PENDENT SPRINKLER(STANDARD & QUICK RESPONSE) HD FIRE PROTECT


PVT. LTD.

TECHNICAL DATA
STYLE Upright, Pendent and
Recessed Pendent
TEMPERATURE Standard Response- 5mm
RESPONSE glass bulb
Quick Response- 3mm glass bulb
COVERAGE Standard Coverage
K-FACTOR 5.6 US (80 metric)
NOMINAL THREAD ½” BSPT (NPT Optional)
SIZE
MAXIMUM WORKING 175 psi (12 bar)
PRESSURE
FACTORY 500 psi (35 bar)
HYDROSTATIC
TEST PRESSURE
MINIMUM 7 psi (0.5 bar)
OPERATING DESCRIPTION
PRESSURE
HD Pendent and Upright sprinklers are designed for
TEMPERATURE 57°C (135° F), 68°C (155° F), use in light and ordinary hazards. The temperature
RATING 79°C (175° F), 93°C (200° F), response is standard response (5mm glass bulb)
141°C (286°F),182°C (360°F) and quick response (3mm glass bulb). The sprinklers
APPROVALS Refer Table come with compact design, glass bulb type, available
in several different finishes and temperature ratings.
FINISH Brass, Chrome Plated, White The pendent sprinklers must be installed in pendent
Painted. White shade is position, and upright sprinklers are to be installed in
RAL9010. For other shades, the upright position.
contact HD Sales.
For SIN Nos. HD401/HD402/ Pendent Recessed Sprinklers are installed with
HD501/HD502, chrome plating adjustable or non-adjustable Escutcheon plates (also
will not be done on the termed as Rosette plates). These are intended to
threaded portion. be installed with finished ceilings. Escutcheon plate
adjustment provides convenience in Pendent Sprinkler
ORDERING Style,Temperature Rating & installation in case of areas with finished ceilings or
INFORMATION Response,Thread type, Finish, walls.
Approval required- UL or
UL & FM SPRINKLER RATINGS
SIN NUMBER Pendent, SR: NORMAL NFPA MAXIMUM
HD401/ HD601/ HD101 SPRINKLER
SPRINKLER CEILING
GLASS
TEMPERATURE BULB
Upright, SR: TEMPERATURE TEMPERATURE
CLASSIFICATION COLOUR
HD402/ HD602/ HD102 RATING ALLOWED
Pendent, QR:
HD501/ HD701/ HD201 Ordinary 57°C (135°F) 38°C (100°F) Orange
Upright, QR: Ordinary 68°C (155°F) 38°C (100°F) Red
HD502/ HD702/ HD202
Intermediate 79°C (175°F) 66°C (150°F) Yellow

Intermediate 93°C (200°F) 66°C (150°F) Green

High 141°C (286°F) 107°C (225°F) Blue

Extra High 182°C (360°F) 149°C (300°F) Purple


As per Table 6.2.5.1 NFPA 13

JULY, 2022 PAGE 1 OF 6 HD 237


HD FIRE PROTECT
PVT. LTD.

APPROVALS Sprinkler Operation


Orientation Approval The Sprinkler operating device is state of the art
Response Temperature
Type / Code No heat responsive frangible glass bulb supplied by a
Type Rating UL FM
SIN No. world leader in this innovative technology. The glass
SR PENDENT 57°C (135°F) √ √ T10021 bulb contains fluid which expands when exposed to
HD401 68°C (155°F) √ √ T10022 heat. When rated temperature is reached, the bulb
79°C (175°F) √ √ T10023 shatters and water flows through the sprinkler and
93°C (200°F) √ √ T10024 strikes deflector, forming a uniform water spray
SR UPRIGHT 57°C (135°F) √ √ T10055 pattern to control or extinguish fire.
HD402 68°C (155°F) √ √ T10056
79°C (175°F) √ √ T10057 Care and Handling
93°C (200°F) √ √ T10058 Sprinklers must be handled with due care, they must
QR PENDENT 57°C (135°F) √ √ T10050 be stored at ambient temperature for best results
HD501 68°C (155°F) √ √ T10002 and in a separate space in order NOT to allow metal
79°C (175°F) √ √ T10003 parts coming in contact with sprinkler or bulb.
93°C (200°F) √ √ T10004 Storage as well as any onward shipment is to be made
QR UPRIGHT 57°C (135°F) √ √ T10051 in original packaging only.
HD502 68°C (155°F) √ √ T10042
79°C (175°F) √ √ T10043
Always store the sprinklers with protective sprinkler
93°C (200°F) √ √ T10044 caps. Do not remove the protective sprinkler caps
until the sprinklers are installed in the system, in
SR PENDENT 57°C (135°F) √ — T10021U
order to protect sprinklers from mechanical damage.
HD601 68°C (155°F) √ — T10022U
Sprinklers caps must be removed carefully without
79°C (175°F) √ — T10023U
93°C (200°F) √ — T10024U
touching / damaging the bulb element, before placing
141°C (286°F) √ — T10025U
the system in service.
SR UPRIGHT 57°C (135°F) √ — T10055U Sprinklers must be visually inspected carefully before
HD602 68°C (155°F) √ — T10056U installation. Sprinklers visibly damaged, dropped or
79°C (175°F) √ — T10057U exposed to temperature in excess of the maximum
93°C (200°F) √ — T10058U ambient temperature permitted, should never be
141°C (286°F) √ — T10059U installed.
QR PENDENT 57°C (135°F) √ — T10001U
Never install any glass blub sprinkler if the bulb is
HD701 68°C (155°F) √ — T10002U
T10003U
cracked or if there is a loss of liquid from the bulb.
79°C (175°F) √ —
93°C (200°F) √ — T10004U Sprinkler must be installed after the piping is in place
141°C (286°F) √ — T10005U to prevent mechanical damage.
QR UPRIGHT 57°C (135°F) √ — T10041U Use Teflon Tape or soft thread sealent on male thread
HD702 68°C (155°F) √ — T10042U of the Sprinkler for the leak tight Sprinkler joint. Use
79°C (175°F) √ — T10043U proper wrench. The sprinkler must be hand tightened
93°C (200°F) √ — T10044U into the fitting. After hand tightening, use Sprinkler
141°C (286°F) √ — T10045U Wrench Model SP-M for wrench tightening into
SR PENDENT 57°C (135°F) √ √ T10021F sprinkler fittings. A leak-tight 1/2 NPT/BSPT Sprinkler
HD101 68°C (155°F) √ √ T10022F joint should be obtained by applying maximum torque
79°C (175°F) √ √ T10023F of 19.0 N-m (14 lb-ft). Excessive tightening torque
93°C (200°F) √ √ T10024F may distort the Sprinkler inlet and cause leakage.
141°C (286°F) √ — T10035
182°C (360°F) √ — T10037 Sprinkler must never be painted, plated or coated
after they leave factory.
SR UPRIGHT 57°C (135°F) √ √ T10055F
HD102 68°C (155°F) √ √ T10056F The HD Sprinkler described herein must be installed
79°C (175°F) √ √ T10057F and maintained in accordance with the latest edition
93°C (200°F) √ √ T10058F of HD technical data, the latest standard of National
QR PENDENT 57°C (135°F) √ — T10001 Fire protection Association (NFPA) and Factory Mutual
HD201 68°C (155°F) √ √ T10002F (FM) or to the standard of any other authorities
79°C (175°F) √ √ T10003F having jurisdiction. The owner is solely responsible for
93°C (200°F) √ √ T10004F maintaining their fire protection system and device in
141°C (286°F) √ — T10036 proper operating condition.
QR UPRIGHT 57°C (135°F) √ — T10041
HD202 68°C (155°F) √ √ T10042F
79°C (175°F) √ √ T10043F
93°C (200°F) √ √ T10044F

JULY, 2022 PAGE 2 OF 6 HD 237


HD FIRE PROTECT
PVT. LTD.

Exposure to ultraviolet or direct sunlight for extended Note:


period may cause the liquid dye in glass bulb to fade
or lose colour. Colourless or faded coloured bulbs are In case of using HD 101/102 & HD 201/202 sprinklers
not a problem, as long as the fluid level has not been as part of FM Approved Low Expansion Foam Sys-
affected. The loss of colour in the liquid will not effect tems, the certification of the system is contingent
sprinkler performance, as long as the bulb is intact upon piping designed and installed in accordance with
and not damaged. The loss of colour may be an issue NFPA 11 and/ or FM Global Property Loss Prevention
in identifying sprinkler temperature rating, but the Data Sheet 4-12, Foam-Water Sprinkler Systems.
temperature rating is still stamped on the sprinkler
deflector.

Inspection Testing and Maintenance


Refer to NFPA 25 for inspection testing and
maintenance requirement or to the authority having
jurisdiction. For details of warranty, refer HD’s current
price list, conditions of sale or contact HD directly.

MATERIAL SPECIFICATION

Deflector Brass

Bulb Glass
Cap Copper *

Frame Brass

Seal Teflon Coated Washer

Standard Response 5.0mm


Bulb Nominal Diameter
Quick Response 3.0mm

*Note: For SIN Nos. HD601/HD701/ HD602/ HD702 the Cap material is Brass.

JULY, 2022 PAGE 3 OF 6 HD 237


HD FIRE PROTECT
PVT. LTD.

PENDENT & UPRIGHT SPRINKLER


SIN # HD401/HD501 SIN # HD402/HD502 SIN # HD601/HD701 SIN # HD602/HD702

Ø32mm
Ø36mm

HD
HD

54.8mm
55mm

54.8mm
55mm

HD HD

Ø30mm
Ø26mm

SIN # HD101/HD201 SIN # HD102/HD202


Ø33.7mm

HD
50mm

50mm

HD

Ø30mm

Note: For T10002F/T10003F/T10004F Deflector diameter is 25 mm.

RECESSED PENDENT
HOLE-Ø60 Max.
HOLE-Ø51 Min.
15mm

23.5mm
39mm

20mm

Maximum Recess
Ø75mm

Maximum Extension

JULY, 2022 PAGE 4 OF 6 HD 237


HD FIRE PROTECT
PVT. LTD.

REPRESENTATIVE IMAGES OF SPRINKLERS

HD401/HD501 HD402/HD502 HD601/HD701 HD602/HD702

HD101/HD201 HD102/HD202 T10002F/T10003F/T10004F

RECESSED PENDENT HD101 (WHITE)

NOTE: These are representative images of sprinklers. Please contact HD Sales for any further details.

JULY, 2022 PAGE 5 OF 6 HD 237


HD FIRE PROTECT
PVT. LTD.

SPRINKLER WRENCH

MODEL SP-M

LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.

NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.

D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA.
HD FIRE PROTECT PVT. LTD. • TEL: + (91) 22 2158 2600 • FAX: +(91) 22 2158 2602
Protecting What Matters Most to You • EMAIL: [email protected] • WEB: www.hdfire.com

JULY, 2022 PAGE 6 OF 6 HD 237