ORMAZABAL Cpg.0 Primary
ORMAZABAL Cpg.0 Primary
ORMAZABAL Cpg.0 Primary
Substation Solutions
CONTENTS
INTRODUCTION _________________________ 1
Preface 1
Your electrical network 2
Your business and SSS applications 2
Our product map (SSS and DNS) 3
HANDLING, INSTALLATION
AND AFTER-SALES ______________________ 47
Handling 47
Connection between cubicles 47
Inside buildings 48
Inside moving substations 49
Inside wind turbine generator system substation and wind farms 49
Commissioning and after-sales 49
Recycling and end of service life 49
The quality of the products designed, manufactured and installed by Ormazabal is backed up by the implementation and certification of a quality management system, based
on international standard ISO 9001:2008.
Our commitment to the environment is reaffirmed with the implementation and certification of an environmental management system as laid down in international standard
ISO 14001.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification.
These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal.
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Introduction
Preface
MV/MV and HV/MV substations are some Ormazabal is the leading provider of Velatia is a family-run, industrial,
of the most critical nodes in any electrical customised solutions to electrical utilities, technological and benchmark global group
network. to electrical end users as well as renewable which operates in the areas of electricity
energy systems applications based on its networks, electronics and communication
The growing demand for electricity and own technology. networks as well as in the consultancy,
the increased power in these substations security and aeronautics component
requires guaranteed maximum reliability We encourage the development of the
sectors, where safety, efficiency and
and continuity of service in rated current electricity sector towards the challenges
reliability are valued.
levels in the medium-voltage cubicles. of the future energy needs. We collaborate
with the world's leading local, regional and Our customer orientation has led to the
After many years of experience in global companies in the electricity sector development of our extensive network of
designing, developing, manufacturing and with a strong commitment to innovation factories in Spain, France, Germany, Poland,
commissioning gas-insulated switchgear towards personal safety, network Mexico, Brazil and China, helping to meet
(GIS) in secondary distribution, in 2005 reliability, energy efficiency and our customers’ needs in more than
Ormazabal launched the cpg system sustainability. 50 countries.
on markets around the world:
high-performance, flexible and extensible Our highly qualified and focused team of The solutions provided by Velatia
GIS-type cubicles both single and double innovation-motivated professionals have companies seek to make the world a more
busbar. developed our own products and solutions connected, more sustainable, smarter, safer,
during our more than a century long more humane place.
Over the last few years the cpg system has consolidated history, always by establishing
been extended with higher electrical values, close relationship with our customers aimed
such as up to 2500 A and up to 40.5 kV. at achieving mutual long-term benefits.
The cpg system has now been integrated
into many applications for utilities,
renewable energy, industry and major
infrastructure. There are currently more than
9600 units of this system in service in over
40 countries.
1
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
2
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Underground Walk-in Kiosk Compact kiosk Rural kiosk Rural kiosk Kiosk Non-walk-in Grouped
3
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
Main characteristics
Safety Reliability
Protection for people, environment and Interlocks Helps maintain uninterrupted supply of the
electrical installations. electricity network.
cpg cubicles have mechanical and electrical
Special attention is paid to the personal interlocks as standard in accordance with Lifetime sealtight insulation
safety of the operators and the general IEC 62271-200 to enable safe and reliable
public, even under fault conditions. service. Insulation inside a stainless steel gas tank
provides an extended service life and
Internal arc The interlocks prevent unsafe operations: requires no maintenance of the live parts.
cpg cubicles have been designed to ● They prevent the feeder disconnector Installation, assembly on site, extension and
withstand the effects of an internal arc in from opening if the circuit-breaker replacement with no need to handle gas.
accordance with IEC 62271-200 (IAC class). is closed
● They make it impossible to close the Environmental adaptation
Gas-insulated and screened feeder disconnector and the earthing Resistance to normal environmental
The making and breaking devices are switch at the same time conditions stipulated in standard
housed in lifetime hermetically sealed ● They allow the access cover to the IEC62271-1*.
stainless steel gas tanks. This provides medium-voltage cable compartment
(*) Please ask Ormazabal for other specific
resistance in accordance with normal to be opened when the earthing switch
conditions.
service conditions for indoor switchgear, and circuit-breaker are closed
as set out in Standard IEC 62271-1.
Padlocks, keyed and electrical interlocks 100% routine tests
The whole power circuit is fully insulated, are optionally available based on customer All switchgear is 100% subjected to
including the cable terminals, and it is all specifications. routine electrical and mechanical tests in
screened, earthed and installed inside a
accordance with the relevant standards. We
metal enclosure. Indicators
also perform 100% water-tightness tests on
Additional safety by using: our switchgear as a routine test in order to
● Position indicators for the connection guarantee reliability throughout its service
switchgear: visual indication in the life.
mimic diagram, validated through the ● Sealtight integrity test
kinematic chain test in accordance ● Power frequency test
with current standards (IEC 62271-102)
● Main circuit resistance measurement
● Capacitive indicating relays for
presence/absence of voltage ● Mechanical operations test
(IEC 61243-5). ● Partial discharge test
Permanent indication (multi-LED)
and optional contacts for remote
signalling and performing
electromagnetic interlocks
● Gas pressure signalling inside each
cubicle gas tank via volt-free contacts
4
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
5
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type cubicle system Substation Solutions
Technical details
Family
cpg.0
With single busbar (up to 36/38/40.5 kV)
v vl f fl
s rb c pt
Circuit-breaker Disconnector Busbar coupling Circuit-breaker Fuse protection Disconnector Longitudinal Transverse busbar
busbar coupling
coupling
6
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type cubicle system
Technical data
Electrical specifications
cpg.0 cpg.0 lite cpg.1 cpg.0
Rated voltage Ud [kV] 24 36 40.5 24 24 36 27 38
Rated frequency fr [Hz] 50/60 60
Rated current Ir
Busbars and cubicle interconnection [A] Up to 2500 Up to 1600 Up to 1250 Up to 20002) Up to 2500
In outgoing line1) [A] Up to 2500 Up to 1250 Up to 1250 Up to 2000 Up to 2500
Rated short-time withstand current
with tk = 1 s – 3 s Ik [kA] 25/31.5 25 25/31.5 25/31.5
50 Hz: 62.5/80 50 Hz: 62.5 50 Hz: 62.5/80
Peak value (max) Ip [kA] 60 Hz: 65/82 60 Hz: 65 60 Hz: 65/82
65/82
Service conditions
Type of switchgear Indoor
Ambient temperature
Minimum | Maximum - 5 °C4) | + 40 °C4) 23 °F4) | 104 °F4)
Maximum average ambient temperature, measured over a 24-hour period + 35 °C 95 °F
Relative humidity
Maximum mean relative humidity, measured over a 24-hour period < 95 %
Maximum height above sea level 1000 m4) 3250 feet4)
Solar radiation Negligible
Ambient air pollution (dust, smoke, corrosive and/or flammable gases, vapours or salt) acc. normal service conditions indicated in IEC 62271-1.
4)
Please ask Ormazabal for other specific conditions.
7
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
Construction structure
cpg.0
Front view Side view
1. Gas tank(s)
1.1. Vacuum circuit-breaker
1.2. Three-position disconnector
1.4. Gas pressure relief duct
2. Busbar compartment
2.1. Main busbars
3. Base: Cable compartment
3.1. Bushing
3.2. Current transformers
3.3. Voltage transformers
3.4. Cable connectors
4. Low-voltage compartment
5. Operations interface
5.1. Circuit-breaker driving
mechanism
5.2. Driving mechanism for feeder
disconnector(s)
5.3. Earthing switch mechanism
5.4. Pressure indicating relay: Pressure
gauge
5.5. Voltage presence/absence
indicating relay
5.6. Mimic diagram
cpg.0 lite
Front view Side view
8
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
cpg.1
Front view Side view
1. Gas tank(s)
1.1. Vacuum circuit-breaker
1.2. Feeder disconnectors
1.3. Earthing switch
1.4. Gas pressure relief duct
2. Busbar compartment
2.1. Main busbars
3. Base: Cable compartment
3.1. Bushing
3.2. Current transformers
3.3. Voltage transformers
3.4. Cable connectors
4. Low-voltage compartment
5. Operations interface
5.1. Circuit-breaker driving
mechanism
5.2. Driving mechanism for feeder
disconnector(s)
5.3. Earthing switch mechanism
5.4. Voltage presence/absence
indicating relay
5.5. Mimic diagram
9
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
Design characteristics
Key components
Vacuum circuit-breaker Main busbars
Compact circuit-breaker with vacuum switching technology and excellent reliability, The function of the main busbars is the
certified according to IEC 62271-100, including extended electrical endurance (class E2) electrical connection between cubicles.
with fast reclosing cycle and, as a result, maintenance-free for the whole of its service life.
They have a single-phase arrangement and
Circuit-breaker are located on the top sealed gas tank. This
allows modularity and future extensibility
cpg.0 cpg.0 lite cpg.1 with no need to handle gas on site.
Switching capacity
This top busbar assembly consists of three
Short-circuit (asymmetry) [kA] 25/31.5 25 25/31.5
independent cylindrical, shielded, solid
DC < 40 %
insulated copper conductors (6 conductors
31.5 (24 kV) 31.5 (24 kV)
Rated no-load cable-charging breaking capacity [A]
50 (36/40.5 kV)
31.5
50 (36 kV) in double busbar configurations). The
Capacitor banks breaking capacity [A] 400
cubicles are connected using a busbar
section and "T" or "X" shaped connectors.
Electrical endurance E2
Automatic reclosing sequence O-0.3”-CO-15”-CO The whole set is protected against dirt and
Mechanical endurance M2 condensation; in addition, it has a metal
Rated current [A]
Up to 2500 (24/36 kV)
1250 Up to 2000 cover to protect it against impacts.
Up to 1250 (40.5 kV)
Disconnector
High-performance disconnector designed and developed by Ormazabal.
Disconnector and earthing switch
cpg.0 cpg.0 lite cpg.1
Disconnector
Mechanical endurance M1
24/36 kV: Up to 2500
Rated current [A]
40.5 kV: Up to 1250
1250 Up to 2000 A
25 25
Short-time current [kA –1/3 s]
31.5
25
31.5
Earthing switch
62.5-80 (50 Hz) / 62.5 (50 Hz) / 62.5-80 (50 Hz) /
Making capacity [kA]
65-82 (60 Hz) 65 (60 Hz) 65-82 (60 Hz)
Electrical endurance E2*
* In combination with the circuit-breaker
Characteristics:
● Independent drive and levers for the
operations:
● Connection - disconnection [option of motorised ● Disconnection - earthing [option of motorised
driving mechanism] driving mechanism]
10
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Main compartments
The cpg system structure is divided into Driving elements compartment Driving mechanisms
independent compartments:
The lifetime sealed driving elements The driving mechanism is used to carry
compartment houses the switching and out making and breaking operations in the
breaking switchgear, where the insulating medium-voltage circuits.
4
medium is gas SF6.
2 The front distribution of the driving
cpg.0 and cpg.0 lite contain a single gas mechanisms and the use of levers allows
tank, while cpg.1 is characterised by having safe, comfortable and simple operations
1
5 a gas tank for the circuit-breaker and the with minimum effort.
earthing switch, and a gas tank for each
The front mimic diagrams include the
feeder disconnector.
position indicating devices. Maximum
3 Made of stainless steel, it is designed and reliability verified by kinematic chain test
tested to withstand an internal arc. The of the signalling mechanism in accordance
gases generated as a result of an internal arc with IEC 62271-102.
are cooled and can optionally be channelled
cpg.0 Characteristics:
through a duct located at the rear.
● Mimic diagram and pushbuttons
The following elements are located inside,
● Position indication (kinematic chain)
depending on their functionality:
● Making and breaking elements
4 ● Feeder disconnector and earthing switch
● Fuse tripping
2
● Vacuum circuit-breaker ● Voltage capacitive indicating relay
● Fuse holders ● Interlocks (electrical and mechanical)
1 Using top and bottom bushings it is ● Optimised operator interface
5
possible to connect to the main busbar and
medium-voltage cables, respectively.
The gas pressure is tested in each cubicle by
3
means of a pressure indicating relay with a
volt-free contact, allowing it to be used as a
remote alarm.
cpg.0 lite Characteristics:
● Lifetime sealed insulation system
● Internal arc-tested (optional)
4
● Stainless steel – IP65 rating
2
● Switching, breaking and main circuit
devices
● Plug-in terminal for external bushings
acc/ EN 50181
1 5
● Pressure indicating relay
● Pressure relief membrane
cpg.1
1. Gas tank(s):
Circuit-breaker/
disconnector compartments
2. Busbar compartment
3. Base: Cable compartment
4. Low-voltage compartment
5. Operations interface
11
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
12
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
13
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
Type of modules
cpg.0-v
Single busbar circuit-breaker cubicle.
Includes a vacuum circuit-breaker and a three-position disconnector in series with it. Both components are inside the driving elements
compartment.
Electrical specifications
Rated voltage Un [kV] 24 36 40.5 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500 Up to 1600 Up to 2500
Feeder Ir [A] Up to 2500 Up to 1250 Up to 2500
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70 95 60 70**
Across isolating distance Ud [kV] 60 80 118 66 77**
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170 185 125 150**
Across isolating distance Up [kV] 145 195 215 138 165**
Internal arc classification according to IEC 62271-200 IAC AFL[R] 25 / 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] Up to 2500* Up to 1250 Up to 2500*
Short-circuit breaking capacity ISC [kA] 25/31.5
Capacitive current capacity Capacitor bank [A] 400
Rated operating sequence
Without automatic reclosing CO-15 s-CO/CO-3 min-CO
With automatic reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Feeder disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/82 (60 Hz) 65
Main switch making capacity (peak value) Ima [kA] 62.5/80 (50 Hz) - 65/82 (60 Hz) 65/82
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
* With forced ventilation ** For other values, please contact Ormazabal
Applications
Main transformer protection, feeder protection, busbar coupling protection, capacitor bank protection and auxiliary services transformer
protection.
14
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control manometer with volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised earthing switch
Voltage presence indicating relay
Vacuum circuit-breaker
Motor
Tripping coil
cpg.0-v
2nd tripping coil
Closing coil
Undervoltage coil
Blocking open/close push-button
Cubicle height *1378 mm / 4' 6 1/4" in the case of cubicles with IAC AFLR rating.
Standard
Optional
15
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-vl
Single busbar circuit-breaker cubicle with side connection on the left
Includes a vacuum circuit-breaker and a three-position disconnector in series with it. Both components are inside the switch
compartment.
Electrical specifications
Rated voltage Un [kV] 24 36 40.5 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500 Up to 1600 Up to 2500
Feeder Ir [A] Up to 1250
Side connection Ir [A] Up to 1250
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70 95 60 70*
Across isolating distance Ud [kV] 60 80 118 66 77*
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170 185 125 150*
Across isolating distance Up [kV] 145 195 215 138 165*
Internal arc classification IAC AFL[R] 25 / 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] Up to 1250
Short-circuit breaking capacity ISC [kA] 25/31.5
Capacitive current capacity Capacitor bank [A] 400
Rated operating sequence
Without reclosing CO-15 s-CO/CO-3 min-CO
With reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Feeder disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/82 (60 Hz) 65/82
Main switch making capacity (peak value) Ima [kA] 62.5/80 (50 Hz) - 65/82 (60 Hz) 65/82
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
* For other values, please ask Ormazabal
Applications
Main transformer protection, feeder protection, busbar coupling protection, capacitor bank protection and auxiliary services transformer
protection.
16
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control manometer with volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised earthing switch
Voltage presence indicating relay
Vacuum circuit-breaker
Motor
Tripping coil
cpg.0-vl
2nd tripping coil
Closing coil
Undervoltage coil
Blocking open/close push-button
Standard
Optional
17
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-f
Single busbar fuse protection cubicle
Fitted with a three-position switch-disconnector (closed/open/earthed), including fuse protection. The fuses are housed inside sealtight
fuse holder tubes, which are in turn inside the switch compartment, reinforcing its level of insulation.
The three-core opening switch via combined action due to a fuse blowing can be motorised as an option.
Electrical specifications
Rated voltage Un [kV] 24 36 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500 Up to 2500
Transformer outgoing line Ir [A] 200
Switch-disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Mainly active current breaking capacity I1 [A] 630
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
65/82
Switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2
Combined switch-relay take-over current
Imax breaking according to TDitransfer > 800
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 1
Value Ip [kA] 2.5/2.6 2.6
Earthing switch making capacity (peak value) Ima [kA] 2.5/2.6 2.6
Earthing switch category
Mechanical endurance (manual) M0
Operations cycles (short-circuit making current)- class E2
* For higher values, please ask Ormazabal
Applications
Auxiliary services transformer protection.
18
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Fuses combined with the
switch-disconnector
Control manometer with
volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position switch-disconnector
Motorised switch-disconnector cpg.0-f
Additional interlocks
Electrical interlocks
Locking with key lock a h hp f Weight
Ioutgoing
Interlocking with padlock [mm] [mm] [mm] [mm] [kg]
[A]
(ft in) (ft in) (ft in) (ft in) (Lbm)
Cable compartment [600] [2425] [665] [1402*] [550]
200
Toroidal-core current transformers (1' 11 5/8") (7' 11 15/32") (2' 2 3/16") (4' 7 3/16"*) (1212.5)
Plug-in voltage transformer *1415 mm / 4' 7 23/32" in the case of cubicles with IAC AFLR rating.
Low-voltage compartment
Cubicle height The weight shown does not include busbars,
2425 mm [7' 11 15/32") medium-voltage cables, side trim panels,
metering transformers or equipment
2625 mm [8' 7 11/32") inside the control box.
Signalling, control, automation and
protection devices
Standard
Optional
19
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-fl
Single busbar fuse-protection cubicle with side connection on the right
Fitted with a three-position switch-disconnector (closed/open/earthed), including fuse protection. The fuses are housed inside sealtight
fuse holder tubes, which are in turn inside the switch compartment, reinforcing its level of insulation.
The three-core opening switch via combined action due to a fuse blowing can be motorised as an option.
Electrical specifications
Rated voltage Un [kV] 24 36 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500 Up to 2500
Transformer outgoing line Ir [A] 200
Switch-disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
Mainly active current breaking capacity I1 [A] 630
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
65/82
Switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2
Combined switch-relay take-over current
Imax breaking according to TDitransfer > 800
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 1
Value Ip [kA] 2.5/2.6 2.6
Earthing switch making capacity (peak value) Ima [kA] 2.5/2.6 2.6
Earthing switch category
Mechanical endurance (manual) M0
Operations cycles (short-circuit making current)- class E2
* For other values, please ask Ormazabal
Applications
Auxiliary services transformer protection.
20
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Fuses combined with the
switch-disconnector
Control manometer with
volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position switch-disconnector
Motorised switch-disconnector cpg.0-fl
Additional interlocks
Electrical interlocks
Locking with key lock a h hp f Weight
Ioutgoing
Interlocking with padlock [mm] [mm] [mm] [mm] [kg]
[A]
(ft in) (ft in) (ft in) (ft in) (Lbm)
Cable compartment [600] [2425] [665] [1402*] [850]
200
Up to 4 cables per phase (1' 11 5/8") (7' 11 15/32") (2' 2 3/16") (4' 7 3/16""*) (1873.9)
Toroidal-core current transformers *1415 mm / 4' 7 23/32" in the case of cubicles with IAC AFLR rating.
Standard
Optional
21
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-s
Single busbar disconnector cubicle
Fitted with a three-position disconnector without load switching capability.
Electrical specifications
Rated voltage Un [kV] 24 36 40.5 27 38
Rated current
General busbar Ir [A] Up to 2500 Up to 1600 Up to 2500
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
65/82
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
65/82
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
65/82
Applications
Feeder/transformer disconnection, busbar coupling riser and busbar voltage metering.
22
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control pressure switch with
volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised earthing switch
cpg.0-s
Voltage presence indicating relay
Additional interlocks
Electrical interlocks
Locking with key lock
Locking with a padlock a h hp f Weight
Ioutgoing
[mm] [mm] [mm] [mm] [kg]
[A]
Cable compartment (ft in) (ft in) (ft in) (ft in) (Lbm)
Standard
Optional
23
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-c
Single busbar coupling cubicle
Includes a vacuum circuit-breaker and two 3-position disconnectors in series with it, one upstream and the other downstream from the
circuit-breaker.
These elements are inside the driving elements compartments.
Electrical specifications
Rated voltage Un [kV] 24 36 40.5 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500* Up to 1250 Up to 2500*
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70 95 60 70**
Across isolating distance Ud [kV] 60 80 118 66 77**
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170 125 125 150**
Across isolating distance Up [kV] 145 195 145 138 165**
Internal arc classification IAC AFL[R] 25 / 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
65/82
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
65/82
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
65/82
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
65/82
Applications
Longitudinal busbar coupling.
24
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control pressure switch with free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised earthing switch
Voltage presence indicating relay
cpg.0-c
Vacuum circuit-breaker
Motor
Tripping coil
2nd tripping coil
Closing coil a h f Weight
Ioutgoing
[mm] [mm] [mm] [kg]
Undervoltage coil [A]
(ft in) (ft in) (ft in) (Lbm)
Blocking open/close push-button [1200] [2425] [1365*] [1300]
1250
(3' 11 1/4") (7' 11 15/32") (4' 5 3/4"*) (2866.0)
Additional interlocks
[1400] [2425] [1365*] [1550]
1600
Electrical interlocks (4' 7 1/8") (7' 11 15/32") (4' 5 3/4"*) (3417.2)
Locking with key lock [2000] [2425] [1365*] [2300/2500]
2000/2500
(6' 6 3/4") (7' 11 15/32") (4' 5 3/4"*) (5070.6/5511.6)
Interlocking with padlock
*1378 mm / 4' 6 1/4" in the case of cubicles with IAC AFLR rating.
Cable compartment
Bottom busbar
Toroidal-core current transformers The weight shown does not include busbars,
medium-voltage cables, side trim panels,
Low-voltage compartment
metering transformers or equipment
Cubicle height inside the control box.
2425 mm [7' 11 15/32")
2625 mm [8' 7 11/32")
Signalling, control, automation and
protection devices
Standard
Optional
25
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-rb
Single busbar riser cubicle
Allows side cable input or output connection to connect to the main cubicle busbar and its earthing.
Electrical specifications
Rated voltage Un [kV] 24 36 27 38
Rated current
General busbar Ir [A] Up to 2500 Up to 2500
Applications
Side connection to the busbar.
26
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control pressure switch with free contact
Voltage presence indicating relay
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Cable compartment
Toroidal-core current transformers
Low-voltage compartment
Cubicle height cpg.0-rb
2425 mm [7' 11 15/32")
2625 mm [8' 7 11/32")
Signalling, control, automation and
protection devices
a h f Weight
Ioutgoing
[mm] [mm] [mm] [kg]
[A]
(ft in) (ft in) (ft in) (Lbm)
[600] [2425] [1365*] [500]
1250
(1' 11 5/8") (7' 11 15/32") (4' 5 3/4"*) (1102.3)
*1378 mm / 4' 6 1/4" in the case of cubicles with IAC AFLR rating.
Standard
Optional
27
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0-pt
Busbar earthing cubicle
Includes a vacuum circuit-breaker and an earthing switch in series with it. Both components are inside the driving elements compartment.
Electrical specifications
Rated voltage Un [kV] 24 36 40.5 27 38
Rated frequency fr [Hz] 50/60 60
Rated current
General busbar Ir [A] Up to 2500 Up to 1600 Up to 2250
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70 95 60 70*
Across isolating distance Ud [kV] 60 80 118 66 77*
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170 185 125 150*
Across isolating distance Up [kV] 145 195 215 138 165*
Internal arc classification IAC AFL[R] 25 / 31.5 kA 1 s
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 65/82
60 Hz: 65/82
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
65/82
Applications
Earthing the top busbar
28
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
IAC 31.5 kA 1 s
Gas tank
Control manometer with volt-free contact
Busbar compartment
Up to 2500 A
Current transformers
Voltage transformers
Driving mechanisms
Earthing switch
Motorised earthing switch
Voltage presence indicating relay
Vacuum circuit-breaker
Motor
Tripping coil
cpg.0-pt
2nd tripping coil
Closing coil
Undervoltage coil
Blocking open/close push-button
a h hp f Weight
Additional interlocks [mm] [mm] [mm] [mm] [kg]
(ft in) (ft in) (ft in) (ft in) (Lbm)
Electrical interlocks
[600] [2425] [665] [1365*] [850]
Locking with key lock (1' 11 5/8") (7' 11 15/32") (2' 2 3/16") (4' 5 3/4"*) (1873.9)
Interlocking with padlock
*1378 mm / 4' 6 1/4" in the case of cubicles with IAC AFLR rating.
Low-voltage compartment
Cubicle height
The weight shown does not include busbars,
2425 mm [7' 11 15/32") medium-voltage cables, side trim panels,
2625 mm [8' 7 11/32") metering transformers or equipment
inside the control box.
Signalling, control, automation and
protection devices
Standard
Optional
29
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0 lite-v
Single busbar circuit-breaker cubicle
Includes a vacuum circuit-breaker and a three-position disconnector in series with it. Both components are inside the driving elements
compartment.
Electrical specifications
Rated voltage Un [kV] 24
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] Up to 1250
Feeder Ir [A] Up to 1250
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50
Across isolating distance Ud [kV] 60
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125
Across isolating distance Up [kV] 145
Internal arc classification according to IEC 62271-200 IAC AFL[R] 25 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] Up to 1250
Short-circuit breaking capacity ISC [kA] 25
Capacitive current capacity Capacitor bank [A] 400
Rated operating sequence
Without automatic reclosing CO-15 s-CO/CO-3 min-CO
With automatic reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
Feeder disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 25
Peak value Ip [kA] 62.5 (50 Hz) - 65 (60 Hz)
Main switch making capacity (peak value) Ima [kA] 62.5 (50 Hz) - 65 (60 Hz)
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
Applications
Main transformer protection, feeder protection, busbar coupling protection, capacitor bank protection and auxiliary services transformer
protection.
30
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
Gas tank
Control manometer with volt-free contact
Busbar compartment
Up to 1250 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised feeder disconnector and
earthing
Voltage presence indicating relay
Vacuum circuit-breaker
Motor
cpg.0 lite-v
Tripping coil
2nd tripping coil
Closing coil
Undervoltage coil
Blocking open/close push-button Ioutgoing
a h hp f Weight
[mm] [mm] [mm] [mm] [kg]
[A]
Additional interlocks (ft in) (ft in) (ft in) (ft in) (Lbm)
Standard
Optional
31
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0 lite-s
Single busbar disconnector cubicle
Fitted with a three-position disconnector without load switching capability.
Electrical specifications
Rated voltage Un [kV] 24
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] Up to 1250
Feeder Ir [A] Up to 1250
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50
Across isolating distance Ud [kV] 60
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125
Across isolating distance Up [kV] 145
Internal arc classification IAC AFL[R] 25 kA 1 s
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
Feeder disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
50 Hz: 62.5
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
* For other values, please ask Ormazabal
Applications
Feeder/transformer disconnection, busbar coupling riser and busbar voltage metering.
32
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Busbar compartment
Up to 1250 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised feeder disconnector and
earthing
Voltage presence indicating relay
Additional interlocks
cpg.0 lite-s
Interlocking with padlock
Cable compartment
Up to 3 cables per phase
Toroidal-core current transformers
Plug-in voltage transformer a h hp f Weight
Ioutgoing
[mm] [mm] [mm] [mm] [kg]
[A]
Low-voltage compartment (ft in) (ft in) (ft in) (ft in) (Lbm)
[600] [2300] [600] [1160] [450]
Cubicle height 630/1250
(1' 11 5/8") (7' 6 9/16") (1' 11 5/8") (3' 9 21/32") (990)
2300 mm [7' 6 9/16")
Signalling, control, automation and
protection devices The weight shown does not include busbars,
medium-voltage cables, side trim panels,
metering transformers or equipment
inside the control box.
Standard
Optional
33
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0 lite-c
Single busbar coupling cubicle
Includes a vacuum circuit-breaker and two 3-position disconnectors in series with it, one upstream and the other downstream from the
circuit-breaker.
These elements are inside the driving elements compartment.
Electrical specifications
Rated voltage Un [kV] 24
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] Up to 1250
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50
Across isolating distance Ud [kV] 60
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125
Across isolating distance Up [kV] 145
Internal arc classification IAC AFL[R] 25 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] Up to 1250
Short-circuit breaking capacity ISC [kA] 25
Rated operating sequence
Without automatic reclosing CO-15 s-CO/CO-3 min-CO
With automatic reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Feeder disconnector
Admissible rated short-time withstand current (main circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
Feeder disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value tk = 1 s - 3 s Ik [kA] 25
50 Hz: 62.5
Peak value Ip [kA]
60 Hz: 65
50 Hz: 62.5
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
Applications
Longitudinal busbar coupling.
34
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Busbar compartment
Up to 1250 A
Current transformers
Voltage transformers
Driving mechanisms
Three-position disconnector
Motorised feeder disconnector
Motorised feeder disconnector and
earthing
Voltage presence indicating relay
Vacuum circuit-breaker
Motor cpg.0 lite-c
Tripping coil
2nd tripping coil
Closing coil
Undervoltage coil a h f Weight
Ioutgoing
Blocking open/close push-button [mm] [mm] [mm] [kg]
[A]
(ft in) (ft in) (ft in) (Lbm)
Additional interlocks [650] [2300] [1160] [580]
1250
Interlocking with padlock (2' 1 19/32") (7' 6 9/16") (3' 9 21/32") (1280)
Low-voltage compartment
Cubicle height The weight shown does not include busbars,
2300 mm [7' 6 9/16") medium-voltage cables, side trim panels,
metering transformers or equipment
Signalling, control, automation and inside the control box.
protection devices
Standard
Optional
35
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.1-v2
Double busbar circuit-breaker cubicle
Incorporates, in independent compartments, a vacuum switching circuit-breaker and an earthing switch in series with it, as well as a
feeder disconnector.
Electrical specifications
Rated voltage Un [kV] 24 36
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] Up to 2000*
Feeder Ir [A] Up to 2000
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70
Across isolating distance Ud [kV] 60 80
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170
Across isolating distance Up [kV] 145 195
Internal arc classification IAC AFL[R] 25 / 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] Up to 2000
Short-circuit breaking capacity Isc [kA] 25/31.5
Capacitive current capacity (50 Hz). Capacitor bank [A] 400
Rated operating sequence
With automatic reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
Disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
* For other values, please ask Ormazabal.
Applications
Main transformer protection, feeder protection, capacitor bank protection, auxiliary services transformer protection, longitudinal coupling
with medium-voltage cables.
36
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 31.5 kA 1 s
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Busbar compartment
Up to 2000 A
Current transformers
Voltage transformers
Driving mechanisms
Feeder disconnector
Motorisation
Earthing switch
Motorisation
Voltage presence indicating relay
cpg.1-v2
Vacuum circuit-breaker
Motor
Tripping coil
2nd tripping coil
Closing coil a h hp f Weight
Configuration [mm] [mm] [mm] [mm] [kg]
Undervoltage coil (ft in) (ft in) (ft in) (ft in) (Lbm)
Blocking open/close push-button [600] [2720] [640] [2004*] [1400]
cpg.1-v2
(1' 11 5/8") (8' 11 3/32") (2' 1 3/16") (6' 6 29/32"*) (3086)
Additional interlocks
*2044 mm/6' 8 15/32" in the case of cubicles with IAC AFLR rating.
Electrical interlocks
Locking with key lock The weight shown does not include busbars,
Interlocking with padlock medium-voltage cables, side trim panels,
metering transformers or equipment
Cable compartment inside the control box.
Up to 4 cables per phase
Toroidal-core current transformers
Plug-in voltage transformer
Low-voltage compartment
Cubicle height
2720 mm [8' 11 3/32")
2920 mm [9' 6 31/32")
Signalling, control, automation and
protection devices
Standard
Optional
37
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.1-f2
Double busbar fuse protection cubicle
Fitted with a switchgear compartment with a three-position switch-disconnector (closed/open/earthed), including fuse protection, with
two separate switchgear compartments with feeder disconnectors.
The fuses are housed inside sealtight fuse holder tubes, which are in turn inside the switchgear compartment, reinforcing its level of
insulation. The combined action by blowing a fuse allows three-core opening of the switch.
Electrical specifications
Rated voltage Un [kV] 24 36
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] Up to 2000*
Transformer outgoing line Ir [A] 200
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70
Across isolating distance Ud [kV] 60 80
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170
Across isolating distance Up [kV] 145 195
Internal arc classification IAC AFL[R] 25 /31.5 kA 1 s
Switch-disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
Mainly active load-breaking current I1 [A] 630
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
Switch-disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E3
Combined switch-relay take-over current
Imax breaking according to TD itransfer > 800
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s - 3 s Ik [kA] 1/3
Peak value Ip [kA] 2.5
Main switch making capacity (peak value) Ima [kA] 2.5/7.5
Earthing switch category
Mechanical endurance M0
Operations cycles (short-circuit making current)- class E3
* For other values, please ask Ormazabal.
Applications
Auxiliary services transformer protection.
38
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 31.5 kA 1 s
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Fuses combined with the switch-
disconnector
Busbar compartment
Up to 2000 A
Current transformers
Voltage transformers
Driving mechanisms
Feeder disconnector
Motorisation cpg.1-f2
Earthing switch
Motorisation
Voltage presence indicating relay
*2044 mm/6' 8 15/32" in the case of cubicles with IAC AFLR rating.
Cable compartment
Up to 4 cables per phase
The weight shown does not include busbars,
Toroidal-core current transformers medium-voltage cables, side trim panels,
Plug-in voltage transformer metering transformers or equipment
inside the control box.
Low-voltage compartment
Cubicle height
2720 mm [8' 11 3/32")
2920 mm [9' 6 31/32")
Signalling, control, automation and
protection devices
Standard
Optional
39
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.1-s2
Double busbar disconnector cubicle
Incorporates feeder and earthing switches, located in independent compartments.
Electrical specifications
Rated voltage Un [kV] 24 36
Rated frequency fr [Hz] 50/60
Rated current
General busbar and cubicle interconnection Ir [A] Up to 2000*
Feeder Ir [A] Up to 2000
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70
Across isolating distance Ud [kV] 60 80
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170
Across isolating distance Up [kV] 145 195
Internal arc classification IAC AFL[R] 25 31.5 kA 1 s
Disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
Disconnector category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
Combined switch-relay take-over current (ekorRPT)
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s - 3 s Ik [kA] 25/31.5
50 Hz: 62.5/80
Peak value Ip [kA] 60 Hz: 65/82
50 Hz: 62.5/80
Main switch making capacity (peak value) Ima [kA] 60 Hz: 65/82
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E0
* For other values, please ask Ormazabal.
Applications
Longitudinal busbar coupling with medium-voltage cables. Busbar voltage metering with voltage transformer disconnection.
40
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 31.5 kA 1 s
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Busbar compartment
Up to 2000 A
Current transformers
Voltage transformers
Driving mechanisms
Feeder disconnector
Motorisation
Earthing switch
Motorisation
Voltage presence indicating relay
cpg.1-s2
Additional interlocks
Electrical interlocks
Locking with key lock
Interlocking with padlock
a h f Weight
Cable compartment Configuration [mm] [mm] [mm] [kg]
Up to 3 + 3 cables per phase (ft in) (ft in) (ft in) (Lbm)
[600] [2720] [2004*] [1200]
Low-voltage compartment cpg.1-s2
(1' 11 5/8") (8' 11 3/32") (6' 6 29/32"*) (2645)
Cubicle height *2044 mm/6' 8 15/32" in the case of cubicles with IAC AFLR rating.
Standard
Optional
41
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.1-c/cpg.1-cl
Single (c) and double (cl) longitudinal busbar coupling cubicle
Includes the following items for each busbar in separate compartments: a vacuum circuit-breaker and earthing switches in series with it, in
a switchgear compartment and two feeder disconnectors in their respective compartments.
Electrical specifications
Rated voltage Un [kV] 24 36
Rated frequency fr [Hz] 50/60
Rated current
General busbar Ir [A] 1250/1600/2000*
Feeder Ir [A] 630/1250/1600/2000
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70
Across isolating distance Ud [kV] 60 80
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170
Across isolating distance Up [kV] 145 195
AFL[R] 25 kA 1 s
Internal arc classification IAC AFL 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] 630/1250/1600/2000
Short-circuit breaking capacity Isc [kA] 25/31.5
Rated operating sequence
With reclosing O-0.3 s-CO-15 s-CO/O-0.3 s-CO-3 min-CO
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Disconnector category
Mechanical endurance M0
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Main switch making capacity (peak value) Ima [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
* For other values, please ask Ormazabal.
Applications
Longitudinal busbar coupling.
42
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 31.5 kA 1 s
IAC 25 kA 1 s
Gas tank
Control pressure switch with volt-free
contact
Busbar compartment
Up to 2000 A
Current transformers
Voltage transformers
Driving mechanisms
Feeder disconnector
Motorisation
Earthing switch
Motorisation
Voltage presence indicating relay
cpg.1-c
Additional interlocks
Electrical interlocks
Locking with key lock
Interlocking with padlock
a h f Weight
Low-voltage compartment Configuration [mm] [mm] [mm] [kg]
(ft in) (ft in) (ft in) (Lbm)
Cubicle height
cpg.1-c [600] [1400]
2720 mm [8' 11 3/32") (1' 11 5/8") (3086)
cpg.1-c (tipo c) [2720] [2004*]
2920 mm [9' 6 31/32") (8' 11 3/32") (6' 6 29/32"*)
[1200] [2800]
cpg.1-cl
Signalling, control, automation and (3' 11 1/4") (6172)
protection devices *2044 mm/6' 8 15/32" in the case of cubicles with IAC AFLR rating.
cpg.1-cl
Standard
Optional
43
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.1-ct
Transverse busbar coupling cubicle
Includes the following elements in separate switchgear compartments:
A vacuum circuit-breaker and two earthing switches in series with it, in the switchgear compartment and two feeder disconnectors in
their respective compartments.
Electrical specifications
Rated voltage Un [kV] 24 36
Rated frequency fr [Hz] 50/60
Rated current
General busbar and cubicle interconnection Ir [A] 1250/1600/2000*
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 50 70
Across isolating distance Ud [kV] 60 80
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 125 170
Across isolating distance Up [kV] 145 195
AFL[R] 25 kA 1 s
Internal arc classification IAC AFL 31.5 kA 1 s
Circuit-breaker
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Making and breaking rated capacity
Mainly active current rated breaking capacity I1 [A] 1250/1600/2000
Short-circuit breaking capacity Isc [kA] 25/31.5
Rated operating sequence
Without reclosing CO-15 s-CO - CO-3 min-CO
With reclosing –
Circuit-breaker category
Mechanical endurance (operations class) M2
Electrical endurance (class) E2
Disconnector
Admissible rated short-time withstand current (main circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz)
Disconnector category
Mechanical endurance M0
Operations cycles (short-circuit making current)- class E0
Earthing switch
Admissible rated short-time withstand current (earthing circuit)
Value t k = 1 s or 3 s Ik [kA] 25/31.5
Peak value Ip [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz) 65/85
Main switch making capacity (peak value) Ima [kA] 62.5/80 (50 Hz) - 65/85 (60 Hz) 65
Earthing switch category
Mechanical endurance M1
Operations cycles (short-circuit making current)- class E2 (in combination with circuit-breaker)
* For other values, please ask Ormazabal.
Applications
Transverse busbar coupling.
44
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
Dimensions
Configuration
Cubicle structure
Internal arc
IAC 31.5 kA 1 s
IAC 25 kA 1 s
Busbar compartment
Up to 2000 A
Current transformers
Voltage transformers
Driving mechanisms
Feeder disconnector
Motorisation
Earthing switch
Motorisation
Voltage presence indicating relay
Additional interlocks
Electrical interlocks
Locking with key lock
cpg.1-ct
Interlocking with padlock
Low-voltage compartment
Cubicle height
2720 mm [8' 11 3/32") a h f Weight
2920 mm [9' 6 31/32") Configuration [mm] [mm] [mm] [kg]
(ft in) (ft in) (ft in) (Lbm)
Signalling, control, automation and
[600] [2720] [2004*] [2200]
protection devices cpg.1-ct
(1' 11 5/8") (8' 11 3/32") (6' 6 29/32"*) (4850)
*2044 mm/6' 8 15/32" in the case of cubicles with IAC AFLR rating.
Standard
Optional
45
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
cpg.0
HRC Fuses
Short-circuit protection in the medium-
voltage network is performed via the fuse
protection functions.
The fuse holder tubes reach a uniform
cpg.1 Voltage transformers
temperature all along the tube when they
Characteristics: are placed horizontally inside the gas tank.
Cable connectors
● Plug-in type When the cover is closed, they are fully
Characteristics: sealed against floods and external pollution.
● Single-phase
● For single-core and three-core cables. Characteristics:
● Insulated
● For dry or impregnated cables. ● Horizontal fuse holders
● Reinforced
● Screened ● Front access
● Inductive type
● Angled ● Separate compartments per phase
● Installed outside the driving elements
● Up to 4 screw-in connectors per phase compartment ● Protected within the gas tank
(6 for cpg.0 2000/2500 A)
● Unaffected by environmental conditions ● Insulation and sealing against external
● Number of reinforced connection shielded agents (pollution, temperature changes,
connectors (screw-in): adverse weather conditions, including
● cpg.0 lite: up to 3 connectors per phase. floods)
● cpg.0: up to 4 connectors per phase ● Internal interlocks for safe access to the fuse
(up to 1600 A); up to 6 connectors per phase (up
holder area
to 2500 A).
● cpg.1: up to 4 connectors per phase.
Contact Ormazabal for more information
about fuse selection.
46
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
● Handling methods:
● Elevation: Forklift truck or manual pallet jack
Alternative method: placing wheels underneath
● Lifting: Slings and lifting beams
Actuating levers
Fuse protection
● Fuse holder carriage
47
cpg.0, cpg.0 lite & cpg.1 Medium-voltage switchgear for
Single and double busbar GIS-type switchgear system Substation Solutions
Inside buildings
● Simple handling with pallet jack The minimum distances [mm] (inches) recommended for correct installation, once located
● Reduced dimensions and minimum space at their final location, are:
required for its location due to the precise
design and use of SF6 gas as an insulating For cpg.0: For cpg.1
medium
● Modularity and extensibility on both sides,
allowing a fast and economical installation
process, in a small space and without having
to move adjacent cubicles to remove a
central cubicle.
● Reduced dimensions of the cubicle room,
due to its front access and its design with no
removable switchgear and not requiring rear
access passage
● Optimisation of installation costs and civil
works due to the reduced dimensions and
little need for manoeuvring space
48
Medium-voltage switchgear for cpg.0, cpg.0 lite & cpg.1
Substation Solutions Single and double busbar GIS-type switchgear system
49
www.ormazabal.com
CA-110-EN-2009