Large Prefabricated Modular Data

Center FusionDC1000C
Product Overview
FusionDC1000C is a prefabricated modular data center that adopts
the modular design, Lego block concept, and factory pre-integration
test to minimize onsite workload and support fast deploy.
Pre-fab. modules are classified into five types based on functions:
equipment module, MEP module (cooling), power module and
hydropower module(Valves & Pumps).
The prefabricated modular data center is configured with the data
center infrastructure management (DCIM) system. In addition, the AI
technologies (iCooling, iPower, and iManager) are used to improve
the TCO and cash flow of the customer throughout the data center
life cycle, helping the customer achieve business success. Reference Layout 1

Application
Scenario
• Public cloud, large colocation data centers, and ultra-large Internet
service data centers
• Medium- and large-sized data centers of enterprises or governments
• AI computing and HPC
Feature and Value
Simplified
• Pre-integration and pre-test of devices in the factory, synchronous
basic civil work and module factory production, reducing TTM by 50%① Reference Layout 2
• Modularized components, modularized functions, and PODs②, on-
demand deployment, and phased capacity expansion
• Less onsite workload and simple project management
Green
• Indirect evaporative cooling maximizes the use of natural cooling sources
and reduces the PUE.
• Optional smart fanwall cooling technology and high-temperature chilled
water reduce power consumption by 3%.
• Green building, no dust and noise on the construction site, and less
construction waste
Intelligent
• AI-based intelligent optimization continuously reduces data center energy
consumption
• Use smart sensors and big data analysis to precisely manage available
resources and tenant information, maximizing the value of data center
resources. Reference Layout 3

Reliable
• The prefabricated data center complies with the TIA 942 standard.
• Huawei iPower technology implements full-link monitoring of power
supply and distribution and core components fault prediction to ensure
uninterrupted operation.

1. China: 1000 cabinets, 20 months for traditional civil engineering, 9 months for prefabricated modular data centers; Middle East: 600 cabinets, 30 months for
traditional civil construction, 15 months for prefabricated modular data centers
2 POD: point of delivery
Typical Reference Design
Based on customer requirements and the granularity of power distribution and cooling, we can match
various combinations. The following uses the FusionDC1000C IT load of 4 MW as an example to describe
the reference design.

Reference design for the Smart FanWall cooling scenario


• Introduction: 2 layers, 336 racks, maximum IT power load of 1920 kW per layer (including 6 IT micro-modules, 28
racks per micro-module, 320 kW load, and maximum of 15 kW/R)
• Highlights: The power supply and distribution devices and IT devices are deployed at the same layer,“one layer, one
DC ”. The Smart Busway is adopted to support power density expansion. Adopts Fanwall, no raised floor, and high
space utilization in vertical.

Typical Reference Design Layout

Stairwells Stairwells

Data Hall

FanWalls

Power Reference design layout 1 Power


distribution distribution
room(including (FanWall Cooling solution) room (including
batteries) Symmetric design on both sides, 6 IT micro-modules, 28 cabinets, batteries)
and each module

Data Hall

Corridors

Evaporative Cooling Zone

Reference design layout 2


(Indirect evaporative cooling scenario)
Main parameters of the reference design(POD)

Item Overall specifications of the intelligent air wall cooling scenario


• Altitude ≤ 4,000 m①;
• Class A/B environment: Class B environment is at least 3,700m away from strong corrosive
Environment adaptability environments (such as seaside, garbage pileup, and heavily polluted chemical plants)②.
• The operating temperature ranges from –20°C to +45°C. If the temperature is lower than –
5°C, external wall insulation is required.
Tier Level Tier III
General Stack Layers Two layers(reference design), stackable, up to five layers
parameters
Prefab module life 25-year standard, 50-year customization for specific environments③

Total capacity/Density of
≤ 5,040 kW/12 kW (maximum 15 kW/R)
a single cabinet
Total number and
dimensions of IT cabinets 336; 600*1200*2000/2200mm④
(H x W x D)
Power supply area: 15 kN/m2; equipment area: 12 kN/m2; corridors and public areas: 5
live load
kN/m2; ceilings: 2.4 kN/m2; rooftops: 0.75 kN/m2
load design Other payloads Wind load ≤ 1,000 mph

load combination ASCE7-10

Power System 380/400/415V 50/60Hz 3P+N+PE


Electrical
specifications
Backup time 2N, Lithium Battery 10 minutes@full load

Cooling redundancy N+1, 10 minutes continuous cooling @ full load


Temperature range of
Temperature 20-28°C
the device area
control
Humidity range of the
parameters 20%~80%
equipment area
heat transfer coefficient
Total heat transfer coefficient ≤ 0.3 W/(m*K)
of envelope
Including gas fire extinguishing in equipment areas, water spray in non-equipment areas,
Fire extinguishing system
non-addressable (customized addressing type)
Fire resistance time of
bearing beam and 120 minutes
column
fire protection Fire resistance time of
coefficient the external protective Standard: 90 minutes; customizable: 120 minutes
structure
Other fire resistance
60 minutes fire resistance for internal partitions; Fireproof door fire resistance: 90 minutes
time
Fire Extinguishing
Heptafluropropane, equipped with suction smoke detectors
Agent and Detector
DCIM Configuration iManager NetEco
Work order management, energy efficiency management, temperature map, mobile app
Optional Features
O&M, asset capacity management, iCooling, and third-party southbound access
Northbound access SNMP NBI, WebService NBI, CTCC C NBI, and FTP NBI
Power and environment
Yes, collected by the ECC
monitoring system
In-room access control
Yes, third-party security platform
system - security
Modular Access Control
Yes, managed by the ECC800
System - Operation
Monitoring
Cabinet-level access
parameters
control system - None. The ECC800 supports customization.
operation
In-room CCTV system - Yes. Facial recognition is available at entrances and exits. The default storage duration is 90
security days.
Module-level CCTV
Yes. The default storage duration is 90 days.
system-operation
Hydrogen detection Yes, sir.

Water immersion system Yes, addressable

Intelligent lighting Optional

1. The power supply and distribution capability derating is according to EN/IEC 62040-3 when the altitude exceeds 1000m. For details about the cooling parameters, see
Huawei smart cooling product data sheet. The overall derating is the one with the larger derating coefficient.
2. For the definition of class 2A/B/C environments refer to Huawei enterprise standards. The corresponding ISO9223/12944 environment classification is C1/C2/C3/C4
3. According to ISO12944-2/ISO12944-1, the equivalent service life of a 1440-hour salt spray test in a C4-High environment is 25 years. 50 years in the C3 environment and 40
years in the C4/C5 environment (A third-party certification report can be provided.)
4. Cabinets are not defaulted, only showing the dimension limitation.
Introduction to Core Modules

• 380/400/415V 50/60Hz; 3P, four-wire+PE, 2*1,200 kW, input


power factor 0.99
• SmartLi-512V-80Ah, SmartLi 10min@full load
• Dimensions (mm): 12,192 (40ft) (L) * (2*2,438)(W)*4,150(H)
• Busbar connection
Power Module

• 4* CRAH210Hs (210 kW), total cooling capacity of 840 kW


• Dimensions(mm): 9,827 (L)*3,495 (W)*4,150 (H)
• Inlet/return water temperatures: 20°C/28°C;
• Cold aisle temperature control: 18°C to 27°C
• 10min continuous cooling@full load
MEP Module
(intelligent wind wall)

• Cooling capacity: 220 kW; air volume: 55,000 m3/h; maximum


non-cooling capacity: 110 kW
• Supply air temperature (°C)/Humidity (%): 25°C/50%
• Return air temperature (°C)/Humidity (%): 38°C/25%
• Dimensions (mm): 6,058(L)*2,438(20ft)(W)*3,600(H)
• Net weight/Gross weight (excluding air channels):
MEP Module 5,150kg/5,700 kg
(indirect evaporative cooling)

• 28 IT cabinets: 1,320 kW (a single cabinet supports a maximum of


15 kW)
• Dimensions (mm): 12,192 (40 ft)(L)*4,901(W)*4,150(H)
• Support cabinet dimensions (mm): 600(W)*1,200(D)-
2,000/2,200(H)①
• With aisle containment
• 400A busway, A/B dual power supply for each row
• 2 pcs 3P/32A rPDUs for each cabinet
• No raised floor, floor-mounted
IT Equipment Module
1. Support only provide white space.

FusionDC is combination of Huawei latest solution and technology. It helps customer to build more efficiency, more reliable
and future proof data center. All above showing is only the concept and some reference solution. More information please
contact Huawei region interface.

Copyright Huawei Technologies Co., Ltd. 2020. All rights reserved. Huawei Technologies Co., Ltd.
No part of this document may be reproduced or transmitted in any form or by any means without the prior
written consent of Huawei Technologies Co., Ltd . Huawei Industrial Base, Bantian,
Longgang District, Shenzhen
Tel: (0755) 28780808
Postal code: 518129 www.huawei.com

You might also like