Distance Protection
Distance Protection
ZS = 10 Ω
ZL = 4 Ω
ZS = 10 Ω
IF1 F1
115kV 50
ZS = 10 Ω
F2
IF2
50
ZS ZL
Generation IR
Distance
Relay 21 VR
jX
ZL
Relay
ZS PT.
IR ZL
Normal
VS VR ZLOAD
Load
VR
Impedance measured ZR = = Z L + Z LOAD
ΙR
ZL
ZS IR ZF
VS VR ZLOAD Fault
jX ZL Impedance Seen At
Measuring Location
For Line Faults
TRIP STABLE
jIX
IF zF
IZ
V2 V1
VF V3
IR
Trip TRIP STABLE
Spring
I1/I2 ZP
IR
V1
21 VR VFP
V2
C.T. RATIO
ZR = Z P x
V.T. RATIO
> Distance Protection - January 2004
Example
C.T. RATIO
ZR = ZP x
V.T. RATIO
B-E
C-E
IRA Z1
∑IZN Z1 = Phase replica impedance
Z1 ZN = Neutral replica impedance
Z1
IRA passes through Z1
IRN passes through ZN
IRN ZN
N ZT = Z1 + ZN
ZT = (Z1 + Z2 + Z0)/3 = Z1 + ZN
ZN = (Z1 + Z2 + Z0)/3 - Z1
= (2Z1 + Z0)/3 - Z1
= - Z1 + Z0
3 3
= KN Z1
ZN IN Z N
Set Z PH = ZF1
Set Z = (ZF0 - Z F1 )
N
3
Usually ∠ Z N = ∠ Z PH for OHL’s
KN = Z0 - Z1 = ⏐KN⏐ ∠∅N
3Z1
jX
jX
jX jX
Zn
Zn Zn Zn
R R R R
MHO OFFSET
Zs Zn ′
IMPEDANCE MHO
CROSS-
POLARISED
MHO
jX
Zn Zn
Zn
R R R
LENTICULAR QUADRILATERAL POLYGON
X Simple
RESTRAIN
X Less sensitive to power swings
Z
X Inherently directional
X Operates for F1, but not for F2 OPERATE
X Mho = 1/OHM F1
ϕ
R
Settings :-
Z = reach setting F2
ϕ = characteristic angle
jX
ZPH
ZN
ZE ZE = Earth-loop impedance
for ∅ - earth fault on a
R
cable
jX
X Normally used as
backup protection
X Operates for zero
faults (close up faults)
R
X Generally time
-Z’
delayed (as not
discriminative)
X VF → self polarised
X VSOUND PHASE → fully cross-polarised
X VF + xVS.F. → partially cross-polarised
X VPRE-FAULT → ‘memory’ polarised
jX
ZL
Z1 Load
RF
R
RS
jIX
Lenticular characteristic
created from two offset
Mho comparators
IR
R
Z3 reverse
Time
Z3A Z3C
T3
Z2A Z2C
T2
Z1A Z1C
A Z1B B C D
T2
Z2B
jX
D Z3A
C Z2A
B
Z1A
A
R
X FAST OPERATION
Trips circuit breaker without delay as soon as
fault within Zone 1 reach is detected.
X REACH SETTING
Cannot be set to 100% of protected line or may
overreach into next section.
Overreach caused by possible errors in :-
CTs
VTs
ZLINE information
Relay Measurement
Possible
Overreach
ZONE 1 = ZL
ZL
F
Possible incorrect tripping for fault at ‘F’
ZONE 1 = 0.8ZL
ZL
Z1A
A ZL
Z1B B
Z1A
Send Receive
Trip ‘B’
Z1B
Receive Send
Z1A
A
Z1B B
F
Dictated by :-
SIR = ZS/Zn
SIRMAX = ZS MAX
Zn MIN
∴ Zn MIN ≡ ZS MAX
SIRMAX
> Distance Protection - January 2004
Zone 2
TIME
Z1G Z1H
G H
F
Z1G Z1H
‘G’ ‘H’
F
Z2H
Z1G Z1H
‘G’ ‘H’
Problem with this :-
Zone 2 time delays near source on systems with several line
sections will be large.
End zone faults on lines nearest the infeed source point will be
cleared very slowly.
> Distance Protection - January 2004
Maximum Allowable Zone 2 Reach to Allow for
Equal Zone 2 Time Settings
ZL 1 ZL2
A B
i.e. Z2A(EFF) MAX must not reach further than Z1B(EFF) MIN
Z1BSETTING = 0.8ZL2
Z1B(EFF) MIN = 0.8 x 0.8ZL2 = 0.64ZL2
∴ Z2A(EFF) MAX < ZL1 + 0.64ZL2
∴ 1.2 Z2ASETTING < ZL1 + 0.64ZL2
Z2G
Z3H
Z3J
Z2H
Z2J
G H K
ZA ZB
IA IA+IB
IB
Relay Location
IR = IA
ZR = ZA + ZB + IB . ZB
IA
ZK
IG+IP F
ZG
IG
RELAY
Z2 ‘Boost’ G/F
Z2 PH
Zmo
Z2 ‘reduced’ G/F
Z2 PH
Z1 G/F (optional)
Z1 G/F (normal)
Zmo
X
X
X
Power Swing
Locus
ZP
Z3
ZT
ZL
21
Zone 1 = ZL + 0.5ZT
T1 = Instantaneous
Zone 3
- Back-up use as appropriate
T3
ZT
ZL
21