm)
Marking CE
Surge withstand 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
1 kV power lines common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines differential mode conforming to EN/IEC 61000-4-5
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height 90 mm
Depth 95 mm
Width 54 mm
Environment
Standards ANSI/ISA 12-12-01
CSA C22.2 No 142
CSA C22.2 No 213
EN/IEC 61131-2:2007
Marine specification (LR, ABS, DNV, GL)
UL 1604
UL 508
2
Dec 11, 2022
Resistance to electrostatic 8 kV in air conforming to EN/IEC 61000-4-2
discharge 4 kV on contact conforming to EN/IEC 61000-4-2
Electromagnetic emission Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/
IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC
55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC
55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to
EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/
IEC 55011
Pollution degree 2
Packing Units
Unit Type of Package 1 PCE
Offer Sustainability
Sustainable offer status Green Premium product
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
known to the State of California to cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
4
Dec 11, 2022
Product data sheet TM251MESE
Dimensions Drawings
Dimensions
Clearance
6
Dec 11, 2022
Product data sheet TM251MESE
Mounting and Clearance
Mounting Position
NOTE: Keep adequate spacing for proper ventilation and to maintain an ambient temperature between -10°C (14°F) and 55°C (131°F).
Acceptable Mounting
Incorrect Mounting
8
Dec 11, 2022
Product data sheet TM251MESE
Connections and Schema
USB Connection to a PC
Ethernet Connection to a PC
Recommended replacement(s)
10
Dec 11, 2022