Daikin SL Service Manual 18K 24K
Daikin SL Service Manual 18K 24K
Daikin SL Service Manual 18K 24K
Service Manual
MODEL
FTKS18SL216/RKS18SL216
FTXS18SL216/RXS18SL216
FTKS24SL216/RKS24SL216
FTXS24SL216/RXS24SL216
Service Manual
Table of Contents
Table of contents
Service Manual
9. Maintenance.............................................................................................................50
9.1 Precautions before Maintenance.....................................................................................50
9.2 Error Code List................................................................................................................51
9.3 Troubleshooting for Main Malfunction.............................................................................54
9.4 Troubleshooting for Normal Malfunction..........................................................................69
10. Exploded View and Parts List...............................................................71
10.1 Indoor Unit.....................................................................................................................71
10.2 Outdoor Unit..................................................................................................................75
11. Removal Procedure........................................................................................80
11.1 Removal Procedure of Indoor Unit................................................................................80
11.2 Removal Procedure of Outdoor Unit.............................................................................85
Appendix:.........................................................................................................................90
Appendix 1: Reference Sheet of Celsius and Fahrenheit.....................................................90
Appendix 2: Configuration of Connection Pipe......................................................................90
Appendix 3: Pipe Expanding Method....................................................................................91
Appendix 4: List of Resistance for Temperature Sensor.......................................................92
Table of contents
Service Manual
FTKS18SL216
FTXS18SL216
FTKS24SL216
FTXS24SL216
Outdoor Unit:
RKS18SL216
RXS18SL216
RKS24SL216
RXS24SL216
Remote Controller:
YU1F
Technical Information 1
Service Manual
2. Specifications
2.1 Specification Sheet
2 Technical Information
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 3
Service Manual
Model FTKS24SL216/RKS24SL216
Product Code CB459004700_L75033
Rated Voltage V~ 208/230
Power Supply Rated Frequency Hz 60
Phases 1
Power Supply Mode Outdoor
Cooling Capacity(Min~Max) Btu/h 22000(8630~23200)
Heating Capacity(Min~Max) Btu/h /
Cooling Power Input(Min~Max) W 2260(600~27000)
Heating Power Input(Min~Max) W /
Cooling Power Current A 10.03
Heating Power Current A /
Rated Input W 2700
Rated Current A 11.98
Air Flow Volume(SH/H/M/L) CFM 1200/1050/900/750
Dehumidifying Volume Pint/h 2.5
EER (Btu/h)/W 9.73
COP (Btu/h)/W /
SEER 18
HSPF /
Application Area yd2 32.29-50.23
Model of indoor unit FTKS24SL216
Indoor Unit Product Code CB459N04700_L75033
Fan Type Cross-flow
Diameter Length(DXL) inch Φ4 1/4X32 11/16
Fan Motor Cooling Speed(SH/H/M/L) r/min 1300/1150/1000/850
Fan Motor Heating Speed(SH/H/M/L) r/min /
Output of Fan Motor W 30
Fan Motor RLA A 0.32
Fan Motor Capacitor μF 3
Evaporator Form Aluminum Fin-copper Tube
Pipe Diameter inch Φ5/16
Indoor Unit Row-fin Gap inch 2-1/16
Coil Length (LXDXW) inch 33 1/4X1X13 1/2
Swing Motor Model MP35CJ
Output of Swing Motor W 2.5
Fuse A 3.15
Sound Pressure Level(SH/H//M/L) dB (A) 49/46/42/36
Sound Power Level(SH/H//M/L) dB (A) 59/56/52/46
Dimension (WXHXD) inch 42 7/16X12 13/16X9 11/16
Dimension of Carton Box (LXWXH) inch 45X16 1/8X13 3/16
Dimension of Package (LXWXH) inch 45 3/16X16 1/4X13 3/4
Net Weight Ib 38.58
Gross Weight Ib 45.19
4 Technical Information
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 5
Service Manual
Model FTXS24SL216/RXS24SL216
Product Code CB459004300_L84775
Rated Voltage V~ 208/230
Power Supply Rated Frequency Hz 60
Phases 1
Power Supply Mode Outdoor
Cooling Capacity(Min~Max) Btu/h 22000(8630~23200)
Heating Capacity(Min~Max) Btu/h 24000(8650~26000)
Cooling Power Input(Min~Max) W 2260(600~27000)
Heating Power Input(Min~Max) W 2300(610~2750)
Cooling Power Current A 10.03
Heating Power Current A 10.20
Rated Input W 2750
Rated Current A 11.98
Air Flow Volume(SH/H/M/L) CFM 1200/1050/900/750
Dehumidifying Volume Pint/h 2.5
EER (Btu/h)/W 9.73
COP (Btu/h)/W 10.40
SEER 18.00
HSPF 10.00
Application Area yd2 32.29-50.23
Model of indoor unit FTXS24SL216
Indoor Unit Product Code CB459N04300_L84775
Fan Type Cross-flow
Diameter Length(DXL) inch Φ4 1/4X32 11/16
Fan Motor Cooling Speed(SH/H/M/L) r/min 1300/1150/1000/850
Fan Motor Heating Speed(SH/H/M/L) r/min 1300/1150/1000/850
Output of Fan Motor W 30
Fan Motor RLA A 0.32
Fan Motor Capacitor μF 3
Evaporator Form Aluminum Fin-copper Tube
Pipe Diameter inch Φ5/16
Indoor Unit Row-fin Gap inch 2-1/16
Coil Length (LXDXW) inch 33 1/4X1X13 1/2
Swing Motor Model MP35CJ
Output of Swing Motor W 2.5
Fuse A 3.15
Sound Pressure Level(SH/H//M/L) dB (A) 49/46/42/36
Sound Power Level(SH/H//M/L) dB (A) 59/56/52/46
Dimension (WXHXD) inch 42 7/16X12 13/16X9 11/16
Dimension of Carton Box (LXWXH) inch 45X16 1/8X13 3/16
Dimension of Package (LXWXH) inch 45 3/16X16 1/4X13 3/4
Net Weight Ib 38.58
Gross Weight Ib 45.19
6 Technical Information
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 7
Service Manual
Cooling
Cooling Heating
Heating
11 11
10 Conditions 10
9 Indoor:DB80°F/WB66.9°F 9
8 Outdoor:DB95°F 8
Indoor air flow:Super High
7 7
Current (A)
Current (A)
Pipe length:24.6ft
6 6
5 5
4 4 Conditions
3 3 Indoor:DB70°F/WB60°F
2 2 Outdoor:DB19.94°F/WB19.04°F
1 1 Indoor air flow:Super High
Pipe length:24.6ft
0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120
Compressor speed (rps) Compressor speed (rps)
FTKS24SL216/RKS24SL216 FTXS24SL216/RXS24SL216
FTKS18SL216/RKS18SL216 FTXS18SL216/RXS18SL216
Cooling Heating
105 110
100
100
95
90
90
85
Capacity ratio (%)
80 80
75
70
70 Conditions
Conditions
Indoor:DB80°F/WB66.9°F
65 60 Indoor:DB70°F
Outdoor:DB95°F
Outdoor:DB19.94°F/WB19.04°F
60 Indoor air flow:Super High
Indoor air flow:Super High
Pipe length:24.6ft 50 Pipe length:24.6ft
55
50 40
89.6 91.4 93.2 95 96.8 98.6 100.4 102.2 104 105.8 107.6 109.4 -4 5 14 23 32 41 50
Outdoor temp.(°F) Outdoor temp.(°F)
8 Technical Information
Service Manual
50 60
58
Heating
56
Noise/dB(A)
40
Noise dB(A)
54
Cooling
52
30
50
48
20 46
L M H SH 20 30 40 50 60 70 80 90 100
RXS24SL216
FTXS24SL216 RXS18SL216
FTKS24SL216
FTKS18SL216 RKS18SL216
FTXS18SL216 RKS24SL216
Heating:
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6ft.
Technical Information 9
Service Manual
W D
H
4 27 7 3/16
FTKS18SL216
Φ2 3/16 FTXS18SL216
Φ2 3/16
1 1/2
7 1/2 5 1/2
8 1/8 27 7 5/16
FTKS24SL216
Φ2 3/4 Φ2 3/4 FTXS24SL216
1 11/16
6 3 1/8
Unit:inch
Models W H D
FTKS18SL216
38 3/16 11 13/16 8 13/16
FTXS18SL216
FTKS24SL216
42 7/16 12 13/16 9 11/16
FTXS24SL216
10 Technical Information
Service Manual
13 3/8 35
27 9/16
38 15 5/8
22
14 5/16
Unit: inch
Technical Information 11
Service Manual
FTKS24SL216/RKS24SL216
Gas pipe
side
Valve
Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor Heat
exchanger
(condenser)
Liquid pipe
side
Valve Electron Strainer
expansion
valve
COOLING
FTXS18SL216/RXS18SL216
FTXS24SL216/RXS24SL216
Gas pipe
side
Valve
4-Way valve
Discharge
12 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
FTKS18SL216
FTXS18SL216
FTKS24SL216
FTXS24SL216
:,5('
7(036(1625
7(036(1625
&21752//(5
5(&(,9(5$1' $3
5220
78%(
',63/$<%2$5'
$3
&211(&725
57 57 7(50,1$/
%/2&.
%8 :+%8
1 1
287'22581,7
<(*1
; (9$325$725 *
0
0
)$1 67(33,1* :,),02'8/( *
(/(&75,&%2;
02725 02725 237,21$/ 600007000575
Technical Information 13
Service Manual
● Outdoor Unit
RKS18SL216 RKS24SL216
7(036(1625
7(036(1625
7(036(1625
6$7
WKHYROWDJHRIWHUPLQDO3'&DQG 8 &203 *
&203
28778%(
2875220
(;+$867
1'&DW$3LVKLJKHUWKDQ9WR 9 :
0$*1(7,& <(*1
SUHYHQWWKHULVNRIHOHFWULFDOVKRFN
5,1*
57 57 57 :+ :+ / / /
%8 <( 5' *
*1<(*1 &211(&725 ;
,1'22581,7
(/(&7521,& )$102725 *
(;3$16,21 1RWH0RWRUJURXQG
* 9$/9( RQO\DSSOLHVWRWKH
60000700023002 LURQVKHOOPRWRU
RXS18SL216
7(036(1625
7(036(1625
6$7
WKHYROWDJHRIWHUPLQDO3'&DQG 8 &203 *
&203
28778%(
2875220
(;+$867
1'&DW$3LVKLJKHUWKDQ9WR 9 :
0$*1(7,& <(*1
SUHYHQWWKHULVNRIHOHFWULFDOVKRFN
5,1*
57 57 57 :+ :+ / / /
%8 <( 5' *
*1<(*1 &211(&725 ;
,1'22581,7
:+%8
/ %1
/ %8
$&B/ $3
/
*1<(*1
*
1
35,17('&,5&8,7%2$5'
;7 <(*1
:$< )$ 2)$1
+($7%
* 3(
/ / 5' 5'
32:(5 0$*1(7,& /
5,1* 97 97 0 *
<(*1 (.9 <(*1
(+
<9 (/(&7521,& )$102725 *
%27720 :$< (;3$16,21 1RWH0RWRUJURXQG
* %21' 9$/9( 9$/9( RQO\DSSOLHVWRWKH
+($7(5 LURQVKHOOPRWRU
600007000230
14 Technical Information
Service Manual
RXS24SL216
7(036(1625
7(036(1625
7(036(1625
:$51,1* 29(5/2$'3527(&725
3OHDVHGRQ
WWRXFKDQ\ 6$7
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH &203
RIWHUPLQDO3'&DQG :+ :+ 8 &203 * <(*1
1'&DW$3LVKLJKHU 9 :
WKDQ9WRSUHYHQWWKH 0$*1(7,&
57 57 57 5,1* / / / *
ULVNRIHOHFWULFVKRFN
%8 <( 5'
*1<(*1 . . .
;
:+ %. %8 <( 5'
,1'22581,7
* 7(50,1$/
%/2&. 0$*1(7,& 8%8 9<( :5'
:+%8 5,1*
1 7B6(1625 29&B&203
%. / %.
&20B,11(5
5'%1
%8 $3
%.%1 %1 / 35,17('&,5&8,7%2$5'
/ %1
$&B/
:+%8 / / %8
1 :$< )$ 2)$1
*1<(*1 +($7B%
* 3(
;7 <(*1 <(*1 5' 5'
* 97 97
/ / 32:(5 0 *
/ <(*1
(+ (.9
0$*1(7,&
5,1* <9
)$102725 *
%27720 (OHFWURQLF
1RWH0RWRUJURXQG
60000700078601 * %$1' :$< ([SDQVLRQ RQO\DSSOLHVWRWKH
+($7(5 9$/9( 9DOYH LURQVKHOOPRWRU
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Technical Information 15
Service Manual
● Top view
1 2 3 4 5 6
No. Name
Neutral wire interface of cold
1 plasma(only for the mode
with this function)
Neutral wire interface of
2
power supply
3 Interface of indoor fan
Interface of health function
4 live wire(only for the mode
with this function)
Interface of up&down swing
7 5
motor
8 6 Interface of PG feedback
7 WIFI
8 Temperature sensor
9
9 Wired controller
10 Interface of diaplay
11 Jumper cap
12 Communication wire
13 Live wire
14 Fuse
14 13 12 11 10
● Bottom view
16 Technical Information
Service Manual
Outdoor Unit
● Top view
1 Interface of compressor
1 2 3 4 5 6 7 8 9 10 11 High pressure protection of
2
system
Low-temperature cooling
3
12 temperature sensor
Overload protection of
4
19 compressor
5 Interface of temperature sensor
6 Electronic expansion valve
Low pressure protection of
13 7
system
14 8 Interface of fan
18 9 Interface of 4-way valve
15 10 Interface of 2-way valve
11 Electric heating belt of chassis
17 12 lectric heating belt of chassis
Communication interface for
13
16 indoor unit and outdoor unit
14 Live wire
15 Earthing wire
16 Neutral wire
Technical Information 17
Service Manual
ON/OFF button
MODE button
+/- button
FAN button
SWING button
SAVE button
X-FAN button
TIMER button
TURBO button
SLEEP button
LIGHT button
Child Lock
Dry mode
Auto mode
Cool mode Set temp
Heat mode
Fan mode
Up & down swing
X-fan
Sleep mode
Set time
18 Technical Information
Service Manual
Technical Information 19
Service Manual
TIMER
The TIMER OFF function is resetted when the CHILD LOCK function is unlocked.
TURBO
When pressing this button u nder cooling or heating mo de, the air conditioner will enter into quick cooling or quick heating
mode. The "TURBO" icon is displayed on the remote controller. Press this button again to exit turbo fu nction and the "TURBO"
icon will disappear on the remote controller.
Press this button to turn o ff the light on the display of the indoor unit. Press this
button again to turn on the light on the display of the indoor unit.
20 Technical Information
Service Manual
2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto button
If press this auto button when turning off the unit, the complete unit will operate at auto mode. Indoor fan operates at auto fan speed
and swing function is turned on. Press this auto button at ON status to turn off the unit.
(3) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(4) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(5) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(6) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is defaulted ON.
Technical Information 21
Service Manual
22 Technical Information
Service Manual
Outdoor Units
1. Input Parameter Compensation and Calibration
(1) Check the ambient temperature compensation function Indoor ambient temperature compensation function.
a. In cooling mode, the indoor ambient temperature participating in computing control = (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature
compensation)
b. In heating mode, the indoor ambient temperature participating in computing control= (Tindoor ambient temperature – ⊿ Theating indoor ambient temperature
compensation)
40Hz, and Tpipe temperature ≥(Texhaust+37.4), the outdoor exhaust temperature thermobulb can be judged not to be connected into place (judging
once when power is on the first time).
2. Basic Functions
(1) Cooling Mode
1. Conditions and processes of cooling operation:
(1) If the compressor is shut down, and [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)] ≤ 32.9ºF , start up the
machine for cooling, the cooling operation will start;
(2) During operations of cooling, if 32ºF ≤ [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)] < 35.6ºF , the cooling
operation will be still running;
(3) During operations of cooling, if 35.6ºF ≤ [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)], the cooling operation
will stop after reaching the temperature point.
2. Temperature setting range
(1) If Toutdoor ambient temperature ≥ [Tlow-temperature cooling temperature], the temperature can be set at: 60.8~86ºF (Cooling at room temperature);
(2) If Toutdoor ambient temperature < [Tlow-temperature cooling temperature], the temperature can be set at: 77~86ºF (Cooling at low temperature), that is, the
minimum setting temperature for outer units judgment is 77ºF .
(2) Dehumidifying Mode
1. Conditions and processes of dehumidifying operations: Same as the cooling mode;
2. The temperature setting range is: 60.8~86ºF;
(3) Air-supplying Mode
1. The compressor, outdoor fans and four-way valves are switched off;
2. The temperature setting range is: 60.8~86ºF.
(4) Heating Mode
1. Conditions and processes of heating operations: (Tindoor ambient temperature is the actual detection temperature of indoor environment
thermo-bulb, Theating indoor ambient temperature compensation is the indoor ambient temperature compensation during heating
operations)
(1) If the compressor is shut down, and [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup] ≤ 32.9ºF , start the machine
to enter into heating operations for heating;
(2) During operations of heating, if 32ºF ≤ [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup] < 35.6ºF , the heating
operation will be still running;
(3) During operations of heating, if 35.6ºF ≤ [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup], the heating operation
will stop after reaching the temperature point.
2. The temperature setting range in this mode is: 60.8~86ºF .
Technical Information 23
Service Manual
3. Special Functions
Defrosting Control
① Conditions for starting defrosting
After the time for defrosting is judged to be satisfied, if the temperature for defrosting is satisfied after detections for continuous 3minutes,
the defrosting operation will start.
② Conditions of finishing defrosting
The defrosting operation can exit when any of the conditions below is satisfied:
③ Toutdoor pipe temperature ≥ (Toutdoor ambient temperature – [Ttemperature 1 of finishing defrosting];
④ The continuous running time of defrosting reaches [tmax. defrosting time].
4. Control Logic
(1) Compressor Control
Start the compressor after starting cooling, heating, dehumidifying operations, and the outer fans start for 5s; When the machine is
shutdown, in safety stops and when switching to air-supplying mode, the compressor will stop immediately. In all modes: once the
compressor starts up, it will not be allowed to stop until having run for the [tmin. compressor running time] (Note: including cases of
shutdown when the temperature point is reached; except the cases requiring stopping the compressor such as fault protection, remote
shutdown, mode switching etc.); In all modes: once the compressor stops, it will be allowed be restart after 3-minute delay (Note: The
indoor units have a function of power memory, the machine can be restarted after remote shutdown and powering up again without
delay).
1. Cooling mode
Start the machine to enter into cooling operation for cooling, the compressor is switched on.
2. Dehumidifying mode
Same as the cooling mode.
3. Air-supplying mode
The compressor is switched off.
4. Heating mode
(1) Start the machine to enter into heating operation for heating, the compressor is switched on.
(2) Defrosting:
a. Defrosting starts: the compressor is shut down, and restarts it after 55-second delay.
b. Defrosting ends: the compressor stops, then starts it after 55-second delay.
(2) Outer Fans Control
Notes:
Only the outer fans run for at least 80s in each air flow speed can the air flow be switched;
After the outer fans run compulsively in high speed for 80s when the machine starts up, control the air flow according to the logic.
After remote shutdown, safety stops, and when the machine stops after reaching the temperature point, as well as after the compressor
stops, extend 1 minute, the outer fans will stop (During the period in the 1 minute, the air flow of outer fans can be changed according to
the outdoor ambient temperature changes); When running with force, the outdoor fans shall run in the highest air flow.
(3) 4-way valve control
1. The 4-way valve control under the modes of Cooling, dehumidification and supplying air: closing;
2. The status of 4-way valve control under the heating mode: getting power;
(1) 4-way valve power control under heating mode
a. Starts the machine under heating mode, the 4-way valve will get power immediately.
(2) 4-way valve power turn-off control under heating mode
a. When you should turn off the power or switch to other mode under heating mode, the power of 4-way valve will be cut after 2 minutes
of the compressor stopped.
b. When all kinds of protection stops, the power of 4-way valve will be cut after delaying 4 minutes.
(3) Defrosting control under heating mode:
a. Defrosting begins: The power of 4-way valve will be cut after 50s of entering into the defrosting
compressor.
b. Defrosting stops: The 4-way valve will get power after 50s of exiting the defrosting compressor.
(4) Evaporator frozen-preventing protection function
At the mode of Cooling, dehumidifying:
Evaporator frozen-preventing protection function is allowed to begin after 6 min of starting the compressor.
24 Technical Information
Service Manual
1. Starting estimation:
After the compressor stopped working for 180s, if Tinner pipe> [Tfrozen-preventing frequency-limited temperature (the temperature of hysteresis is 35.6ºF )],
the machine is only allowed to start for operating, otherwise it should not be started, and should be stopped to treat according to the frozen-
preventing protection: Clear the trouble under the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
[Tfrozen-preventing normal speed frequency-reducing temperature] ≤[Tinner pipe T frozen-preventing frequency-limited temperature] , you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed:
If [Tfrozen-preventing high speed frequency-reducing temperature] ≤[Tinner pipe T frozen-preventing normal speed frequency-reducing temperature], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit;
4. Reducing frequency at high speed:
If [Tfrozen-preventing power turn-off temperature] ≤T inner pipe [Tfrozen-preventing high speed frequency-reducing temperature] you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit;
5. Power turn-off:
If the Tinner pipe <[Tfrozen-preventing power turn-off temperature], then frozen-preventing protect to stop the machine; If T[frozen-preventing frequency-limited temperature]
<Tinner pipe , and the compressor has stopped working for 3 minutes, the whole machine should be allowed to operate.
6. If the frozen-preventing protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should
press the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t
evaporator frozen-preventing protection times zero clearing time , the times of frozen-preventing power turn-off should be cleared to recount.
The mode of stopping the machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed,
mode transferring will not clear it).
(5) Overload protection function
Overload protection function at the mode of Cooling and dehumidifying
1. Starting estimation:
After the compressor stopped working for 180s, if Touter pipe <[TCooling overload frequency-limited temperature] (the temperature of hysteresis is 35.6ºF ), the
machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the overload protection: Clear the
trouble at the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
If [TCooling overload frequency-limited temperature] ≤[Touter pipe T Cooling overload frequency reducing temperature at normal speed], you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed and power turn-off:
If [TCooling overload frequency reducing temperature at high speed] ≤T outer pipe< [TCooling overload power turn-off temperature] , you should adjust the compressor frequency
by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [TCooling overload frequency reducing temperature at normal speed]≤Touter pipe,
then Cooling overload protects machine stopping;
4. Reducing frequency at high speed and stop machine:
If [TCooling overload frequency reducing temperature at high speed]≤Touter pipe [TCooling overload power turn-off temperature], you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [TCooling overload frequency reducing temperature at normal speed] ≤[T outer pipe],
then Cooling overload protects machine stopping;
5. Power turn-off:
If the [TCooling overload power turn-off temperature] ≤Touter pipe, then Cooling overload protects machine stopping; If [Touter pipe]<[TCooling overload frequency-limited
temperature]and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.
6. If the Cooling overload protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should
press the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t
overload protection times zero clearing time , the times of overload protection power turn-off should be cleared to recount. The mode of
stopping the machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring
mode will not clear it).
Overload protection function at the mode of heating
Starting estimation :
After the compressor stopped working for 180s, if T inner pipe T heating overload frequency-limited temperature (the temperature of
hysteresis is 35.6ºF ), the machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the
overload protection:
Clear the trouble at the mode of power turn-off / heating, and the protection times are not counted.
Technical Information 25
Service Manual
1. Frequency limited
If [Theating overload frequency-limited temperature]≤Tinner pipe <[Theating overload frequency reducing temperature at normal speed] , you should limit the frequency raising of
compressor.
2. Reducing frequency at normal speed and stopping machine:
If T[heating overload frequency reducing temperature at normal speed]≤Tinner pipe<[Theating overload frequency reducing temperature at high speed], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if T heating overload frequency reducing
temperature at normal speed ≤T inner pipe, then overload protects machine stopping;
3. Reducing frequency at high speed and power turn-off:
If [Theating overload frequency reducing temperature at high speed]≤Tinner pipe<[Theating overload power turn-off temperature], you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if T heating overload frequency reducing temperature at normal
speed ≤T outer pipe, then Cooling overload protects machine stopping;
4. Power turn-off:
If the [Theating overload power turn-off temperature] ≤Tinner pipe, then overload protects machine stopping; If T inner pipe T heating overload frequency-limited
temperature and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.
5. If the overload protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should press
the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t overload
protection times zero clearing time , the times of overload protection power turn-off should be cleared to recount. The mode of stopping the
machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring mode will not clear
it). Protective function for discharge temperature of compressor
1. Starting estimation:
After the compressor stopped working for 180s, if TDischarge <TDischarge limited temperature (the temperature of hysteresis is 35.6ºF ), the machine is
allowed to start, otherwise it should not be started, and should be stopped to treat according to the discharge temperature:
The machine should be stopped or transferred to supply air, the trouble should be cleared immediately, and the protection times are not
counted.
2. Frequency limited
If [TLimited frequency temperature during discharging] ≤TDischarge<[Tfrequency reducing temperature at normal speed during discharging] , you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed and stopping machine:
If [Tfrequency reducing temperature at normal speed during discharging] ≤TDischarge<[Tfrequency reducing temperature at high speed during discharging], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [Tfrequency reducing temperature at normal speed during discharging]
≤TDischarge, you should discharge to protect machine stopping;
4. Reducing frequency at high speed and power turn-off:
If [Tfrequency reducing temperature at high speed during discharging] ≤TDischarge <[TStop temperature during discharging], you should adjust
the compressor frequency by reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [Tfrequency reducing temperature at normal
speed during discharging] ≤TDischarge, you should discharge to protect machine stopping;
5. Power turn-off:
If the [TPower turn-off temperature during discharging] ≤TDischarge, you should discharge to protect machine stopping; If [TDischarge]<[TLimited frequency temperature during
discharging] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.
6. If the discharging temperature protection of compressor continuously occurs for six times, it should not be resumed automatically, and you
should press the ON/OFF button to resume. During the process of running, if the running time of compressor exceeds the t Protection times
clearing of discharge , the discharge protection is cleared to recount. Stopped or transferred to supply air mode will clear the trouble times
immediately (if the trouble can not be resumed, mode transferring also will not clear it).
7. Frequency limited
If [ILimited frequency when overcurrent] ≤IAC Electric current <[I frequency reducing when overcurrent], you should limit the frequency raising of compressor.
8. Reducing frequency:
If [IFrequency reducing when overcurrent] ≤[IAC Electric current I Power turn-off when overcurrent] , you should reduce the compressor frequency till the lower limit or exit
the frequency reducing condition;
9. Power turn-off:
If [IPower turn-off machine when overcurrent] ≤[IAC Electric current] , you should carry out the overcurrent stopping protection; If I AC Electric current<[T Limited frequency when
overcurrent] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.
10. If the overcurrent protection continuously occurs for six times, it should not be resumed automatically, and you should press the ON/OFF
button to resume. During the process of running, if the running time of compressor exceeds the [t Protection times clearing of over current] , the discharge
protection is cleared to recount.
26 Technical Information
Service Manual
4. If the overcurrent protection of compressor phase current continuously occurs for six times, it should not be resumed automatically, and
you should press the ON/OFF button to resume. During the process of running, if the running time of compressor exceeds the [t Clearing Time of
Compressor Phase Current Times] , the overcurrent protection is cleared to recount.
Technical Information 27
Service Manual
protection for four-way valve 3 min; and if it still cant run when the reversion abnormity protection for four-way valve happens to stop working
for 3 times in succession, it is available if presses ON/OFF.
Attention: the protection shall be shielded during the testing mode and defrosting process, and it shall be cleared out the failure and its times
immediately when turning off or delivering wind / cooling / dehumidifying mode conversed (the inverted mode dont clear out the failure when it
cant recover to operate).
(16) PFC Protection
1. After start up the PFC, it should detect the protection signal of PFC immediately; under the condition of PFC protection, it should turn off the
PFC and compressor at one time;
2. It shows the failure is cleared out if PFC Protection stopped working 3 min and recovers to run automatically;
3. If it still cant run when it occurs PFC protection for 3 times in succession, it is available if presses ON/OFF; and clear the PFC Protection
times when start up PFC for 10min.
(17) Failure Detection for Sensor
1. Outdoor Ambient Sensor: detect the failure of sensor at all times.
2. Outdoor Tube Sensor: You should not detect the failure of outdoor tube sensor within 10 minutes heating
operation compressor except the defrosting, and you could detect it at other time.
3. Outdoor Exhaust Sensor:
(a) The compressor only detect the sensor failure after it start up 3 min in normal mode;
(b) It should detect the exhaust sensor failure immediately in the testing mode.
4. Module Temperature Sensor:
(a) Short-Circuit Detection: the compressor should be detected immediately when the module temperature
sensor occurs short-circuits;
(b) Open-Circuit Detection: the compressor should be detected on open-circuit when it runs 3min (it neednt 30s
avoiding the module over-heated).
(c) Detect the sensor failure at all times in the testing mode.
5. Disposal for Sensor Protection
(1) When the short-circuit of sensor is detected within 30s, It is regarded as the temperature of sensor over-high (or infinitely high), and now
according to the over-high sensor, the machine should carry out the corresponding protection to stop working, and show the corresponding
temperature shutdown protection and sensor failure at the same time (for example: the compressor stops immediately when the outdoor tube
sensor short-circuit, and the machine shall show the overload protection and outdoor tube sensor failure).
(2) When the open-circuit of sensor is detected within 30s, The protection shall be stopped and it shall show the corresponding sensor failure.
28 Technical Information
Service Manual
Technical Information 29
Service Manual
Warnings
1. When installing or relocating the unit, be sure to keep the
refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant
circuit will cause system pressure rise or compressor rupture,
resulting in injury.
2.When installing or moving this unit, do not charge the
refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action,
mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating
or repairing the unit, be sure that the unit is running in
cooling mode.Then, fully close the valve at high pressure
side (liquid valve).About 30-40 seconds later, fully close the
valve at low pressure side (gas valve), immediately stop
the unit and disconnect power. Please note that the time for
refrigerant recovery should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in
and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and
gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and
connection pipe is not yet connected, air will be sucked in and
cause pressure rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is
securely connected before the compressor starts running.
If compressor starts running when stop valve is open and
connection pipe is not yet connected, air will be sucked in and
cause pressure rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be
leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and
other accidents.
7.Do not use extension cords for electrical connections. If
the electric wire is not long enough, please contact a local
service center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections
between the indoor and outdoor units. Firmly clamp the
wires so that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections
and insecure wire terminals may cause electric shock or fire.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Installation Dimension Diagram
At least 8
8
str
At least 72
t 11
ob
eas
he
At l
ot
et
ac
Sp
n
tio
At least 24
tr uc
o bs
he
tot
Sp ce
ac Sp
a t 12
et eas
ot
he At l
wa
At l ll
eas
t 12
Drainage pipe
o
u cti
str
ob 78 Sp
o the le ast ac
et
et At ot
ac he
Sp At l
eas ob
t 24 str
uc
tio
n
unit:inch
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Note:
Left Rear left (1) Add insulating pipe in the indoor drain hose in order to
Rear right
prevent condensation.
Fig.3 Right (2) The plastic expansion particles are not provided.
(As show in Fig.10)
Cut off
Insulating pipe
the hole Fig.10
Fig.4
(2) Fix the wire crossing board on connection wire sleeve at Indoor and
the bottom case; let the connection wire sleeve go through the outdoor power cord
Indoor unit Gas
wire crossing hole at the back of indoor unit, and then pull it out pipe
from the front.(As show in Fig.12)
Liquid
Fig.14 Band pipe
Drain hose
(3) Remove the wire clip; connect the power connection wire Fig.15
to the wiring terminal; tighten the screw and then fix the power Indoor power cord
connection wire with wire clip.(As show in Fig.13)
Note:
(1) The power cord and control wire cant be crossed or
winding.
N(1) 2 3 (2) The drain hose should be bound at the bottom.
white black red green
(blue) (brown) (yellow- 9. Hang the Indoor Unit
green)
(1) Put the bound pipes in the wall pipe and then make them
pass through the wall hole.
Outdoor unit connection (2) Hang the indoor unit on the wall-mounting frame.
(3) Stuff the gap between pipes and wall hole with sealing gum.
Note: the wiring board is for reference only,please refer to the (4) Fix the wall pipe.(As show in Fig.16)
Note: the wiring board is for reference only,please refer to the actual one.
actual one. (5) Check if the indoor unit is installed firmly and closed to the
wall.(As show in Fig.17)
Fig.13
(4) Put wiring cover back and then tighten the screw.
(5) Close the panel. Indoor Outdoor
Wall pipe Fig.17
Note: Sealing gum
(1) All wires of indoor unit and outdoor unit should be Upper hook
connected by a professional.
(2) If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be Fig.16
Lower hook of
reachable after finishing installation. wall-mounting frame
(4) For the air conditioner without plug, an air switch must be
installed in the line. The air switch should be all-pole parting Note:
and the contact parting distance should be more than 3mm. Do not bend the drain hose too excessively in order to prevent
blocking.
8.6 Installation of Outdoor Unit Refer to the following table for wrench moment of force:
1. Fix the Support of Outdoor Unit(Select it according to Hex nut diameter(inch) Tightening torque(ft·Ibf)
the actual installation situation) Φ1/4 11.10~14.75
(1) Select installation location according to the house structure. Φ3/8 22.12~29.50
(2) Fix the support of outdoor unit on the selected location with Φ1/2 33.19~40.56
expansion screws. Φ5/8 44.24~47.94
Φ3/4 51.32~55.31
Note:
(1) Take sufficient protective measures when installing the 5. Connect Outdoor Electric Wire
outdoor unit. (1) Let the connection wire sleeve go through the two holes of
(2) Make sure the support can withstand at least four times the baffle; tighten the connection joint of sleeve and baffle; remove
unit weight. the wire clip; connect the power connection wire and power
(3) The outdoor unit should be installed at least 1 3/16 inch cord to the wiring terminal according to the color; fix them with
above the floor in order to install drain joint.(As show in Fig.18) screws.(As show in Fig.23)
(4) For the unit with cooling capacity of 2300W~5000W, 6 Handle
expansion screws are needed; for the unit with cooling capacity
of 6000W~8000W, 8 expansion screws are needed; for the
N(1) 2 3 L1 L2 G
unit with cooling capacity of 10000W~16000W, 10 expansion
screws are needed. green white red
(yellow- (blue) black (brown)
black white green
(brown) (blue) (yellow-
green) green)
L1 L2
Drain vent Chassis Note: the wiring board is for reference only,please refer to the
At least 1 3/16 inch above the floor Outdoor drain joint
Drain hose actual one.
Fig.23
Fig.18 Fig.19
2. Install Drain Joint(only for cooling and heating unit)
(2) Fix the power connection wire and power cord with wire clip.
(1) Connect the outdoor drain joint into the hole on the chassis.
(3) Fix the stopper on handle with screw.
(2) Connect the drain hose into the drain vent.
(As show in Fig.19) Note:
(1) After tightening the screw, pull the power cord slightly to
3. Fix Outdoor Unit
check if it is firm.
(1) Place the outdoor unit on the support.
(2) Never cut the power connection wire to prolong or shorten
(2) Fix the foot holes of outdoor unit with bolts.
the distance.
(As show in Fig.20)
Foot holes 6. Neaten the Pipes
Handle (1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. semidiameter of bending the pipe is 3
15/16inch.
Valve cover (2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
Foot holes
in order to prevent rain from getting into the room.(As show in
Fig.20 Fig.21 Fig.24)
4. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle and valve cover of The drain hos
outdoor unit and then remove the handle and valve cover.(As can't raise
upwards
show in Fig.21)
(2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe.(As show in Fig.22) Wall
2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.
1 Swing function
2 Air exchange function (this function is yet unavailable for this unit)
3 Sleep function (Only sleep 1)
4 Each kind of running mode of indoor unit (auto mode)
5 Cooling mode
6 Dry mode
7 Fan mode
8 Heating mode
9 Defrosting function for the outdoor unit
10 Gate-control function (this function is yet unavailable for this unit)
11 Lock function
Shield functions (Button operation, temperature setting, On/Off operation,Mode setting are
12 SHIELD
disabled by the remote monitoring system.)
13 TURBO Turbo function state
Memory function (The indoor unit resumes the original setting state after power failure and
14 MEMORY
then power recovery)
15 It blinks under on state of the unit without operation of any button
16 SAVE Energy-saving function
17 Ambient/setting temperature value
18 E-HEATER Electric auxiliary heating function(this function is yet unavailable for this unit)
19 BLOW Blow function
20 Timing value
21 QUIET Quiet function (two types: quiet and auto quiet)(this function is yet unavailable for this unit).
2 Buttons
2.1 Layout of Buttons
3 Operation Instructions
3.1 On/Off
Press On/Off to turn on the unit and turn it off by another press.
Note: The state shown in Fig.3.1.1 indicates the “Off” state of the unit after power on. The state shown in Fig.3.1.2 indicates the “On”
state of the unit after power on.
3.3 Temperature Setting
Press ▲or ▼ to increase/decrease the preset temperature. If pressing either of them continuously, the temperature will be increased or
decreased by 1°C every 0.5s,as shown in Fig.3.3.1.
In the Cooling, Dry, Fan or Heating mode, the temperature setting range is 16~30°C(61~86°F).
In the Auto mode, the setting temperature is unadjustable.
Fig.3.3.1 Fig.3.4.1
3.4 Fan Setting
Under the “On” state of the unit, press Fan and then fan speed of the indoor unit will change circularly as shown in Fig.3.4.1.
Low Middle High
Turn on the unit,without Timer Press Timer repeatedly unitll go Press ▲/▼ to adjust the time
activated to the setting status
Press Timer to cancel this setting Press Enter/Cancel to confirm this setting
Fig.3.5.1 Timer off Setting under the “On” State of the Unit
Timer on setting under the “Off” state of the unit is shown as Fig.3.5.2.
Turn off the unit,without Timer Press Timer repeatedly unitll go Press ▲/▼ to adjust the time
activated to the setting status
Press Timer to cancel this setting Press Enter/Cancel to confirm this setting
Fig.3.5.2 Timer on Setting under the “Off” State of the Unit
Timer range: 0.5-24hr. Every press of ▲or ▼ will make the set time increased or decreased by 0.5hr. If either of them is pressed
continuously, the set time will increase/ decrease by 0.5hr every 0.5s.
Turn off the unit,without Swing Press Function repeatedly unitll Press Enter/Cancel to activated the Swing
function activated go to the Swing setting status function
Notes:
(1)Sleep, Turbo or Blow setting is the same as the Swing setting.
(2)After the setting has been done, it has to press the key “Enter/Cancel” to back to the setting status or quit automatically five seconds
later.
Turn off the unit,without Sleep Press Function repeatedly unitll Press Enter/Cancel to activated the Sleep
function activated go to the Sleep setting status function
Turn off the unit,without Turbo Press Function repeatedly unitll Press Enter/Cancel to activated the Turbo
function activated go to the Turbo setting status function
Turn off the unit,without E-heater Press Function repeatedly unitll Press Enter/Cancel to activated the E-heater
function activated go to the E-heater setting status function
Turn off the unit,without Blow Press Function repeatedly unitll Press Enter/Cancel to activated the Blow
function activated go to the Blow setting status function
Notes:
(1)When the Blow function is activated, if turning off the unit by pressing On/Off or by the remote controller, the indoor fan will run at the
low fan speed for 2 min, with “BLOW” displayed on the LCD. While, if the Blow function is deactivated, the indoor fan will be turned off
directly.
(2)Blow function is unavailable in the Fan or Heating mode.
PVC Pipe
1 2 3 4 5
No. 1 2 3 4 5
Socket box embedded Soleplate of the Wired Front Panel of the
Name Screw M4X25 Screw ST 2.9X6
in the wall Controller Wired Controller
1 2 3 4
6 5
7
Fig.4.2
8 9 10
Fig.4.2
Fig.4.2 shows the installation steps of the wired controller, but there are some issues that need your attention.
(1) Prior to the installation, please firstly cut off the power supply of the wire buried in the installation hole, that is, no operation is allowed
with electricity during the whole installation.
(2) Pull out the four-core twisted pair line from the installation holes and then let it go through the rectangular hole behind the soleplate of
the wired controller.
(3) Stick the soleplate of the wire controller to the wall over the installation hole and then fix it with screws M4X25.
(4) Insert the four-core twisted pair line into the slot of the wired controller and then buckle the front panel and the soleplate of the wired
controller together.
(5) Finally, fix the front panel and the soleplate of the wired controller tightly by screws ST2.9X6.
CAUTION!
Please pay special attention to the followings during the connection to avoid the malfunction of the air conditioning unit due to
electromagnetic interference.
(1) Separate the signal and communication lines of the wired controller from the power cord and connection lines between the indoor and
outdoor unit, with a minimum interval of 20cm, otherwise the communication of the unit will probably work abnormally.
(2) If the air conditioning unit is installed where is vulnerable to electromagnetic interference,then the signal and communication lines of
the wired controller must be the shielding twisted pair lines.
5 Errors Display
If there is an error occurring during the operation of the system, the error code will be displayed on the LCD, as show in Fig.5.1. If multi
errors occur at the same time, their codes will be displayed circularly.
Note: In event of any error, please turn off the unit and contact the professionally skilled personnel.
Fig.5.1
9. Maintenance
9.1 Precautions before Maintenance
There are high-capacity electrolytic capacitors on the outdoor mainboard. Thus, even the power is cut off, there is high voltage inside
the capacitors and it needs more than 20min to reduce the voltage to safety value. Touching the electrolytic capacitor within 20min after
cutting the power will cause electric shock. If maintenance is needed, follow the steps below to discharge electricity of electrolytic ca-
pacitor after power off.
(1) Open the top cover of outdoor unit and then remove the cover of electric box.
outdoor mainboard
(2) As shown in the fig below, connect the plug of discharge resistance (about 100ohm, 20W) (if there is no discharge resistance, you
can use the plug of soldering iron) to point A and B of electrolytic capacitor. There will be sparks when touching them. Press them forc-
ibly for 30s to discharge electricity of electrolytic capacitor.
(3) After finish discharging electricity, measure the voltage between point A and B with universal meter to make sure if electricity dis-
charging is completed, in order to prevent electric shock. If the voltage between the two points is below 20V, you can perform mainte-
nance safely.
Malfunction
of detecting JF
13
plate(WIFI )
Complete unit
Off 3s
current
U5 and blink
detection
13 times
malfunction
Off 3s
Defrosting will occur in
and blink
heating mode.Compressor
once
will operate while indoor It’s the normal state
(during
fan will stop.
blinking,
ON 10s
and Off
05s)
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
Turn unit on
Yes to check whether the
No malfunction is
eliminated.
Turn unit on
No No to check whether the Yes
malfunction is
eliminated.
Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.
Yes
Yes
Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.
Yes
Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the same model.
of the motor interface.
Yes
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
4. Communication malfunction E6
Start
yes
no
yes
no
Replace
Communication cord is damaged? yes communication Malfunction eliminated? yes
cord
no
no
Replace IDU's
main board
yes
Replace ODU's
Malfunction eliminated? no
main board.
yes
End
Start
Yes
Is malfunction
eliminated
The end
●Outdoor unit:
"Test point NO." Test point Related elements Test value under normal condition
Test 1 Between A and C Neutral wire ,live wire 160V-265V
Test 2 Between B and C Neutral wire ,live wire 160V-265V
Test 3 Between D and E Electrolytic capacitor of DC bas bar DC 180V-380V
Test 4 Between F and G Electrolytic capacitor of switch power DC 180V-380V
Test 5 Both ends of diode D59 D59(IPM module +15V) DC 14.5V-15.5
Both ends of electrolytic
Test 6 C47(+12V power) DC 12V-13V
capacitor C47
Both ends of electrolytic
Test 7 C60(+5V power) DC 5V
capacitor C60
Both ends of electrolytic
Test 8 C73(+3.3V power) DC 3.3V
capacitor C73
Test 9 Between S and T Communication circular current DC 56V
C50 to N terminal (ground) (signal receiving terminal of
Test 10 Between point N and GND Jumping between 0V and 3.3V
outdoor unit)
Test 11 U7 Between 1 and 2 at leading foot of U7 Jumping between 0V and 3.3V
R77 to N terminal (ground) (signal receiving terminal of
Test 12 Between point M and GND Jumping between 0V and 3.3V
outdoor unit)
Test 13 U8 Between 3 and 4 at leading foot of U8 Jumping between 0V and 3.3V
1.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)
● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter;
● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged?
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
End
2.IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (AP1 below is control board
of outdoor unit)
● If control board AP1 and compressor COMP is well connected? If they are loosened? If the connection sequence is correct?
● Is voltage input in the normal range (Test the voltage between L, N of wiring board XT by DC voltage meter)?
● If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● If the work load of unit is heavy? If radiating of unit is well?
● If the refrigerant charging is appropriate?
Energize and
switch on
Use ohmmeter to
measure the resistance
between the three If the Replace the
terminals on compressor resistance is compressor
COMP, and compare the normal? N
measurements with the COMP
compressor resistance on
Service Manual.
N
Use ohmmeter to
measure the resistance Resistance higher
between the two than 500MΩ?
terminals of compressor
COMP and copper tube.
Y
Replace the
control panel
AP1
END
3.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)
Anti-high temperature,
overload protection
Improve the
If the radiating of outdoor Y radiating
and indoor unit is well? environment of
unit
Replace fan
Replace capacitor C1
control board
AP1
Replace
outdoor fan
End
4.Diagnosis for failure start up malfunction (AP1 below is control board of outdoor unit)
Charge the
refrigerant according
to service manual
If malfunction is
removed?
Replace the
compressor
End
5. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)
Remove
malfunction?
End
N Y
Replace
compressor
End
6.Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)
● If the electron expansion valve is connected well? Is the expansion valve damaged?
● If the refrigerant is leakage?
● If the overload protector is damaged?
Connect wire
If the wiring terminal FA of electron N well with wiring
N expansion is well connected?
diagram
Y
Remove
malfunction?
Remove
Y
malfunction?
Replace
control board
AP1
End
● Check if the connection wire and the built-in wiring of indoor and outdoor unit is connected well and no damaged;
● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is dam-
aged
Start
Check built-
in wiring of Connection
Y
indoor and N
correct?
outdoor unit
N
Problem of
Replace outdoor
communication Y
mainboard AP11
circuit
N If the
malfunction is
removed?
N
Replace indoor
board
Y End Y
Start
Test voltage
value with Test
10 position in
diagram with
voltage meter
Number jumping
N
Y
Test voltage
value with Test
13 position in
diagram with
voltage meter
Number jumping N
Y
Outdoor unit
End
Test voltage malfunction
value with Test
11 position in
diagram with
voltage meter
Number jumping N
Y
Test voltage
value with Test
12 position in
diagram with
voltage meter
Number jumping
The circuit of
outdoor unit
communication
is normal
35 36 37
15
16
14
38 39
13 17
18
12
19
11
10
20
9
8
7
6
5 21
22
23
4
3 24
25
2 26
27
10 28
1 29
30
31
33 32
34
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. FTKS18SL216 FTXS18SL216 Qty
Product Code CB459N04600_L75033 CB459N04200_L84775
1 Front Panel 200003000015S 200003000015S 1
2 Filter Sub-Assy 11122089 11122089 2
3 Decoration board(left and right) 20192662 20192662 1
4 Front Case 2002248401 2002248401 1
5 Guide Louver 1051276501 1051276501 1
6 Axile Bush 10542036 10542036 2
7 Air Louver(Manual) 10512732 10512732 3
8 Helicoid Tongue 26112512 26112512 1
9 Left Axile Bush 10512037 10512037 1
10 Display Board 300001000036 300001000036 1
11 Rear Case assy 22202571 22202571 1
12 Rubber Plug (Water Tray) 76712012 76712012 1
13 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
14 O-Gasket of Cross Fan Bearing 76512203 76512203 1
15 Evaporator Support 24212177 24212177 1
16 Evaporator Assy 011001000207 011001000207 1
17 Cross Flow Fan 10352060 10352060 1
18 Fan Motor 1501214503 1501214503 1
19 Motor Press Plate 26112511 26112511 1
20 Wall Mounting Frame 01362026 01362026 1
21 Connecting pipe clamp 2611218801 2611218801 1
22 Crank 73012005 73012005 1
23 Stepping Motor 1521240212 1521240212 1
24 Drainage Hose 05230014 05230014 1
25 Electric Box Assy 100002004017_L75033 100002003962_L84775 1
26 Lower Shield of Electric Box 01592139 01592139 1
27 Electric Box 2011221102 2011221102 1
28 Jumper 4202021919 4202021919 1
29 Main Board 300002000313 300002000312 1
30 Terminal Board 42011233 42011233 1
31 Electric Box Cover 2011220901 2011220901 1
32 Shield Cover of Electric Box 01592139 01592139 1
33 Screw Cover 2425201726 2425201726 3
34 Electric Box Cover2 2011221001 2011221001 1
35 Power Cord / / /
36 Connecting Cable / / /
37 Remote Controller 30510537 30510537 1
38 Cold Plasma Generator / / /
39 Detecting plate(WIFI) 30070077 30070077 1
14 15 16
35 36 37 38 39
13
12
11 17
10
9
8
7 18
6
5 19
4 20
3
2
1 8
21
22
23
24
25
26
27
28 34
33
29
32
31
30
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. FTKS24SL216 FTXS24SL216 Qty
Product Code CB459N04700 CB459N04300_L84775
1 Front Panel 200003000014 200003000014 1
2 Filter Sub-Assy 11012007 11012007 2
3 Screw Cover 2425245301 2425245301 3
4 Front Case 2002248603 2002248603 1
5 Air Louver(Manual) 10512737 10512737 3
6 Helicoid Tongue 26112513 26112513 1
7 Left Axile Bush 10512037 10512037 1
8 Display Board 300001000036 300001000036 1
9 Rear Case assy 22202570 22202570 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 011001000095 011001000095 1
16 Cold Plasma Generator / / /
17 Wall Mounting Frame 01252229 01252229 1
18 Motor Press Plate 26112515 26112515 1
19 Fan Motor 1501214501 1501214501 1
20 Connecting pipe clamp 26112514 26112514 1
21 Drainage Hose 0523001405 0523001405 1
22 Stepping Motor 1521240212 1521240212 1
23 Crank 73012005 73012005 1
24 Guide Louver 1051232001 1051232001 1
25 Axile Bush 10542036 10542036 2
26 Electric Box 2011221102 2011221102 1
27 Terminal Board 42011233 42011233 1
28 Electric Box Cover2 2011221001 2011221001 1
29 Main Board 300002000314 300002000316 1
30 Shield Cover of Electric Box 01592139 01592139 1
31 Electric Box Cover 2011220901 2011220901 1
32 Jumper 4202021924 4202021924 1
33 Lower Shield of Electric Box 01592139 01592139 1
34 Electric Box Assy 100002003988_L75033 100002003961_L84775 1
35 Power Cord / / /
36 Connecting Cable / / /
37 Temperature Sensor 3900031302 3900031302 1
38 Remote Controller 30510537 30510537 1
39 Detecting plate(WIFI) 30070077 30070077 1
31 25 24 23 22 21 20 19 18
30
29
28 32 17
27
16
26
15
14
13
12
11
1 2 3 4 5 6 7 8 9 10
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. RKS18SL216 RKS24SL216 Qty
Product Code CB425W07500_L75033 CB425W07600_L75033
1 Front Grill 01473049 01473049 1
2 Cabinet 01433047P 01433047P 1
3 Axial Flow Fan 10335008 10335008 1
4 Fan Motor 1501506402 1501506402 1
5 Chassis Sub-assy 01700000094P 01700000161P01 1
6 Clapboard Assy 01233153 01702100008 1
7 Compressor and Fittings 00105249G 00105249G 1
8 Inhalation Tube Sub-assy 030010000499 030010000130 1
9 Discharge Tube Sub-assy 030013000571 030013000417 1
10 Valve Support Assy 01715010P 01705046 1
11 Cut off Valve Assy 07130239 07133844 1
12 Cut off Valve Sub-Assy 07133204 03005700125 1
13 Valve Cover 22245002 22245002 1
14 Right Side Plate 0130509403P 0130329208 1
15 Retaining Plate 02115006P 02115006P 1
16 Handle Assy 02113109 02113109 1
17 Wire Clamp 71010003 71010003 1
18 Temperature Sensor 3900030901 3900030902 1
19 Rear Grill 01473043 01475020 1
20 Condenser Assy 011002000479 011002000058 1
21 Coping 012049000007P 012049000007P 1
22 Motor Support Sub-Assy 01705043 01705067 1
23 Condenser Support Plate 0117313201 01795031 1
24 Left Side Plate 01305093P 01305093P 1
25 Handle 26233053 26233053 1
26 Electric Box Assy 100002001527 100002001405 1
27 Terminal Board 42010255 42010255 1
28 Electric Box 20113027 20113027 1
29 Main Board 300027000298 300027000302 1
30 Radiator 49013060 49013060 1
31 Insulated Board (Cover of Electric Box) 20113003 20113003 1
32 Electronic Expansion Valve assy 030174000064 030174000008 1
Above data is subject to change without notice.
31
The component picture is only for reference; please refer to the actual product.
31
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. RXS18SL216 RXS24SL216 Qty
Product Code CB425W07400_L84775 CB425W07700_L84775
1 Front Grill 01473049 01473049 1
2 Cabinet 01433047P 01433047P 1
3 Axial Flow Fan 10335008 10335008 1
4 Fan Motor 1501506402 1501506402 1
5 Chassis Sub-assy 01700000093P 01700000161P 1
6 Drainage hole Cap 06813401 06813401 3
7 Clapboard Assy 01233153 01235081 1
8 4-Way Valve Assy 030152000291 030152000073 1
9 Compressor and Fittings 00105249G 00105249G 1
10 Valve Support Assy 01715010P 01705046 1
11 Cut off Valve 07130239 07133844 1
12 Cut off Valve Sub-Assy 07133204 07133843 1
13 Right Side Plate 0130509403P 0130509002P 1
14 Valve Cover 22245002 22245002 1
15 Retaining Plate 02115006P 02115006P 1
16 Handle Assy 02113109 02113109 1
17 Valve Support Block / 26115007 1
18 Temperature Sensor 3900030901 3900030902 1
19 Rear Grill 01473043 01475020 1
20 Condenser Assy 011002000513 011002000244 1
21 Coping 012049000007P 012049000007P 1
22 Motor Support Sub-Assy 01703154 01705067 1
23 Condenser Support Plate 01173127 01795031 1
24 Left Side Plate 01305093P 01305093P 1
25 Handle 26233053 26233053 1
26 Electric Box Assy 100002001525 100002001406 1
27 Terminal Board 42010255 42010255 1
28 Electric Box 20113027 20113027 1
29 Main Board 300027000297 300027000301 1
30 Radiator 49013076/49013060 49013076/49013060 1
31 Electronic Expansion Valve assy 030026000208 030174000041 1
1. Remove filter as s y
Front panel
Detecting plate
(WIFI)
Indoor tube
Cut off the wire binder and pull out the temperature s ensor
indoor tube temperature sensor.
Screw off one grounding screw.
Main
Remove the wiring terminals of motor and
stepping motor. board
Remove the electric box assy. G rounding
Screw off the screws that are locking each s c rew Wi ring
lead wire. terminal
of motor
Wire binder
Wiring
terminal
of stepping
S crew motor
Wire clip
G roove
R ear case ass y
Steps Procedure
a Remove the screw connecting the big handle and big handle
right side plate, and then remove the big handle.
Remove the screw connecting the valve cover and
right side plate, and then remove the valve cover.
valve cover
grille
Steps Procedure
outer case
Steps Procedure
4. Remove axial flow blade
motor support
fan motor
electric box
Steps Procedure
6. Remove the soundproof sponge
soundproof sponge
isolation plate
Unsolder the welding joints connecting the 4-way 4-way valve assy
valve assy with capillary sub-assy, compressor and
condenser; remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.
Steps Procedure
9. Remove compressor
support
a Remove the screws connecting the support
(condenser) and condenser assy,and then remove
the support(condenser).
condenser
sub-assy
b Remove the 2 screws fixing the condenser and
chassis, and then lift the condenser upwards to
remove it.
chassis subassy
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(inch) Gas pipe(inch) Cooling only(oz/ft.) Cooling and heating(oz/ft.)
Ф1/4 Ф3/8or Ф1/2 0.53 0.71
Ф1/4 or Ф3/8 Ф5/8 or Ф3/4 0.53 1.76
Ф1/2 Ф3/4 or Ф7/8 1.06 4.23
Ф5/8 Ф1 or Ф1 1/4 2.12 4.23
Ф3/4 / 8.82 8.82
Ф7/8 / 12.35 12.35
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)