PMWSCWDC 2
PMWSCWDC 2
PMWSCWDC 2
Table of Contents
Introduction..............................................................3 Refrigerant Recovery Units ................................... 40
Customer Benefits Summary....................................5 Refrigerant Monitors ............................................. 42
Heat Recovery Models ...........................................12 Unit Selection ........................................................ 44
Control Features.....................................................15 Application Considerations ................................... 46
Building Automation Systems................................20 Chiller Identification.............................................. 57
Unit Design Features..............................................22 Physical Data and Weights .................................... 58
Options and Accessories ........................................32 Dimensions ............................................................ 60
Motor Controllers...................................................34 Specifications......................................................... 73
Cover pictures: Upper unit: Model WSC 087, 500 ton single compressor chiller with factory-mounted starter
Lower unit: Model WDC 126, 2000 ton, dual compressor chiller
Document: PM WSCWDC-2
Revision: July 2003
Replaces: PM WSCWDC-1
There is an excellent reason for naming McQuay’s centrifugal chiller products as “THE
DISTINCTION SERIES”. Our chillers offer customers an unbeatable combination of
performance, reliability, unique construction features, a long-term refrigerant, and
advanced control technology, all adding up to a superior value. After reviewing our
features and benefits, choose the superior value of McQuay centrifugal chillers for your
next project.
“THE DISTINCTION SERIES”.
McQuay Offers the Widest Choice of ARI Certified, Ozone Safe Centrifugal Chillers
TONS 0 500 1000 1500 2000 2500
NOTE: The upper capacity limit for ARI certification on 60 Hz service is 2,000 tons, on 50 Hz service, the range is
703kW to 3516 kW. McQuay dual compressor chillers with or without VFD are available up to 2,500 tons.
Distributed Control
Each chiller has a microprocessor controller for unit function plus a separate microprocessor for
each compressor. Should the operator interface panel and/or the unit controller be unavailable,
the compressor controller(s) will maintain chiller operation, greatly increasing unit reliability.
Sustainable Performance
Although frequently overlooked, an important point to consider when selecting a chiller is the
sustainability of the purchased performance. All McQuay centrifugal chillers are positive
pressure design, using R-134a refrigerant (the first manufacturer to do so) and the chiller
performance is sustainable for the life of the unit. On the other hand, chillers using R-123, with
negative pressure designs, will loose capacity as air and moisture seep into the refrigeration
system. As the volume of air and moisture increases, the performance penalty increases. For
example, if a negative pressure design chiller is purchased at 0.58 kW/ton with the assumption of
100% refrigerant in the unit, the performance, with a 3% penalty for air and moisture
contamination, will deteriorate to 0.60 kW/ton. The owner will not be receiving the purchased
efficiency. With McQuay’s positive pressure design, there is no penalty for non-condensables
entering the unit.
R-134a Refrigerant
All McQuay centrifugal chillers use R-134a instead of R-123 refrigerant, which is still being
used by a few manufacturers. R-134a offers the following distinct customer benefits.
Positive Pressure Design
R-134a chillers operate with the entire system above atmospheric pressure at all times. In the
event of a small leak, refrigerant escapes from the chiller to the atmosphere, which allows easy
detection and repair. With R-123, air leaks into the system, making leak detection and repair a
difficult task.
No Purge Unit
Even with the best and newest purge units, some refrigerant will be discharged to the
atmosphere. Purge units, with their compressor, tanks and piping can be high maintenance
components.
No Annual Lubricant Maintenance
Annual oil maintenance is required with low-pressure designs, increasing owning cost. When air
and moisture seep into a negative pressure machine, the acid and corrosion that can form must be
removed periodically. McQuay’s positive pressure design does not require this maintenance.
Under normal operation, the oil charge and filter are good for the life of the unit!
Unmatched Unloading
McQuay’s Distinction Series chillers offer unloading to 10% of full load for a WSC single
compressor chiller and 5% for a WDC dual compressor unit, without using inefficient hot gas
bypass. This unloading capability, unique in the industry, provides improved stability of the
chilled water temperature and less harmful cycling of compressors in installations subject to
operation at low cooling loads. There are significant reasons for this beneficial operating
characteristic, including.......
Quiet Operation
McQuay chillers have two unique features to limit sound generation. One is the unique liquid
injection system and the other is that McQuay chillers get quieter as they unload.
Liquid Injection
A small amount of liquid refrigerant is taken from
the condenser and injected into the compressor
discharge area. The liquid droplets absorb sound
energy and reduce the compressor’s overall sound
level. The droplets evaporate and reduce discharge
superheat.
Lubricant reservoir
McQuay Startup
All McQuay centrifugal chillers are commissioned by McQuayService personnel, or by
authorized McQuay startup technicians. This procedure helps assure that proper starting and
checkout procedures are employed and helps in a speedy commissioning process.
AUXILIARY
HEATER
OPEN TC
CIRCUIT RECOVERY
TOWER CONDENSER
TC
LEGEND
TC TEMPERATURE CONTROL POINT EVAPORATOR
PUMP
COOLING
LOAD
Typical COPs
Hot Water Temperatures 110°F 120°F 130°F 140°F
COP (Based on 85°F off Chiller to Templifier) 8.3 6.8 6.0 4.5
The Templifier Water heater has also found innumerable applications in industries such as food
processing, recovering waste heat and supplying hot process water, as high as 140°F, at high
COPs and low cost. See the McQuay PM Templifier catalog for additional information.
STORAGE
TANK
140°F
STANDBY /
(60°C)
AUXILIARY HEAT
140°F
T-C (60°C)
CONDENSER
EVAPORATOR
TEMPLIFIER
HEAT
SOURCE
Controls
Chillers Feature MicroTech II
McQuay has incorporated the latest microprocessor technology into the MicroTech II control
system to give you the ultimate in chiller control. The control includes many energy-saving
features to keep your chiller running efficiently . . . day in, day out, for years to come.
FEATURE BENEFIT
Easy integration into a building management Designer can to select any BAS supplier using
system via McQuay’s exclusive Protocol industry standard protocols and know the
Selectability feature. MicroTech II control will interface directly with it.
Easy to read, adjustable, 10 inch, Super VGA Operators can observe chiller operation at a
color touchscreen operator interface glance, easily select various detail screens and
change setpoints
Precise ± 0.2 °F chilled water control Provides stability in chilled water system
Automatic control of chilled water and Integrated lead/lag and automatic engagement
condenser water pumps of backup pump
Controls up to four stages of tower fans and Optimum integrated control of cooling tower
modulation of tower fan and/or bypass valve water based on system conditions
Proactive Control
By constantly monitoring chiller status, the MicroTech II controller will automatically take
proactive measures to relieve abnormal conditions or shut the unit down if a fault occur. For
example, if a problem occurs in the cooling tower and discharge pressure starts to rise, the
controller will automatically hold the load point and activate an alarm signal. A further rise in
pressure will initiate compressor unloading in an effort to maintain the setpoint pressure. If the
pressure continues to rise, the unit will shut off at the cutout pressure setting.
The Home Screen shown above is the primary viewing screen. It gives real time data on unit
status, water temperatures, chilled water setpoint and motor amp draw. This display answers the
vital question-is the chiller doing what it is supposed to be doing?
If an alarm occurs, a red button
appears on the screen (a remote
signal is also available). Pressing
this button accesses the Active
Fault Screen that gives complete
fault information. The fault can be
quickly and easily cleared at this
point.
Changing Setpoints
Changing setpoints is easy with
the McQuay MicroTech II control.
For example, to change the chilled
water set point, press SET from
any screen, then press the WATER
button and this screen appears,
press button #1, Leaving Water
Temperature, and you are ready to
input a new value.
25% or greater annual kWh savings over the range of 5% to 60% design tons
The majority of comfort cooling systems operate at 60% or less of building design tons for most
of the year. A great number of those operating hours occur between 50% and 60% design
cooling capacity.
For that reason, the Model WDC chiller was designed to produce up to 60% unit capacity with a
single operating compressor, efficiently and reliably.
That performance is achieved by a combination of individual component features that include
compressor design, operating control, double heat transfer surface, and refrigerant flow control.
Benefits
Protocol Selectability
• Easy to integrate into your building automation system of choice
• Factory-installed and tested communication module
• Comprehensive point list for system integration, equipment monitoring and alarm
notification
• Provides efficient equipment operation
• Owner/designer can select the BAS that best meets building requirements
• Comprehensive data exchange
Protocol Options
• BACnet MS/TP • LONWORKS (FTT-10A)
• BACnet IP • Modbus RTU
• BACnet Ethernet
The BAS communication module can be ordered with a chiller and factory-mounted or can be
field-mounted at any time after the chiller unit is installed.
Compressor Design
Gear Drive Offers Greater Operating Efficiency Than Direct Drive
Centrifugal compressor efficiency is a function of impeller design and application to the
refrigeration system. The increased heat transfer surface and efficiency of modern heat
exchangers have changed compressor head and impeller tip speed requirements. Direct drive
designs limit the manufacturer’s ability, within a single compressor size, to select impellers at or
near peak impeller efficiency. While a unit selected at poor impeller efficiency might produce
the required performance at peak load, its operating characteristics over the entire range of part
load performance are sharply curtailed, resulting in increased annual operating costs. McQuay
gear drive centrifugal chillers provide a variety of tip speed ratios to permit selection of
impellers for maximum efficiency over their entire part load to full load range and are ideal for
50 Hz application. Mechanical gear losses are limited by design standards to less than one-half
of 1%. The impeller efficiency obtained by alternate gear selections can increase chiller
efficiency by as much as 7%. As energy costs continue to rise, the economic advantages of gear
drive to obtain maximum efficiencies will be even more advantageous. The efficiency of either
direct drive or gear drive compressor can be improved through the use of variable frequency
drives to reduce compressor speed at low load/low head conditions.
Bearings
Since the impeller shaft must be sized to support the static, rotational and torsional loads applied
by the impeller, as impellers become larger, shafts must also become proportionally larger.
These factors also come into play in the design or selection of a bearing. The primary criteria
used in bearing design are:
1. The load-per-unit of bearing area.
2. The relative velocity of the two bearing surfaces.
3. The bearing dimensions.
4. The viscosity of the lubricating oil.
Notice that item 2 returns to the phenomenon of tip speed. Surface velocity is simply the tip
speed of the inner bearing surface or shaft with respect to the outer bearing surface as illustrated
in the following diagram.
Figure 9, Bearing Loading
A hydrodynamic bearing is basically two infinite surfaces passing over one another with a
velocity equal to the surface velocity.
Lubrication System
A separately driven electric oil pump
assembly supplies lubrication at controlled
temperature and pressure to all bearing
surfaces and is the source of hydraulic
pressure for the capacity control system.
The control system will not allow the
compressor to start until oil pressure, at the
proper temperature, is established. It also
allows the oil pump to operate after
compressor shutdown to provide lubrica-
tion during coast-down.
Lubricant from the pump is supplied to the
compressor through a water-cooled, brazed-
plate heat exchanger and single or dual
five-micron oil filters internal to the
compressor. All bearing surfaces are
pressure lubricated. Drive gears are
operated in a controlled lubrication mist
atmosphere that efficiently cools and
lubricates them.
Lubricant is made available under pressure
from the compressor oil filter to the unit
capacity control system and is used to
position the inlet guide vanes in response to changes in leaving chiller water temperature.
If a power failure occurs, an emergency oil reservoir provides adequate lubrication flow under
pressure, and prevents damage that could occur during the coast-down period with the oil pump
stopped.
Since the McQuay chillers are positive pressure, there is no need to change the lubricant or filter
on a regular basis. As with any equipment of this type, an annual oil check is recommended to
evaluate the lubricant condition.
Refrigerant Comparison
The table at the right compares refrigerants
Refrigerant R-123 R-134a
in common use today in centrifugal
Condenser Press. psig @ 100°F 6.10 124.1
compressors. Note that required compressor Evaporator Press. psig @ 40°F
(18.1) 35.0
tip speeds are all within eight percent of each (Inches of Mercury Vacuum)
other. Refrigerant. Circulated lbs/min./ton 3.08 3.00
Gas Flow cfm/ton 18.15 3.17
All McQuay centrifugal chillers use Tip Speed ft./sec. 656 682
Ozone Depletion Potential (ODP) 0.02 0.00
refrigerant R-134a. The machine design
characteristics of this refrigerant (and its predecessor, R-12) such as small moving parts, low
mass, low inertia, quick spin-up and coast-down, and simplicity of design, have continuously
proven themselves since the first chiller was introduced in 1962. The small and lightweight
rotating parts lend themselves to easy servicing of the compressor and its associated parts and
piping.
Heat Exchangers
McQuay packaged centrifugal chillers are equipped with new high performance heat exchangers.
The unique design greatly increases heat transfer and reduces unit footprint and refrigerant
charge compared to previous designs. In many cases vessel length has been reduced by 40
percent. Chillers are designed, constructed and tested in accordance with ASME Section VIII,
ASHRAE Standard 15 requirements and TEMA recommendations.
The replaceable water tubes are internally rifled and externally enhanced copper and are
mechanically bonded to steel tube sheets. Standard tubes are 0.025-inch wall thickness.
Optional tubes include 0.028 inch and 0.035-inch wall thickness on either vessels and 90/10
cupro-nickel, 304 stainless steel or titanium material. Clad tube sheets and epoxy-coated heads
can be provided.
Vessels are available for 1, 2 or 3 pass water flow. A ¾-inch or 1½-inch thick, flexible foam
evaporator insulation is optional. With either of these options, all seams are glued to form an
effective vapor barrier and the entire chiller barrel, including non-connection heads and tube
sheets, are insulated. Detailed information on the insulation can be found in the “Physical Data”
section of this catalog.
Electrical
Optional starters for factory or field mounting
See details in the Motor Starter section of this manual and catalog PM Starter.
Variable frequency drives (VFD)
Efficiency: The variable frequency drive option is a technology that has been used for decades to
control motor speed on a wide variety of motor-drive applications. When applied to centrifugal
compressor motors, significant gains in compressor part load performance can be realized. The
improvement in efficiency and reduction of annual energy cost is maximized when there are long
periods of part load operation, combined with low compressor lift (lower condenser water
temperatures). When atmospheric conditions permit, McQuay chillers equipped with VFDs can
operate with entering condenser as low as 50°F (10°C), which results in extremely low kW/ton
values.
Combining the attributes of VFD drives and the extremely efficient McQuay WDC Dual
Centrifugal Chiller produces the industry's most efficient chiller based on the all-important IPLV
value. See “IPLV/NPLV Defined” on page 45 for details on the ARI IPLV efficiency rating.
Water-Side Economizers: Free cooling systems utilizing cold cooling tower water to remove
heat from the chilled water system through a heat exchanger are becoming popular because the
ability of a chiller to move seamlessly from mechanical cooling to the free cooling mode is an
important operational feature. When equipped with a VFD, McQuay chillers can operate with
condenser water down to 50°F (10°C) at which point the economizer heat exchanger can be
activated and the free cooling can go into effect.
Starting Inrush: The use of a VFD on centrifugal chillers also provides an excellent method of
reducing motor starting inrush,-even better than solid state starters. Starting current can be
closely controlled since both the frequency and voltage are regulated. This can be an important
benefit to a building's electrical distribution system.
Sound: The sound level of centrifugal compressors is largely dependent on the impeller tip
speed. By reducing compressor speed the sound level is also reduced.
Controls
English or Metric Display
Either English or metric units for operator ease of use.
BAS interface module for the applicable protocol being used.
Factory-installed on the unit controller (can also be retrofitted). See page 20 for details.
Unit
Export packaging
Can be either slat or full crate for additional protection during shipment. Units normally shipped
in containers.
Pumpout Unit, Model RRU with or without storage vessel
Available in a variety of sizes. Details under the Pumpout section on page 40 of this manual.
Refrigerant monitor
For remote mounting, including accessories such as 4-20ma signal, strobe light, audible horn, air
pick-up filter. Details on page 42.
Hot gas bypass
For operation below 10% on WSC and 5% on WDC units. Reduces compressor cycling and its
attendant chilled water temperature swings.
Sound attenuation package
Consists of acoustical insulation on the discharge line.
Extended warranties
Extended 1, 2, 3, or 4-year warranties for parts only or for parts and labor are available for the
entire unit or compressor/motor only.
Optional Certified Test
A McQuay engineer oversees the testing, certifies the accuracy of the computerized results, and
then translates the test data onto an easy-to-read spreadsheet. The tests can be run at ARI load
points between 10% and 100% and are run to ARI tolerance of capacity and power. 50 Hz units
are run tested at 60 Hz to their maximum motor power.
Optional Witness Test
A McQuay engineer oversees the testing in the presence of the customer or their designate and
translates the test data onto an easy-to-read spreadsheet. The tests can be run at ARI load points
between 10% and 100%. It takes two to three hours of test time per load point specified. Tests
are run to ARI tolerances of capacity and power. 50 Hz units can be run-tested at 50 Hz using an
onsite 50 Hz generator.
.505
.5
IPLV
.403
.4
.365
.337
.3
WSC WDC WSC w/VFD WDC w/VFD
The IPLV values (defined on page 45) are ARI Certified Ratings based on ARI Standard
550/590-1998, Standard for Water Chilling Packages Using the Vapor Compression Cycle. Full
load is at 44°F chilled water temperature with 2.4 gpm/ton, 85°F entering condenser water
temperatures with 3 gpm/ton. Part load points of 75%, 50%, and 25% employ condenser water
temperature relief (reduction) per the standard.
General
Single and dual compressor units can be equipped with a variable frequency drive (VFD). A
VFD modulates the compressor speed in response to load and evaporator and condenser
pressures as sensed by the microprocessor. Due to the outstanding part load efficiency, and
despite the small power penalty attributed to the VFD, the chiller can achieve outstanding
overall efficiency. VFDs really prove their worth when there is reduced load combined with low
compressor lift (lower condenser water temperatures) dominating the operating hours.
The traditional method of controlling centrifugal compressor capacity is by inlet guide vanes.
Capacity can also be reduced by slowing the compressor speed and reducing the impeller tip
speed, providing sufficient tip speed is retained to meet the discharge pressure requirements.
This method is more efficient than guide vanes by themselves.
In actual practice a combination of the two techniques is used. The microprocessor slows the
compressor (to a fixed minimum percent of full load speed) as much as possible, considering the
need for tip speed to make the required compressor lift. Guide vanes take over to make up the
difference in required capacity reduction. This methodology provides the optimum efficiency
under any operating condition.
Options
Reactor
Used for control of line harmonics in some installations.
Incoming Line Termination (Chose one)
• Terminal block
• Non-fused disconnect with through-the-door handle
• Fused disconnect with time delay fuses with through-the-door handle
• Standard interrupting circuit breaker with through-the-door handle
• High interrupting circuit breaker with through-the-door handle
• Ultra high circuit breaker with through-the-door handle
Current Harmonics
An increase in reactive impedance in front of the VFD helps reduce the harmonic currents.
Reactive impedance can be added in the following ways:
1. Mount the drive far from the source transformer.
2. Add line reactors.
3. Use an isolation transformer.
Voltage Harmonics
Voltage distortion is caused by the flow of harmonic currents through a source impedance. A
reduction in source impedance to the point of common coupling (PCC) will result in a reduction in
voltage harmonics. This may be done in the following ways:
1. Keep the PCC as far from the drives (close to the power source) as possible.
2. Increase the size (decrease the impedance) of the source transformer.
3. Increase the capacity (decrease the impedance) of the busway or cables from the source to the
PCC.
4. Make sure that added reactance is downstream (closer to the VFD than the source) from the
PCC.
CHILLER
WATER
REGULATING
VALVE
(Factory Mounted)
VFD HEAT
EXCHANGER
SOLENOID
VALVE
(Factory Mounted)
* STOP
VALVE * STRAINER
MAX. 40 MESH * DRAIN VALVE * STOP
OR PLUG VALVE
Refrigerant Compatibility
Units are suitable for use with the following refrigerants normally found on McQuay chillers; R-12, R-22, R-
134a, R-410A, and R-500.
Standard Equipment
Model
Equipment
RRU134 RRU570
Power Cord X X
Filter-Driers (2) 30 cu. in. (1) 48 cu. in
Electromechanical Control X X
Hoses (4) 10 ft. (1) 10 ft + (2) 20 ftX
Reducing Fittings X
12 ft. Tank Float Switch Cable X
Connection Sizes ½ in. Flare ¾ in. Flare
Model RRU134
Large 1 ½-HP open drive compressor, ½-inch lines, two-
point vapor extraction and oversized air-cooled condenser
speed recovery on smaller size chillers. Purging and
switching from liquid to vapor recovery only involves
turning 3-way valves-no switching of hoses is necessary.
Capacity with R-134a is 55 lb/min liquid, 1.34 lb/min vapor.
Accessories
RHK-120 1.25 in. x 10 ft. hose with ball valves
RHK-240 1.25 in. x 20 ft. hose with ball valves
MODELS
Model RM-1 1 Zone Monitor
Model RM-4 4 Zone Monitor
Model RM-8 8 Zone Monitor
Model RM-16 16 Zone Model
SPECIFICATIONS
Sensitivity: As low as 1 PPM Range: 0 to 1000 PPM Weight: 25 lbs. (11 kg)
Power: 120/240 Volt, 50/60 Hz Operating Environment: 32°F-125°F Size: W=16.5in. D=6.75in. H=15in.
Alarm Trip Points (Percent of Full Scale): Low Alarm=0 to 100, Main Alarm=0 to 100, High Alarm=100
Alarm Outputs: Indicator Light, Alarm Relays, RS232 Computer Interface
The program excludes the following applications: air and evaporative cooled chillers, capacity exceeding 2000 tons (7000 kW) on 60
hertz service, voltages above 5000 volts, brine and special fluids other than water and heat recovery units. The capacity range for 50
hertz is 200 to 1,000 tons (700 to 3500 kW).
Oil Coolers
McQuay centrifugal chillers, sizes 063 through 126, have a factory-mounted, water-cooled oil
cooler with a temperature controlled water regulating valve and solenoid valve for each
compressor. Cooling water connections are located at the rear of the unit, near the compressor
and are shown on the specific unit certified drawings. Models WDC 063 through 087 have the
cooling water connections in the lower portion of one tube sheet. Models WSC and WDC 050
chillers have refrigerant-cooled oil coolers and do not require a cooling water connection.
WDC 063, 079, 087, 100 and 126 dual compressor chillers are equipped as above, but the water
piping for the two oil coolers is factory piped to a common inlet and outlet connection.
When supplied with city water, the oil piping must discharge through a trap into an open drain to
prevent draining the cooler by siphoning. The city water can also be used for cooling tower
makeup by discharging it into the tower sump from a point above the highest possible water
level.
NOTE: Particular attention must be paid to chillers with variable chilled water flow through the
evaporator. The pressure drop available at low flow rates can very well be insufficient to supply
the oil cooler with enough water. In this case an auxiliary booster pump can be used or city
water employed.
Cooling Water Connection Sizes: WDC 100/126 have 1 1/2 in. FPT connections, all other
WDC and WSCs are 1 in. FPT.
CHILLER
OIL COOLER S
STOP
SOLENOID VALUE
VALVE
STOP
VALVE
STRAINER
MAX. 40 MESH
DRAIN VALVE
OR PLUG
OIL COOLER S
SOLENOID
VALVE
Pumps
Model WSC and WDC chiller compressor motors operate at 3600 rpm on 60 Hz power (3000
rpm on 50 Hz). When VFDs are employed, the hertz/speed can be reduced by 70%. To avoid
the possibility of objectionable harmonics in the system piping, 4-pole, 1800/1500 rpm system
pumps should be used. The condenser water pump(s) must be cycled off when the last chiller of
the system cycles off. This will keep cold condenser water from migrating refrigerant to the
condenser. Cold liquid refrigerant in the condenser can make start-up difficult. In addition,
turning off the condenser water pump(s) when the chillers are not operating will conserve
energy.
Piping
Piping must be adequately supported to remove weight and strain on the chiller’s fittings and
connections. Be sure piping is adequately insulated. Install a cleanable 20-mesh water strainer
upstream of the evaporator and condenser. Install enough shutoff valves to permit draining water
from the evaporator or condenser without draining the complete system.
CAUTION
Freeze Notice: The evaporator and condenser are not self-draining. Both must be blown
out to completely remove water to help prevent freezup.
Thermal Storage
McQuay chillers are designed for use in thermal storage systems. The chillers have two
operating conditions that must be considered. The first is normal air-conditioning duty where
leaving evaporator fluid temperatures range from 40°F to 45°F (4.4°C to 7.2°C). The second
condition occurs during the ice making process when leaving fluid temperatures are in the 22°F
to 26°F (-5.6°C to -3.3°C) range.
Vibration Mounting
Every McQuay chiller is run tested and compressor vibration is measured and limited to a
maximum rate of 0.14 inches per second, which is considerably more stringent than other
available compressors. Consequently, floor-mounted spring isolators are not usually required.
Rubber mounting pads are shipped with each unit. It is wise to continue to use piping flexible
connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction.
Operating Limits
The maximum temperature of water entering the chiller on standby must not exceed 110°F
(43.3°C). Maximum temperature entering on start-up must not exceed 90°F (32.2°C). Minimum
chilled water leaving temperature without antifreeze is approximately 38°F (3.3°C), but can vary
up or down two degrees depending on actual component selection.
Relief Valves
Vessel Relief Valves Figure 14, Typical Vent Piping
Relief valve connection sizes are 1-inch FPT and
are in the quantity shown in Table 8 and Table 9.
Relief valves must be piped to the outside of the
building in accordance with ANSI/ASHRAE 15-
2001. The new 2001 standard has revised the
calculation method compared to previous issues.
Twin relief valves, mounted on a transfer valve,
are used on the condenser so that one relief valve
can be shut off and removed for testing or
replacement, leaving the other in operation. Only
one of the two valves is in operation at any time.
Where 4 valves are shown, on some large vessels,
they consist of two relief valves mounted on each
of two transfer valves. Only two relief valves of
the four are active at any time.
Vent piping is sized for only one valve of the set
since only one can be in operation at a time.
L=
(
0.215d 5 PO2 − P22 )− d * ln
(PO / P2 )
L=
(
7.4381 x 10 −15 d 5 PO2 − P22 )− d *ln
(PO / P2
fC r2 6f fC r2 500 f
Where
L = equivalent length of discharge piping
Rr = rated capacity as stamped on the relief valve in lb/min (kg/s)
f = Moody friction factor in fully turbulent flow. Typical values given in
Table 6, Moody friction factor (f)
Piping NPS DN ID (in.) f
1 25 1.049 0.0225
2 50 2.067 0.0190
3 80 3.068 0.0173
4 100 4.026 0.0163
Per ASHRAE Standard 15, the pipe size cannot be less than the relief device. The discharge
from more than one relief valve can be run into a common header, the area of which shall not be
less than the sum of the areas of the connected pipes. For further details, refer to ASHRAE
Standard 15. The common header can be calculated by the formula:
0.5
DCommon = §¨ D12 + D22 ....D n2 ·¸
© ¹
The above information is a guide only. Consult local codes and/or latest version of ASHRAE
Standard 15 for sizing data.
GND PE 54
85 * REMOTE
POWER ON/OFF
* NOTE 7 (NOTE 5)
86
NEUTRAL
* NOTE 10 70 * MODE
H
80
SWITCH
* COOLING O
55 *NOTE 8
C4 74 H
TOWER A
FOURTH 86 O
STAGE A C
STARTER 86 EP2
NOTE 11
* CHILLED
* NOTE 10 EWI-2 WATER
H 79
PUMP
* COOLING O
C3 * NOTE 8 STARTERS
73
TOWER A H
THIRD O
STAGE
STARTER EP1
A C
78
77 NOTE 11
* NOTE 10 EWI-1
H 76
* COOLING O
C2 75
TOWER A
SECOND
STAGE (NOTE 6) (NOTE 6)
STARTER SWITCH SWITCH * NOTE 9
DELTA P DELTA P H
FLOW OR FLOW OR O
* NOTE 10 EVAP. COND. A
H CP2 C
O
* COOLING C1
TOWER A NOTE 11
FIRST CWI-2
STAGE
STARTER
COMMON 81
ALARM RELAY
82(NO) (NOTE 4) * CONDENSER
A WATER
* NOTE 4 83(NC) PUMP
STARTERS
POWER 84
CTB2 * NOTE 9
H
T3-S
O
EF A C
CP1
CF
NOTE 11
CWI-1
52
CP1 L1
-STARTER LOAD SIDE TERMINALS-
CP2 L2 WYE- DELTA
T4 T5 T6
23(5A) 23 T1 T2 T3
24(5) 24
COMPRESSOR
25 25
T1 T2 T3 T4 T5 T6
MOTOR -COMPRESSOR TERMINALS-
STARTER
1 1 -STARTER LOAD SIDE TERMINALS-
(NOTE 1) SOLID STATE
2 2
NOTE 12
T1 T2 T3
3 3
4 4
6 11 T1 T6 T2 T4 T3 T5
S = Single Compressor
COMPRESSOR
D = Dual Compressor
Compressor/Impeller Code
Gear Ratio
Motor/Voltage Code
Connection Type
Connection Type
Motor Manufacturer
R
Compressor
Table 10, Compressor Weights
Compressor Size 048/050 063 079 087 100 113 126
870 3200 3200 3200 6000 6000 6000
Weight lb (kg)
(390) (1440) (1440) (1440) (2700) (2700) (2700)
Figure 17, WSC 048/WSC 050, 85 to 165 Tons, (300 to 580 kW)
ADJUSTABLE OPERATOR
INTERFACE PANEL
UNIT
CONTROL
BOX
1” FPT VESSEL RELIEF
VALVE CONNECTIONS
FACTORY
MOUNTED EVAPORATOR
STARTER
B
(OPTIONAL)
1” FPT OIL
COOLER CONNECTION
CONDENSER
X
A
IN OUT
F G
OUT
Y IN
Z
C
C +16”
ADJUSTABLE OPERATOR
INTERFACE PANEL
UNIT
CONTROL
BOX
1” FPT VESSEL RELIEF
VALVE CONNECTIONS
FACTORY
MOUNTED EVAPORATOR
STARTER
B
(OPTIONAL)
1” FPT OIL
COOLER CONNECTION
CONDENSER
X
A
IN OUT
F G
OUT
Y IN
Z
C
C +17”
FACTORY
MOUNTED EVAPORATOR
STARTER
B
(OPTIONAL)
1” FPT OIL
COOLER CONNECTION
CONDENSER
X
A
IN OUT
F G
OUT
Y IN
Z
C
C +17”
ADJUSTABLE OPERATOR
INTERFACE PANEL
UNIT
CONTROL
BOX
1” FPT VESSEL RELIEF
VALVE CONNECTIONS
FACTORY
MOUNTED EVAPORATOR
STARTER
B
(OPTIONAL)
1” FPT OIL
COOLER CONNECTION
CONDENSER
X
A
IN OUT
F G
OUT
Y IN
Z
C
C +28”
B STARTER
(OPTIONAL) EVAPORATOR STARTER
(OPTIONAL)
1” FPT OIL COOLER CONNECTION
Y CONDENSER
X
OUT
IN
OUT
FOOTPRINT Y IN
C
C + 20”
B STARTER
(OPTIONAL) EVAPORATOR STARTER
(OPTIONAL)
1” FPT OIL COOLER CONNECTION
Y CONDENSER
X
OUT
IN
OUT
FOOTPRINT Y IN
C
C + 15”
B STARTER
(OPTIONAL) EVAPORATOR STARTER
(OPTIONAL)
1” FPT OIL COOLER CONNECTION
Y CONDENSER
X
OUT
IN
OUT
FOOTPRINT Y IN
C
SEE NOTE 1
ADJUSTABLE OPERATOR
INTERFACE PANEL UNIT
CONTROL
BOX
B
EVAPORATOR
1” FPT OIL COOLER CONNECTION
1” FPT VESSEL RELIEF
VALVE CONNECTIONS
Y CONDENSER
X
OUT
IN
OUT
FOOTPRINT Y IN
.50
“A” “D”
“B”
“F”
2 and 4 Pass Cond. (Except 18 in. 2 Pass) All 2 Pass Evap. - All 3 Pass Cond.
18 in. 2 Pass Cond.
Nozzle Flanges
Are Optional Nozzle Flanges
Are Optional
“E” “E”
“E”
“E”
.50
.50
“D”
“D”
SECTION 15XXX
CENTRIFUGAL CHILLERS
SINGLE COMPRESSOR
PART 1 — GENERAL
1.1 SUMMARY
Section includes design, performance criteria, refrigerants, controls, and installation requirements for
water-cooled centrifugal chillers.
1.2 REFERENCES
Comply with the following codes and standards
ARI 550/590 NEC
ANSI/ASHRAE 15 OSHA as adopted by the State
ASME Section VIII
1.3 SUBMITTALS
Submittals shall include the following:
A. Dimensioned plan and elevation view drawings, including motor starter cabinet, required
clearances, and location of all field piping and electrical connections.
B. Summaries of all auxiliary utility requirements such as: electricity, water, air, etc.
Summary shall indicate quality and quantity of each required utility.
C. Diagram of control system indicating points for field interface and field connection.
Diagram shall fully depict field and factory wiring.
D. Manufacturer’s certified performance data at full load plus IPLV or NPLV.
E Before shipment, submit a certification of satisfactory completion of factory run test
signed by a company officer. The test shall be performed on an ARI Certified test stand
and conducted according to ARI Standard 550/590.
F Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A. Qualifications: Equipment manufacturer must specialize in the manufacture of the
products specified and have five years experience with the equipment and refrigerant
offered.
B. Regulatory Requirements: Comply with the codes and standards in Section 1.2.
C. Chiller manufacturer plant shall be ISO Registered.
1.5 DELIVERY AND HANDLING
A. Chillers shall be delivered to the job site completely assembled and charged with
refrigerant and oil.
B. Comply with the manufacturer’s instructions for rigging and transporting units. Leave
protective covers in place until installation.
1.6 WARRANTY
-- Or --
-- Or --
Medium Voltage (601 through 5000 volts) and High Voltage (5001 through 7200 volts).
The starter shall be:
Across-the-Line type with primary contactor allowing locked rotor amps to reach the
motor when energized.
--OR--
Primary Reactor type with drawout magnetic, three-pole, vacuum break shorting
assembly, and three-phase starting reactor, factory set at the 65% tap
All medium and high voltage starters shall have the following components:
Main Control Relays
Redundant motor control relays with coils in parallel and contacts in series to interlock
the starter with the chiller. These two relays shall constitute the only means of
energizing the motor contractors. No other devices (manual or automatic) with the
capability of energizing the starter can be used. The starter is controlled by the unit
microprocessor.
System specific, chiller plant architecture software shall be employed to display the
chiller, piping, pumps and cooling tower. Chiller plant optimization software for up to 4
chillers shall also be included to provide automatic control of: evaporator and condenser
pumps (primary and standby), up to 4 stages of cooling tower fans and a cooling tower
modulating bypass valve or cooling tower variable frequency drives. There shall be five
possible tower control strategies:
• Tower fan staging only – up to 4 stages controlled by either the entering condenser
water temperature or lift differential temperature between the condenser and
evaporator saturated temperatures.
• Tower fan staging plus low limit - controlled as in # 1 plus tower bypass valve set at
a minimum entering condenser water temperature
• Tower staging with staged bypass control – similar to # 2 with additional control of
the bypass valve between fan staging to smooth control and minimize fan staging.
• VFD staging only – in this mode, a variable speed drive controls the first fan with up
to 3 more fans to be staged on and off and there is no bypass valve.
The information communicated between the building automation system and the factory
mounted unit controllers shall include the reading and writing of data to allow unit
monitoring, control and alarm notification as specified in the unit sequence of operation and
the unit points list.
-- Or --
--OR--
Primary Reactor type with drawout magnetic, three-pole, vacuum break shorting assembly,
and three-phase starting reactor, factory set at the 65% tap
All medium and high voltage starters shall have the following components:
Main Control Relays
Redundant motor control relays with coils in parallel and contacts in series to interlock the
starter with the chiller. These two relays shall constitute the only means of energizing the
motor contractors. No other devices (manual or automatic) with the capability of
energizing the starter can be used. The starter is controlled by the unit microprocessor.
In addition to the trended items above, other real-time operating parameters are also
shown on the touchscreen. These items can be displayed in two ways: by chiller graphic
showing each component or from a color-coded, bar chart format. At a minimum, the
following critical areas must be monitored:
System specific, chiller plant architecture software shall be employed to display the
chiller, piping, pumps and cooling tower. Chiller plant optimization software for up to 4
chillers shall also be included to provide automatic control of: evaporator and condenser
pumps (primary and standby), up to 4 stages of cooling tower fans and a cooling tower
modulating bypass valve or cooling tower variable frequency drives. There shall be five
possible tower control strategies:
• Tower fan staging only – up to 4 stages controlled by either the entering condenser
water temperature or lift differential temperature between the condenser and
evaporator saturated temperatures.
• Tower fan staging plus low limit - controlled as in # 1 plus tower bypass valve set at
a minimum entering condenser water temperature
• Tower staging with staged bypass control – similar to # 2 with additional control of
the bypass valve between fan staging to smooth control and minimize fan staging.
• VFD staging only – in this mode, a variable speed drive controls the first fan with up
to 3 more fans to be staged on and off and there is no bypass valve.