Module-2 Fire Safety
Module-2 Fire Safety
MODULE-2
FIRE SAFETY
OBJECTIVES OF FIRE SAFETY:
The main objectives of fire safety are
FIRE TRIANGLE:
We have three elements of fire. These elements must be present in the right proportion before fire
outbreak can occur. The condition for fire to occur is usually represented by a triangle. This is known as the
Fire Triangle. Below is the fire triangle.
AIR
FUEL
(OXYGEN)
FIRE
HEAT
Fire is started/ignited/begin at a hot spot and spreads along the combustible material to neighbouring
area subject to availability of
1. Combustible material
2. Air (oxygen)
3. Heat and local temperature rise.
All the three above must be present for fire to be initiated and continue
Various materials differ in their ignition temperatures and fire characteristics
CLASSIFICATION OF FIRE:
Class A Fire – These fires are fuelled by ordinary combustible materials, such as wood, cloth, paper, and
many plastics. This type of fire burns with an ember, leaves an ash, and is best extinguished by removing the
heat side of the triangle. Extinguishers suitable for Class "A" fires should be identified by a triangle
containing the letter "A"; if color-coded, the triangle will be green.
Class B Fire – These fires are fueled by flammable liquids, combustible liquids, petroleum greases, tars,
oils, oil-based paints, solvents, lacquers, alcohols and flammable gases. This type of fire burns on the
surface of the fuels, and is best extinguished by a blanketing or smothering action. A fire of this type is fast-
spreading and capable of engulfing a large area in a very short time. Extinguishers suitable for Class "B"
fires should be identified by a square containing the letter "B". If color-coded, the square is red.
Class C Fire - These fires occur in energized electrical equipment, where the electrical non-conductivity of
the extinguishing media is of importance. Blanketing or smothering this type of fire with a non-conducting
extinguishing agent is of prime importance. If the electrical equipment is dead then it becomes Class A or
Class B. Water, or solutions containing water, is never to be used on a Class "C" fire. Extinguishers suitable
for Class "C" fires should be identified by a circle containing the letter "C"; if color-coded, the circle is blue.
Class D Fire – These fires involve combustible metals, such as magnesium, sodium, lithium and potassium.
Generally the extinguishing agent is referred to as DRY POWDER. These extinguishers should be identified
by a star containing the letter “D”, if color-coded, the star is yellow.
Class E Fire – Fires involving flammable gases under pressure and fuels including liquefied gases.
Examples are Hydrogen, Ammonia, Acetylene, LPG, Petrol, Furnace oil etc. The extinguishing agent is
referred to as WET CHEMICAL. These extinguishers should be identified by the letter “K.”
Fire Extinguishing aims at rapidly removing one, two or all the three of essentials of fire.
Cooling is the removal of heat. Temperature of the fire zone and combustion zone must be reduced
below ignition temperature rapidly so that fire does not sustain. Rate of cooling must be higher than
the rate of heat generated by combustion. Water is the most commonly used coolant for class A fires.
Ventilation helps in cooling and fire extinction by release of heat to atmosphere,
When the plunger is struck, the acid bottle on the top ruptures. The sulphuric acid reacts with soda
ash present in the container to release the CO2 gas which creates internal pressure. This internal pressure
forces water contained in the cylinder to jet out through the nozzle.
To operate the extinguishers, remove the cap on the top and strike the plunger against a hard surface
like the floor. Direct the nozzle jet towards the base of fire.
The fire risk can be quantified based on Dow index and Mond Index (Fire and explosion index).
These indices give a realistic value of risk of individual process unit due to potential fires and explosion.
Computer models are available to simulate the fire conditions and estimate the potential consequences.
Fire Hazard analysis should include the following factors:
a) Concentration of combustible materials including transient fire loads due to combustibles expected to
be used in normal operations
b) Combustible contents, furnishings, building materials or combination of combustible materials which
are conductive to fire spread.
c) Exposure to fire, heat, smoke that may necessitate evacuation from the areas that are to be attended
for safety functions
d) Fire in control rooms or other locations having critical safety related functions
e) Lack of adequate access or of smoke removal facility
f) Lack of explosion prevention measures
g) Loss of Electric power
h) Inadvertent operation of fire suppression systems
i) Possibility of fire spreading from one unit to another unit
The analysis and consequences to be done by trained and experienced persons.
PREVENTION OF FIRE:
Fire prevention includes procedures for preventing, detecting and extinguishing fire. This needs
several preventive actions during design, installation, testing, commissioning, operation and maintenance of
plants and equipment. Safety documentation should include safety instructions related to fire prevention.
Fire preventive systems and sub systems should form part of the plant and equipment.
Fire prevention programme utilises the concept of fire triangle and applying principles of triangle of
extinction. Following shall be observed for prevention of fire:
All Inflammable material such as transformer oil, furnace oil, fuels, paints, varnishes should be
stored separately, used and handled with necessary precaution. Such material should be guarded
against heat/temp source like flames, sparks, hot surface, flashover etc
Insulating material should not be exposed to hot temperatures beyond certain limits
Special precautions to be taken while welding, grinding, heating, gas cutting etc and while carrying
open flames so that fire is not initiated.
Smoking, open flames, match boxes, inflammable material, open resistor heaters etc should not be
allowed inside the protected area and in control room
LPG cylinders, Acetylene cylinders valves/pipes/tanks should be leak proof. Gas cylinders must be
stored separately as per safety recommendation
Inflammable materials should not be used in electrical equipment as far as possible. Modern non
explosive/ fire free equipment must be preferred. Eg. Dry transformer in place of oil filled
transformers, SF6 breakers in place of oil filled breakers, XLPE cable in place of oil insulated cables
etc.
Inflammable material should be avoided as much as possible in construction site
Electrical equipment should not be over loaded. Various safety devices such as overload protection,
over current protection, temperature rise protection, temperature monitoring must be provided with
oil filled equipment and electrical equipment having inflammable insulation.
Good housekeeping helps in prevention of fire. Scrap, waster paper, waste wood, waste oil etc
should be segregated, stored and disposed off periodically.
Leakages should be attended immediately.
Precautions are necessary in storage, erection, testing, commissioning, operation, and maintenance
that fires are not initiated due to carelessness.
Sub systems should not be energised unless the fire protection systems are commissioned and are in
alert workable state
The following steps should be followed when responding to incipient stage fire:
Sound the fire alarm and call the fire department, if appropriate.
Identify a safe evacuation path before approaching the fire.
Do not allow the fire, heat, or smoke to come between you and your evacuation path.
Select the appropriate type of fire extinguisher.
Discharge the extinguisher within its effective range using the P.A.S.S. technique (pull, aim,
squeeze, and sweep).
Back away from an extinguished fire in case it flames up again.
Evacuate immediately if the extinguisher is empty and the fire is not out.
Evacuate immediately if the fire progresses beyond the incipient stage.
The fire detectors are located in various zones of the power plant/ substations and are connected to
the fire alarm and fire control panel located in the control room and to the automatic fire fighting system
distributed in the plant.
The detection of smoke/ fire, sounding of alarm and initiating the fire extinguishing action can be
achieved by various methods.
Fire Detector System initiates Fire Alarm System. Fire Alarm/ Control panel is installed in Control
Room of the power plant/ substation. The operation of a fire detector is immediately indicated and Buzzer is
sounded on the respective zone-window of the panel.
The function of alarm system are to sound fire alarm, send signals to fire brigade and indicating
zone of fire. The fire alarm is initiated by the fire detectors.
Depending upon the design features and specifications, the functions of fire detection and alarm
system include one or more of the following:
To detect smoke, fire and sound alarm, siren, warning indication of fire control panels and warn
personnel about occurrence of smoke/ fire and its location by sounding alarm/ horn.
To initiate operation of automatic fire fighting system in the affected zone.
To initiate operation of deluge valves and to admit water through projectors.
To initiate tripping of circuit breakers feeding power to electrical plants in the affected areas, via fire
control and relay panel.
SAFETY BOARDS:
*_*_*_*_*_*_*